Compressor Selection Criteria: PAGE 1 of 21
Compressor Selection Criteria: PAGE 1 of 21
Copyright Ó2001
All rights reserved.
No part of this document shall be reproduced in whole or in
part without the permission of SCA Australia Pty Ltd. This
includes reproduction or copies in any form or by any means
including photocopying, printing or electronic media.
IMPORTANT DISCLAIMER
This is an educational package in professional selection
guidelines using representative graphs, charts and tables.
Manufacturers specifications must be consulted for specific
guidelines and performance data. Unicla published data,
specific to all models is available via their promotional
literature and from SCA Australia Pty Ltd upon request.
Alternatively contact your Unicla supplier.
SCA Australia Pty Ltd and Unicla expressly disclaim all and
any liability and responsibility to any person or business as a
result of any actions taken on the basis of information in this
publication.
Copyright Ó2001. All rights reserved. No part of this document shall be reproduced in whole or in part
without the permission of SCA Australia Pty Ltd. SCA Australia Pty Ltd and Unicla expressly disclaim
all and any liability and responsibility to any person or business as a result of any actions taken on the
basis of information in this Bulletin. Manufacturers specifications must be consulted for specific
guidelines and performance data.
PAGE 1 of 21
COMPRESSOR SELECTION CRITERIA
Introduction
System design, including the compressor to be used, is based on a heat load calculation
conducted for the environment we are aiming to cool and dehumidify.
In professional design this is done using test vehicles in environmental chambers where heat
loads can be controlled, together with, and based on, theoretical calculation.
Technicians reading this bulletin must be familiar with reading a pressure / temperature
relationship chart to identify evaporating and condensing temperatures from gauge readings.
Definitions
HEAT
Heat is a form of energy. In this application heat will be defined as both temperature and
humidity contained within a nominated environment. (ie: the cabin).
CAPACITY
The capacity of the system is the amount of heat that the system is capable of removing from a
nominated environment (ie: the cabin). This includes the cooling and dehumidification of that
environment.
ENTHALPY
Enthalpy is the sum of the energy (heat) applied to a medium. Enthalpy is often referred to as
the total heat content of a substance. In this application Enthalpy will relate to the amount of
heat absorbed by the refrigerant as it passes through the evaporator.
The purpose of this guidelines document is to enable you to gain an appreciation of system
design and the importance of correct compressor selection in ensuring adequate capacity of the
system to cater for the heat loads under which the system will operate.
Copyright Ó2001. All rights reserved. No part of this document shall be reproduced in whole or in part
without the permission of SCA Australia Pty Ltd. SCA Australia Pty Ltd and Unicla expressly disclaim
all and any liability and responsibility to any person or business as a result of any actions taken on the
basis of information in this Bulletin. Manufacturers specifications must be consulted for specific
guidelines and performance data.
PAGE 2 of 21
Relationship Between Cooling Capacity And Heat Load
When entering a vehicle that has been parked in the sun or when a vehicle is operating in areas
of high temperature and / or high humidity the heat load is high. ÒHeat LoadÓ is Temperature
and Humidity. As the system continues to operate the heat load will reduce as the air is cooled
and dehumidified.
With the high heat loads the cooling capacity of the system is inadequate to instantly reduce the
cabin temperature down to a desirable level (ie 20¼C). With the continued operation the
progressive reduction in heat load will enable the cooling capacity of the system to increase
(with respect to attaining desired cabin temperatures). When we reach balancing point (B.P.)
the capacity of the system exceeds the heat load and we are capable of cooling the cabin to
specified levels or below.
Any system must be capable of reaching B.P. to ensure adequate cabin cooling and
customer satisfaction at predetermined heat loads within an acceptable time frame Ð this
is commonly referred to as the pull down test (see graph 2).
BP
60 40 20¼C
Cabin Temperature
GRAPH 1 COOLING CAPACITY VERSES HEAT LOAD
Copyright Ó2001. All rights reserved. No part of this document shall be reproduced in whole or in part
without the permission of SCA Australia Pty Ltd. SCA Australia Pty Ltd and Unicla expressly disclaim
all and any liability and responsibility to any person or business as a result of any actions taken on the
basis of information in this Bulletin. Manufacturers specifications must be consulted for specific
guidelines and performance data.
