1) General Concept of Subutation:-: Fig. 1 - High Voltage Substation
1) General Concept of Subutation:-: Fig. 1 - High Voltage Substation
Electrical power station, substations and power lines are intended for
generating, transmitting and distributing electrical energy among users. In present day
electrical power system is A.C. i.e. electrical power is generated, transmitted and
distributed in the form of alternating current. The electrical power is produced at the
power stations which are located at favorable places. It is deliverable to the customer
through a large network of transmission and distribution. This is accompanied by
suitable apparatus called substation.
and municipal utilities. The break down in the production process may result in damage
to the products on line and to the production equipment.
Power users are sensitive not only to the power failures but also to
variation from rated supply line voltage and frequency. A voltage drop slows down the
electric motors abruptly, browns out electric device, radio and TV sets, etc. A decreases
of output of the driven machinery and often involve a break down in production process
and hence the manufacture of defective products. Therefore if a specific component of
electric power plant is out of order, or its performance is erratic, it should be quickly
disconnected from the supply lines in order to reduce the harmful consequences of the
failures.
The voltage of generator at the power plants is usually, 6.6, 13.2 or
15.7 KV to transmit the power over long distances the power and the distance in order
to reduce transmission losses and to affect the economy also the customer do not use
such high voltage and so they must be transferred to 11 KV by means of the transformer
as s/s which is further stepped down at 230 V phase to neutral by means of pole
mounted transformer. Thus s/s may be called as link between the generator and
consumer.
1.1 substation :-
“The assembly of apparatus used to change some characteristic (e.g.
voltage, current, frequency, p.f. etc.) of electric supply is called a Sub-station.”
400 KV Bus
500 MVA
400/220 KV Transformer
220 KV Bus
The following are the important points which must be kept in view
while laying out a substation :-
2. It should provide safe and reliable arrangement. For safety, consideration must be
given to the maintenance of regulation clearances, facilities, for carrying out repairs and
maintenance, abnormal occurrences of regulation such as possibility of explosion or fire
etc.
There are several ways of classifying substations. However, the two most important
ways of classifying them are according to (1) service requirement, (2) constructional
future.
Location of substations:-
Sub transmission circuit should reach as near the load possible and
practicable in order to take advantage of sub transmission voltage before it is stepped
down. It would, however, be a fallacy to extend these circuits to such a point that their
additional cost would exceed the savings in distribution circuit. The balance is
influenced greatly by the size and spacing of substations as well as the difference in
voltage.
6. The loads on the substations should be within such limit that an unduly large area or
number of consumers will not be affected in case the station is shut down.
7. Cost of the land is less.
8. It should provide safe and reliable arrangement.
9. It should easily operate and maintained.
2.1 INTRODUCTION:-
There are nine substation of 400 KV in Gujarat electricity board
FIRST at ASOJ which supplies power to north Gujarat 20 % of G.E.B power is
supplies via SOJA substation. It covers 95 % of demand of north Gujarat. SECOND is
SOJA substation, which supplies power to south Gujarat. THIRD is JETPUR which
supplies power to saurashtra. FOURTH substation is KASOR in kheda. FIFTH is near
CHORANIYA at limdi highway. SIXTH is VADAVI and SEVEN is HADALA. EIGHTH
is at KANSARI and NINE is AMRELI. And one substation is under construction at
KOSAMBA of SCADA base.
GETCO
400 KV SOJA S/S
FAULT LEVEL
400 KV 220 KV
The layout of substation is done in such a way that the equipment flexible,
no. of circuit is limited it the equipment of the load, and the no. Of circuit breakers is
reduced. The double bus sections are provided where necessary and the correct size
of equipment is chosen. The layout of the equipment in the substation should be
such as to avoid consequential damage in case of faults and should have protection.
The layout should provide case of inspection and maintenance of the equipment.
Fire proof and explosion proof screens and brickwork walls for separation out parts
of the equipment for safety should be provided.
DATA OF COMMISSIONING:-
400/220/33 KV TRANSFORMER-1 16/01/1987
26/11/1986
= 500 MVA
WINDING : 55’’C
3.4 CIRCUIT-BREAKERS:-
Most of the breakers installed at this S/S are ABCB. Working
pressure for these is 27-31 kg/cm 2. In other S/S the working pressure of breaker is
17-21 kg/cm2. When the air is fed in the CB. The center air resaved plant is providing
the air to the CB. Compressors having capacity of 58 kg/cm 2 also work
simultaneously. In SOJA per compressors 5 kg/m2 capacity is for air resurved.
