Power System
Power System
Modern electric power systems have three separate components - generation, transmission and
distribution. Electric power is generated at the power generating stations by synchronous
alternators that are usually driven either by steam or hydro turbines. Most of the power generation
takes place at generating stations that may contain more than one such alternator-turbine
combination. Depending upon the type of fuel used, the generating stations are categorized as
thermal, hydro, nuclear etc. Many of these generating stations are remotely located. Hence the
electric power generated at any such station has to be transmitted over a long distance to load
centers that are usually cities or towns. This is called the power transmission. In fact power
transmission towers and transmission lines are very common sights in rural areas.
Modern day power systems are complicated networks with hundreds of generating stations and
load centers being interconnected through power transmission lines. Electric power is generated at
a frequency of either 50 Hz or 60 Hz.
In an interconnected ac power system, the rated generation frequency of all units must be the
same. In India the frequency is 50 Hz.
where ρ is the resistivity of the wire in Ω - m, l is the length in meter and A is the cross sectional area
in m2 . Unfortunately however the resistance of an overhead conductor is not the same as that given
by the above expression. When alternating current flows through a conductor, the current density is
not uniform over the entire cross section but is somewhat higher at the surface. This is called the skin
effect and this makes the ac resistance a little more than the dc resistance. Moreover in a stranded
conductor, the length of each strand is more that the length of the composite conductor. This also
increases the value of the resistance from that calculated in (1.1).
Finally the temperature also affects the resistivity of conductors. However the temperature rise in
metallic conductors is almost linear in the practical range of operation and is given by
where R1 and R2 are resistances at temperatures t1 and t2 respectively and T is a constant that
depends on the conductor material and its conductivity. Since the resistance of a conductor cannot be
determined accurately, it is best to determine it from the data supplied by the manufacturer
Inductance of a Straight Conductor
From the knowledge of high school physics we know that a current carrying conductor produces a
magnetic field around it. The magnetic flux lines are concentric circles with their direction specified by
Maxwell's right hand thumb rule ( i.e., if the thumb of the right hand points towards the flow of
current then the fingers of the fisted hand point towards the flux lines ). The sinusoidal variation in the
current produces a sinusoidal variation in the flux. The relation between the inductance, flux linkage
and the phasor current is then expressed as
where L is the inductance in Henry, λ is the flux linkage in Weber-turns and I is the phasor current in
Ampere.
A. Internal Inductance
Consider a straight round (cylindrical) conductor, the cross-section of which is shown in Fig. 1.3. The
conductor has a radius of r and carries a current I . Ampere's law states that the magnetomotive force
(mmf) in ampere-turns around a closed path is equal to the net current in amperes enclosed by the
path. We then get the following expression
where H is the magnetic field intensity in At/m, s is the distance along the path in meter and I is the
current in ampere.
Let us denote the field intensity at a distance x from the center of the conductor by Hx. It is to be
noted that Hxis constant at all points that are at a distance x from the center of the conductor.
Therefore Hx is constant over the concentric circular path with a radius of x and is tangent to it.
Denoting the current enclosed by Ix we can then write
Assuming a relative permeability of 1, the flux density at a distance of x from the center of the
conductor is given by
Note that the entire conductor cross section does not enclose the above flux. The ratio of the cross
sectional area inside the circle of radius x to the total cross section of the conductor can be thought
about as fractional turn that links the flux dφ x. Therefore the flux linkage is
Integrating (1.10) over the range of x , i.e., from 0 to r , we get the internal flux linkage as
Wbt/m
Then from (1.3) we get the internal inductance per unit length as
H/m
For μ≠1, μr H/m
It is interesting to note that the internal inductance is independent of the conductor radius.
B. External Inductance
Let us consider an isolated straight conductor as shown in Fig. 1.4. The conductor carries a current I .
Assume that the tubular element at a distance x from the center of the conductor has a field intensity
Hx . Since the circle with a radius of x encloses the entire current, the mmf around the element is
given by
(1.13)
and hence the
flux density at a radius x becomes
The external flux linkage between any two points D1 and D2, external to the conductor is
Wbt/m
From (1.3) we can then write the inductance between any two points outside the conductor as
H/m
Therefore from (1.12) and (1.17) we can specify the inductance of conductor 1 due to internal and
external flux as
(1.18)
We can H/m
rearrange L1 given in (1.18) as follows
The radius r1 can be assumed to be that of a fictitious conductor that has no internal flux but with
the same inductance as that of a conductor with radius r1 .
In a similar way the inductance due current in the conductor 2 is given by
where r = re1/4.
Inductance of Three-Phase Lines with Symmetrical Spacing
Consider the three-phase line shown in Fig. 1.6. Each of the conductors has a radius of r and their
centers form an equilateral triangle with a distance D between them. Assuming that the currents are
balanced, we have
Consider a point P external to the conductors. The distance of the point from the phases a, b and c
are denoted by Dpa, Dpband Dpcrespectively.
The flux linkage with the conductor of phase-a due to the current Ib , excluding all flux beyond the
point P , is given by (1.17) as
The above
expression can
be expanded as (1.27)
Note that due to symmetry, the inductances of phases b and c will be the same as that of phase-a
given above, i.e., Lb= Lc = L a .
Inductance of Three-Phase Lines with Asymmetrical Spacing
It is rather difficult to maintain symmetrical spacing as shown in Fig. 1.6 while constructing a
transmission line. With asymmetrical spacing between the phases, the voltage drop due to line
inductance will be unbalanced even when the line currents are balanced. Consider the three-phase
asymmetrically spaced line shown in Fig. 1.7 in which the radius of each conductor is assumed to be
r . The distances between the phases are denoted by Dab, Dbcand Dca. We then get the following flux
linkages for the three phases
(1.31)
(1.32)
(1.33)
Note that for the above operator the following relations hold
Let as assume that the current are balanced. We can then write
Substituting the above two expressions in (1.31) to (1.33) we get the inductance of the three phases
as
(1.36)
(1.37)
(1.38)
It can be seen
that the inductances contain imaginary terms. The imaginary terms will vanish only when Dab= Dbc =
Dca. In that case the inductance will be same as given by (1.30).
Transposed Line
The inductances that are given in (1.36) to (1.38) are undesirable as they result in an unbalanced
circuit configuration. One way of restoring the balanced nature of the circuit is to exchange the
positions of the conductors at regular intervals. This is called transposition of line and is shown in
Fig.1.8. In this each segment of the line is divided into three equal sub-segments. The conductors
of each of the phases a, b and c are exchanged after every sub-segment such that each of them is
placed in each of the three positions once in the entire segment. For example, the conductor of the
phase-a occupies positions in the sequence 1, 2 and 3 in the three sub-segments while that of the
phase-b occupies 2, 3 and 1. The transmission line consists of several such segments.
(1.39)
This implies
Notice that (1.43) is of the same form as (1.30) for symmetrically spaced conductors. Comparing
these two equations we can conclude that GMD can be construed as the equivalent conductor
spacing. The GMD is the cube root of the product of conductor spacings.
Composite Conductors
So far we have considered only solid round conductors. However as mentioned at the beginning of
Section 1.1, stranded conductors are used in practical transmission line. We must therefore modify
the equations derived above to accommodate stranded conductors. Consider the two groups of
conductors shown in Fig. 1.9. Of these two groups conductor x contains n identical strands of radius
rx while conductor y contains m identical strands of radius ry . Conductor x carries a current I the
return path of which is through conductor y . Therefore the current through conductor y is - I .
In a similar way the inductances of the other conductors are also obtained. For example,
The average inductance of any one of the strands in the group of conductor x is then
Conductor x is composed of n strands that are electrically parallel. Even though the inductance of the
different strand is different, the average inductance of all of them is the same as Lav, x . Assuming that
the average inductance given above is the inductance of n parallel strands, the total inductance of the
conductor x is
(1.49)
Substituting the values of La , Lbetc. in the above equation we get
where the geometric mean distance ( GMD ) and the geometric mean radius ( GMR ) are given
respectively by
(1.51)
(1.52)
The inductance
of the conductor y can also be similarly obtained. The geometric mean radius GMRy will be different
for this conductor. However the geometric mean distance will remain the same.
Bundled Conductors
So far we have discussed three-phase systems that have only one conductor per phase. However for
extra high voltage lines corona causes a large problem if the conductor has only one conductor per
phase. Corona occurs when the surface potential gradient of a conductor exceeds the dielectric
strength of the surrounding air. This causes ionization of the area near the conductor. Corona
produces power loss. It also causes interference with communication channels. Corona manifests
itself with a hissing sound and ozone discharge. Since most long distance power lines in India are
either 220 kV or 400 kV, avoidance of the occurrence of corona is desirable.
The high voltage surface gradient is reduced considerably by having two or more conductors per
phase in close proximity. This is called conductor bundling . The conductors are bundled in groups of
two, three or four as shown in Fig. 1.10. The conductors of a bundle are separated at regular intervals
with spacer dampers that prevent clashing of the conductors and prevent them from swaying in the
wind. They also connect the conductors in parallel.
The geometric
mean radius
(GMR) of two- (1.53)
conductor
bundle is given by
where Ds is the GMR of conductor. The GMR for three-conductor and four-conductor bundles are
given
respectively by
(1.54)
(1.55)
The inductance of the bundled conductor is then given by where n=2,3 ....
where the geometric mean distance is calculated assuming that the center of a round conductor is the
same as that of the center of the bundle.
Fig. 1.10 Bundled conductors: (a) 2-conductor, (b) 3-conductor and (c) 4-conductor bundles
Section II: Shunt Parameters Of Transmission Lines
Capacitance of a Straight Conductor
Capacitance of a Single-Phase Line
Capacitance of a Three-Phase Transposed Line
Effect of Earth on the Calculation of Capacitance
Capacitance in a transmission line results due to the potential difference between the conductors.
The conductors get charged in the same way as the parallel plates of a capacitor. Capacitance
between two parallel conductors depends on the size and the spacing between the conductors.
Usually the capacitance is neglected for the transmission lines that are less than 50 miles (80 km)
long. However the capacitance becomes significant for longer lines with higher voltage. In this
section we shall derive the line capacitance of different line configuration.
The charge on the conductor gives rise to an electric field with radial flux lines where the total electric
flux is equal to the charge on the conductor. By Gauss's law, the electric flux density at a cylinder of
radius x when the conductor has a length of 1 m is
C/m2
The electric filed intensity is defined as the ratio of electric flux density to the permittivity of the
medium. Therefore
V/m
Fig. 1.11 Cylindrical conductor with radial flux lines.
Now consider the long straight conductor of Fig. 1.12 that is carrying a positive charge q C/m. Let two
points P1 and P2 be located at distances D1 and D2 respectively from the center of the conductor. The
conductor is an equipotential surface in which we can assume that the uniformly distributed charge is
concentrated at the center of the conductor. The potential difference V12 between the points P1 and
P2 is the work done in moving a unit of charge from P2 to P1 . Therefore the voltage drop between the
two points can be computed by integrating the field intensity over a radial path between the
equipotential
surfaces, i.e.,
(1.60)
V
Fig. 1.12 Path of integration between two points external to a round straight conductor.
Capacitance of a Single-Phase Line
Consider the single-phase line consisting of two round conductors as shown in Fig. 1.5. The
separation between the conductors is D . Let us assume that conductor 1 carries a charge of q1 C/m
while conductor 2 carries a charge q2 C/m. The presence of the second conductor and the ground will
disturb field of the first conductor. However we assume that the distance of separation between the
conductors is much larger compared to the radius of the conductor and the height of the conductor is
much larger than D for the ground to disturb the flux. Therefore the distortion is small and the charge
is uniformly distributed on the surface of the conductor.
Assuming that the conductor 1 alone has the charge q1 , the voltage between the conductors is
Similarly if the conductor 2 alone has the charge q2 , the voltage between the conductors is
The above equation implies that
For a single-phase line let us assume that q1 (= -q2 ) is equal to q . We therefore have
The above equation gives the capacitance between two conductors. For the purpose of transmission
line modeling, the capacitance is defined between the conductor and neutral. This is shown in Fig.
1.13. Therefore the value of the capacitance is given from Fig. 1.13 as
Fig. 1.13 (a) Capacitance between two conductors and (b) equivalent capacitance to ground.
Capacitance of a Three-Phase Transposed Line
Consider the three-phase transposed line shown in Fig. 1.14. In this the charges on conductors of
phases a, b and c are qa, qband qc espectively. Since the system is assumed to be balanced we have
This implies
(1.73)
The GMD of the V
conductors is
given in (1.42). We can therefore write
(1.78)
V
where
(1.80)
The mutual inductances between the field coil and the stator windings vary as a function of θd and are
given by
(1.82)
(1.83)
(1.84)
(1.85)
(1.86)
(1.87)
(1.88)
Hence the flux linkage equations for the stator windings (1.85) to (1.87) can be modified as
(1.89)
(1.90)
(1.91)
(1.92)
Also assuming that the rotor rotates at synchronous speed ωs we obtain the following two equations
(1.93)
(1.94)
where θd0 is the initial position of the field winding with respect to the phase-a of the stator winding at
time t = 0. The mutual inductance of the field winding with all the three stator windings will vary as a
function of θd,
i.e., (1.95)
(1.96)
(1.97)
Substituting (1.92), (1.94), (1.95), (1.96) and (1.97) in (1.89) to (1.91) we get
(1.98)
(1.99)
(1.100)
Since we assume balanced operation, we need to treat only one phase. Let the armature resistance
of the generator be R . The generator terminal voltage is given by
where the negative sign is used for generating mode of operation in which the current leaves the
terminal. Substituting (1.98) in (1.101) we get
Since θd0 is the position of the d -axis at time t = 0, we define the position of the q -axis at that instant
as
(1.105)
(1.107)
(1.108)
The equivalent circuit is shown in Fig. 1.16. Let the current ia lag the internal emf ea by θa . The stator
currents are then
(1.109)
(1.110)
(1.111)
Fig. 1.16 Three-phase equivalent circuit of a synchronous generator.
The single-phase equivalent circuit is shown in Fig. 1.17. The phase angle θabetween eaand ia is
rather difficult to measure under load as ea is the no load voltage. To avoid this, we define the phase
angle between νa and ia to be θ . We assume that ea leads νaby δ . Therefore we can write
(1.112)
Then the voltages and currents shown in Fig. 1.17 are given as
(1.113)
(1.114)
(1.115)
(1.116)
(1.117)
(1.118)
Fig. 1.19 Simplified equivalent circuit of a single-phase transformer: (a) when referred to the primary
side and (b) when referred to the secondary side.
Section V: Balanced Operation Of a Three-Phase Citcuit
In the language of Power Systems, a three-phase circuit is said to be balanced if the following
conditions are true.
If all the sources and loads are y-connected.
There is no mutual inductance between the phases.
All neutrals are at the same potential.
As a consequence of the points (2) and (3) above, all phases are decoupled.
All network variables are balanced sets in the same sequence as the sources.
Consider the three-phase circuit shown in Fig. 1.20 that contains three balanced sources Ea , Eband
Ec along with three balanced source impedances, each of value Zs. The sources supply two
balanced loads - one wye-connected with impedance of Zy and the other Δ-connected with
impedance of ZΔ . Since this is a balanced network, the sum of the currents at the neutrals N (or n )
is zero. Therefore the neutral are at the same potential. Transforming the Δ-connected load to an
equivalent y, we get the per phase equivalent circuit as shown in Fig. 1.21. In this fashion an entire
power system can be converted into its per phase equivalent. The line diagram showing a per
phase equivalent circuit is called a single-line diagram.
Section VI: Per Unit Representation
In a power system different power equipment with different voltage and power levels are connected
together through various step up or step down transformers. However the presence of various
voltage and power levels causes problem in finding out the currents (or voltages) at different points
in the network. To alleviate this problem, all the system quantities are converted into a uniform
normalized platform. This is called the per unit system . In a per unit system each system variable
or quantity is normalized with respect to its own base value. The units of these normalized values
are per unit (abbreviated as pu) and not Volt, Ampere or Ohm. The base quantities chosen are:
VA base ( Pbase ): This is the three-phase apparent power (Volt-Ampere) base that is
common to the entire circuit.
Voltage Base ( Vbase ): This is the line-to-line base voltage. This quantity is not uniform for
the entire circuit but gets changed by the turns ratio of the transformer.
Fig. 1.20 Three balanced sources supplying two balanced load through balanced source
impedances.
Fig. 1.21 Per phase equivalent circuit of the network of Fig. 1.20.
Based on the above two quantities the current and impedance bases can be defined as
(1.119)
(1.121)
The
impedance now has to be represented in a new base value denoted as Z base_new . Therefore
(1.122)
From (1.120)
Z2 can be defined in terms of old and new values of VA base and voltage base as
(1.123)
Let us consider the circuit shown in Fig. 1.19 (a) which contains the equivalent circuit of a
transformer. Let the transformer rating be
500 MVA, 220/22 kV with a leakage reactance of 10%.
The VA base of the transformer is 500 MVA and the voltage bases in the primary and secondary side
are 200 kV and 22 kV respectively. Therefore the impedance bases of these two sides are
Ω and W
where the subscripts 1 and 2 refer to the primary (high tension) and secondary (low tension) sides
respectively. Assume that the leakage reactance is referred to the primary side. Then for 10%, i.e.,
0.1 per unit leakage reactance we have
Ω
The above reactance when referred to the secondary side is
Ω
Hence the per unit impedance in the secondary side is 0.0968/0.968 = 0.1. Therefore we see that the
per unit leakage reactance is the same for both sides of the transformer and, as a consequence, the
transformer can be represented by only its leakage reactance. The equivalent circuit of the
transformer is then as shown in Fig. 1.22. Since this diagram only shows the reactance (or
impedance) of the circuit, this is called the reactance (or impedance ) diagram .