PAGE 3 of 21
60
CABIN TEMPERATURE ¼C
40
20
10 20 30 40
TIME (MINUTES)
System Design
To enable B.P. to be reached within an acceptable time frame the capacity of the system must
cater for
Table 1 (over) gives an example of the heat Quantities for a small / medium passenger vehicle
of modern design (Actual data Ð use as example only)
Copyright Ó2001. All rights reserved. No part of this document shall be reproduced in whole or in part
without the permission of SCA Australia Pty Ltd. SCA Australia Pty Ltd and Unicla expressly disclaim
all and any liability and responsibility to any person or business as a result of any actions taken on the
basis of information in this Bulletin. Manufacturers specifications must be consulted for specific
guidelines and performance data.
PAGE 4 of 21
TABLE 1 Ð HEAT LOAD QUANTITIES
OPERATING CONDITIONS
Heat
Transmitted Entry Heat Internal
Entry Heat Generated by Total Heat
Heat Through Floor Generated
(Ventilation) Occupants Load
Glass Firewall etc Heat
(x4)
1370 490 320 400 110 2690
To cater for the above heat loads and additional heat soak the system must:
Have refrigerant in the evaporator at a sufficiently low Temperature to enable it to absorb heat
from the cabin air
And
Therefore
The evaporator is the basis for capacity calculation Ð it is the component directly
responsible for absorbing heat energy from the cabin.
Copyright Ó2001. All rights reserved. No part of this document shall be reproduced in whole or in part
without the permission of SCA Australia Pty Ltd. SCA Australia Pty Ltd and Unicla expressly disclaim
all and any liability and responsibility to any person or business as a result of any actions taken on the
basis of information in this Bulletin. Manufacturers specifications must be consulted for specific
guidelines and performance data.
PAGE 5 of 21
Capacity Ratings
Refrigeration capacity has historically been loosely referred to in Tons of refrigeration based on
a 24 hour period.
1 ton of Refrigeration is the amount of heat required to melt one ton of ice. If we are going to
use tons of refrigeration as a measurement of the capacity of a system strictly it must be time
referenced, normally to an hour rating.
This is the amount of energy required to melt the one ton of ice (based on a 24 hour period)
TABLE 2
REFRIGERATING CAPACITIES Ð CROSS REFERENCE CHART
TONS OF
.5 1 1.5 2 2.5 3 3.5 4
REFRIGERATION
Copyright Ó2001. All rights reserved. No part of this document shall be reproduced in whole or in part
without the permission of SCA Australia Pty Ltd. SCA Australia Pty Ltd and Unicla expressly disclaim
all and any liability and responsibility to any person or business as a result of any actions taken on the
basis of information in this Bulletin. Manufacturers specifications must be consulted for specific
guidelines and performance data.
PAGE 6 of 21
Application Chart - Refrigeration Capacities
- Air Conditioning applications R134a at 0¼C
To be used for approximation purposes only
.5 Ton Special application Ð low capacity Ð (ice box, small compartment cooling)
1Ton Small / compact vehicles / low heat load / preferably tinted windows
1.5 Ton Medium vehicles Ð common evaporator capacity / size
2.0 Ton Large vehicles Ð higher capacity Ð higher heat loads
Larger vehicles / station wagons / high glass surface area applications
2.5 Ton
- ie agricultural / plant
Over 2.5 Ton Special application only Ð bus / locomotive etc.
SPECIAL NOTES
Evaporator ratings may be stamped / plated onto the unit or evaporator coil itself or available ex
manufacturer or specified in parts manuals / promotional literature in BtuÕs / kW / kcal / hr.
Alternatively the part number may relate to the capacity of the unit ie RT9E may be roof top unit
9 kW capacity Ð Externally equalized TX Valve.
The capacity of the evaporator ie 16,000 BTU / hr 4030 kcal / hr will be determined principally by
To accurately calibrate evaporators the heat load and refrigerant temperature are referenced ie:
Copyright Ó2001. All rights reserved. No part of this document shall be reproduced in whole or in part
without the permission of SCA Australia Pty Ltd. SCA Australia Pty Ltd and Unicla expressly disclaim
all and any liability and responsibility to any person or business as a result of any actions taken on the
basis of information in this Bulletin. Manufacturers specifications must be consulted for specific
guidelines and performance data.