3.5 REACTORS:-
Shunt reactor is used for long E.H.V. transmission lines to control
voltage during low load period and to compensate shunt capacitance of transmission
line during low load periods. In soja S/S reactor is provided on 400 KV side to control
voltage which is oil filled usually switched when it is necessary to control voltage it is
switch on from remote.
Micro mho:-
P- 40 :-
disturbed and gets printed immediately on printer. This of fault condition and pre
fault condition except 400KV S/S are now here such facilities are provided.
3.14 CONDUCTOR:-
An insulator, also called a dielectric, is a material that resists the flow
of electric current. An insulating material has atoms with tightly bonded valence
electrons. These materials are used in parts of electrical equipment, also called
insulators or insulation, intended to support or separate electrical conductors
without passing current through themselves. The term is also used more specifically
to refer to insulating supports that attach electric power transmission wires to utility
poles or pylons.
In SOJA ACSR conductor are used. In ACSR 54 Al. and 7 copper conductor are used.
Some materials such as glass, paper or Teflon are very good electrical
insulators. A much larger class of materials, for example rubber-like polymers and
most plastics are still "good enough" to insulate electrical wiring and cables even
though they may have lower bulk resistivity. These materials can serve as practical
and safe insulators for low to moderate voltages (hundreds, or even thousands, of
volts).
3.14.1 Breakdown:-
3.14.2 Uses:-
Insulators are commonly used as a flexible coating on electric wire and
cable. Since air is an insulator, no other substance is needed to "keep the electricity
within the wires." However, wires which touch each other will produce cross
connections, short circuits, and fire hazards. In coaxial cable the center conductor
must be supported exactly in the middle of the hollow shield in order to prevent EM
wave reflections. And any wires which present voltages higher than 60V can cause
human shock and electrocution hazards. Insulating coatings prevent all of these
problems.
In electronic systems, printed circuit boards are made from epoxy plastic and
fiberglass. The nonconductive boards support layers of copper foil conductors. In
electronic devices, the tiny and delicate active components are embedded within
nonconductive epoxy or phenol plastics, or within baked glass or ceramic coatings.
In high voltage systems containing transformers and capacitors, liquid insulator oil is
the typical method used for preventing sparks. The oil replaces the air in any spaces
which must support significant voltage without electrical breakdown. Other methods
of insulating high voltage systems are ceramic or glass wire holders and simply
placing the wires with a large separation, using the air as insulation.
3.14.4 Material:-
Insulators used for high-voltage power transmission are made from
glass, porcelain, or composite polymer materials. Porcelain insulators are made from
clay, quartz or alumina and feldspar, and are covered with a smooth glaze to shed
water. Insulators made from porcelain rich in alumina are used where high
mechanical strength is a criterion. Porcelain has a dielectric strength of about 4–10
kV/mm. Glass has a higher dielectric strength, but it attracts condensation and the
thick irregular shapes needed for insulators are difficult to cast without internal
strains. Some insulator manufacturers stopped making glass insulators in the late
1960s, switching to ceramic materials.
The electrical breakdown of an insulator due to excessive voltage can occur in one of
two ways:
• Puncture voltage is the voltage across the insulator (when installed in its normal
manner) which causes a breakdown and conduction through the interior of the
insulator. The heat resulting from the puncture arc usually damages the insulator
irreparably.
• Flashover voltage is the voltage which causes the air around or along the surface
of the insulator to break down and conduct, causing a 'flashover' arc along the
outside of the insulator. They are usually designed to withstand this without damage.
Most high voltage insulators are designed with a lower flashover voltage than
puncture voltage, so they will flashover before they puncture, to avoid damage.
FIG.Cap and pin insulator string (the vertical string of discs) on a 275 kV suspension pylon.