Generator G1
Generator G2
Generator G3
Transformer T 1
Transformer T 2
Transformer T 3
Ω
Therefore the per unit values of the line impedances are
pu and pu
The impedance diagram is shown in Fig. 1.24.
(2.3)
This implies that
A is the ratio of sending end voltage to the open circuit receiving end voltage. This quantity is
dimension less.
Similarly,
(2.4)
Ω
i.e., B , given in Ohm, is the ratio of sending end voltage and short circuit receiving end current. In a
similar way we
can also define
(2.5)
mho
(2.6)
The parameter
D is dimension less.
(2.8)
Therefore the
ABCD
parameters are (2.9)
given by
(2.10)
(2.11)
Substituting
(2.11) in (2.10)
we get
(2.12)
Therefore from (2.11) and (2.12) we get the following ABCD parameters of the nominal- p
representation
Nominal- T
Representatio (2.13)
n
In this (2.14)
representation
the shunt
admittance is
placed in the middle and the series impedance is divided into two equal parts and these parts are
placed on either side of the shunt admittance. The nominal-T representation is shown in Fig. 2.4. Let
us denote the midpoint voltage as VM . Then the application of KCL at the midpoint results in
Fig. 2.4
Nominal-T
representation.
Rearranging the
above equation
can be written (2.16)
as
Now the
receiving end
current is given (2.17)
by
Then
substituting the
value of VM (2.20)
from (2.16) in
(2.19) and solving
(2.25)
Again as x
0, from (2.25) we get
(2.26)
Now for the current through the strip, applying KCL we get
(2.27)
The second
term of the above equation is the product of two small quantities and therefore can be neglected.
For x 0 we then have
(2.28)
Taking
derivative with respect to x of both sides of (2.26) we get
Substitution of
(2.28) in the above equation results
(2.29)
The roots of
the above equation are located at ±√( yz ). Hence the solution of (2.29) is of the form
(2.30)
Taking
derivative of (2.30) with respect to x we get
(2.31)
Combining
(2.26) with (2.31) we have
(2.32)
Let us define
the following two quantities
(2.33)
(2.34)
Then (2.30) and (2.32) can be written in terms of the characteristic impedance and propagation
constant as
(2.35)
(2.36)
Let us
assume that x = 0. Then V = VR and I = IR . From (2.35) and (2.36) we then get
(2.37)
(2.38)
Solving (2.37)
and (2.38) we get the following values for A1 and A2 .
Also note that for x = l we have V = Vs and I = IS . Therefore replacing x by l and substituting the
values of A1 and A2 in (2.35) and (2.36) we get
(2.39)
(2.40)
Noting that
We can
rewrite (2.39) and (2.40) as
(2.41)
(2.42)
The ABCD
parameters of the long transmission line can then be written as
(2.43)
(2.44)
(2.45)
Let's do an Example
Example 2.1
Consider a 500 km long line for which the per kilometer line impedance and admittance are given
respectively by z = 0.1 + j 0.5145 W and
y = j 3.1734 x 10 -6 mho. Therefore
and
We shall now use the following two formulas for evaluating the hyperbolic forms
Therefore from (2.43) to (2.45) the ABCD parameters of the system can be written as
(2.47)
(2.48)
where Z = zl is the total impedance of the line. Again comparing (2.43) with (2.46) we get
(2.50)
(2.51)
where Y = yl is
the total admittance of the line. Note that for small values of l , sinh γl = γl and tanh ( γl /2) = γl /2.
Therefore from (2.49) we get Z = Z and from (2.51) we get Y = Y . This implies that when the
length of the line is small, the nominal- p representation with lumped parameters is fairly accurate.
However the lumped parameter representation becomes erroneous as the length of the line
increases.
Example 2.2
Consider the transmission line given in Example 2.1. The equivalent system parameters for both
lumped and distributed parameter representation are given in Table 2.1 for three different line
lengths. It can be seen that the error between the parameters increases as the line length
increases.
Table 2.1 Variation in equivalent parameters as the line length changes
Length of the Lumped Parameters Distributed Parameters
Line (km) Z(Ω) Y(mho)
3.17 X 10-4 <
100 52.41 < 79o 3.17 X 10-4 < 90o 52.27< 79o
89.98o
128.81<
250 131.032 < 79o 7.93 X 10-4 < 90o 8.0 X 10-4 < 89.9o
79.2o
500 262.064 < 79o 1.58 X 10-3 < 90o 244.61<79.8o 1.64 X 10-3 < 89.6o
(2.53)
The term surge
impedance loading or SIL is often used to indicate the nominal capacity of the line. The surge impedance is
the ratio of voltage and current at any point along an infinitely long line. The term SIL or natural power is a
measure of
power delivered
by a transmission (2.54)
line when
terminated by surge impedance and is given by
(2.55)
(2.56)
This implies that as the distance x changes, the magnitudes of the voltage and current in the above equations
do not change. The voltage then has a flat profile all along the line. Also as ZC is real, V and I are in phase with
each other all through out the line. The phase angle difference between the sending end voltage and the
receiving end voltage is then θ = β l. This is shown in Fig. 2.7.
where δ is angle between the sources and is usually called the load angle . As the total length of
the line is l , we replace x by l to obtain the sending end voltage from (2.39) as
(2.58)
(2.59)
Substituting (2.59) in (2.52), the voltage equation at a point in the transmission line that is at a
distance x from the receiving end is obtained as
(2.60)
(2.61)
When the system is unloaded, the receiving end current is zero ( IR = 0). Therefore we can rewrite
(2.58) as
(2.62)
Substituting the above equation in (2.52) and (2.53) we get the voltage and current for the unloaded
system as
(2.63)
Example 2.4
Consider the system given in Example 2.3. It is assumed that the system is unloaded with VS = VR =
1< 0° per unit. The voltage and current profiles for the unloaded system is shown in Fig. 2.9. The
maximum voltage of 1.2457 per unit occurs at the receiving end while the maximum current of 0.7428
per unit is at the sending end. The current falls monotonically from the sending end and voltage rises
monotonically to the receiving end. This rise in voltage under unloaded or lightly loaded condition is
called Ferranti effect .
Fig. 2.9 Voltage and current profile over an unloaded transmission line.
Mid Point Voltage and Current of Loaded Lines
The mid point voltage of a transmission line is of significance for the reactive compensation of
transmission lines. To obtain an expression of the mid point voltage, let us assume that the line is
loaded (i.e., the load angle d is not equal to zero). At the mid point of the line we have x = l /2 such
that βx = q /2. Let us denote the midpoint voltage by VM . Let us also assume that the line is
symmetric, i.e., VS = VR = V. We can then rewrite equation (2.60) to obtain
(2.65)
(2.66)
The phase angle of the mid point voltage is half the load angle always. Also the mid point voltage and
current are in phase, i.e., the power factor at this point is unity. The variation in the magnitude of
voltage with changes in load angle is maximum at the mid point. The voltage at this point decreases
with the increase in δ . Also as the power through a lossless line is constant through out its length and
the mid point power factor is unity, the mid point current increases with an increase in δ
Example 2.5
Consider the transmission line discussed in Example 2.4. Assuming the magnitudes of both sending
and receiving end voltages to be 1.0 per unit, we can compute the magnitude of the mid point voltage
as the load angle ( δ ) changes. This is given in Table 2.2. The variation in voltage with δ is shown in
Fig. 2.10.
Table 2.2 Changes in the mid-point voltage magnitude with load angle
δ in degree VM in per unit
20 1.0373
25 1.0283
30 1.0174
Fig. 2.10 Variation in voltage profile for a loaded line
Power in a Lossless Line
The power flow through a lossless line can be given by the mid point voltage and current equations
given in (2.66) and (2.67). Since the power factor at this point is unity, real power over the line is
given by
(2.71)
If V = V0 , the
rated voltage, we can rewrite the above expression in terms of the natural power as
(2.72)
(2.73)
where X is the total reactance of the line. Equation (2.71) then can be modified to obtain the well
known power transfer relation for the short line approximation as
(2.74)
In general it is not necessary for the magnitudes of the sending and receiving end voltages to be
same. The power transfer relation given in (2.72) will not be valid in that case. To derive a general
expression for power transfer, we assume
and
If the receiving end real and reactive powers are denoted by PR and QR respectively, we can write
from (2.52)
Equating real and imaginary parts of the above equation we get
and (2.75)
(2.76)
Rearranging (2.76) we get the power flow equation for a losslees line as
(2.77)
To derive expressions for the reactive powers, we rearrange (2.75) to obtain the reactive power
delivered to the receiving end as
(2.78)
(2.79)
Equating the imaginary parts of the above equation we get the following expression for the reactive
generated by the source
(2.80)
(2.81)
It is important to note that if the magnitude of the voltage at the two ends is equal, i.e., VS = VR
= V, the reactive powers at the two ends become negative of each other, i.e., QS = QR . The net
reactive power absorbed by the line then becomes twice the sending end reactive power, i.e., QL =
2QS . Furthermore, since cosθ ≈ 1 for small values of θ, the reactive powers at the two ends for a
short transmission line are given by
(2.82)
The reactive power absorbed by the line under this condition is given by
Example 2.6
Consider a short, lossless transmission line with a line reactance of 0.5 per unit. We assume that the
magnitudes of both sending and receiving end voltages to be 1.0 per unit. The real power transfer
over the line and reactive power consumed by the line are shown in Fig. 2.11. The maximum real
power is 2.0 per unit and it occurs for δ = 90° . Also the maximum reactive power consumed by the
line occurs at δ = 180 ° and it has a value of 8 per unit.
Fig. 2.11 Real power flow and reactive power consumed by a transmission line.
Chapter 3: Network Admittance and Impedance Matrices
As we have seen in Chapter 1 that a power system network can be converted into an equivalent
impedance diagram. This diagram forms the basis of power flow (or load flow) studies and short
circuit analysis. In this chapter we shall discuss the formation of bus admittance matrix (also known
as Ybus matrix) and bus impedance matrix (also known as Zbus matrix). These two matrices are
related by
(3.1)
We shall discuss the formation of the Ybus matrix first. This will be followed by the discussion of the
formation of the Zbus matrix.
Section I: Formation of Bus Admittance Matrix
Node Elimination by Matrix Partitioning
Node Elimination by Kron Reduction
Inclusion of Line Charging Capacitors
Formation of Bus Admittance Matrix
Consider the voltage source VS with a source (series) impedance of ZS as shown in Fig. 3.1 (a).
Using Norton's theorem this circuit can be replaced by a current source IS with a parallel admittance
of YS as shown in Fig. 3.1 (b). The relations between the original system and the Norton equivalent
are
We shall use this Norton's theorem for the formulation of the Ybus matrix.
Fig. 3.1 (a) Voltage source with a source impedance and (b) its Norton equivalent.
For the time being we shall assume the short line approximation for the formulation of the bus
admittance matrix. We shall thereafter relax this assumption and use the π -representation of the
network for power flow studies. Consider the 4-bus power system shown in Fig. 3.2. This contains
two generators G1 and G2 that are connected through transformers T1 and T2 to buses 1 and 2. Let us
denote the synchronous reactances of G1 and G2 by XG1 and XG2 respectively and the leakage
reactances of T1 and T2 by XT1 and XT2 respectively. Let Zij, i = 1, ..., 4 and j = 1, ... , 4 denote the line
impedance between buses i and j .
Fig. 3.2 Single-line diagram of a simple power network.
Then the system impedance diagram is as shown in Fig. 3.3 where Z11 = j ( XG1 + XT1 ) and Z22 = j (
XG2 + XT2 ).
(3.3)
or,
(3.4)
It can be easily seen that we get (3.1) from (3.3) and (3.4).
Consider node (bus) 1 that is connected to the nodes 2 and 3. Then applying KCL at this node we get
(3.5)
In a similar way application of KCL at nodes 2, 3 and 4 results in the following equations
(3.6)
(3.7)
(3.8)
(3.9)
(3.10)
In general the format of the Ybus matrix for an n -bus power system is as follows
(3.11)
where
(3.12)
It is to be noted
that Ybus is a symmetric matrix in which the sum of all the elements of the k th column is Ykk .
Example 3.1
Consider the impedance diagram of Fig. 3.2 in which the system parameters are given in per unit by
Z11 = Z22 = j0.25, Z12 = j0.2, Z13 = j0.25, Z23 = Z34 = j0.4 and Z24 = j0.5
The system admittance can then be written in per unit as
Y11 = Y22 = j4, Y12 = j5, Y13 = j4, Y23 = Y34 = j2.5 and Y24 = j2
The Ybus is then given from (3.10) as
per unit
Consequently the bus impedance matrix is given by
per unit
It can be seen that like the Ybus matrix the Zbus matrix is also symmetric.
Let us now assume that the voltages EG1 and EG2 are given by
p.u.
Solving the above equation we get the node voltages as
per unit
Node Elimination by Matrix Partitioning
Sometimes it is desirable to reduce the network by eliminating the nodes in which the current do not
enter or leave.
Let (3.3) be
written as (3.13)
In the above equation IA is a vector containing the currents that are injected, Ix is a null vector and the
Ybus matrix is portioned with the matrices K , L and M . Note that the Ybus matrix contains both L and
LT due to its symmetric nature.
We get the following two sets of equations from (3.13)
(3.14)
(3.15)
Substituting (3.15) in (3.14) we get
(3.16)
Example 3.2
Let us consider the system of Example 3.1. Since there is no current injection in either bus 3 or bus 4,
from the Ybus computed we can write
We then have
per unit
Substituting I1 = 460 per unit and I2 = 490 per unit we shall get the same values of V1 and V2
as given in Example 3.1.
Inspecting the reduced Ybus matrix we can state that the admittance between buses 1 and 2 is - j
6.8978. Therefore the self admittance (the admittance that is connected in shunt) of the buses 1 and
2 is - j4 per unit (= - j 10.8978 + j 6.8978). The reduced admittance diagram obtained by eliminating
nodes 3 and 4 is shown in Fig. 3.5. It is to be noted that the impedance between buses 1 and 2 is the
Thevenin impedance between these two buses. The value of this impedance is 1/( - j 6.8978) = j
0.145 per unit.
Fig. 3.5 Reduced admittance diagram after the elimination of buses 3 and 4.
where A is an ( n X n ) real or complex valued matrix, x and b are vectors in either Rn or Cn . assume
that the b vector has a zero element in the n th row such that (3.18) is given as
(3.19)
We can then eliminate the kth row and kth column to obtain a reduced ( n - 1) number of equations of
the form
(3.20)
(3.21)
Example 3.3
Let us consider the same system of Example 3.1. We would like to eliminate the last two rows and
columns. Let us first eliminate the last row and last column. Some of the values are given below
In a similar way we can calculate the other elements. Finally eliminating the last row and last column,
as all these elements are zero, we get the new Ybus matrix as
Further reducing the last row and the last column of the above matrix using (3.21), we obtain the
reduced Ybus matrix given in Example 3.2.
Inclusion of Line Charging Capacitors
So far we have assumed that the transmission lines are modeled with lumped series impedances
without the shunt capacitances. However in practice, the Ybus matrix contains the shunt admittances
for load flow analysis in which the transmission lines are represented by its π -equivalent. Note that
whether the line is assumed to be of medium length or long length is irrelevant as we have seen in
Chapter 2 how both of them can be represented in a p -equivalent.
Consider now the power system of Fig. 3.2. Let us assume that all the lines are represented in an
equivalent- π with the shunt admittance between the line i and j being denoted by Ychij . Then the
equivalent admittance at the two end of this line will be Ychij/2. For example the shunt capacitance at
the two ends of the line joining buses 1 and 3 will be Ych13/2. We can then modify the admittance
diagram Fig. 3.4 as shown in Fig. 3.6. The Ybus matrix of (3.10) is then modified as
(3.22)
where
(3.23)
Fig. 3.6 Admittance diagram of the power system Fig. 3.2 with line charging capacitors.
(3.24)
This implies that Y11 is the admittance measured at bus-1 when buses 2, 3 and 4 are short circuited.
The admittance Y11 is defined as the self admittance at bus-1. In a similar way the self admittances
of buses 2, 3 and 4 can also be defined that are the diagonal elements of the Ybus matrix. The off
diagonal elements are denoted as the mutual admittances . For example the mutual admittance
between buses 1 and 2 is defined as
(3.26)
The mutual admittance Y12 is obtained as the ratio of the current injected in bus-1 to the voltage of
bus-2 when buses 1, 3 and 4 are short circuited. This is obtained by applying a voltage at bus-2 while
shorting the other three buses.
The voltage-current relation can be written in terms of the Zbus matrix as
(3.27)
(3.28)
i.e., the driving point impedance is obtained by injecting a current at bus-1 while keeping buses 2, 3
and 4 open-circuited. Comparing (3.26) and (3.28) we can conclude that Z11 is not the reciprocal of
Y11 . The transfer impedance between buses 1 and 2 can be obtained by injecting a current at bus-2
while open-circuiting buses 1, 3 and 4 as
(3.29)
(3.30)
The aim is to modify the matrix Zorig when a new bus or line is connected to the power system.