PAGE 7 of 21
Of these factors the critical one is the amount of refrigerant flowing through the evaporator.
Remember:
It is the refrigerant that absorbs the heat Ð therefore refrigerant flows must be optimized.
Condenser - Radiate all heat absorbed into the refrigerant by the evaporator, in the
suction run and in the process of compression (superheat of compression)
6 SPECIFICATIONS
Model SAMPLE
Displacement 200 cc/rev.
4 Cylinders 10
Max. speed 4,500 r.p.m.
0 1 2 3 4
Copyright Ó2001. All rights reserved. No part of this document shall be reproduced in whole or in part
without the permission of SCA Australia Pty Ltd. SCA Australia Pty Ltd and Unicla expressly disclaim
all and any liability and responsibility to any person or business as a result of any actions taken on the
basis of information in this Bulletin. Manufacturers specifications must be consulted for specific
guidelines and performance data.
PAGE 9 of 21
From graph 3 we can now relate compressor performance to system design and specifications
and the conditions under which it will operate.
Taking them one item at a time.
Discharge Pressure
The specified discharge pressure in this example is 15.5 kg/cm2G (1520kPaG) (220psig)
In an R134 application this corresponds to a condensing temperature of 65¼C (R134a)
Therefore
This condenser is calibrated to deliver its specified performance under a condensing pressure of
15.5 kg/cm2G (60¼C Condensing Temperature) (Refer to pressure / temperature chart) which
using industry standards relate to an ambient (day) temperature of approximately 30¼C
Therefore
This compressor will deliver performance, as specified on a 30¼C day providing condensing is
adequate.
Suction Pressure
With a specified suction pressure of 1.86 kg / cm 2 G (182 kPaG) (27 psig) the refrigerant
vaporization (evaporating) temperature is 0¼C. We can therefore deduct this compressor is
matched to medium temperature application ie R134a where an evaporating temperature of 0¼ is
ÒnormalÓ.
Copyright Ó2001. All rights reserved. No part of this document shall be reproduced in whole or in part
without the permission of SCA Australia Pty Ltd. SCA Australia Pty Ltd and Unicla expressly disclaim
all and any liability and responsibility to any person or business as a result of any actions taken on the
basis of information in this Bulletin. Manufacturers specifications must be consulted for specific
guidelines and performance data.
PAGE 10 of 21
Superheat And Subcool Specifications
Superheat and subcool specifications are detailed as a calibration parameter for the compressor
since they both have an effect on the capacity of the system. The graphed system capacity is
based on the system having a superheat of 10¼C and a subcool of 5¼C Ð an increase in either of
these will have a direct effect on system capacity. For compressor selection purposes these
readings are indicative of a Ònormal systemÓ and are of minor significance in compressor
selection unless either condition is significantly different than specified.
The performance / capacity graph principally indicates the level of performance from the
compressor corresponding to itÕs speed. To ensure the reliability and validity of this data the
operating conditions under which it is operating must be identified and related to the service
environment into which it is being placed. These operating conditions are the previously stated
head pressure (the pressure the compressor is working against) the suction pressure /
evaporating temperature, superheat and subcooling levels and most importantly the refrigerant
in the system.
In principle reading the graph is simple. The size or capacity of the evaporator or TX
Valve size can be directly related to the graph to correlate the speed at which evaporator /
system capacity will be achieved. (ie when the compressor is providing adequate flow
through the system).
Copyright Ó2001. All rights reserved. No part of this document shall be reproduced in whole or in part
without the permission of SCA Australia Pty Ltd. SCA Australia Pty Ltd and Unicla expressly disclaim
all and any liability and responsibility to any person or business as a result of any actions taken on the
basis of information in this Bulletin. Manufacturers specifications must be consulted for specific
guidelines and performance data.
PAGE 11 of 21
GRAPH 4 COMPRESSOR PERFORMANCE 1
10 OPERATING CONDITIONS
4 SPECIFICATIONS
Model SAMPLE
Displacement 115 cc/rev.
2 Cylinders 10
Max. speed 7,000 r.p.m.
0 1 2 3 4
From this graph it can be observed that a system fitted with a 5.3 kW evaporator coil (= 4,550
kcal / hr = 1.5 Ton refrigerating effect) will not provide adequate capacity until a compressor
speed of approximately 2,500 r/min.