Higher voltage transmission lines use modular cap and pin insulator
designs (see picture above). The wires are suspended from a 'string' of identical disk-
shaped insulators which attach to each other with metal clevis pin or ball and socket
links. The advantage of this design is that insulator strings with different breakdown
voltages, for use with different line voltages, can be constructed by using different
numbers of the basic units. Also, if one of the insulator units in the string breaks, it
can be replaced without discarding the entire string. They are constructed of a
ceramic or glass disk with a metal cap and pin cemented to opposite sides. In order to
make defective units obvious, glass units are designed with Class B construction: an
overvoltage causes a puncture arc through the glass. The glass is heat-treated so it
will shatter, making the damaged unit visible. However the mechanical strength of
the unit is unchanged, so the insulator string will stay together. Standard disk
insulator units are 10 inches (25 cm) in diameter and 53⁄4 in (15 cm) long, can support
a load of 80-120 kN (18-27 klbf), have a dry flashover voltage of about 72 kV, and are
rated at an operating voltage of 10-12 kV.[5] However, the flashover voltage of a
string is less than the sum of its component disks, because the electric field is not
distributed evenly across the string but is strongest at the disk nearest to the
conductor, which will flashover first. Metal grading rings are sometimes added
around the lowest disk, to reduce the electric field across that disk and improve
flashover voltage.
Line voltage
Disks
(kV)
34.5 3
46 4
69 5
92 7
115 8
138 9
161 11
196 13
230 15
287 19
8TH Sem Electrical Engg. Page 25
345 22
360 23
STUDY ABOUT HIGH VOLTAGE SUBSTATIONS.
tension, so it can withstand greater load, and that if the insulator breaks the cable
ends will still be linked.
“The phenomenon of violet glow, hissing noise and production of ozone gas in
an overhead transmission line is known as corona.”
2) Conductor size: - the corona effect depends upon the shape and condition of
the conductors. The rough and irregular surface will give rise to more coronas
because unevenness of the surface decreases the value of breakdown voltage.
4) Line voltage: - the line voltage greatly affects corona. If it is low, there is no
change in the conductor of surrounding the conductor and hence no corona is
formed.
Corona loss:-
“ The power is dissipated in the power system due to corona
discharge is known as corona loss.”
When the surface voltage gradient at line conductor exceeds the critical breakdown
stress, corona appears and energy is dissipated in form of light and heat. This called
corona loss.
I. Effect of frequency
II. Effect of system voltage
III. Effect of conductivity of air
IV. Effect of conductor diameter
V. Effect of conductor’s surface
VI. Effect of atmospheric condition
Advantages:-
1. Due to corona formation, the surrounding the conductor becomes
conducting and hence virtual diameter of the conductor is increased.
Disadvantages:-
1. Corona is accompanied by a loss of energy. This affected the transmission
efficiency of the line.
2. Ozone is produced by corona and may cause corrosion of the conductor
due to chemical action.
In substation corona losses are less produced in round shape. So corona is reduces
by using the corona ring.
The CB plays an important role in the design and performance of power system
during normal operating condition. A circuit breaker is a switching and current
interrupting device in switchgear.
Operation:-
All circuit breakers have common features in their operation, although details vary
substantially depending on the voltage class, current rating and type of the circuit
breaker.
In low-voltage circuit breakers this is usually done within the breaker enclosure.
Circuit breakers for large currents or high voltages are usually arranged with pilot
devices to sense a fault current and to operate the trip opening mechanism. The trip
solenoid that releases the latch is usually energized by a separate battery, although
some high-voltage circuit breakers are self-contained with current transformers,
protection relays, and an internal control power source.
Once a fault is detected, contacts within the circuit breaker must open to interrupt
the circuit; some mechanically-stored energy (using something such as springs or
compressed air) contained within the breaker is used to separate the contacts,
although some of the energy required may be obtained from the fault current itself.
Small circuit breakers may be manually operated; larger units have solenoids to
trip the mechanism, and electric motors to restore energy to the springs. The circuit
breaker contacts must carry the load current without excessive heating, and must
also withstand the heat of the arc produced when interrupting the circuit. Contacts
are made of copper or copper alloys, silver alloys, and other materials. Service life
of the contacts is limited by the erosion due to interrupting the arc. Miniature and
molded case circuit breakers are usually discarded when the contacts are worn, but
power circuit breakers and high-voltage circuit breakers have replaceable contacts.
Finally, once the fault condition has been cleared, the contacts must again be closed
to restore power to the interrupted circuit.
Arc interruption:-
Miniature low-voltage circuit breakers use air alone to extinguish the arc. Larger
ratings will have metal plates or non-metallic arc chutes to divide and cool the arc.