Adding a New Bus to the Reference Bus
It is assumed that a new bus p ( p > n ) is added to the reference bus through an impedance Zp . The
schematic diagram for this case is shown in Fig. 3.7. Since this bus is only connected to the reference
bus, the voltage-current relations the new system are
(3.31)
(3.32)
In a similar way the current Ip will also alter the voltages of all the other buses as
(3.33)
(3.34)
Therefore the new voltage current relations are
(3.35)
Similarly we have
(3.37)
and
(3.38)
(3.40)
(3.41)
where
(3.42)
We can now eliminate the last row and last column using the Kron's reduction given in (3.21).
Direct Determination of Zbus Matrix
We shall now use the methods given in Sections 3.3.1 to 3.3.4 for the direct determination of the Zbus
matrix without forming the Ybus matrix first. To accomplish this we shall consider the system of Fig. 3.2
and shall use the system data given in Example 3.1. Note that for the construction of the Z bus matrix
we first eliminate all the voltage sources from the system.
Step-1 : Start with bus-1. Assume that no other buses or lines exist in the system. We add this bus to
the reference bus with the impedance of j 0.25 per unit. Then the Zbus matrix is
(3.43)
Step-2 : We now add bus-2 to the reference bus using (3.31). The system impedance diagram is
shown in Fig. 3.10. We then can modify (3.43) as
(3.44)
Eliminating the last row and last column using the Kron's reduction of (3.31) we get
(3.45)
Step-4: We now
add bus-3 to bus-1 through an impedance of j 0.25 per unit as shown in Fig. 3.12. The application of
(3.35) on (3.45) will then result in the following matrix
(3.46)
(3.47)
Step-6 : We now add a new bus-4 to bus-2 through an impedance of j 0.5 as shown in Fig. 3.14.
Then the application of (3.35) on (3.47) results in the following matrix
(3.48)
Eliminating the
5th row and column through Kron's reduction we get the final Zbus as
(3.49)
Example 3.4
Consider the two bus power system shown in Fig. 3.15. It can be seen that the open-circuit voltages
of buses a and b are Va and Vb respectively. From (3.11) we can write the Ybus matrix of the system
as
(3.50)
Now consider the system of Fig. 3.15. The Thevenin impedance of looking into the system at bus- a
is the parallel combination of Zaa and Zab + Zbb, i.e.,
(3.51)
Similarly the Thevenin impedance obtained by looking into the system at bus- b is the parallel
combination of Zbb and Zaa + Zab, i.e.,
(3.52)
Hence the driving point impedances of the two buses are their Thevenin impedances.
Let us now consider the Thevenin impedance while looking at the system between the buses a and b
. From Fig. 3.15 it is evident that this Thevenin impedance is the parallel combination of Zab and Zaa +
Zbb, i.e.,
(3.53
As we have seen in the above example in the relation V = Zbus I , the node or bus voltages Vi, i = 1, ...
, n are the open circuit voltages. Let us assume that the currents injected in buses 1, ... , k - 1 and k +
1, ... , n are zero when a short circuit occurs at bus k . Then Thevenin impedance at bus k is
(3.54)
From (3.51), (3.52) and (3.54) we can surmise that the driving point impedance at each bus is the
Thevenin impedance.
Let us now find the Thevenin impedance between two buses j and k of a power system. Let the open
circuit voltages be defined by the voltage vector V° and corresponding currents be defined by I° such
that
(3.55)
Now suppose the currents are changed by ΔI such that the voltages are changed by ΔV . Then
(3.56)
(3.57)
Let us now assume that additional currents ΔIk and ΔIk are injected at the buses k and j respectively
while the currents injected at the other buses remain the same. Then from (3.57) we can write
(3.58)
(3.59)
(3.60)
Since Zjk = Zkj the network can be drawn as shown in Fig. 3.16. By inspection we can see that the
open circuit voltage between the buses k and j is
(3.61)
(3.62)
Also during the short circuit Vk- Vj = 0. Therefore combining (3.59) and (3.60) we get
(3.63)
Combining (3.61) to (3.63) we find the Thevenin impedance between the buses k and j as
(3.64)
The above equation agrees with our earlier derivation of the two bus network given in (3.53).
(4.1)
(4.2)
Similarly the mutual admittance between the buses i and j can be written as
(4.3)
Let the power system contains a total number of n buses. The current injected at bus- i is given as
(4.4)
It is to be noted we shall assume the current entering a bus to be positive and that leaving the bus to
be negative. As a consequence the power and reactive power entering a bus will also be assumed to
be positive. The complex power at bus- i is then given by
(4.5)
Note that
(4.6)
Let the injected power calculated by the load flow program be Pi, calc . Then the mismatch between
the actual injected and calculated values is given by
(4.9)
In a similar way the mismatch between the reactive power injected and calculated values is given
by
(4.10)
The purpose
of the load flow is to minimize the above two mismatches. It is to be noted that (4.6) and (4.7) are
used for the calculation of real and reactive power in (4.9) and (4.10). However since the
magnitudes of all the voltages and their angles are not known a priori, an iterative procedure must
be used to estimate the bus voltages and their angles in order to calculate the mismatches. It is
expected that mismatches ΔPi and ΔQi reduce with each iteration and the load flow is said to have
converged when the mismatches of all the buses become less than a very small number.
For the load flow studies we shall consider the system of Fig. 4.1, which has 2 generator and 3 load
buses. We define bus-1 as the slack bus while taking bus-5 as the P-V bus. Buses 2, 3 and 4 are
P-Q buses. The line impedances and the line charging admittances are given in Table 4.1. Based
on this data the Y bus matrix is given in Table 4.2. This matrix is formed using the same procedure
as given in Section 3.1.3. It is to be noted here that the sources and their internal impedances are
not considered while forming the Ybus matrix for load flow studies which deal only with the bus
voltages.
Fig. 4.1 The simple power system used for load flow studies.
Table 4.1 Line impedance and line charging data of the system of Fig. 4.1.
Line(bus to bus) Impedance Line charging ( Y /2)
Table 4.3 Bus voltages, power generated and load - initial data.
Bus no. Bus voltage Power generated Load
Magnitude (pu) Angle (deg) P (MW) Q (MVAr) P (MW) P (MVAr)
1 1.05 0 - - 0 0
2 1 0 0 0 96 62
3 1 0 0 0 35 14
4 1 0 0 0 16 8
5 1.02 0 48 - 24 11
(4.11)
(4.12)
In this fashion the voltages of all the buses are updated. We shall outline this procedure with the help
of the system of Fig. 4.1, with the system data given in Tables 4.1 to 4.3. It is to be noted that the real
and reactive powers are given respectively in MW and MVAr. However they are converted into per
unit quantities where a base of 100 MVA is chosen.
Updating Load Bus Voltages
Let us start the procedure with bus-2 of the 5 bus 7 line system given in fig: 4.1. Since this is load
bus, both the real and reactive power into this bus is known. We can therefore write from (4.12)
(4.13)
From the data given in Table 4.3 we can write
It is to be noted that since the real and reactive power is drawn from this bus, both these quantities
appear in the above equation with a negative sign. With the values of the Y bus elements given in
Table 4.2 we get V21 = 0.9927 < − 2.5959° .
The first iteration voltage of bus-3 is given by
(4.14)
Note that in the above equation since the update for the bus-2 voltage is already available, we used
the 1st iteration value of this rather than the initial value. Substituting the numerical data we get V3(1) =
0.9883 < − 2. 8258° . Finally the bus-4 voltage is given by
(4.15)
Solving we get
V4(1) = 0. 9968 < −3.4849° .
Updating P-V Bus Voltages
It can be seen from Table 4.3 that even though the real power is specified for the P-V bus-5, its
reactive power is unknown. Therefore to update the voltage of this bus, we must first estimate the
reactive power of this bus. Note from Fig. 4.11 that
(4.16)
(4.17)
For the system of Fig. 4.1 we have
(4.18)
This is computed as 0.0899 per unit. Once the reactive power is estimated, the bus-5 voltage is
updated as
(4.19)
It is to be noted that even though the power generation in bus-5 is 48 MW, there is a local load that is
consuming half that amount. Therefore the net power injected by this bus is 24 MW and consequently
the injected power P5, inj in this case is taken as 0.24 per unit. The voltage is calculated as V5(1) =
1.0169 < − 0.8894° . Unfortunately however the magnitude of the voltage obtained above is not equal
to the magnitude given in Table 4.3. We must therefore force this voltage magnitude to be equal to
that specified. This is accomplished by
(4.20)
This will fix the voltage magnitude to be 1.02 per unit while retaining the phase of − 0.8894 ° . The
corrected voltage is used in the next iteration.
Convergence of the Algorithm
As can be seen from Table 4.3 that a total number of 4 real and 3 reactive powers are known to us.
We must then calculate each of these from (4.6) and (4.7) using the values of the voltage magnitudes
and their angle obtained after each iteration. The power mismatches are then calculated from (4.9)
and (4.10). The process is assumed to have converged when each of ΔP2 , ΔP3, ΔP4 , ΔP5 , ΔQ2 ,
ΔQ3 and ΔQ4 is below a small pre-specified value. At this point the process is terminated.
Sometimes to accelerate computation in the P-Q buses the voltages obtained from (4.12) is multiplied
by a constant. The voltage update of bus- i is then given by
(4.21)
where λ is a constant that is known as the acceleration factor . The value of λ has to be below 2.0
for the convergence to occur. Table 4.4 lists the values of the bus voltages after the 1 st iteration and
number of iterations required for the algorithm to converge for different values of λ. It can be seen that
the algorithm converges in the least number of iterations when λ is 1.4 and the maximum number of
iterations are required when λ is 2. In fact the algorithm will start to diverge if larger values of
acceleration factor are chosen. The system data after the convergence of the algorithm will be
discussed later.
Table 4.4 Gauss-Seidel method: bus voltages after 1 st iteration and number of iterations required for
convergence for different values of l .
k Bus voltages (per unit) after 1st iteration No of iterations
V2 V3 V4 V5 for convergence
1 0.9927 2.6 0.9883 2.83 0.9968 3.48 1.02 0.89 28
2 0.9874 5.22 0.9766 8.04 0.9918 14.02 1.02 4.39 860
1.8 0.9883 4.7 0.9785 6.8 0.9903 11.12 1.02 3.52 54
1.6 0.9893 4.17 0.9807 5.67 0.9909 8.65 1.02 2.74 24
1.4 0.9903 3.64 0.9831 4.62 0.9926 6.57 1.02 2.05 14
1.2 0.9915 3.11 0.9857 3.68 0.9947 4.87 1.02 1.43 19
Section V: Solution of a Set of Nonlinear Equations by Newton-Raphson Method
In this section we shall discuss the solution of a set of nonlinear equations through Newton-Raphson
method. Let us consider that we have a set of n nonlinear equations of a total number of n variables
x1 , x2 , ... , xn. Let these equations be given by
(4.22)
Let us assume
that the initial estimates of the n variables are x1(0) , x2(0) , ... , xn(0) . Let us add corrections Δx1(0) ,
Δx2(0) , ... , Δxn(0) to these variables such that we get the correct solution of these variables defined by
(4.24)
The functions in (4.23) then can be written in terms of the variables given in (4.24) as
(4.25)
We can then expand the above equation in Taylor 's series around the nominal values of x1(0) , x2(0) ,
... , xn(0) . Neglecting the second and higher order terms of the series, the expansion of gk , k = 1, ... ,
n is given as
(4.26)
(4.27)
The square matrix of partial derivatives is called the Jacobian matrix J with J (1) indicating that the
matrix is evaluated for the initial values of x2(0) , ... , xn(0) . We can then write the solution of (4.27) as
(4.28)
, k= 1, ....n
Since the Taylor 's series is truncated by neglecting the 2 nd and higher order terms, we cannot expect
to find the correct solution at the end of first iteration. We shall then have
(4.29)
These are then used to find J (1) and Δgk (1) , k = 1, ... , n . We can then find Δx2(1) , ... , Δxn(1) from an
equation like (4.28) and subsequently calculate x2(1) , ... , xn(1). The process continues till Δgk , k = 1,
... , n becomes less than a small quantity.
(4.30)
(4.31)
It can be seen that the size of the Jacobian matrix is ( n + np − 1) x ( n + np −1). For example for the 5-
bus problem of Fig. 4.1 this matrix will be of the size (7 x 7). The dimensions of the submatrices are
as follows:
J11: (n 1) (n 1), J12: (n 1) np, J21: np (n 1) and J22: np np
(4.33)
Load Flow
Algorithm
(4.34)
The Newton-
Raphson
procedure is as
follows:
Step-1: Choose
the initial values
of the voltage
magnitudes |V|
(0)
of all np load
buses and n − 1
angles δ (0) of the voltages of all the buses except the slack bus.
Step-2: Use the estimated |V|(0) and δ (0) to calculate a total n − 1 number of injected real power
Pcalc(0) and equal number of real power mismatch ΔP (0) .
Step-3: Use the estimated |V| (0) and δ (0) to calculate a total np number of injected reactive power
Qcalc(0) and equal number of reactive power mismatch ΔQ (0) .
Step-3: Use the estimated |V| (0) and δ (0) to formulate the Jacobian matrix J (0) .
Step-4: Solve (4.30) for δ (0) and Δ |V| (0) ÷ |V| (0).
Step-5 : Obtain the updates from
(4.36)
(4.37)
Step-6: Check if all the mismatches are below a small number. Terminate the process if yes.
Otherwise go back to step-1 to start the next iteration with the updates given by (4.36) and (4.37).
(4.38)
(4.39)
A. Formation of J11
Let us define J11 as
(4.40)
It can be seen from (4.32) that Lik's are the partial derivatives of Pi with respect to δk. The derivative Pi
(4.38) with respect to k for i ≠ k is given by
(4.41)
(4.42)
B. Formation of J21
Let us define J21 as
(4.43)
From (4.34) it is evident that the elements of J21 are the partial derivative of Q with respect to δ . From
(4.39) we can write
(4.44)
(4.45)
The last equality of (4.45) is evident from (4.38).
C. Formation of J12
(4.46)
As evident from (4.33), the elements of J21 involve the derivatives of real power P with respect to
magnitude of bus voltage |V| . For i ≠ k , we can write from (4.38)
(4.47)
For i = k we have
(4.48)
Formation of J22
For the formation of J22 let us define
(4.49)
For i ≠ k we can
write from (4.39)
(4.50)
(4.51)
We therefore see that once the submatrices J11 and J21 are computed, the formation of the
submatrices J12 and J22 is fairly straightforward. For large system this will result in considerable
saving in the computation time.
Solution of Newton-Raphson Load Flow
The Newton-Raphson load flow program is tested on the system of Fig. 4.1 with the system data and
initial conditions given in Tables 4.1 to 4.3. From (4.41) we can write
In a similar way the rest of the components of the matrix J11(0) are calculated. This matrix is given by
For forming the off diagonal elements of J21 we note from (4.44) that
Similarly the rest of the elements of the matrix J21 are calculated. This matrix is then given as
For calculating the off diagonal elements of the matrix J12 we note from (4.47) that they are negative
of the off diagonal elements of J21 . However the size of J21 is (3 X 4) while the size of J12 is (4 X 3).
Therefore to avoid this discrepancy we first compute a matrix M that is given by
The elements of the above matrix are computed in accordance with (4.44) and (4.45). We can then
define
Furthermore the diagonal elements of J12 are overwritten in accordance with (4.48). This matrix is
then given by
Finally it can be noticed from (4.50) that J22 = J11 (1:3, 1:3). However the diagonal elements of J22 are
then overwritten in accordance with (4.51). This gives the following matrix
From the initial conditions the power and reactive power are computed as
Then the updates at the end of the first iteration are given as
The load flow converges in 7 iterations when all the power and reactive power mismatches are below
10−6 .
Section VII: Load Flow Results
In this section we shall discuss the results of the load flow. It is to be noted here that both Gauss-
Seidel and Newton-Raphson methods yielded the same result. However the Newton-Raphson
method converged faster than the Gauss-Seidel method. The bus voltage magnitudes, angles of
each bus along with power generated and consumed at each bus are given in Table 4.4. It can be
seen from this table that the total power generated is 174.6 MW whereas the total load is 171 MW.
This indicates that there is a line loss of about 3.6 MW for all the lines put together. It is to be noted
that the real and reactive power of the slack bus and the reactive power of the P-V bus are computed
from (4.6) and (4.7) after the convergence of the load flow.
Table 4.4 Bus voltages, power generated and load after load flow convergence.
Bus Bus voltage Power generated Load
no. Magnitude (pu) Angle (deg) P (MW) Q (MVAr) P (MW) P (MVAr)
1 1.05 0 126.60 57.11 0 0
2 0.9826 5.0124 0 0 96 62
3 0.9777 7.1322 0 0 35 14
4 0.9876 7.3705 0 0 16 8
5 1.02 3.2014 48 15.59 24 11
The current flowing between the buses i and k can be written as
(4.52)
(4.53)
(4.54)
(4.55)
The real power flow over different lines is listed in Table 4.5. This table also gives the I2 R loss along
various segments. It can be seen that all the losses add up to 3.6 MW, which is the net difference
between power generation and load. Finally we can compute the line I2X drops in a similar fashion.
This drop is given by
(4.56)
Consider the line segment 1-2. The voltage of bus-1 is V1 = 1.05 < 0° per unit while that of bus-2 is V2
= 0.9826 < − 5.0124° per unit. From (4.52) we then have
per unit
Therefore the complex power dispatched from bus-1 is
where the negative signal indicates the power is leaving bus-1. The complex power received at bus-2
is
MW
Therefore out of a total amount of 101.0395 MW of real power is dispatched from bus-1 over the line
segment 1-2, 98.6494 MW reaches bus-2. This indicates that the drop in the line segment is 2.3901
MW. Note that
MW
where R12 is resistance of the line segment 1-2. Therefore we can also use this method to calculate
the line loss.
