Systems Control: Heating Coil
Systems Control: Heating Coil
The function of a heating or air conditioning system is to maintain comfortable conditions within
a space for a specified period of time. This is achieved through the use of a well designed control
system.
heating coil
Qo
θ s
valve
position
controller +/-
error (e) θ sp
set
point
This type of control mechanism is commonly termed feedback control, where the controlled
variable (temperature) is fed back to the control system.
ON/OFF Control
This is the simplest type of control used in buildings:
• If the sensed temperature is below the set-point then the heating system is fully ON.
• If the sensed temperature rises above the set-point then the heating system is OFF.
Figure 2 shows the temperature and heat output in a room controlled by an ON/OFF controller. In
practice the use of ON/OFF control can cause problems. As can be seen in Figure 2, the heating
system rapidly switches ON an OFF leading to inefficient system operation and increased
mechanical wear.
o
C OFF OFF upper set point OFF
ON OFF
o
C
ON ON lower set point ON
o
C room air temperature
heat output
To address this deficiency a 'dead band' may be introduced. Effectively this defines an upper and
lower set-point. The control mechanism is now as summarised in Figure 3:
• if the sensed temperature is below the lower set-point then the heating system is ON;
• if the sensed temperature rises above the lower set-point but is still below the upper set-point
then the heating system is ON;
• if the sensed temperature is above the upper set-point then the heating system is OFF; and
• if the sensed temperature falls below the upper set-point but is still above the lower set-point
then the heating system is ON.
o
C room air temperature
heat output
upper temp.
Qmax
lower temp.
The addition of the upper and lower set-points acts to reduce the frequency of the plant switching
at the expense of poorer control of the controlled variable (here temperature).
ON/OFF control offers a crude means of controlling conditions in a building and is typically
employed where close control is not required, e.g. temperature control of domestic boilers.
Proportional Control
This is a more advanced control algorithm, where the control action is proportional to the size of
the error:
(t ) = Ke (t )
Q o
Figure 4 shows the operation of a proportional controller. Notice that as the sensed temperature
gets closer to the set-point temperature, so the output of the heating system is reduced
o
C room air temperature
heat output
upper temp.
Qmax
lower temp.
offset error
In practice the operation of a proportional controller is often limited as the output of the heating
system is limited (i.e. it has a maximum capacity). This is achieved by introducing a 'proportional
band' or 'throttling range'—this is similar to a dead band in that a single set-point is replaced by
an upper and lower limit. With reference to Figure 4, the control action now follows the
following rules:
• if the temperature lies above the throttling range then the heating system is OFF;
• if the temperature lies below the throttling range then the heating system is ON at full
power; and
• if the sensed temperature is within the throttling range then the output is a function of the
error.
Qmax
where K = .
θu − θl
Figure 5: Proportional control action.
heat output
throttling range
θ l
0
0 Qmax
As with ON/OFF control, proportional control is not a perfect mechanism because the throttling
range affects the operation of the system:
• a narrow throttling range gives close control (a small error) at the expense of the system
switching ON/OFF frequently; and
• a wide throttling range reduces the ON/OFF switching off the system (cycling) at the
expense of poorer control.
It is impossible to completely eliminate the error between the desired temperature and the sensed
temperature using only proportional control. There is always an offset error, where the controlled
temperature never quite reaches the desired temperature.
PID Control
A PID controller incorporates a mix of proportional, integral and derivative control action. In this
case the control output is a function of the size of the error (e(t)), the rate of change of the error
t
de (t ) 1
with time Td
dt
and the integral of the error over time
Ti ∫e(t )dt
0
:
de (t ) 1
t
Q o = K e(t ) + Td
dt
+
Ti ∫ e(t )dt
o
where Td is the derivative action time (s), Ti the integral action time (s) and K the gain.
As shown in Figure 6, PID control offers close control in that the control action now responds to
the rate of change of the error, while the integral control acts to eliminate the set-point error
experienced with proportional control.
o
C room air
heat output
temperature
set point
Qmax
temp.
Control Location
In the cases considered above control is applied to room temperatures. Many other control targets
may be considered within a building design context. For example:
• control of blinds located on the façade;
• control of fan speed;
• control of damper/valve positions;
• control of hot water temperature; and
• control of recirculated air .
In conclusion, good control is vital to acceptable performance in terms of comfort and energy
efficiency. The control algorithms considered here—ON/OFF, proportional and PID—must be
configured for optimum performance:
• selection of set-points;
• selection of proportional/dead band values; and
• selection of integral/derivative action times.
Inappropriate control parameters leads to a poorly configured control system, which in turn may
give rise to uncomfortable conditions, energy waste and a reduction in the lifetime of system
components. It is important that a building's control system is well designed, commissioned and
maintained.