Magnetic blowout coils deflect the arc into the arc chute. In larger ratings, oil circuit
breakers rely upon vaporization of some of the oil to blast a jet of oil through the
arc. Gas (usually sulfur hexafluoride) circuit breakers sometimes stretch the arc
using a magnetic field, and then rely upon the dielectric strength of the sulfur
hexafluoride (SF6) to quench the stretched arc. Vacuum circuit breakers have
minimal arcing (as there is nothing to ionize other than the contact material), so the
arc quenches when it is stretched a very small amount (<2–3 mm). Vacuum circuit
breakers are frequently used in modern medium-voltage switchgear to 35,000
volts. Air circuit breakers may use compressed air to blow out the arc, or
alternatively, the contacts are rapidly swung into a small sealed chamber, the
escaping of the displaced air thus blowing out the arc. Circuit breakers are usually
able to terminate all current very quickly: typically the arc is extinguished between
30 ms and 150 ms after the mechanism has been tripped, depending upon age and
construction of the device.
Under short-circuit conditions, a current many times greater than normal can exist
(see maximum prospective short circuit current). When electrical contacts open to
interrupt a large current, there is a tendency for an arc to form between the opened
contacts, which would allow the current to continue. Therefore, circuit breakers
must incorporate various features to divide and extinguish the arc. In air-insulated
and miniature breakers an arc chutes structure consisting (often) of metal plates or
ceramic ridges cools the arc, and magnetic blowout coils deflect the arc into the arc
chute. Larger circuit breakers such as those used in electrical power distribution
may use vacuum, an inert gas such as sculpture hexafluoride or have contacts
immersed in oil to suppress the arc. The maximum short-circuit current that a
breaker can interrupt is determined by testing. Application of a breaker in a circuit
with a prospective short-circuit current higher than the breaker's interrupting
capacity rating may result in failure of the breaker to safely interrupt a fault. In a
worst-case scenario the breaker may successfully interrupt the fault, only to
explode when reset.
Miniature circuit breakers used to protect control circuits or small appliances may
not have sufficient interrupting capacity to use at a panel board; these circuit
breakers are called "supplemental circuit protectors" to distinguish them from
distribution-type circuit breakers.
Classification of CB:-
The type of CB is usually classified according to the medium of arc extinction and is
as follow:-
1. Air break CB, miniature CB
2. Air blast circuit CB (A.B.C.B.)
3. Oil filled CB
4. Minimum oil CB
5. SF6 CB
6. Vacuum CB
COSTRUCTION OF AN A.B.C.B.:-
In A.B.C.B high pressure air is forced on the arc through a nozzle at the instant of
contact separation. The ionized medium between the contacts is blown away by the
blast of the air. The ionized medium between the contacts is blown away by the
blast of the air. After the arc extinction the chamber is filled with high pressure air
which prevents restike. In some low capacity C.B. the isolator is an integrals part of
the C.B. the C.B. opens and immediately after that the isolator opens.
The EHV- A.B.C.B. is outdoor equipment. The air pressure in the receivers of the C.B.
is of the order of 20-30 kgf/cm2. The local receivers are of such a size that the air
pressure is maintained for some 4 to 12 repeated operations. When the pressure in
the receiver of the breaker recues below a certain limit {say 20 kgf/cm 2} the
pneumatic valves automatically open and air system of higher pressure {30 to 40
kgf/cm2} and pressure in the air receiver in maintained a desired value.
MAKE : A.B.B.
REATED VOLTAGE : 420 KV
FREQUENCY : 50 Hz
NORMAL CURRENT : 2000 AMP
BREAKING CURRENT : 37.5 KA
OUT OF PHASE CURRENT : 7.78 KA
SHORT TIME CURRENT : 31.5 KA TO 35 KA
TRIP COLI VOLTAGE : 220 V D.C.
CLOSE COIL VOLTAGE : 220 V D.C.
RIL AT 50 Hz : 680 KV
IMPULSE VOLTAGE : 1.2/50 MS, 1425 KV PEAK
AWITCHING IMPULSE : 1050 KV
MASS : 3120 kgS
OPERATING PRESSURE : 27.21 Kg/Cm2
MAKE : A.B.B.
REATED VOLTAGE : 245 KV
FREQUENCY : 50 Hz
MARITS:-
Air can be used at high pressure.