Now the reactive drop in the line segment 1-2 is
MV Ar
We also get this quantity by subtracting the reactive power absorbed by bus-2 from that supplied by
bus-1. The above calculation however does not include the line charging. Note that since the line is
modeled by an equivalent- p , the voltage across the shunt capacitor is the bus voltage to which the
shunt capacitor is connected. Therefore the current I 12 flowing through line segment is not the
current leaving bus-1 or entering bus-2 - it is the current flowing in between the two charging
capacitors. Since the shunt branches are purely reactive, the real power flow does not get affected by
the charging capacitors. Each charging capacitor is assumed to inject a reactive power that is the
product of the half line charging admittance and square of the magnitude of the voltage of that at bus.
The half line charging admittance of this line is 0.03. Therefore line charging capacitor will inject
MV Ar
at bus-1. Similarly the reactive injected at bus-2 will be
MV Ar
The power flow through the line segments 1-2 and 1-5 are shown in Fig. 4.2.
(a)
(b)
Fig. 4.2 Real and reactive power flow through (a) line segment 1-2 and (b) line segment 1-5. The thin
lines indicate reactive power flow while the thick lines indicate real power flow.
Section VIII: Load Flow Programs In Matlab
The load flow programs are developed in MATLAB. Altogether there are 4 mfiles that are attached
with this chapter. The program listings and descriptions of these mfiles are given below. It must
however be emphasized that these are not general purpose programs and are written only for the
examples of this chapter.
Forming Ybus Matrix
Gauss- Seidel Load Flow
Solving Nonlinear Equations using Newton- Raphson
Newton - Raphson Load Flow
Forming Ybus Matrix
This is a function that can be called by various programs. The function can be invoked by the
statement
[yb,ych]=ybus;
where 'yb' and 'ych' are respectively the Ybus matrix and a matrix containing the line charging
admittances. It is assumed that the system data of Table 4.1 are given in matrix form and the matrix
that contains line impedances is 'zz', while 'ych' contains the line charging information. This program
is stored in the file ybus.m. The program listing is given below.
(5.1)
Rs./h
The operating cost given by the above quadratic equation is obtained by approximating the power in
MW versus the cost in Rupees curve. The incremental operating cost of each unit is then computed
as
(5.2)
Rs./MWh
Let us now assume that only two units having different incremental costs supply a load. There will be
a reduction in cost if some amount of load is transferred from the unit with higher incremental cost to
the unit with lower incremental cost. In this fashion, the load is transferred from the less efficient unit
to the more efficient unit thereby reducing the total operation cost. The load transfer will continue till
the incremental costs of both the units are same. This will be optimum point of operation for both the
units.
The above principle can be extended to plants with a total of N number of units. The total fuel cost will
then be the summation of the individual fuel cost fi , i = 1, ... , N of each unit, i.e.,
(5.3)
Let us denote
that the total power that the plant is required to supply by PT , such that
(5.4)
(5.6)
Multiplying (5.6)
by λ and subtracting from (5.5) we get
(5.7)
The equality in (5.7) is satisfied when each individual term given in brackets is zero. This gives us
(5.8)
Also the partial derivative becomes a full derivative since only the term fi of fT varies with Pi, i = 1, ...,
N . We then have
Generating Limits
It is not always necessary that all the units of a plant are available to share a load. Some of the units
may be taken off due to scheduled maintenance. Also it is not necessary that the less efficient units
are switched off during off peak hours. There is a certain amount of shut down and start up costs
associated with shutting down a unit during the off peak hours and servicing it back on-line during the
peak hours. To complicate the problem further, it may take about eight hours or more to restore the
boiler of a unit and synchronizing the unit with the bus. To meet the sudden change in the power
demand, it may therefore be necessary to keep more units than it necessary to meet the load
demand during that time. This safety margin in generation is called spinning reserve . The optimal
load dispatch problem must then incorporate this startup and shut down cost for without endangering
the system security.
The power
generation limit
of each unit is (5.10)
then given by
the inequality constraints
The maximum limit Pmax is the upper limit of power generation capacity of each unit. On the other
hand, the lower limit Pmin pertains to the thermal consideration of operating a boiler in a thermal or
nuclear generating station. An operational unit must produce a minimum amount of power such that
the boiler thermal components are stabilized at the minimum design operating temperature.
Example 5.2
let us consider a generating station that contains a total number of three generating units. The fuel
costs of these units are given by
Rs./h
Rs./h
Rs./h
The generation limits of the units are
The total load that these units supply varies between 90 MW and 1250 MW. Assuming that all the
three units are operational all the time, we have to compute the economic operating settings as the
load changes.
The incremental costs of these units are
Rs./MWh
Rs./MWh
Rs./MWh
Rs./MWh
Rs./MWh
Rs./MWh
Since units 1 and 3 have higher incremental cost, they must therefore operate at 30 MW each. The
incremental cost during this time will be due to unit-2 and will be equal to 26 Rs./MWh. With the
generation of units 1 and 3 remaining constant, the generation of unit-2 is increased till its incremental
cost is equal to that of unit-1, i.e., 34 Rs./MWh. This is achieved when P2 is equal to 41.4286 MW, at
a total power of 101.4286 MW.
An increase in the total load beyond 101.4286 MW is shared between units 1 and 2, till their
incremental costs are equal to that of unit-3, i.e., 43.5 Rs./MWh. This point is reached when P1 =
41.875 MW and P2 = 55 MW. The total load that can be supplied at that point is equal to 126.875.
From this point onwards the load is shared between the three units in such a way that the incremental
costs of all the units are same. For example for a total load of 200 MW, from (5.4) and (5.9) we have
Solving the above three equations we get P1 = 66.37 MW, P2 = 80 MW and P3 = 50.63 MW and an
incremental cost ( λ ) of 63.1 Rs./MWh. In a similar way the economic dispatch for various other load
settings are computed. The load distribution and the incremental costs are listed in Table 5.1 for
various total power conditions.
Table 5.1 Load distribution and incremental cost for the units of Example 5.1
PT (MW) P1 (MW) P2 (MW) P3 (MW) λ (Rs./MWh)
90 30 30 30 26
101.4286 30 41.4286 30 34
120 38.67 51.33 30 40.93
126.875 41.875 55 30 43.5
150 49.62 63.85 36.53 49.7
200 66.37 83 50.63 63.1
300 99.87 121.28 78.85 89.9
400 133.38 159.57 107.05 116.7
500 166.88 197.86 135.26 143.5
600 200.38 236.15 163.47 170.3
700 233.88 274.43 191.69 197.1
800 267.38 312.72 219.9 223.9
906.6964 303.125 353.5714 250 252.5
1000 346.67 403.33 250 287.33
1100 393.33 456.67 250 324.67
1181.25 431.25 500 250 355
1200 450 500 250 370
1250 500 500 250 410
At a total load of 906.6964, unit-3 reaches its maximum load of 250 MW. From this point onwards
then, the generation of this unit is kept fixed and the economic dispatch problem involves the other
two units. For example for a total load of 1000 MW, we get the following two equations from (5.4) and
(5.9)
Solving which we get P1 = 346.67 MW and P2 = 403.33 MW and an incremental cost of 287.33
Rs./MWh. Furthermore, unit-2 reaches its peak output at a total load of 1181.25. Therefore any
further increase in the total load must be supplied by unit-1 and the incremental cost will only be
borne by this unit. The power distribution curve is shown in Fig. 5.1.
For a particular time of a year, the total load in a day varies as shown in Fig. 5.2. Also an additional
cost of Rs. 5,000 is incurred by switching of a unit during the off peak hours and switching it back on
during the during the peak hours. We have to determine whether it is economical to have both units
operational all the time.
Fig. 5.2 Hourly distribution of load for the units of Example 5.2.
Since both the units have identical fuel costs, we can switch of any one of the two units during the off
peak hour. Therefore the cost of running one unit from midnight to 9 in the morning while delivering
200 MW is
Rs.
Adding the cost of Rs. 5,000 for decommissioning and commissioning the other unit after nine hours,
the total cost becomes Rs. 167,225.
On the other hand, if both the units operate all through the off peak hours sharing power equally, then
we get a total cost of
Rs.
which is significantly less that the cost of running one unit alone.
Economic Sharing of Loads between Different Plants
So far we have considered the economic operation of a single plant in which we have discussed how
a particular amount of load is shared between the different units of a plant. In this problem we did not
have to consider the transmission line losses and assumed that the losses were a part of the load
supplied. However if now consider how a load is distributed between the different plants that are
joined by transmission lines, then the line losses have to be explicitly included in the economic
dispatch problem. In this section we shall discuss this problem.
When the transmission losses are included in the economic dispatch problem, we can modify (5.4) as
(5.11)
where PLOSS is
the total line loss. Since PT is assumed to be constant, we have
(5.12)
In the above equation dPLOSS includes the power loss due to every generator, i.e.
(5.13)
Also minimum generation cost implies dfT = 0 as given in (5.5). Multiplying both (5.12) and (5.13) by λ
and combining we get
(5.14)
(5.15)
(5.16)
Again since
(5.17)
(5.18)
Example 5.4
Consider an area with N number of units. The power generated are defined by the vector
(5.19)
The elements Bij of the matrix B are called the loss coefficients . These coefficients are not constant
but vary with plant loading. However for the simplified calculation of the penalty factor Li these
coefficients are often assumed to be constant.
When the incremental cost equations are linear, we can use analytical equations to find out the
economic settings. However in practice, the incremental costs are given by nonlinear equations that
may even contain nonlinearities. In that case iterative solutions are required to find the optimal
generator settings.
Section II: Automatic Generation Control
Load Frequency Control
Automatic Generation Control
Electric power is generated by converting mechanical energy into electrical energy. The rotor mass,
which contains turbine and generator units, stores kinetic energy due to its rotation. This stored
kinetic energy accounts for sudden increase in the load. Let us denote the mechanical torque input by
Tm and the output electrical torque by Te . Neglecting the rotational losses, a generator unit is said to
be operating in the steady state at a constant speed when the difference between these two elements
of torque is zero. In this case we say that the accelerating torque
(5.20)
is zero.
When the electric power demand increases suddenly, the electric torque increases. However, without
any feedback mechanism to alter the mechanical torque, Tm remains constant. Therefore the
accelerating torque given by (5.20) becomes negative causing a deceleration of the rotor mass. As
the rotor decelerates, kinetic energy is released to supply the increase in the load. Also note that
during this time, the system frequency, which is proportional to the rotor speed, also decreases. We
can thus infer that any deviation in the frequency for its nominal value of 50 or 60 Hz is indicative of
the imbalance between Tm and Te. The frequency drops when Tm < Te and rises when Tm > Te .
The steady state power-frequency relation is shown in Fig. 5.3. In this figure the slope of the ΔPref line
is negative and
is given by
(5.21)
where R is called the regulating constant . From this figure we can write the steady state power
frequency relation as
(5.22)
Suppose an interconnected power system contains N turbine-generator units. Then the steady-state
power-frequency relation is given by the summation of (5.22) for each of these units as
(5.23)
In the above equation, ΔPm is the total change in turbine-generator mechanical power and ΔPref is the
total change in the reference power settings in the power system. Also note that since all the
generators are supposed to work in synchronism, the change is frequency of each of the units is the
same and is denoted by Δf. Then the frequency response characteristics is defined as
(5.24)
Example 5.5
Consider an interconnected 50-Hz power system that contains four turbine-generator units rated 750
MW, 500 MW, 220 MW and 110 MW. The regulating constant of each unit is 0.05 per unit based on
its own rating. Each unit is operating on 75% of its own rating when the load is suddenly dropped by
250 MW. We shall choose a common base of 500 MW and calculate the rise in frequency and drop in
the mechanical power output of each unit.
The first step in the process is to convert the regulating constant, which is given in per unit in the base
of each generator, to a common base. This is given as
(5.26)
Therefore
p.u.
We can therefore calculate the total change in the frequency from (5.25) while assuming ΔPref = 0,
i.e., for no change in the reference setting. Since the per unit change in load - 250/500 = - 0.5 with the
negative sign accounting for load reduction, the change in frequency is given by
Then the change in the mechanical power of each unit is calculated from (5.22) as
It is to be noted that once ΔPm2 is calculated to be - 79.11 MW, we can also calculate the changes in
the mechanical power of the other turbine-generators units as
This implies that each turbine-generator unit shares the load change in accordance with its own
rating.
Load Frequency Control
Modern day power systems are divided into various areas. For example in India , there are five
regional grids, e.g., Eastern Region, Western Region etc. Each of these areas is generally
interconnected to its neighboring areas. The transmission lines that connect an area to its
neighboring area are called tie-lines . Power sharing between two areas occurs through these tie-
lines. Load frequency control, as the name signifies, regulates the power flow between different areas
while holding the frequency constant.
As we have in Example 5.5 that the system frequency rises when the load decreases if ΔPref is kept
at zero. Similarly the frequency may drop if the load increases. However it is desirable to maintain the
frequency constant such that Δf=0 . The power flow through different tie-lines are scheduled - for
example, area- i may export a pre-specified amount of power to area- j while importing another pre-
specified amount of power from area- k . However it is expected that to fulfill this obligation, area- i
absorbs its own load change, i.e., increase generation to supply extra load in the area or decrease
generation when the load demand in the area has reduced. While doing this area- i must however
maintain its obligation to areas j and k as far as importing and exporting power is concerned. A
conceptual diagram of the interconnected areas is shown in Fig. 5.4.
where Ptie and Psch are tie-line power and scheduled power through tie-line respectively and the
constant Bf is called the frequency bias constant .
The change in the reference of the power setting ΔPref, i , of the area- i is then obtained by the
feedback of the ACE through an integral controller of the form
(5.28)
where Ki is the integral gain. The ACE is negative if the net power flow out of an area is low or if the
frequency has dropped or both. In this case the generation must be increased. This can be achieved
by increasing ΔPref, i . This negative sign accounts for this inverse relation between ΔPref, i and ACE.
The tie-line power flow and frequency of each area are monitored in its control center. Once the ACE
is computed and ΔPref, i is obtained from (5.28), commands are given to various turbine-generator
controls to adjust their reference power settings.
Example 5.6
Consider a two-area power system in which area-1 generates a total of 2500 MW, while area-2
generates 2000 MW. Area-1 supplies 200 MW to area-2 through the inter-tie lines connected
between the two areas. The bias constant of area-1 ( β1 ) is 875 MW/Hz and that of area-2 ( β2 ) is
700 MW/Hz. With the two areas operating in the steady state, the load of area-2 suddenly increases
by 100 MW. It is desirable that area-2 absorbs its own load change while not allowing the frequency
to drift.
The area control errors of the two areas are given by
and
Since the net change in the power flow through tie-lines connecting these two areas must be zero, we
have
Also as the transients die out, the drift in the frequency of both these areas is assumed to be
constant, i.e.,
If the load frequency controller (5.28) is able to set the power reference of area-2 properly, the ACE of
the two areas will be zero, i.e., ACE1 = ACE2 = 0. Then we have
This will imply that Δf will be equal to zero while maintaining ΔPtie1 =ΔPtie2 = 0. This signifies that area-
2 picks up the additional load in the steady state.
Coordination Between LFC And Economic Dispatch
Both the load frequency control and the economic dispatch issue commands to change the power
setting of each turbine-governor unit. At a first glance it may seem that these two commands can be
conflicting. This however is not true. A typical automatic generation control strategy is shown in Fig.
5.5 in which both the objective are coordinated. First we compute the area control error. A share of
this ACE, proportional to αi , is allocated to each of the turbine-generator unit of an area. Also the
share of unit- i , γi X Σ( PDK - Pk ), for the deviation of total generation from actual generation is
computed. Also the error between the economic power setting and actual power setting of unit- i is
computed. All these signals are then combined and passed through a proportional gain Ki to obtain
the turbine-governor control signal.
(6.1)
(6.2)
Since the initial current i (0) = 0 and since νs ( τ ) = Vdc for 0 £ t < ¥ , we can rewrite the above
equation as
(6.3)
(6.4)
(6.6)
(6.7)
A
(6.8)
A
,
The system response for V m = 100 V and α = 45° is shown in Fig. 6.3. In this figure both iac and i dc
are also shown. It can be seen that iac is the steady state waveform of the circuit, while idc dies out
once the initial transient phase is over. Fig. 6.4 shows the response of the current for different values
of a . Since the current is almost inductive, it can be seen that the transient is minimum when α = 90°
, i.e., the circuit is switched on almost at the zero-crossing of the current. On the other hand, the
transient is maximum when α = 0° , i.e., almost at the peak of the current.
Fig 6.3 Transient in current and its ac and dc components at the instant of switch closing
A
This means that the pre-fault current has a peak value of 15.97 A.
Fig. 6.5 A single-phase circuit in which a source supplies a load through a source impedance.
Fig 6.6 The current waveform of the circuit of Fig 6.5 before and after the closing of the switch S
Once the fault occurs and the system is allowed to reach the steady state, the current phasor is given
by
This current has a peak value of 95.28 A. However it can be seen that the current rises suddenly and
the first peak following the fault is 124 A which is about 30% higher than the post-fault steady-state
value. Also note that the peak value of the current will vary with the instant of the occurrence of the
fault. However the peak value of the current is nearly 8 times the pre-fault current value in this case.
In general, depending on the ratio of source and load impedances, the faulted current may shoot up
anywhere between 10 and 20 times the pre-fault current.
Short Circuit in an Unloaded Synchronous Generator
Fig. 6.7 shows a typical response of the armature current when a three-phase symmetrical short
circuit occurs at the terminals of an unloaded synchronous generator.