A 6.8 kW evaporator coil (5,840 kcal / hr = 1.93 ton refrigerating effect) will require a compressor
speed of approximately 3,100 r/min.
In essence the performance graph is simply indicating the speed at which the system capacity
matches the compressor capacity, which in turn is compared to the operating conditions under
which the system normally operates.
LetÕs use a selection example using the graph above (Graph 4) and compare it to Graph 5 (over)
A 6.8 kW (5,840 kcal / hr) system operating at 2,500 r / min governed speed and a drive ratio of
1:1 will produce an effective performance of 5.2 kW (4,500 kcal / hr.) If the system has been
designed on a heat load calculation basis then performance levels will be substandard under this
operating condition) (ie it does not achieve the 6.8 kW 5840 kcal / at is rated speed.
The next compressor (Graph 5) has a performance graph which indicates the 6.8 kW
(5,840ÊkcalÊ/ hr) capacity is achieved at approximately 1,700 r / min. For this operating condition
this is the compressor of choice.
Copyright Ó2001. All rights reserved. No part of this document shall be reproduced in whole or in part
without the permission of SCA Australia Pty Ltd. SCA Australia Pty Ltd and Unicla expressly disclaim
all and any liability and responsibility to any person or business as a result of any actions taken on the
basis of information in this Bulletin. Manufacturers specifications must be consulted for specific
guidelines and performance data.
PAGE 12 of 21
GRAPH 5 COMPRESSOR PERFORMANCE 2
12
OPERATING CONDITIONS
10
Capacity x 1000 kcal / hr
SPECIFICATIONS
4 Model SAMPLE
Displacement 200 cc/rev.
Cylinders 10
2 Max. speed 4,500 r.p.m.
NOTE:
All or selected items may be published
dependent on the compressor and its
0 1 2 3 4 application.
Compressor speed (x 1/000 r/min)
When an evaporator is rated there are a number of operating conditions attached (see
specifications over) but the most critical in its relationship to the compressor is the flow rating of
the evaporator.
Copyright Ó2001. All rights reserved. No part of this document shall be reproduced in whole or in part
without the permission of SCA Australia Pty Ltd. SCA Australia Pty Ltd and Unicla expressly disclaim
all and any liability and responsibility to any person or business as a result of any actions taken on the
basis of information in this Bulletin. Manufacturers specifications must be consulted for specific
guidelines and performance data.
PAGE 13 of 21
Evaporator Specifications Ð Sample Only
COIL SPECIFICATIONS
Coil Type - Sample only
Tub Type - Rifled Bore
Fin Height - 150mm
Fin Length - 495 mm
No of Rows - 5.0
Fins / Metre - 510
No of Circuits - 3.0
Fin material - Aluminum
Evaporating Temp. - 0¼C
Superheat - 5¼C
Airflow 1/5 - 187
Liquid Temp - 48¼C
Refrigerant - R134a
RATINGS
Capacity - 6.8 kW 5,840 kcal / hr Flow Rating
Refrigerant Flow - 3.2 kg / min - the critical factor
Refrigerant Charge - 0, 1 kg
Pressure Drop (oil) - 67.2 kPa
(header) - 14.0 kPa
Air Pressure Drop - 190 Pa
Leaving Vapor Velocity - 16.5 m/s
If we now relate this to the flow ratings of the compressor (under the previously mentioned head
pressure, suction pressure, superheat, subcool conditions) we can draw some conclusions
Copyright Ó2001. All rights reserved. No part of this document shall be reproduced in whole or in part
without the permission of SCA Australia Pty Ltd. SCA Australia Pty Ltd and Unicla expressly disclaim
all and any liability and responsibility to any person or business as a result of any actions taken on the
basis of information in this Bulletin. Manufacturers specifications must be consulted for specific
guidelines and performance data.
PAGE 14 of 21
From Table 4 it can be clearly seen the flow rating at 1000 and 1500 r / min is below the
specified rating of the evaporator Ð we need 3.2kg of refrigerant flow. We only have 1.66 kg/m
at 1000 and 2.71 kg/m at 1500 r/min.
Remember
It is the refrigerant flowing through the evaporator that absorbs heat from the cabin. At lower
flow rates evaporator and system capacities are dramatically reduced Ð There is simply not
enough refrigerant flow at 1,000 and 1500 r / min.