Reliable operation due to external source of extinguishing energy.
Free from decomposition.
Clean, non inflammable.
Freely available everywhere.
Suitable pressure, the small contract travel is enough.
High speed of operation.
Rapid auto recourse.
Clean service no need of maintenance of oil.
The risk of fore is eliminated.
Demerits:-
The air has relatively inferior arc extinguishing properties.
The air blast C.B. is very sensitive to the variation in the rate of rise of
restricting voltage.
Considerable maintenance is required for the compressor plant which
supplies the air blast.
SF6 is an inter gas having good dielectric and arc extinguishing properties. The
dialectic strength of the gas increased with pressure and is more than that of
dielectric of oil at a pressure of 3 kg/cm 2. Several types of SF6 C.B. have been
developed by various manufactures for rated voltage 3.6 KV to 760 KV.
At SOJA S/S in 220 KV yard single pressure type C.B. are used and in 400 kv yard
double pressure type are used.
4.2.1 FUNCTION:-
In SF6 C.B. gas is used as an arc quenching medium dielectric strength of SF 6 gas is
more than that of air so the process of arc extinction is fast.In fig. shown single
pressure puffer SF6 C.B. the two interrupters are mounted on hollow support
insulator. The principal of are interruption is illustrated in fig. the operating
mechanism installed at the base of the insulator is linked with the movable contact
in the interrupter by means of insulating operating rod and a link mechanism.
During the operating operation, the operating rod is pulled down motion in to
horizontal motion. The link mechanism converts thee vertical. The contact and the
movable cylinder in the interrupter are moved against the fixed position.
ADVANTAGES:-
Due to superior arc quenching properly of SF6, such C.B. has very short
arcing time.
Since the dielectric strength of SF6 is 2 to 3 times, such C.B. can interrupt
much larger currents.
The SF6 C.B>gives noiseless operation due to its closed gas circuit and no
exhaust to atmosphere unlike the air blast circuit breaker.
The closed gas enclosure keeps the interior dry so that there is no
moisture problem.
There is no risk of fire.
There are no carbon deposits.
No frequent contact replacement.
No over voltage problems.
DISADVANTAGES:-
SF6 BREAKER is costly due to high cost of SF6.
Since SF6 gas has to be reconditioned after every operation of the breaker,
additional equipment is required for this purpose.
Double pressure sf6 C.B. is very costly.
MAKE : A.B.B.
Va : 220 V D.C.
FREQUENCY : 50 Hz
VW : 1425 KV
VS : 1050 KV
MAKE : A.B.B.
RIL AT 50 Hz : 460 KV
BREAKING SYM : 40 KA
SYSM : 48 KA
MASS : 2310 kg
As shown the basic form of a surge diverter. It consists of a spark gap in series with
a non-liner resistor. One end of the diverter is connected to the terminal of
equipment to be protected and the other end is effectively ground. The length of the
gap is so set that normal line voltage is not enough to cause an arc across the gap
but a dangerously high voltage will break down the air insulation and form an arc.
The property of the non-liner resistance is that its resistance decreases as the
voltage increase and vice versa. LA should not carry any current during the normal
operation. But during the over voltage surges are must provide and easy path to the
earth. It means that power frequency is not function when abnormal frequency is
applied. When the voltage is normal the resistance of L.A. is high and when the
voltage is high the resistance of L.A. is low. The L.A. is worked on this function.
The following are the different types of L.A. which are commonly used.
1. Rod gape arrestor
2. Sphere gap arrestor
3. Horn gap L.A.
4. Impulsive protective gap with electrolyte L.A.
5. Expolsion type L.A.
6. Electrolytic type L.A.
7. Lead oxide peroxide type
8. Pellet type peroxide type
9. Thyrite type
10. Valve type
SELACTION OF L.A.:-
It should take no current during normal power frequency condition.
Transient over voltage of L.A. more than insulation withstand level should
be diverted to earth.
The voltage across arrestor during discharge should not be too low or too
high.
Normal condition should be restored soon after the surge has been
diverted.
When L.A. is connected between phase and earth the rated voltage of arrestor must
be equal of more than the highest r.m.s .value of the power frequency voltage which
can applied to it under normal condition.