Fig. 6.7 Armature current of a synchronous generator as a short circuit occurs at its terminals.
It is assumed that there is no dc offset in the armature current. The magnitude of the current
decreases exponentially from a high initial value. The instantaneous expression for the fault current is
given by
(6.9)
where Vt is the
magnitude of the terminal voltage, α is its phase angle and
(6.10)
which is called the subtransient fault current. The duration of the subtransient current is dictated by
the time constant Td . As the time progresses and Td < t < Td , the first exponential term of (6.9)
will start decaying and will eventually vanish. However since t is still nearly equal to zero, we have the
following rms value of the current
(6.11)
This is called the transient fault current. Now as the time progress further and the second
exponential term also decays, we get the following rms value of the current for the sinusoidal steady
state
(6.12)
In addition to the ac, the fault currents will also contain the dc offset. Note that a symmetrical fault
occurs when three different phases are in three different locations in the ac cycle. Therefore the dc
offsets in the three phases are different. The maximum value of the dc offset is given by
(6.13)
per unit
Also the base impedance in the circuit of the transmission line is
per unit
The impedance diagram for the circuit is shown in Fig. 6.9 in which the switch S indicates the fault.
per unit
per unit
Hence the subtransient fault currents fed by the motor and the generator are
per unit
per unit
and the total current flowing to the fault is
per unit
Note that the base current in the circuit of the motor is
A
Therefore while the load current was 1603.8 A, the fault current is 7124.7 A.
Example 6.2
We shall now solve the above problem differently. The Thevenin impedance at the circuit between the
terminals A and B of the circuit of Fig. 6.9 is the parallel combination of the impedances j 0.4 and j
0.5148. This is then given as
per unit
Since voltage at the motor terminals before the fault is 1.0 per unit, the fault current is
per unit
If we neglect the pre-fault current flowing through the circuit, then fault current fed by the motor and
the generator can be determined using the current divider principle, i.e.,
per unit
per unit
If, on the other hand, the pre-fault current is not neglected, then the fault current supplied by the
motor and the generator are
per unit
per unit
Calculation of Fault Current Using Z bus Matrix
Consider the circuit of Fig. 3.3 which is redrawn as shown in Fig. 6.10.
Fig. 6.10 Network depicting a symmetrical fault at bus-4.
We assume that a symmetrical fault has occurred in bus-4 such that it is now connected to the
reference bus. Let us assume that the pre-fault voltage at this bus is Vf . To denote that bus-4 is short
circuit, we add two voltage sources Vf and - Vf together in series between bus-4 and the reference
bus. Also note that the subtransient fault current If flows from bus-4 to the reference bus. This
implies that a current that is equal to - If is injected into bus-4. This current, which is due to the
source - Vf will flow through the various branches of the network and will cause a change in the bus
voltages. Assuming that the two sources and Vf are short circuited. Then - Vf is the only source left in
the network that injects a current - If into bus-4. The voltages of the different nodes that are caused
by the voltage - Vf and the current - If are then given by
(6.14)
where the prefix Δ indicates the changes in the bus voltages due to the current - If .
From the fourth row of (6.14) we can write
(6.15)
(6.16)
We further assume that the system is unloaded before the fault occurs and that the magnitude and
phase angles of all the generator internal emfs are the same. Then there will be no current circulating
anywhere in the network and the bus voltages of all the nodes before the fault will be same and equal
to Vf . Then the new altered bus voltages due to the fault will be given from (6.16) by
Example 6.3
Let us consider the same system as discussed in Example 3.1 except that we assume that the
internal voltages of both the generators are equal to 1.0 < 0° . Then the current injected in both bus-1
and 2 will be given by 1.0/ j 0.25 = - j 4.0 per unit. We therefore get the pre-fault bus voltages using
the Zbus matrix given in Example 3.1 as
Now the altered bus voltages for a symmetrical fault in bus-4 are given from (6.17) as
per unit
per unit
per unit
per unit
Also since the Thevenin impedance looking into the network at bus-4 is Z44 (see Section 3.4), the
subtransient fault current flowing from bus-4 is
pu
Section IV: Circuit Breaker Selection
A typical circuit breaker operating time is given in Fig. 6.11. Once the fault occurs, the protective
devices get activated. A certain amount of time elapses before the protective relays determine that
there is overcurrent in the circuit and initiate trip command. This time is called the detection time.
The contacts of the circuit breakers are held together by spring mechanism and, with the trip
command, the spring mechanism releases the contacts. When two current carrying contacts part, a
voltage instantly appears at the contacts and a large voltage gradient appears in the medium
between the two contacts. This voltage gradient ionizes the medium thereby maintaining the flow of
current. This current generates extreme heat and light that is called electric arc. Different
mechanisms are used for elongating the arc such that it can be cooled and extinguished. Therefore
the circuit breaker has to withstand fault current from the instant of initiation of the fault to the time the
arc is extinguished.
Two factors are of utmost importance for the selection of circuit breakers. These are:
The maximum instantaneous current that a breaker must withstand and
The total current when the breaker contacts part.
In this chapter we have discussed the calculation of symmetrical subtransient fault current in a
network. However the instantaneous current following a fault will also contain the dc component. In a
high power circuit breaker selection, the subtransient current is multiplied by a factor of 1.6 to
determine the rms value of the current the circuit breaker must withstand. This current is called the
momentary current . The interrupting current of a circuit breaker is lower than the momentary
current and will depend upon the speed of the circuit breaker. The interrupting current may be
asymmetrical since some dc component may still continue to decay.
Breakers are usually classified by their nominal voltage, continuous current rating, rated maximum
voltage, K -factor which is the voltage range factor, rated short circuit current at maximum voltage and
operating time. The K -factor is the ratio of rated maximum voltage to the lower limit of the range of
the operating voltage. The maximum symmetrical interrupting current of a circuit breaker is given by K
times the rated short circuit current.
Overview
An unbalanced three-phase system can be resolved into three balanced systems in the sinusoidal
steady state. This method of resolving an unbalanced system into three balanced phasor system has
been proposed by C. L. Fortescue. This method is called resolving symmetrical components of the
original phasors or simply symmetrical components.
In this chapter we shall discuss symmetrical components transformation and then will present how
unbalanced components like Y- or Δ -connected loads, transformers, generators and transmission
lines can be resolved into symmetrical components. We can then combine all these components
together to form what are called sequence networks .
Section I: Symmetrical Components
Symmetrical Component Transformation
Real and Reactive Power
Orthogonal Transformation
Symmetrical Components
A system of three unbalanced phasors can be resolved in the following three symmetrical
components:
Positive Sequence: A balanced three-phase system with the same phase sequence as the
original sequence.
Negative sequence: A balanced three-phase system with the opposite phase sequence as the
original sequence.
Zero Sequence: Three phasors that are equal in magnitude and phase.
Fig. 7.1 depicts a set of three unbalanced phasors that are resolved into the three sequence
components mentioned above. In this the original set of three phasors are denoted by Va , Vb and Vc ,
while their positive, negative and zero sequence components are denoted by the subscripts 1, 2 and
0 respectively. This implies that the positive, negative and zero sequence components of phase-a are
denoted by Va1 , Va2 and Va0 respectively. Note that just like the voltage phasors given in Fig. 7.1 we
can also resolve three unbalanced current phasors into three symmetrical components.
Fig. 7.1 Representation of (a) an unbalanced network, its (b) positive sequence, (c) negative
sequence and (d) zero sequence.
Symmetrical Component Transformation
Before we discuss the symmetrical component transformation, let us first define the α -operator. This
has been given in (1.34) and is reproduced below.
(7.1)
Note that for the above operator the following relations hold
(7.2)
(7.3)
(7.4)
(7.5)
Finally from Fig. 7.1 (d) we get
(7.6)
(7.7)
(7.8)
(7.9)
Therefore,
(7.10)
(7.11)
(7.13)
The original phasor components can be obtained from the inverse symmetrical component
transformation, i.e.,
(7.14)
Finally, if we define a set of unbalanced current phasors as Iabc and their symmetrical components as
Ia012 , we can then define
(7.15)
Example 7.1
Let us consider a set of balanced voltages given in per unit by
These imply
Example 7.2
All the quantities given in this example are in per unit. Let us now consider the following set of three
unbalanced voltages
Therefore we have
(7.16)
where I* is the complex conjugate of the vector I . Now from (7.10) and (7.15) we get
(7.17)
From (7.11) we get
Therefore from
(7.17) we get
(7.18)
We then find that the complex power is three times the summation of the complex power of the three
phase sequences.
Example 7.3
Let us consider the voltages given in Example 7.2. Let us further assume that these voltages are line-
to-neutral voltages and they supply a balanced Y-connected load whose per phase impedance is ZY
= 0.2 + j 0.8 per unit. Then the per unit currents in the three phases are
pu
pu
pu
Then the real and reactive power consumed by the load is given by
pu
From the results given in Example 7.2 and from the above values we can compute the zero sequence
complex power as
pu
The positive sequence complex power is
pu
Finally the negative sequence complex power is
pu
Adding the three complex powers together we get the total complex power consumed by the load as
pu
Orthogonal Transformation
Instead of the transformation matrix given in (7.13), let us instead use the transformation matrix
(7.19)
We then have
(7.20)
Note from (7.19) and (7.20) that C -1 = ( CT )* . We can therefore state C( CT )* = I3 , where I3 is (3 × 3)
identity matrix. Therefore the transformation matrices given in (7.19) and (7.20) are orthogonal. Now
since
we can write from (7.17)
(7.21)
We shall now discuss how different elements of a power system are represented in terms of their
sequence components. In fact we shall show that each element is represented by three equivalent
circuits, one for each symmetrical component sequence.
Section II: Sequence Circuits for Loads
In this section we shall construct sequence circuits for both Y and Δ -connected loads separately.
Sequence Circuit for a Y-Connected Load
Sequence Circuit for a Δ-Connected Load
Therefore there will not be any positive or negative sequence current flowing out of the neutral point.
(7.23)
Now
(7.24)
We can write similar expression for the other two phases. We can therefore write
(7.25)
Pre-multiplying both sides of the above equation by the matrix C and using (7.8) we get
Now since
(7.26)
(7.27)
We then find that the zero, positive and negative sequence voltages only depend on their respective
sequence component currents. The sequence component equivalent circuits are shown in Fig. 7.3.
While the positive and negative sequence impedances are both equal to ZY , the zero sequence
impedance is equal to
(7.28)
If the neutral is grounded directly (i.e., Zn = 0), then Z0 = ZY . On the other hand, if the neutral is kept
floating (i.e., Zn = ∞ ), then there will not be any zero sequence current flowing in the circuit at all.
Fig. 7.3 Sequence circuits of Y-connected load: (a) positive, (b) negative and (c) zero sequence.
Sequence Circuit for a Δ -Connected Load
Consider the balanced Δ -connected load shown in Fig. 7.4 in which the load in each phase is
denoted by ZΔ . The line-to-line voltages are given by
(7.29)
Denoting the zero sequence component Vab , Vbc and Vca as Vab0 and that of Iab , Ibc and Ica as Iab0 we
can rewrite (7.30) as
(7.31)
Again since
We find from (7.31) Vab0 = Iab0 = 0. Hence a Δ -connected load with no mutual coupling has not any
zero sequence circulating current. Note that the positive and negative sequence impedance for this
load will be equal to ZΔ .
Example 7.4
Consider the circuit shown in Fig. 7.5 in which a Δ -connected load is connected in parallel with a Y-
connected load. The neutral point of the Y-connected load is grounded through an impedance.
Applying Kirchoff's current law at the point P in the circuit we get
Now since
we get
Separating the three components, we can write from the above equation
Suppose now if we convert the Δ -connected load into an equivalent Y, then the composite load will
be a parallel combination of two Y-connected circuits - one with an impedance of ZY and the other
with an impedance of ZΔ /3. Therefore the positive and the negative sequence impedances are given
by the parallel combination of these two impedances. The positive and negative sequence impedance
is then given by
This implies that Ia0 = Iay0 and hence Vn = 3Zn Ia0 . We can then rewrite the zero sequence current
expression as
It can be seen that the ZΔ term is absent from the zero sequence impedance.
Section III: Sequence Circuits for Synchronous Generator
The three-phase equivalent circuit of a synchronous generator is shown in Fig. 1.16. This is
redrawn in Fig. 7.6 with the neutral point grounded through a reactor with impedance Zn . The
neutral current is then given by
(7.32)
Fig. 7.6 Equivalent circuit of a synchronous generator with grounded neutral.
The derivation of Section 1.3 assumes balanced operation which implies Ia + Ib + Ic = 0. As per
(7.32) this assumption is not valid any more. Therefore with respect to this figure we can write for
phase-a voltage as
(7.33)
Similar expressions can also be written for the other two phases. We therefore have
(7.34)
(7.35)
Since the synchronous generator is operated to supply only balanced voltages we can assume that
Ean0 = Ean2 = 0 and Ean1 = Ean . We can therefore modify (7.35) as
(7.36)
(7.39)
Furthermore we have seen for a Y-connected load that Va1 = V an1 , Va2 = Van2 since the neutral
current does not affect these voltages. However Va0 = Van0 + Vn . Also we know that Vn = - 3ZnIa0 .
We can therefore rewrite (7.37) as
(7.40)
The sequence diagrams for a synchronous generator are shown in Fig. 7.7.
Fig. 7.7 Sequence circuits of synchronous generator: (a) positive, (b) negative and (c) zero
sequence.
Since the transmission line is assumed to be symmetric, we further assume that the mutual
inductances between the conductors are the same and so are the mutual inductances between the
conductors and the neutral, i.e
The directions of the currents flowing through the lines are indicated in Fig. 7.8 and the voltages
between the different conductors are as indicated.
(7.41)
Again
(7.42)
(7.43)
Substituting (7.42) and (7.43) in (7.41) we get
(7.44)
Since the neutral provides a return path for the currents Ia , Ib and Ic , we can write
(7.45)
Therefore substituting (7.45) in (7.44) we get the following equation for phase-a of the circuit
(7.46)
Denoting
(7.47)
Since (7.47) does not explicitly include the neutral conductor we can define the voltage drop across
the phase-a conductor as
(7.48)
(7.49)
Similar expression can also be written for the other two phases. We therefore get
(7.50)
(7.51)
Now
Hence
Therefore from (7.51) we get
(7.52)
The positive, negative and zero sequence equivalent circuits of the transmission line are shown in
Fig. 7.9 where the sequence impedances are
Fig. 7.9 Sequence circuits of symmetrical transmission line: (a) positive, (b) negative and (c) zero
sequence.
Expanding VA and VAN in terms of their positive, negative and zero sequence components, the above
equation can be rewritten as
(7.53)
Noting that the direction of the neutral current In is opposite to that of IN , we can write an equation
similar to that of (7.53) for the secondary side as
(7.54)
(7.55)
(7.56)
Separating out the positive, negative and zero sequence components we can write
(7.57)
(7.58)
(7.59)
Fig. 7.11 Zero sequence equivalent circuit of grounded neutral Y-Y connected transformer.
From (7.57) and (7.58) we see that the positive and negative sequence relations are the same as that
we have used for representing transformer circuits given in Fig. 1.18. Hence the positive and negative
sequence impedances are the same as the transformer leakage impedance Z . The zero sequence
equivalent circuit is shown in Fig. 7.11.
The total zero sequence impedance is given by
(7.60)
The zero sequence diagram of the grounded neutral Y-Y connected transformer is shown in Fig. 7.12
(a) in which the impedance Z0 is as given in (7.60). If both the neutrals are solidly grounded, i.e., Zn =
ZN = 0, then Z0 is equal to Z . The single line diagram is still the same as that shown in Fig. 7.12 (a). If
however one of the two neutrals or both neutrals are ungrounded, then we have either Zn = ∞ or ZN =
∞ or both. The zero sequence diagram is then as shown in Fig. 7.12 (b) where the value of Z0 will
depend on which neutral is kept ungrounded.
Fig. 7.12 Zero sequence diagram of (a) grounded neutral and (b) ungrounded neutral Y-Y connected
transformer.
Δ - Δ Connected Transformer
The schematic diagram of a Δ - Δ connected transformer is shown in Fig. 7.13. Now we have
(7.61)
Again
Fig. 7.13 Schematic diagram of a Δ - Δ connected transformer.
Therefore from (7.61) we get
(7.62)
The sequence components of the line-to-line voltage VAB can be written in terms of the sequence com
ponents of the line-to-neutral voltage as
(7.63)
(7.64)
(7.65)
Hence we get
(7.66)
Thus the positive and negative sequence equivalent circuits are represented by a series impedance
that is equal to the leakage impedance of the transformer. Since the Δ -connected winding does not
provide any path for the zero sequence current to flow we have
However the zero sequence current can sometimes circulate within the Δ windings. We can then
draw the zero sequence equivalent circuit as shown in Fig. 7.14.
We therefore have
(7.67)
(7.69)
(7.70)
The positive sequence equivalent circuit is shown in Fig. 7.16 (a). The negative sequence circuit is
the same as that of the positive sequence circuit except for the phase shift in the induced emf. This
is shown in Fig. 7.16 (b). The zero sequence equivalent circuit is shown in Fig. 7.16 (c) where Z0 =
Z + 3ZN . Note that the primary and the secondary sides are not connected and hence there is an
open circuit between them. However since the zero sequence current flows through primary
windings, a return path is provided through the ground. If however, the neutral in the primary side is
not grounded, i.e., ZN = ∞ , then the zero sequence current cannot flow in the primary side as well.
