ElecSafety Gen
ElecSafety Gen
(1910.301 - 399)
Live parts
*
515
303(g)(2)(i)
305(b)(1)
*
304(f)(4) Grounding path 396
347
*
305(b)(2)
Electrical box covers
305(g)(1)(iii)
290 *
Use of flexible cords and cables
*
Neutrons = no charge
U N D E R W R IT E R S
L AB O R AT O R IE S
L IST E D
EN C LO S E D S W ITC H
Iss ue AK 32 25
1910.30 3(a)
N E C A rticle 11-20
5
6
Identification of
Disconnecting
Means and Circuits
Each disconnecting means legibly
marked to indicate its purpose
(Unless so arranged so the purpose is
evident)
Hot Neutral
Neutral
Hot
1910.304(a)(2)
NEC Article 200-11
1910. 304(b) Branch circuits
1. Reserved
2. Outlet devices. Outlet devices shall have
an ampere rating not less than the load
to be served
1910. 304 (d)(1) Disconnecting
means
General. Means shall be provided to disconnect
all conductors in a building or other structure
from the service-entrance conductors.
The disconnecting means shall plainly indicate
whether it is in the open or closed position and
shall be installed at a readily accessible
location nearest the point of entrance of the
service-entrance conductors.
1000kV
1910. 304 (d)(2)
Services over 600 volts,
nominal
(i) Guarded to make them accessible only to
qualified persons
(ii) Signs warning of high voltage shall be
posted where other than qualified employees
might come in contact with live parts
Danger
1910. 304 (e)(1)(vi) Circuit
breakers
Circuit breakers shall clearly indicate whether
they are in the open (off) or closed (on) position
1000kV
Danger
1910. 304 (f) Grounding
Damaged cord
improperly repaired
Identification, Splices and
Terminations
Flexible cords shall be connected to devices and
fittings so that strain relief is provided which will
prevent pull from being directly transmitted to joints or
terminal screws
1910.305 (g)(2)(ii)