4.4 ISOLATORS:-
INTRODUCTION:-
Isolator are disconnecting switches which operates under no load condition
isolator are designed to open and close under no load condition. Isolator does not
have any specified current breaking or current making capacity.
Isolator cannot open if C.B. is open and cannot be closed unless the C.B. is closed.
TYPES OF ISOLATORS:-
Vertical break type
Horizontal break type
Center break
Double break
Vertical pantograph type
At SOJA S/S in 400 KV yard pantograph isolator and center break are used. While in
220 KV yard center break isolator are used.
PENTOGRAPH ISOALTOR:-
It is shown fig. the construction of a typical pantograph isolator while closing the
linkage of pantograph are brought nearer by rotating there insulator column. In
closed position the upper two arms of the pantograph close on the overhead station
bus bar given a grip. The current is carried by the upper bus bar to the lower bus
bar through the conducting arms of the pantograph. While operating the rotating
insulator column is rotated about its axis. There by the pantograph blades collapses
isolator in vertical plane and vertical isolation is between the lines terminal and
pictograph upper terminal isolator cover less floor area. At SOJA S/S pantograph
isolator are operated manually and by electric motor mechanism both.
VOLTAGE : 420 kV
FREQUENCY : 50 Hz
Ith : 40 KA
Vb : 1425 KV
Vs : 1050 KV
VM = 415 V D.C.
FREQUENCY : 50 Hz
FREQUENCY : 50 Hz
Normally the earthing switches are mounted on the frame of the isolator.
WHILE OPENING:-
Open C.B. at both end S/S (first receiving end and then the at sending end)
Open isolator -do-
Close earthing switch -do-
WHILE CLOSING:-
Open Earthing switch at both end S/S
Close Isolator -do-
Close C.B. -do-
4.6 Transformer:-
Basic Concepts:-
on a common laminated magnetic core. The winding connected to the A.C source is
called primary winding and one connected to the load is called the secondary
winding. The A.C voltage whose magnitude is changed is connected to the primary
winding. Depending upon the numbers of turns of primary and secondary an
alternating e.m.f is induce in secondary. This induce e.m.f in the secondary causes a
secondary current. Consequently, terminal voltages appear across the load. If
secondary voltage is greater than the primary voltage so it called as step up
transformer, and if it less then so it called as step down transformer.
Working:-
When an alternating voltage is applied across the primary, due to that the current
flows from the core. According to this an alternating flux is produce in the core. This
flux links the both windings and induces e.m.f. according to the Faraday’s law of
electromagnetic induction.
However in the practice, these losses are very small so that output power is nearly
equal to the input primary power. So transformer has very high efficiency.
1. TOP
Core type PLATE.
transformer, Shell type transformer
2. Tap changing transformer
3.
Cooling fan
Auto Transformer
The main disadvantages of this type are that it can’t be used for tap changing at on
load.
CURRENT TRANSFORMER:-
INTERDUCTION:-
CONSTRUCTION:-
The C.T. has a two winding one is primary second is secondary winding. The
primary conductor is at high voltage w.r.t. earth. Hence it is insulated by means of
an insulator column filled with dielectric oil. The secondary winding conductor is
then wound on the insulated core in the form of tutorial winding by hand winding
or insulation resistance as two mega ohms. A polarity marking are properly done
after a careful check. The connection of the various leads from the secondary
winding should be marking. The normal rated secondary current is 5.0. Amp.
Sometimes the current of 5.0 amps or 1.0 amp are also taken as second any current
some also details is shown in figure.
B.I.L. : 420/630/1475 KV
FREQUENCY : 50 Hz
I(thermal) : 40 KA
TIME : 1 sec
RATIO : 2000/1000/500/1-1-1-1-1
POTENTIAL TRANSFORMER:-
INTRODUCTION:-
The function of the potential transformer is to transformer the higher voltage in an
electrical system to lower values which are convenient for the operation of
measuring instrument and protective device.
They also serve to isolate these instruments of device from the high voltage power
circuit.
1) ELECTROMAGNETIC TRANSFORMER:-
Electromagnetic transformer is that which primary and secondary are
wound on magnetic core like as usual as transformer. The construction is largely
depending in the reacted primary voltage. In higher voltage the 66 KV
electromagnetic PT’s are generally in cascade connections. They employ a no. of
series connected primary coils as to keep the effective leakage at a value so an
arrangement is in porcelain enclosure for high speed distance protection this type
of PT are preferred.
