Types of Generator Protection
Types of Generator Protection
PROTECTION
Generator
NER Transformer
Generator
VT
Reverse
Power Overvoltage Buchholz
IDMT
Negative Phase Generator Restricted E/F
Earth Fault
Sequence Diffirential Generator
Overcurrent Transformer
Instantaneous
Loss of Field Diffirential
Earth Fault
END OF PRESENTATION
THANK YOU
FOR YOUR
PARTICIPATION.
DIFFERENTIAL PROTECTION
CT Stator CT
Red
Yellow
Blue
RELAY
Biasing Coil
Operating Coil
STATOR EARTH-FAULT PROTECTION
Stator earth-fault protection comprises an instantaneous
relay and the Inverse Definite Minimum Time (IDMT) relay.
Both relay will be connected to current transformer having a
primary current rating equal to that of the earthing resistor.
Generator
Red
Yellow
Blue
CT Relay
Neutral Earth
Resistance
ROTOR EARTH-FAULT PROTECTION
For detecting earth-faults in the rotor circuit, a high-
resistance potentiometer is connected across the rotor circuit
the centre point of which is connected to earth through a
sensitive relay. The relay will respond to earth faults
occurring over most of the rotor circuit.
OVERCURRENT PROTECTION
An Inverse Definite Minimum Time (IDMT) relay is generally
used as back-up protection but the operation of this relay is
complicated because of the current decrement in the
generator during fault conditions. In some cases a setting is
chosen, such that the relay will not operate for a system fault
but will only respond when fault current is fed into the
generator, in this way it only acts as a back-up to the main
generator protection.
LOSS OF FIELD PROTECTION
Failure of the field system results in acceleration of the rotor
to above synchronous speed where it continuous to generate
power as an induction generator the flux being provided by a
large magnetising components drawn from the system. This
condition can tolerated for a short time but clearly there will
be increased heating of the rotor because of the slip-
frequency currents which flow.
CT
Red
Yellow
Blue
XL R R
X Y
VZB VZR
Positive Sequence Negative Sequence
R
Ir Ir VXY
VZZR
VZR VZB
60o
60o
VZB
Ib Iy
Iy Ib
There is still a risk, however, that the steam valve not close
completely and even a small gap can cause over-speed and so
where urgent tripping is not required. It is usual to lower the
electrical output to about 1% before tripping the CB. A sensitive
under-power relay is used to detect when this value is reached.