At approximately 1800 r/min the refrigerant flow is at 3.2 kg/min. This matches the flow rating of
3.2 kg / min specified in the evaporator coil design to attain an efficiency of the specified 6.8 kW
(5,840 kcal / hr). Above this speed evaporator flows are assured therefore system
performance is optimized.
Inadequate refrigerant flow as a result of the fitment of an undersize compressor will limit
performance at all speeds where the refrigerant flow through the evaporator is below the
specified value.
In reality flow ratings are normally not referred to in compressor selection, - it is simply a match
between the capacity of the compressor and the system Ð it is however important to realize the
controlling factor in capacity attainment is the flow.
In the absence of technical data, compressor selection is often done via Òfield serviceÓ methods.
With a known TX Valve or orifice size the effective maximum capacity of the evaporator can be
presumed.
Example:
The previous evaporator with a 6.8 kW rating would normally have a 2 Ton valve fitted to ensure
adequate evaporator filling under maximum design heat load.
1 Ton = 3.517 kW
1.5 Ton = 5.275 kW
2 Ton = 7.034 kW
Copyright Ó2001. All rights reserved. No part of this document shall be reproduced in whole or in part
without the permission of SCA Australia Pty Ltd. SCA Australia Pty Ltd and Unicla expressly disclaim
all and any liability and responsibility to any person or business as a result of any actions taken on the
basis of information in this Bulletin. Manufacturers specifications must be consulted for specific
guidelines and performance data.
PAGE 15 of 21
Therefore with reference to the performance chart ( table 4) the 7.034 kW is obtained at just
below 2000 r/min. Even though it is only a 6.8 kW coil in the absence of that specification the
TX is the only form of capacity measurement we have Ð even though it is slightly higher than the
actual capacity of the system it is a guide to compressor selection.
In the absence of any data, low side pressures can be used as an indicator of compressor
capacity and / or efficiency. The inability to Òpull downÓ the low side to acceptable / normal levels
may indicate a compressor with the inability to pull refrigerant through the evaporator at an
acceptable rate comparative to the feed rate of the TX Valve or Orifice Tube. Whilst this is a
common practice there are considerable dangers associated with it Ð as presented here.
Since the low side pressure is determined in principle by the TX valve feed rate compared to the
evaporator pull rate (suction) it must be validated that the TX is the correct size, calibrated
correctly, being ÒfedÓ with liquid at nominated pressures and charge rates correct.
In addition to the variable flow of the TX Valve / Orifice Tube, evaporator and suction line
pressure drops can make this form of compressor capacity validation virtually useless. A
vehicle fitted with an evaporator or suction line exhibiting high pressure drop can lead to the
low side ÒpullingÓ extremely low in normal operation. With an undersize compressor and
this condition the low side pressures may appear ÒnormalÓ Ð whereas in reality it is a system with
high evaporator / suction line pressure drops coupled to an ineffective / undersize compressor.
If the compressor is the correct size the low side will pull extremely / abnormally low because of
the pressure drop in this case.
Pressure analysis should only be used by experienced technicians with substantial associated
testing for TX flow rates, pressure / temperature drop analysis etc.
Example
System is fitted with 2 x 4,300 kcal / hr evaporators (2 x 5kW) (2 x 1.5 Ton TX Valves)
Copyright Ó2001. All rights reserved. No part of this document shall be reproduced in whole or in part
without the permission of SCA Australia Pty Ltd. SCA Australia Pty Ltd and Unicla expressly disclaim
all and any liability and responsibility to any person or business as a result of any actions taken on the
basis of information in this Bulletin. Manufacturers specifications must be consulted for specific
guidelines and performance data.
PAGE 16 of 21
From the two graphs (over - page 16. )
Compressor 2 is the compressor of choice. Fitting of compressor 1 will only provide for a total
capacity of 6000 Ð 7600 kcal at the nominated speed of 1500 Ð 2000 r/min.
Compressor 2 provides a capacity of 8,000 Ð 9,600 kcal / hr Ð adequate for peak efficiency at
the nominated compressor speed.
12 OPERATING CONDITIONS
4
Model SAMPLE
Displacement 200 cc/rev.
2 Cylinders 10
Max. speed 4,500 r.p.m.
