Fault Current Calculation
Fault Current Calculation
I=Uo/Ze
The Values of Transformer Rating, per unit impedance & phase/line voltage will usually be
mentioned on the transformer rating plate / data sheet
As an example a 500kVA, 11kV/400V/3-Phase/50Hz transformer with 5% p.u impendence will
have the following fault levels on the secondary side
S=1.732 * VPP * IP
Where:
F = Available fault current at source (A) V = Circuit voltage (use line voltage if three-phase and
phase voltage if single-phase) (V) P = Number of phases (1 or 3) L = Distance from source of
feeder to point of interest (Ft.) R = Resistance of feeder per 1000 Ft. (Ω) X = Reactance of feeder
per 1000 Ft. (Ω) A = Available fault current at the source of the feeder (A) M = Total fault
current contribution of induction motors (A) N = Total fault current contribution of synchronous
motors (A)
The turns ratio is the number of turns on the secondary winding divided by the number of turns
on the primary winding. For a step up transformer, the turns ratio will be greater then one. If it's
a step down transformer, then the turns ratio will be less than one.
If you don't know the turns ratio, divide the secondary voltage by the primary voltage to get the
turns ratio.
Alternately, you can determine the VA burden by the above, VA = V*I = (I*R)*I, using Ohm's
law.
The above answers the question of how to calculate the VA burdon on a current transformer. The
VA burden of a CT is determined by the resistivity of the CT, multiplied by the current squared
through the secondary. In general, this will be provided by the manufacturer in the form of a CT
burden characteristic, developed through testing of the CT in question, not through calculations.