The sequence diagram is then as shown in Fig. 7.16 (d) where Z0 = Z .
Fig. 7.16 Sequence diagram of a Y- Δ connected transformer: (a) positive sequence, (b) negative
sequence, (c) zero sequence with grounded Y-connection and (d) zero sequence with ungrounded
Y-connection.
Fig. 7.18 Positive sequence network of the power system of Fig. 7.17.
Fig. 7.19 Negative sequence network of the power system of Fig. 7.17.
Fig. 7.20 Zero sequence network of the power system of Fig. 7.17.
Unsymmetrical Faults
Introduction
The sequence circuits and the sequence networks developed in the previous chapter will now be
used for finding out fault current during unsymmetrical faults.
Three Types of Faults
(8.1)
Fig. 8.2 Representation of 1LG fault.
Also the phase-a voltage at the fault point is given by
(8.2)
(8.3)
(8.4)
This implies that the three sequence currents are in series for the 1LG fault. Let us denote the zero,
positive and negative sequence Thevenin impedance at the faulted point as Z kk0 , Z kk1 and Z kk2
respectively. Also since the Thevenin voltage at the faulted phase is Vf we get three sequence circuits
that are similar to the ones shown in Fig. 7.7.
(8.5)
(8.6)
Again since
(8.7)
Since no current flows in phases b and c, once the fault occurs, we have from Fig. 8.4
Therefore
From (7.38) we can write Z1 = j ω ( Ls + Ms ) = j 0.225. Then from Fig. 7.7 we have
Comparing the above two values with (7.37) and (7.39) we find that Z 0 indeed is equal to j ω ( Ls - 2
Ms ) and Z2 is equal to j ω ( Ls + Ms ). Note that we can also calculate the fault current from (8.7) as
Line-to-Line Fault
The faulted segment for an L-L fault is shown in Fig. 8.5 where it is assumed that the fault has
occurred at node k of the network. In this the phases b and c got shorted through the impedance Zf .
Since the system is unloaded before the occurrence of the fault we have
(8.8)
Again
(8.13)
Equations (8.12) and (8.15) indicate that the positive and negative sequence networks are in parallel.
The sequence network is then as shown in Fig. 8.6. From this network we get
Then
Therefore
(8.19)
(8.21)
Substituting (8.18) and (8.20) in (8.21) and rearranging we get
The Thevenin equivalent circuit for 2LG fault is shown in Fig. 8.8. From this figure we get
The zero and negative sequence currents can be obtained using the current divider principle as
Fig. 8.9 Equivalent circuit of the generator in Fig. 8.4 for a 2LG fault in phases b and c.
Combining the above three equations we can write the following vector-matrix form
Hence
We can also obtain the above values using (8.24)-(8.26). Note from Example 8.1 that
Then
and Vb = Vc = 0. Therefore
The MVA base of the motor is 40, while the base MVA of the total circuit is 50. Therefore the per unit
impedances of the motor are
Therefore
Let us neglect the phase shift associated with the Y/ Δ transformers. Then the positive, negative and
zero sequence networks are as shown in Figs. 8.11-8.13.
Fig. 8.11 Positive sequence network of the power system of Fig. 8.10.
Fig. 8.12 Negative sequence network of the power system of Fig. 8.10.
Fig. 8.13 Zero sequence network of the power system of Fig. 8.10.
From Figs. 8.11 and 8.12 we get the following Ybus matrix for both positive and negative sequences
Again from Fig. 8.13 we get the following Ybus matrix for the zero sequence
(a) Single-Line-to-Ground Fault : Let a bolted 1LG fault occurs at bus-2 when the system is
unloaded with bus voltages being 1.0 per unit. Then from (8.7) we get
per unit
Also from (8.4) we get
per unit
Also I fb = I fc = 0. From (8.5) we get the sequence components of the voltages as
(b) Line-to-Line Fault : For a bolted LL fault, we can write from (8.16)
per unit
Then the fault currents are
(c) Double-Line-to-Ground Fault : Let us assumes that a bolted 2LG fault occurs at bus-2. Then
per unit
The zero and negative sequence currents are then computed from (8.25) and (8.26) as
per unit
per unit
Therefore the fault currents flowing in the line are
Example 8.5
Let us now assume that a 2LG fault has occurred in bus-4 instead of the one in bus-2.
Therefore
Also we have
Hence
per unit
Also
per unit
per unit
Therefore the fault currents flowing in the line are
We shall now compute the currents contributed by the generator and the motor to the
fault. Let us denote the current flowing to the fault from the generator side by Ig , while
that flowing from the motor by Im . Then from Fig. 8.11 using the current divider
principle, the positive sequence currents contributed by the two buses are
per unit
per unit
Similarly from Fig. 8.12, the negative sequence currents are given as
per unit
per unit
Finally notice from Fig. 8.13 that the zero sequence current flowing from the generator
to the fault is 0. Then we have
per unit
Therefore the fault currents flowing from the generator side are
Fig. 8.15 Negative sequence network of the power system of Fig. 8.10 including transformer phase
shift.
Since the zero sequence remains unaltered, these currents will not change from those computed in
Example 8.6. Thus
per
and unit
Now the positive sequence fault current from the generator Iga1 , being on the Y-side of the Y/ Δ
transformer will lead I ma1 by 30° . Therefore
per unit
per unit
Finally the negative sequence current I ga2 will lag I ma2 by 30° . Hence we have
per unit
per unit
Therefore
Also the fault currents flowing from the motor remain unaltered. Also note that the currents flowing
into the fault remain unchanged. This implies that the phase shift of the Y/ Δ transformers does not
affect the fault currents.
Example 8.7
Let us consider the same power system as given in Example 1.2, the sequence diagrams of which
are given in Figs. 7.18 to 7.20. With respect to Fig. 7.17, let us define the system parameters as:
Generator G1 : 200 MVA, 20 kV, X" = 20%, X0 = 10%
Generator G2 : 300 MVA, 18 kV, X" = 20%, X0 = 10%
Generator G3 : 300 MVA, 20 kV, X " = 25%, X0 = 15%
Transformer T1 : 300 MVA, 220Y/22 kV, X = 10%
Transformer T2 : Three single-phase units each rated 100 MVA, 130Y/25 kV, X = 10%
Transformer T3 : 300 MVA, 220/22 kV, X = 10%
Line B-C : X1 = X2 = 75 Ω , X0 = 100 Ω
Line C-D : X1 = X2 = 75 Ω , X0 = 100 Ω
Line C-F : X1 = X2 = 50 Ω , X0 = 75 Ω
Let us choose the circuit of Generator 3 as the base, the base MVA for the circuit is 300. The base
voltages are then same as those shown in Fig. 1.23. Per unit reactances are then computed as
shown below.
Generator G1 :
, X0 = 0.15
Generator G2 :
, X0 = 0.0656
Generator G3 : , X0 = 0.15
Transformer T1 :
Transformer T2 :
Transformer T3 :
Line B-C :
,
Line C-D :
,
Line C-F :
,
Neglecting the phase shifts of Y/ Δ connected transformers and assuming that the system is
unloaded, we shall find the fault current for a 1LG fault at bus-1 (point C of Fig. 7.17).
From Figs. 7.18 and 7.19, we can obtain the positive and negative sequence Thevenin impedance at
point C as (verify)
X1 = X2 = j 0.2723 per unit
Similarly from Fig. 7.20, the Thevenin equivalent of the zero sequence impedance is
X0 = j 0.4369 per unit
Therefore from (8.7) we get
per unit
Then the fault current is Ifa = 3 Ifa0 = 3.0565 per unit.
Steady State Stability studies are restricted to small and gradual changes in the system operating
conditions. In this we basically concentrate on restricting the bus voltages close to their nominal
values. We also ensure that phase angles between two buses are not too large and check for the
overloading of the power equipment and transmission lines. These checks are usually done using
power flow studies.
Transient Stability involves the study of the power system following a major disturbance. Following a
large disturbance the synchronous alternator the machine power (load) angle changes due to sudden
acceleration of the rotor shaft. The objective of the transient stability study is to ascertain whether the
load angle returns to a steady value following the clearance of the disturbance.
The ability of a power system to maintain stability under continuous small disturbances is investigated
under the name of Dynamic Stability (also known as small-signal stability). These small
disturbances occur due random fluctuations in loads and generation levels. In an interconnected
power system, these random variations can lead catastrophic failure as this may force the rotor angle
to increase steadily.
In this chapter we shall discuss the transient stability aspect of a power system.
Section I: Power-Angle Relationship
The power-angle relationship has been discussed in Section 2.4.3. In this section we shall consider
this relation for a lumped parameter lossless transmission line. Consider the single-machine-
infinite-bus (SMIB) system shown in Fig. 9.1. In this the reactance X includes the reactance of the
transmission line and the synchronous reactance or the transient reactance of the generator. The
sending end voltage is then the internal emf of the generator. Let the sending and receiving end
voltages be
given by
(9.1)
The sending end real power and reactive power are then given by
This is simplified to
(9.3)
Since the line is loss less, the real power dispatched from the sending end is equal to the real power
received at the receiving end. We can therefore write
(9.4)
where Pmax = V1 V2 / X is the maximum power that can be transmitted over the transmission line. The
power-angle curve is shown in Fig. 9.2. From this figure we can see that for a given power P0 . There
are two possible values of the angle δ - δ0 and δmax . The angles are given by
(9.5)
Example 9.1
A generator is connected to a constant voltage bus through an external reactance of 0.3 per unit. The
synchronous reactance of the generator is 0.2 per unit and the voltage magnitude of the constant
voltage bus is 1.0 per unit with its angle being 0° . The generator delivers 0.9 per unit power to the
constant voltage bus when the angle of its terminal voltage is 15° . We have to determine the
magnitude and angle of its internal emf.
Let us denote the angle of the terminal voltage by δt , while its magnitude by Vt. Since the generator
delivers 0.9 per unit power to the constant voltage bus of magnitude 1.0 per unit through a 0.3 per
unit reactance, we can write from (9.4)
Fig. 9.2 A typical power-angle curve.
Solving the above equation we get Vt = 1.0432 per unit. Therefore the current flowing through the line
is
per unit
The internal emf of the generator is then given by
Then the magnitude of the internal emf is 1.1082 per unit angle its angle δ is 23.96° . It can be readily
verified that the power delivered is
per unit
Section II: Swing Equation
Let us consider a three-phase synchronous alternator that is driven by a prime mover. The equation
of motion of the machine rotor is given by
(9.6)
where
J is the total moment of inertia of the rotor mass in kgm2
Tm is the mechanical torque supplied by the prime mover in N-m
Te is the electrical torque output of the alternator in N-m
θ is the angular position of the rotor in rad
Neglecting the losses, the difference between the mechanical and electrical torque gives the net
accelerating torque Ta . In the steady state, the electrical torque is equal to the mechanical torque,
and hence the accelerating power will be zero. During this period the rotor will move at synchronous
speed ωs in rad/s.
The angular position θ is measured with a stationary reference frame. To represent it with respect to
the synchronously rotating frame, we define
(9.7)
where δ is the angular position in rad with respect to the synchronously rotating reference frame.
Taking the time derivative of the above equation we get
(9.8)
(9.9)
We can therefore conclude that the rotor angular speed is equal to the synchronous speed only when
dδ / dt is equal to zero. We can therefore term dδ / dt as the error in speed. Taking derivative of (9.8),
we can then rewrite (9.6) as
(9.10)
(9.11)
where Pm , Pe and Pa respectively are the mechanical, electrical and accelerating power in MW.
We now define a normalized inertia constant as
(9.12)
(9.13)
In steady state, the machine angular speed is equal to the synchronous speed and hence we can
replace ωr in the above equation by ωs. Note that in (9.13) Pm , Pe and Pa are given in MW. Therefore
dividing them by the generator MVA rating Srated we can get these quantities in per unit. Hence
dividing both sides of (9.13) by Srated we get
(9.14)
per unit
Equation (7.14) describes the behaviour of the rotor dynamics and hence is known as the swing
equation. The angle δ is the angle of the internal emf of the generator and it dictates the amount of
power that can be transferred. This angle is therefore called the load angle.
Example 9.2
A 50 Hz, 4-pole turbogenerator is rated 500 MVA, 22 kV and has an inertia constant (H) of 7.5.
Assume that the generator is synchronized with a large power system and has a zero accelerating
power while delivering a power of 450 MW. Suddenly its input power is changed to 475 MW. We have
to find the speed of the generator in rpm at the end of a period of 10 cycles. The rotational losses are
assumed to be zero.
We then have
Noting that the generator has four poles, we can rewrite the above equation as
The machines accelerates for 10 cycles, i.e., 20 × 10 = 200 ms = 0.2 s, starting with a synchronous
speed of 1500 rpm. Therefore at the end of 10 cycles
Speed = 1500 + 43.6332 ´ 0.2 = 1508.7266 rpm.
Section III: Equal Area Criterion
The real power transmitted over a lossless line is given by (9.4). Now consider the situation in which
the synchronous machine is operating in steady state delivering a power Pe equal to Pm when there is
a fault occurs in the system. Opening up of the circuit breakers in the faulted section subsequently
clears the fault. The circuit breakers take about 5/6 cycles to open and the subsequent post-fault
transient last for another few cycles. The input power, on the other hand, is supplied by a prime
mover that is usually driven by a steam turbine. The time constant of the turbine mass system is of
the order of few seconds, while the electrical system time constant is in milliseconds. Therefore, for
all practical purpose, the mechanical power is remains constant during this period when the electrical
transients occur. The transient stability study therefore concentrates on the ability of the power
system to recover from the fault and deliver the constant power Pm with a possible new load angle δ .
Consider the power angle curve shown in Fig. 9.3. Suppose the system of Fig. 9.1 is operating in the
steady state delivering a power of Pm at an angle of δ0 when due to malfunction of the line, circuit
breakers open reducing the real power transferred to zero. Since Pm remains constant, the
accelerating power Pa becomes equal to Pm . The difference in the power gives rise to the rate of
change of stored kinetic energy in the rotor masses. Thus the rotor will accelerate under the constant
influence of non-zero accelerating power and hence the load angle will increase. Now suppose the
circuit breaker re-closes at an angle δc. The power will then revert back to the normal operating curve.
At that point, the electrical power will be more than the mechanical power and the accelerating power
will be negative. This will cause the machine decelerate. However, due to the inertia of the rotor
masses, the load angle will still keep on increasing. The increase in this angle may eventually stop
and the rotor may start decelerating, otherwise the system will lose synchronism.
Note that
Fig. 9.3 Power-angle curve for equal area criterion.
Hence multiplying both sides of (9.14) by and rearranging we get
Multiplying both
sides of the above equation by dt and then integrating between two arbitrary angles δ0 and δc we get
(9.15)
Now suppose the generator is at rest at δ0. We then have dδ / dt = 0. Once a fault occurs, the
machine starts accelerating. Once the fault is cleared, the machine keeps on accelerating before it
reaches its peak at δc , at which point we again have dδ / dt = 0. Thus the area of accelerating is
given from (9.15) as
(9.16)
In a similar way, we can define the area of deceleration. In Fig. 9.3, the area of acceleration is given
by A1 while the area of deceleration is given by A2 . This is given by
(9.17)
Now consider the case when the line is reclosed at δc such that the area of acceleration is larger than
the area of deceleration, i.e., A1 > A2 . The generator load angle will then cross the point δm , beyond
which the electrical power will be less than the mechanical power forcing the accelerating power to be
positive. The generator will therefore start accelerating before is slows down completely and will
eventually become unstable. If, on the other hand, A1 < A2 , i.e., the decelerating area is larger than
the accelerating area, the machine will decelerate completely before accelerating again. The rotor
inertia will force the subsequent acceleration and deceleration areas to be smaller than the first ones
and the machine will eventually attain the steady state. If the two areas are equal, i.e., A1 = A2 , then
the accelerating area is equal to decelerating area and this is defines the boundary of the stability
limit. The clearing angle δc for this mode is called the Critical Clearing Angle and is denoted by δcr.
We then get from Fig. 9.3 by substituting δc = δcr
(9.18)
We can calculate the critical clearing angle from the ab move equation. Since the critical clearing
angle depends on the equality of the areas, this is called the equal area criterion.
Example 9.3:
Consider the system of Example 9.1. Let us assume that the system is operating with Pm = Pe = 0.9
per unit when a circuit breaker opens inadvertently isolating the generator from the infinite bus.
During this period the real power transferred becomes zero. From Example 9.1 we have calculated
δ0 = 23.96 ° = 0.4182 rad and the maximum power transferred as
per unit
We have to find the critical clearing angle.
From (9.15) the accelerating area is computed as by note that Pe = 0 during this time. This is then
given by
To calculate the decelerating area we note that δm = π - 0.4182 = 2.7234 rad. This area is computed
by noting that Pe = 2.2164 sin(δ ) during this time. Therefore
Now a frequently asked question is what does the critical clearing angle mean?
Since we are interested in finding out the maximum time that the circuit breakers may take for
opening, we should be more concerned about the critical clearing time rather than clearing angle.
Furthermore, notice that the clearing angle is independent of the generalized inertia constant H .
Hence we can comment that the critical clearing angle in this case is true for any generator that has a
d-axis transient reactance of 0.20 per unit. The critical clearing time, however, is dependent on H and
will vary as this parameter varies.