1 2 3 4 NOTE:
All or selected items may be
Compressor speed (x 1/000 r/min) published dependent on the
compressor and its application
Copyright Ó2001. All rights reserved. No part of this document shall be reproduced in whole or in part
without the permission of SCA Australia Pty Ltd. SCA Australia Pty Ltd and Unicla expressly disclaim
all and any liability and responsibility to any person or business as a result of any actions taken on the
basis of information in this Bulletin. Manufacturers specifications must be consulted for specific
guidelines and performance data.
PAGE 17 of 21
GRAPH 7 COMPRESSOR 2 PERFORMANCE
14 OPERATING CONDITIONS
8
SPECIFICATIONS
6 Model SAMPLE
Displacement 313 cc/rev.
4
Cylinders 10
Max. speed 4,500 r.p.m.
2
0 1 2 3 4
On dual evaporator systems with one circuit isolated (normally done by a magnetic switching
valve). The low side may pull abnormally low. Careful system design and compressor matching
is required to ensure the low side does not pull into a vacuum in this position. A balance
between efficiency and maintaining position low side pressure is a requirement of compressor
selection in many dual evaporator systems. Ie a large capacity compressor may achieve good
efficiency for a vacuum Ð this is an undesirable condition. An oil separator may be required in
dual evaporator systems.
Copyright Ó2001. All rights reserved. No part of this document shall be reproduced in whole or in part
without the permission of SCA Australia Pty Ltd. SCA Australia Pty Ltd and Unicla expressly disclaim
all and any liability and responsibility to any person or business as a result of any actions taken on the
basis of information in this Bulletin. Manufacturers specifications must be consulted for specific
guidelines and performance data.
PAGE 18 of 21
The power consumption graph is principally used in standby applications where an electric motor
is being used to drive the pump at a nominated r/min. By referring to this graph a standby motor
selection can be made and drive ratioÕs calculated.
8
Power consumption (PS) (KW)
OPERATING CONDITIONS
SPECIFICATIONS
2
Model SAMPLE
Displacement 200 cc/rev.
Cylinders 10
0 1 2 3 4 Max. speed 4,500 r.p.m.
Compressor speed (x 1/000 r/min)
COP is the ratio between the output (measured in cooling capacity) and the input required to
drive the compressor (power consumption). COP in simple terms is output compared to input.
If we input 2.1 kW and output 3.15 kW the COP is 1.5. This COP value will vary with
compressor speed since the dynamics of the system will change as flow rates, internal
resistances, heat absorption and rejection rates etc vary.
A principle factor in COP is the refrigerant being used and the conditions under which the test is
being conducted. All testing must be against a standard as previously identified.
Copyright Ó2001. All rights reserved. No part of this document shall be reproduced in whole or in part
without the permission of SCA Australia Pty Ltd. SCA Australia Pty Ltd and Unicla expressly disclaim
all and any liability and responsibility to any person or business as a result of any actions taken on the
basis of information in this Bulletin. Manufacturers specifications must be consulted for specific
guidelines and performance data.
PAGE 19 of 21
Compressor Capacity & Horsepower Graph
8.0
2.0
C.O.P
6.0
(kW)
Refrigerating
1.5
C.O.P.
Capacity
4.0
1.0
Power
Consumption
2.0
0.5
Copyright Ó2001. All rights reserved. No part of this document shall be reproduced in whole or in part
without the permission of SCA Australia Pty Ltd. SCA Australia Pty Ltd and Unicla expressly disclaim
all and any liability and responsibility to any person or business as a result of any actions taken on the
basis of information in this Bulletin. Manufacturers specifications must be consulted for specific
guidelines and performance data.
PAGE 20 of 21
SUMMARY Ð COMPRESSOR SELECTION
The principle selection criteria is the capacity of the compressor must match
the capacity of the evaporator(s) (system) under the nominated operating
conditions (compressor speed)
Copyright Ó2001. All rights reserved. No part of this document shall be reproduced in whole or in part
without the permission of SCA Australia Pty Ltd. SCA Australia Pty Ltd and Unicla expressly disclaim
all and any liability and responsibility to any person or business as a result of any actions taken on the
basis of information in this Bulletin. Manufacturers specifications must be consulted for specific
guidelines and performance data.
PAGE 21 of 21