HV Winding Phase Overcurrent Protection

This document provides settings and specifications for the ground overcurrent protection function of a P441_51GT relay. It lists the transformer through fault current, CT primary current, pick up setting, time dial multiplier, plug setting multiplier, overcurrent characteristic curve type, actual plug setting multiplier, and operating time for a ground fault at a 380kV system. It also includes a graph showing the time to trip curve for the HV winding phase overcurrent protection.

Uploaded by

386
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
184 views5 pages

HV Winding Phase Overcurrent Protection

This document provides settings and specifications for the ground overcurrent protection function of a P441_51GT relay. It lists the transformer through fault current, CT primary current, pick up setting, time dial multiplier, plug setting multiplier, overcurrent characteristic curve type, actual plug setting multiplier, and operating time for a ground fault at a 380kV system. It also includes a graph showing the time to trip curve for the HV winding phase overcurrent protection.

Uploaded by

386
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 5

GROUND OVERCURRENT PROTECTION FUNCTION OF P441_51GT RELAY

Main setting of low set over current element for a ground fault at 380kV system (Group1)
Trnasformer through fault current 2 18844 A
CT primary current 2500 A
Pick up setting 103% 9.8
TDM 0.30
Plug setting multiplier = 7.32
Over current characteristic curve IEC Very Inverse
Actulal PSM 7.3
Operating time 0.63

HV WINDING PHASE OVERCURRENT PROTECTION

1000.00

100.00

10.00
Time to trip(in seconds)

1.00

0.10

0.01
100 1000 10000 100000

Fault Current (A) @ 230 kV

Column O Column Q Column O Column O


GROUND OVERCURRENT PROTECTION FUNCTION OF T60_51TN RELAY

Main setting of low set over current element for a ground fault at 380kV system (Group1)
Trnasformer through fault current
CT primary current
Pick up setting
TDM
Plug setting multiplier =
Over current characteristic curve IEC Very Inv
Actulal PSM
Operating time

HV WINDING PHASE OVERCURRENT PROTECTION

1000.00

100.00

10.00
Time to trip(in seconds)

1.00

0.10

0.01
100 1000 10000 100000

Fault Current (A) @ 230 kV


IEC Very Inverse
8.41
Relay Setting Calculation Doc.No: EMP24401.
Project: RPP8 Ext.III
(Attachment-9.5.6) Rev.1

GROUND OVERCURRENT PROTECTION FUNCTION OF T60_51TN RELAY

Main setting of low set over current element for a ground fault at 380kV system (Group1)
Trnasformer through fault current 5000 A
CT primary current 16000 A
Pick up setting 6.0%
TDM 0.90
Plug setting multiplier = 5.21
Over current characteristic curve IEC Very Inverse
Actulal PSM 5.2
Operating time 3.787

HV WINDING PHASE OVERCURRENT PROTECTION


1000.00

100.00
Time to trip(in seconds)

10.00

1.00

0.10

0.01
1000 10000 100000
Fault Current (kA) @ 230 kV

Check 5 of 5 11/11/2010