To obtain a description for the critical clearing time, let us consider the period during which the fault
occurs. We then have Pe = 0. We can therefore write from
Integrating the above equation with the initial acceleration being zero we get
Further integration will lead to
Replacing δ by δcr and t by tcr in the above equation, we get the critical clearing time as
Example 9.4:
In Example 9.2, let us choose the system frequency as 50 Hz such that ωs is 100π. Also let us
choose H as 4 MJ/MVA. Then with δcr being 1.5486 rad, δ0 being 0.4182 rad and Pm being 0.9 per
unit, we get the following critical clearing time from (9.20)
s
To illustrate the response of the load angle δ , the swing equation is simulated in MATLAB. The swing
equation of (9.14) is then expressed as
(9.21)
where Δωr is the deviation for the rotor speed from the synchronous speed ωs . It is to be noted that
the swing equation of (9.21) does not contain any damping. Usually a damping term, that is
proportional to the machine speed Δωr, is added with the accelerating power. Without the damping
the load angle will exhibit a sustained oscillation even when the system remains stable when the fault
cleared within the critical clearing time.
Fig. 9.4 Stable and unstable system response as a function of clearing time.
Fig. 9.4 depicts the response of the load angle δ for two different values of load angle. It is assumed
that the fault occurs at 0.5 s when the system is operating in the steady state delivering 0.9 per unit
power. The load angle during this time is constant at 23.96° . The load angle remains stable, albeit
the sustained oscillation when the clearing time tcl is 0.253 s. The clearing angle during this time is
88.72° . The system however becomes unstable when the clearing time 0.2531s and the load angle
increases asymptotically. The clearing time in this case is 88.77° . This is called the Loss of
Synchronism. It is to be noted that such increase in the load angle is not permissible and the
protection device will isolate the generator from the system.
The clearing time of (8.20) is derived based on the assumption that the electrical power Pe becomes
zero during the fault as in (8.19). This need not be the case always. In that even we have to resort to
finding the clearing time using the numerical integration of the swing equation. See example 9.5 to
illustrates the point.
Example 9.5
Consider the system in which a generator is connected to an infinite bus through a double circuit
transmission line as shown in Fig. 9.5. The per unit system reactances that are converted in a
common base, are also shown in this figure. Let us assume that the infinite bus voltage is 1< 0° . The
generator is delivering 1.0 per unit real power at a lagging power factor of 0.9839 to the infinite bus.
While the generator is operating in steady state, a three-phase bolted short circuit occurs in the
transmission line connecting buses 2 and 4 - very near to bus 4. The fault is cleared by opening the
circuit breakers at the two ends of this line. We have to find the critical clearing time for various values
of H .
Fig. 9.5 Schematic diagram of the power system of Example 9.4.
Let the current flowing through the line be denoted by I . Then the power delivered to the infinite bus
is
The total impedance during the time when both the lines are operational, the impedance between the
generator and the infinite bus is j(0.3+0.1+0.1) = j 0.5 per unit. Then the generator internal voltage is
Therefore the machine internal voltage is E' = 1.2 per unit its angle is 24.625° or 0.4298 rad.
The pre-fault equivalent circuit is shown in Fig. 9.6 (a). From this figure we can write the power
transfer equation as
Once the fault is cleared by opening of the breakers connected near buses 2 and 4, only of one the
two lines will be operational. Therefore during the post fault period, the impedance between the
generator and the infinite bus is j (0.3+0.2+0.6) = j 0.5 per unit as shown in Fig. 9.6 (b). Then the
post-fault power transfer equation is given by
per unit
Also the Thevenin voltage is then given by
per unit
The reduced circuit is shown in Fig. 9.8 (b). From this circuit we can write the following power transfer
equation during the fault
Fig. 9.8 Equivalent circuit during the fault: (a) D -Y transformed and (b) Thevenin equivalent.
Three power-angle curves are shown in Fig. 9.9. From this figure we find that
rad
Fig. 9.9 Power-angles curves for the three modes of operation of the system of Example 9.4.
The accelerating area is given by
and the decelerating area is
As mentioned earlier, the critical clearing angle depends on the system network configuration. The
critical clearing time, however, is dependent on H and will vary as this parameter varies. Usually
numerical methods are employed for finding out the clearing time. We shall however demonstrate the
effect of H through a MATLAB program. The program uses the built-in ordinary differential equation
solver though which the swing equations are solved. The results obtained are listed in Table 9.1. It
can be seen that as the value of H increases, the clearing time also increases, even though the
clearing angle remains the same. This is obvious as the value of H increases, the response of the
system becomes more sluggish due to larger inertia. Hence, the rotor takes more time to accelerate.
Table 9.1 Effect of H on critical clearing time
H ( MJ/MVA) Approximate Critical Clearing Time (s)
2 0.2783
4 0.3936
6 0.4821
8 0.5566
10 0.6223
Section IV: Multimachine Stability
Oscillations in a Two Area System
Consider Fig. 9.10, which depicts a number of weights that are suspended by elastic strings. The
weights represent generators and the electric transmission lines being represented by the strings.
Note that in a transmission system, each transmission line is loaded below its static stability limit.
Similarly, when the mechanical system is in static steady state, each string is loaded below its break
point. At this point one of the strings is suddenly cut. This will result in transient oscillations in the
coupled strings and all the weights will wobble. In the best possible case, this may result in the
coupled system settling down to a new steady state. On the other hand, in the worst possible
scenario this may result in the breaking of one more additional string, resulting in a chain reaction in
which more strings may break forcing a system collapse. In a similar way, in an interconnected
electric power network, the tripping of a transmission line may cause a catastrophic failure in which a
large number of generators are lost forcing a blackout in a large area.
Modern power systems are interconnected and operate close to their transient and steady state
stability limits. In large interconnected systems, it is common to find a natural response of a group of
closely coupled machines oscillating against other groups of machines. These oscillations have a
frequency range of 0.1 Hz to 0.8 Hz. The lowest frequency mode involves all generators of the
system. This oscillation groups the system into two parts - with generators in one part oscillating
against those of the the other part. The higher frequency modes are usually localized with small
groups oscillating against each other. Unfortunately, the inter-area oscillation can be initiated by a
small disturbance in any part of the system. These small frequency oscillations fall under the category
of dynamic stability and are analysed in linear domain through the liberalisation of the entire
interconnected systems model.
Inter-area oscillations manifest wherever the power system is heavily interconnected. The
oscillations, unless damped, can lead to grid failure and total system collapse. Low frequency
oscillations in the range of 0.04 Hz to 0.06 Hz were observed in the Pacific North West region as
early as 1950. Improper speed governor control of hydro units created these oscillations. The
Northern and Southern regions of WSCC were interconnected by a 230 kV line in 1964. Immediately
the system experienced a 0.1 Hz oscillation resulting in over 100 instances of opening of the tie line in
the first nine months of operation. Some system damping was provided through the modification in
the hydro turbine governors.
A 500 kV pacific intertie and another ± 400 kV HVDC system was commissioned in 1968. This raised
the frequency of oscillation from 0.1 Hz to 0.33 Hz and these oscillations could no longer be
controlled through governor action alone. In late 1980's a new intertie joined the WSCC system to
Alberta and British Columbia in Canada . As a result of this interconnection, the two different
oscillation frequencies manifested - one at 0.29 Hz and the other at 0.45 Hz.
Ontario Hydro is one of the largest utilities in North America . Due to the vast and sparsely populated
topology of Canada , the operating span of Ontario hydro is over 1000 km from East to West and
from North to South. The Ontario Hydro system is connected to the neighbouring Canadian provinces
and the North Western region of the United States . In 1959 Ontario Hydro was connected to
Michigan in the South and Quebec Hydro in the East. As a result of this connection, a 0.25 Hz
oscillation was observed and a result of this it was decided to remove the tie with Quebec and retain
the tie to Michigan . The Western portion of Ontario was connected to neighbouring Manitoba in 1956
and then Manitoba was connected to its neighbour Saskatchewan in 1960. This resulted in oscillation
in the frequency range 0.35 Hz to 0.45 Hz often tripping the tie. As a result of this, Ontario Hydro
decided to commission power system stabilizers for all their generating units since early 1960's. It has
also sponsored extensive research in this area.
Through research it was established that the action of automatic voltage regulators caused these
oscillations. An automatic voltage regulator (AVR) regulates the generator terminal voltage and also
helps in the enhancement of transient stability by reducing the peak of the first swing following any
disturbance. However, its high gain contributed to negative damping to the system. The knowledge of
this relation resulted in the commissioning of power system stabilizers. It was observed that these
oscillations were results of the periodic interchange of kinetic energy between the generator rotors. A
power system stabilizer (PSS) provides a negative feedback of the changes in rotor kinetic energy
when it is connected to the excitation system thereby providing damping to these small oscillations.
The PSS has been a subject of extensive research. The team of Dr. P. Kundur, then with Ontario
Hydro, and his co-workers has done extensive research in the area of PSS tuning and its
characteristics. Through their vast experience and extensive research, they reported the
enhancement of inter-area and local modes through PSS reported in. Since a power system is piece-
wise linear, its system characteristics changes with operating point. Therefore an adaptive controller
that can tune with the changes in the system has been developed and reported in. It was shown that
the adaptive PSS is effective in damping large as well as small disturbances.
The power flow between generators, as evident from (9.4), is dependent on the angle between those
generators. The stable operating point of the power system is where the generated power at each
station is matched by the electrical power sent out from that station. When there is a mismatch
between electrical power out and the generated mechanical shaft power, the generator will accelerate
at a rate determined by the power mismatch and the machine inertia as given in (9.14).
Oscillations in s Two Area System
Consider the simple power system shown in Fig. 9.11 in which two machines are operating. Let us
assume that starting with the initial angles δ 1 and δ2 with respect to some reference at nominal
frequency, machine 1 accelerates while machine 2 decelerates from this nominal frequency. We then
have
(9.25)
where the subscripts 1 and 2 refer to machines 1 and 2 respectively. Let us assume that the
transmission line is loss less. Then in the simple case where the power from machine 1 flows to
machine 2, we
get
(9.26)
where δ12 = δ1 - δ2 .
Now since the system is lossless, (9.26) will also imply that Pm1 = - Pm2 . This means that in the
steady state, the power generated at machine 1 is absorbed through machine 2. Combining (9.25)
and (9.26) we get
(9.27)
Let us now
assume that H1 = H2 = H , V1 = V2 = 1.0 per unit and Pm1 = 0. We then get from (9.27)
(9.28)
Thus the weighted difference of angles will approximate simple harmonic motion for small changes in
δ12 and the frequency will decrease for an increase in inertia H or impedance X . Another aspect can
be seen by adding the system to give
Thus the overall acceleration of the machine group will depend on the overall balance between power
generated and consumed. Usually there are governors on the generators to reduce generated power
if the system frequency increases.
Introduction
Ideal Shunt Compensator
Improving Volatage Profile
Improving Power-Angle Characteristics
Improving Stability Margin
Improving Damping to Power Oscillations
Ideal Series Compensator
Impact of Series Compensator on Voltage Profile
Improving Power-Angle Characteristics
An Alternate Method of Voltage Injection
Improving Stability Margin
Comparisons of the Two Modes of Operation
Power Flow Control and Power Swing Damping
Introduction
The two major problems that the modern power systems are facing are voltage and angle stabilities.
There are various approaches to overcome the problem of stability arising due to small signal
oscillations in an interconnected power system. As mentioned in the previous chapter, installing
power system stabilizers with generator excitation control system provides damping to these
oscillations. However, with the advancement in the power electronic technology, various reactive
power control equipment are increasingly used in power transmission systems.
A power network is mostly reactive. A synchronous generator usually generates active power that is
specified by the mechanical power input. The reactive power supplied by the generator is dictated by
the network and load requirements. A generator usually does not have any control over it. However
the lack of reactive power can cause voltage collapse in a system. It is therefore important to
supply/absorb excess reactive power to/from the network. Shunt compensation is one possible
approach of providing reactive power support.
A device that is connected in parallel with a transmission line is called a shunt compensator , while a
device that is connected in series with the transmission line is called a series compensator . These
are referred to as compensators since they compensate for the reactive power in the ac system. We
shall assume that the shunt compensator is always connected at the midpoint of transmission
system, while the series compensator can be connected at any point in the line. We shall
demonstrate that such connections in an SMIB power system improves
voltage profile
power-angle characteristics
stability margin
damping to power oscillations
A static var compensator ( SVC ) is the first generation shunt compensator. It has been around since
1960s. In the beginning it was used for load compensation such as to provide var support for large
industrial loads, for flicker mitigation etc. However with the advancement of semiconductor
technology, the SVC started appearing in the transmission systems in 1970s. Today a large number
of SVCs are connected to many transmission systems all over the world. An SVC is constructed
using the thyristor technology and therefore does not have gate turn off capability.
With the advancement in the power electronic technology, the application of a gate turn off thyristor
(GTO) to high power application became commercially feasible. With this the second generation
shunt compensator device was conceptualized and constructed. These devices use synchronous
voltage sources for generating or absorbing reactive power. A synchronous voltage source (SVS) is
constructed using a voltage source converter (VSC). Such a shunt compensating device is called
static compensator or STATCOM . A STATCOM usually contains an SVS that is driven from a dc
storage capacitor and the SVS is connected to the ac system bus through an interface transformer.
The transformer steps the ac system voltage down such that the voltage rating of the SVS switches
are within specified limit. Furthermore, the leakage reactance of the transformer plays a very
significant role in the operation of the STATCOM.
Like the SVC, a thyristor controlled series compensator ( TCSC ) is a thyristor based series
compensator that connects a thyristor controlled reactor ( TCR ) in parallel with a fixed capacitor.
By varying the firing angle of the anti-parallel thyristors that are connected in series with a reactor in
the TCR, the fundamental frequency inductive reactance of the TCR can be changed. This effects a
change in the reactance of the TCSC and it can be controlled to produce either inductive or capacitive
reactance.
Alternatively a static synchronous series compensator or SSSC can be used for series
compensation. An SSSC is an SVS based all GTO based device which contains a VSC. The VSC is
driven by a dc capacitor. The output of the VSC is connected to a three-phase transformer. The other
end of the transformer is connected in series with the transmission line. Unlike the TCSC, which
changes the impedance of the line, an SSSC injects a voltage in the line in quadrature with the line
current. By making the SSSC voltage to lead or lag the line current by 90 ° , the SSSC can emulate
the behavior of an inductance or capacitance.
In this chapter, we shall discuss the ideal behavior of these compensating devices. For simplicity we
shall consider the ideal models and broadly discuss the advantages of series and shunt
compensation.
Section I: Ideal Shunt Compensator
The ideal shunt compensator is an ideal current source. We call this an ideal shunt compensator
because we assume that it only supplies reactive power and no real power to the system. It is
needless to say that this assumption is not valid for practical systems. However, for an introduction,
the assumption is more than adequate. We shall investigate the behavior of the compensator when
connected in the middle of a transmission line. This is shown in Fig. 10.1, where the shunt
compensator, represented by an ideal current source, is placed in the middle of a lossless
transmission line. We shall demonstrate that such a configuration improves the four points that are
mentioned above.
Fig 10.1 Schematic diagram of an ideal, midpoint shunt compensation
Improving Voltage Profile
Let the sending and receiving voltages be given by and respectively. The ideal shunt
compensator is expected to regulate the midpoint voltage to
against any variation in the compensator current. The voltage current characteristic of the
compensator is shown in Fig. 10.2. This ideal behavior however is not feasible in practical systems
where we get a slight droop in the voltage characteristic. This will be discussed later.
(10.5)
We thus have to generate a current that is in phase with the midpoint voltage and has a magnitude of
(4V / XL ){1 - cos( δ /2)}. The apparent power injected by the shunt compensator to the ac bus is then
(10.6)
Since the real part of the injected power is zero, we conclude that the ideal shunt compensator injects
only reactive power to the ac system and no real power.
Improving Power-Angle Characteristics
The apparent power supplied by the source is given by
Similarly the apparent power delivered at the receiving end is
The power-angle characteristics of the shunt compensated line are shown in Fig. 10.3. In this figure
Pmax = V2/X is chosen as the power base.
Fig. 10.4 Variations in transmitted real power and reactive power injection by the shunt compensator
with load angle for perfect midpoint voltage regulation.
Let us now relax the condition that the midpoint voltage is regulated to 1.0 per unit. We then obtain
some very interesting plots as shown in Fig. 10.5. In this figure, the x-axis shows the reactive power
available from the shunt device, while the y-axis shows the maximum power that can be transferred
over the line without violating the voltage constraint. There are three different P-Q relationships given
for three midpoint voltage constraints. For a reactive power injection of 0.5 per unit, the power
transfer can be increased from about 0.97 per unit to 1.17 per unit by lowering the midpoint voltage to
0.9 per unit. For a reactive power injection greater than 2.0 per unit, the best power transfer capability
is obtained for VM = 1.0 per unit. Thus there will be no benefit in reducing the voltage constraint
when the shunt device is capable of injecting a large amount of reactive power. In practice, the level
to which the midpoint voltage can be regulated depends on the rating of the installed shunt device as
well the power being transferred.
Fig. 10.5 Power transfer versus shunt reactive injection under midpoint voltage constraint.
Improving Stability Margin
This is a consequence of the improvement in the power angle characteristics and is one of the major
benefits of using midpoint shunt compensation. As mentioned before, the stability margin of the
system pertains to the regions of acceleration and deceleration in the power-angle curve. We shall
use this concept to delineate the advantage of mid point shunt compensation.
Consider the power angle curves shown in Fig. 10.6.
The curve of Fig. 10.6 (a) is for an uncompensated system, while that of Fig. 10.6 (b) for the
compensated system. Both these curves are drawn assuming that the base power is V2/X . Let us
assume that the uncompensated system is operating on steady state delivering an electrical power
equal to Pm with a load angle of δ0 when a three-phase fault occurs that forces the real power to zero.
To obtain the critical clearing angle for the uncompensated system is δcr , we equate the accelerating
area A1 with the decelerating area A2 , where
with δmax = π - δ0 . Equating the areas we obtain the value of δcr as
Let us now consider that the midpoint shunt compensated system is working with the same
mechanical power input Pm. The operating angle in this case is δ1 and the maximum power that can
be transferred in this case is 2 per unit. Let the fault be cleared at the same clearing angle δcr as
before. Then equating areas A3 and A4 in Fig. 10.6 (b) we get δ2, where
Example 10.1
Let an uncompensated SMIB power system is operating in steady state with a mechanical power
input Pm equal to 0.5 per unit. Then δ0 = 30° = 0.5236 rad and δmax = 150° = 2.6180 rad.
Consequently, the critical clearing angle is calculated as (see Chapter 9) δcr = 79.56° = 1.3886 rad.
Let us now put an ideal shunt compensator at the midpoint. The pre-fault steady state operating angle
of the compensated system can be obtained by solving 2 sin(δ/2) = 0.5, which gives δ1 = 28.96° =
0.5054 rad. Let us assume that we use the same critical clearing angle as obtained above for clearing
a fault in the compensated system as well.
The accelerating area is then given by A3 = 0.4416. Equating with area A4 we get a nonlinear
equation of the form
Fig 10.6 Power-angel curve showing clearing angles: (a) for uncompensated sytem and (b) for
compensated system
Solving the above equation we get δ2 = 104.34° = 1.856 rad. It is needless to say that the stability
margin has increased significantly in the compensated system.
Improving Damping to Power Oscillations
The swing equation of a synchronous machine is given by (9.14). For any variation in the electrical
quantities, the mechanical power input remains constant. Assuming that the magnitude of the
midpoint voltage of the system is controllable by the shunt compensating device, the accelerating
power in (9.14) becomes a function of two independent variables, | VM | and δ . Again since the
mechanical power is constant, its perturbation with the independent variables is zero. We then get the
following small perturbation expression of the swing equation
(10.12)
(10.13)
The 2nd order differential equation given in (10.13) can be written in the Laplace domain by neglecting
the initial conditions as
(10.14
The roots of the above equation are located on the imaginary axis of the s-plane at locations ± j ωm
where
This implies that the load angle will oscillate with a constant frequency of ωm . Obviously, this solution
is not acceptable. Thus in order to provide damping, the mid point voltage must be varied according
to in sympathy with the rate of change in Δδ . We can then write
(10.15)
where KM is a proportional gain. Substituting (10.15) in (10.12) we get
(10.16)
Provided that
KM is positive definite, the introduction of the control action (10.15) ensures that the roots of the
second order equation will have negative real parts. Therefore through the feedback, damping to
power swings can be provided by placing the poles of the above equation to provide the necessary
damping ratio and undamped natural frequency of oscillations.
Example 10.2
Consider the SMIB power system shown in Fig. 10.7. The generator is connected to the infinite bus
through a double circuit transmission line. At the midpoint bus of the lines, a shunt compensator is
connected. The shunt compensator is realized by the voltage source VF that is connected to the
midpoint bus through a pure inductor XF , also known as an interface inductor . The voltage source
VF is driven such that it is always in phase with the midpoint voltage VM . The current IQ is then purely
inductive, its direction being dependent on the relative magnitudes of the two voltages. If the
magnitude of the midpoint voltage is higher than the voltage source VF , inductive current will flow
from the ac system to the voltage source. This implies that the source is absorbing var in this
configuration. On the other hand, the source will generate var if its magnitude is higher than that of
the midpoint voltage.
The system is simulated in MATLAB. The three-phase transmission line equations are simulated
using their differential equations, while the generator is represented by a pure voltage source. The
second order swing equation is simulated in which the mechanical power input is chosen such that
the initial operating angle of the generator voltage is (0.6981 rad). The instantaneous electrical power
is computed from the dot product of the three-phase source current vector and source voltage vector.
The system parameters chosen for simulation are:
Fig. 10.7 SMIB system used in the numerical example.
Sending end voltage, VS = 1 < 40° per unit,
Receiving end voltage, VR = 1 < 0° per unit,
System Frequency ωs = 100 π rad/s,
Line reactance, X=0.5 per unit,
Interface reactance, XF per unit,
Generator inertia constant, H=4.0 MJ/MVA.
Two different tests are performed. In the first one, the midpoint voltage is regulated to 1 per unit using
a proportional-plus-integral (PI) controller. The magnitude of the midpoint voltage is first calculated
using the d-q transformation of the three phase quantities. The magnitude is then compared with the
set reference (1.0) and the error is passed through the PI controller to determine the magnitude of the
source voltage,
ie, (10.17)
The source voltage is then generated by phase locking it with the midpoint voltage using
Fig. 10.8 depicts the system quantities when the system is perturbed for its nominal operating
condition. The proportional gain ( KP ) is chosen as 2.0, while the integral gain ( KI ) is chosen as 10.
In Fig. 10.8 (a) the a-phase of the midpoint voltage, source voltage and the injected current are
shown once the system transients die out. It can be seen that the source and midpoint voltages are
phase aligned, while the injected current is lagging these two voltages by 90° . Furthermore, the
midpoint voltage magnitude is tightly regulated. Fig. 10.8 (b) depicts the perturbation in the load angle
and the injected reactive power. It can be seen that the load angle undergoes sustained oscillation
and this oscillation is in phase with the injected reactive power. This implies that, by tightly regulating
the midpoint voltage though a high gain integral controller, the injected reactive power oscillates in
sympathy with the rotor angle. Therefore to damp out the rotor oscillation, a controller must be
designed such that the injected reactive power is in phase opposition with the load angle. It is to be
noted that the source voltage also modulates in sympathy with the injected reactive power. This
however is not evident from Fig. 10.8 (a) as the time axis has been shortened here.
(a) (b)
Fig. 10.8 Sustained oscillation in rotor angle due to strong regulation of midpoint voltage.
To improve damping, we now introduce a term that is proportional to the deviation of machine speed
in the feedback loop such that the control law is given by
The values of proportional gain KP and integral gain KI chosen are same as before, while the value of
CP chosen is 50. With the system operating on steady state, delivering power at a load angle of 40°
for 50 ms, breaker B (see Fig. 10.7) opens inadvertently. The magnitude of the midpoint voltage is
shown in Fig. 10.9 (a). It can be seen that the magnitude settles to the desired value of 1.0 per unit
once the initial transients die down. Fig. 10.9 (b) depicts perturbations in load angle and reactive
power injected from their prefault steady state values. It can be seen that these two quantities have a
phase difference of about 90 ° and this is essential for damping of power oscillations.
(a) (b)
Fig 10.9 System response with the damping controller
Ideal Series Compensator
Let us assume that the series compensator is represented by an ideal voltage source. This is shown
in Fig. 10.10. Let us further assume that the series compensator is ideal, i.e., it only supplies reactive
power and no real power to the system. It is needless to say that this assumption is not valid for
practical systems. However, for an introduction, the assumption is more than adequate. It is to be
noted that, unlike the shunt compensator, the location of the series compensator is not crucial, and it
can be placed anywhere along the transmission line.
Assuming VS = V < δ and VR = V <0° , we get the following expression for the line current
Thus we see that λ is subtracted from X . This choice of the sign corresponds to the voltage source
acting as a pure capacitor. Hence we call this as the capacitive mode of operation . In contrast, if
we choose VQ = λIS e+j90° , λ is added to X , and this mode is referred to as the inductive mode of
operation . Since this voltage injection using (10.20) add λ to or subtract λ from the line reactance,
we shall refer it as voltage injection in constant reactance mode. We shall consider the implication
of series voltage injection on the transmission line voltage through the following example.
Example 10.3
Consider a lossless transmission line that has a 0.5 per unit line reactance (X). The sending end and
receiving end voltages are given by 1< δ and 1< 0° per unit respectively where δ is chosen as 30° .
Let us choose λ = 0.5 and operation in the capacitive mode. For this line, this implies a 30% level of
line impedance compensation. The line current is then given from (10.21) as IS = 1.479 7 < 15° per
unit and the injected voltage calculated from (10.20) is VQ = 0.2218 < - 75° per unit. The phasor
diagrams of the two end voltages, line current and injected voltage are shown in Fig. 10.11 (a). We
shall now consider a few different cases.
Let us assume that the series compensator is placed in the middle of the transmission line. We then
define two voltages, one at either side of the series compensator. These are:
Voltage on the left: VQL = VS - jXIS / 2 = 0.9723 < 8.45° per unit
Voltage on the right: VQR = VR + jXIS / 2 = 0.9723 < 21.55° per unit
The difference of these two voltages is the injected voltage. This is shown in Fig. 10.11 (b), where
the angle θ = 8.45° . The worst case voltage along the line will then be at the two points on either side
of the series compensator where the voltage phasors are aligned with the line current phasor. These
two points are equidistant from the series compensator. However, their particular locations will be
dependent on the system parameters.
As a second case, let us consider that the series compensator is placed at the end of the
transmission line, just before the infinite bus. We then have the following voltage
Voltage on the left of the compensator: VQL = VR + VQ = 1.0789 < - 11.46° per unit
This is shown in Fig. 10.11 (c). The maximum voltage rise in the line is then to the immediate left of
the compensator, i.e., at VQL . The maximum voltage drop however still occurs at the point where the
voltage phasor is aligned with the line current phasor.
As a third case, let us increase the level of compensation from 30% to 70% (i.e., change λ from 0.15
to 0.35). We however, do not want to change the level of steady state power transfer. The relation
between power transfer and compensation level will be discussed in the next subsection. It will
however suffice to say that this is accomplished by lowering the value of the angle δ of the sending
end voltage to 12.37° . Let us further assume that the series compensator is placed in the middle of
the transmission line. We then have VQL = 1.0255 < - 8.01° per unit and VQR = 1.0255 < 20.38° per
unit. This is shown in Fig. 10.11 (d). It is obvious that the voltage along the line rises to a maximum
level at either side of the series compensator.
Improving Power-Angle Characteristics
Noting that the sending end apparent power is VS IS* , we can write
The power-angle characteristics of a series compensated power system are given in Fig. 10.12. In
this figure the base power is chosen as V2 / X . Three curves are shown, of which the curve P0 is the
power-angle curve when the line is not compensated. Curves which have maximum powers greater
than the base power pertain to capacitive mode of operation. On the other hand, all curves the
inductive mode of operation will have maximum values less than 1. For example, in Fig. 10.12, the
curve P1 is for capacitive mode and the curve P2 is for inductive mode of operation.
Solving the
above equation
we get
(10.25)
In Fig. 10.13, the reactive power injected by the series compensator is plotted against the maximum
power transfer as the compensation level changes from 10% to 60%. As the compensation level
increases, the maximum power transfer also increases. However, at the same time, the reactive
injection requirement from the series compensator also increases. It is interesting to note that at 50%
compensation level, the reactive power injection requirement from a series compensator is same that
from shunt compensator that is regulating the midpoint voltage to 1.0 per unit.
Fig. 10.13 Reactive power injection by a series compensator versus maximum power transfer as the
level of compensation changes in constant reactance mode.
i.e., the voltage source in quadrature with the current is represented as a pure reactance that is either
inductive or capacitive. Since in this form we injected a constant voltage in quadrature with the line
current, we shall refer this as constant voltage injection mode. The total equivalent inductance of
the line is then
Defining VS = V < δ and VR < 0° , we can then write the power transfer equation as
Similarly from the inductive operation phasor diagram shown in Fig. 10.14 (b), we get
Fig. 10.14 Phasor diagram of series compensated system: (a) capacitive operation and (b) inductive
operation.
The power-angle characteristics of this particular series connection are given in Fig. 10.15. In this
figure the base power is chosen as V2/X . Three curves are shown, of which the curve P0 is the
power-angle curve when the line is not compensated. Curves which have maximum powers greater
than the base power pertain to capacitive mode of operation. On the other hand, all curves the
inductive mode of operation will have maximum values less than 1. For example, in Fig. 10.15, the
curve P1 is for capacitive mode and the curve P2 is for inductive mode of operation.
(10.30)
Improving Stability Margin
From the power-angle curves of Figs. 10.13 and 10.15 it can be seen that the same amount of power
can be transmitted over a capacitive compensated line at a lower load angle than an uncompensated
system. Furthermore, an increase in the height in the power-angle curve means that a larger amount
of decelerating area is available for a compensated system. Thus improvement in stability margin for
a capacitive series compensated system over an uncompensated system is obvious.
Comparisons of the Two Modes of Operation
As a comparison between the two different modes of voltage injection, let us first consider the
constant reactance mode of voltage injection with a compensation level of 50%. Choosing V2 / X as
the base power, the power-angle characteristic reaches a maximum of 2.0 per unit at a load angle π /
2. Now | VQ | in constant voltage mode is chosen such that the real power is 2.0 per unit at a load
angle of π / 2. This is accomplished using (10.29) where we get
per unit
The power-angle characteristics of the two different modes are now drawn in Fig. 10.16 (a). It can be
seen that the two curves match at π / 2. However, the maximum power for constant voltage case is
about 2.1 per unit and occurs at an angle of 67° .
Fig. 10.16 (b) depicts the line current for the two cases. It can be seen that the increase in line current
in either case is monotonic. This is not surprising for the case of constant reactance mode since as
the load angle increases, both real power and line currents increase. Now consider the case of
constant voltage control. When the load angle moves backwards from π /2 to 67° , the power moves
from 2.0 per unit to its peak value of 2.1 per unit. The line current during this stage decreases from
about 2.83 to 2.50 per unit. Thus, even though the power through the line increases, the line current
decreases.
Power Flow Control and Power Swing Damping
One of the major advantages of series compensation is that through its use real power flow over
transmission corridors can be effectively controlled. Consider, for example, the SMIB system shown
in Fig. 10.17 in which the generator and infinite bus are connected through a double circuit
transmission line, labeled line-1 and line-2. Of the two transmission lines, line-2 is compensated by a
series compensator. The compensator then can be utilized to regulate power flow over the entire
system.
(a) (b)
Fig. 10.16 Power-angle and line current-angle characteristics of the two different methods of voltage
injection: solid line showing constant reactance mode and dashed line showing constant voltage
mode.
For example, let us consider that the system is operating in the steady state delivering a power of
Pm0 at a load angle of δ0 . Lines 1 and 2 are then sending power Pe1 and Pe2 respectively, such that
Pm0 = Pe1 + Pe2 . The mechanical power input suddenly goes up to Pm1 . There are two ways of
controlling the power in this situation:
Regulating Control: Channeling the increase in power through line-1. In this case the series
compensator maintains the power flow over line-2 at Pe2 . The load angle in this case goes up
in sympathy with the increase in Pe1 .
Tracking Control: Channeling the increase in power through line-2. In this case the series
compensator helps in maintaining the power flow over line-1 at Pe1 while holding the load angle
to δ0 .
Let us illustrate these two aspects with the help of a numerical example.
Example 10.4
Let us consider the system of Fig. 7.8 where the system parameters are given by
System Frequency = 50 Hz, | V S | = | V R | = 1.0 per unit, X = 0.5 per unit and d 0 = 30 ° /
It is assumed that the series compensator operates in constant reactance mode with a compensation
level of 30%. We then have
Pe1 = 1.0 per unit, Pe2 = 1.43 per unit, Pm = 2.43 per unit
The objective of the control scheme here is to maintain the power through line-2 to a pre-specified
value, Pref . To accomplish this a proportional-plus-integral (PI) controller is placed in the feedback
loop of Pe2 . In addition, to improve damping a term that is proportional to the deviation of machine
speed is introduced in the feedback loop. The control law is then given by
(10.31)
where CL = λ / X is the compensation level. For the simulation studies performed, the following
controller parameters are chosen
KP = 0.1, KI = 1.0 and CP = 75
Regulating Control: With the system operating in the nominal steady state, the mechanical power
input is suddenly raised by 10%. It is expected that the series compensator will hold the power
through line-2 constant at line-2 at Pe2 such that entire power increase is channeled through line-1.
We then expect that the power Pe1 will increase to 1.243 per unit and the load angle to go up to 0.67
rad. The compensation level will then change to 13%.
The time responses for various quantities for this test are given in Fig. 10.18. In Fig. 10.18 (a), the
power through the two line is plotted. It can be seen that while the power through line-2 comes back
to its nominal value following the transient, the power through the other line is raised to expected
level. Similarly, the load angle and the compensation level reach their expected values, as shown in
Figs. 10.18 (b) and (c), respectively. Finally, Fig. 10.18 (d) depicts the last two cycles of phase-a of
the line current and injected voltage. It can be clearly seen that these two quantities are in
quadrature, with the line current leading the injected voltage.
Fig. 10.18 System response with regulating power flow controller.
Tracking Control: With the system operating in the nominal steady state, the mechanical power
input is suddenly raised by 25%. It is expected that the series compensator will make the entire power
increase to flow through line-2 such that both Pe1 and load angle are maintained constant at their
nominal values. The power Pe2 through line-2 will then increase to about 2.04 per unit and the
compensation level will change to 51%.
The time responses for various quantities for this test are given in Fig. 10.19. It can be seen that while
the power through line-1 comes back to its nominal value following the transient, the power through
the other line is raised to level expected. Similarly, the load angle comes back to its nominal value
and the compensation level is raised 51%, as shown in Figs. 10.19 (b) and (c), respectively. Finally,
Fig. 7.19 (d) depicts the last two cycles of phase-a of the line current and injected voltage.