At SOJA S/S both P.T. are used for 400 KV and 220 KV.
TYPE : CVBA 420/1425
INTERMEDIATED VOLTS : 223 KV
TOTAL OUTPUT SIMULTANEOUS : 300 VA
OUTPUT MAX. : 750 VA at fix AMB
FREQUENCY : 50 Hz
INSULATION CLASS :A
4.7 RELAYS:-
two sets of contacts in the relay pictured is closed, and the other set is open. Other
relays may have more or fewer sets of contacts depending on their function. The
relay in the picture also has a wire connecting the armature to the yoke. This
ensures continuity of the circuit between the moving contacts on the armature, and
the circuit track on the printed circuit board (PCB) via the yoke, which is soldered
to the PCB.
Tripping relay, directional over current relay, definite time relay, control relay,
auxiliary relay, local breaker back up relay, trip CKT relay, numerical distance relay,
carrier relay, lock out auxiliary relay, direction earth fault relay, bus-bar
supervision relay, auto reclose relay, etc…
Types:-
1.Latching relay:-
Latching relay, dust cover removed, showing pawl and ratchet mechanism. The
ratchet operates a cam, which raises and lowers the moving contact arm, seen edge-
on just below it. The moving and fixed contacts are visible at the left side of the
image.
A latching relay has two relaxed states (bitable). These are also
called "impulse", "keep", or "stay" relays. When the current is switched off, the relay
remains in its last state. This is achieved with a solenoid operating a ratchet and
cam mechanism, or by having two opposing coils with an over-center spring or
permanent magnet to hold the armature and contacts in position while the coil is
relaxed, or with a remnant core. In the ratchet and cam example, the first pulse to
the coil turns the relay on and the second pulse turns it off. In the two coil example,
a pulse to one coil turns the relay on and a pulse to the opposite coil turns the relay
off. This type of relay has the advantage that it consumes power only for an instant,
while it is being switched, and it retains its last setting across a power outage. A
remnant core latching relay requires a current pulse of opposite polarity to make it
change state.
2. Reed relay:-
A reed relay has a set of contacts inside a vacuum or inert gas filled glass tube,
which protects the contacts against atmospheric corrosion. The contacts are closed
by a magnetic field generated when current passes through a coil around the glass
tube. Reed relays are capable of faster switching speeds than larger types of relays,
but have low switch current and voltage ratings.
3. Mercury-wetted relay:-
vertically to work properly. Because of the toxicity and expense of liquid mercury,
these relays are rarely specified for new equipment. See also mercury switch.
4. Polarized relay:-
A polarized relay placed the armature between the poles of a permanent magnet
to increase sensitivity. Polarized relays were used in middle 20th Century
telephone exchanges to detect faint pulses and correct telegraphic distortion. The
poles were on screws, so a technician could first adjust them for maximum
sensitivity and then apply a bias spring to set the critical current that would
operate the relay.
A machine tool relay is a type standardized for industrial control of machine tools,
transfer machines, and other sequential control. They are characterized by a large
number of contacts (sometimes extendable in the field) which are easily converted
from normally-open to normally-closed status, easily replaceable coils, and a form
factor that allows compactly installing many relays in a control panel. Although
such relays once were the backbone of automation in such industries as automobile
assembly, the programmable logic controller (PLC) mostly displaced the machine
tool relay from sequential control applications.
6. Contactor relay:-
A contactor is a very heavy-duty relay used for switching electric motors and
lighting loads. Continuous current ratings for common contactors range from 10
amps to several hundred amps. High-current contacts are made with alloys
containing silver. The unavoidable arcing causes the contacts to oxidize; however,
silver oxide is still a good conductor.[2] Such devices are often used for motor
starters. A motor starter is a contactor with overload protection devices attached.
The overload sensing devices are a form of heat operated relay where a coil heats a
bi-metal strip, or where a solder pot melts, releasing a spring to operate auxiliary
contacts. These auxiliary contacts are in series with the coil. If the overload senses
excess current in the load, the coil is de-energized. Contactor relays can be
extremely loud to operate, making them unfit for use where noise is a chief concern.
7. Solid-state relay:-
FIG. Solid relay, which has no moving, parts FIG. 25 A or 40 A solid state contactors
A solid state relay (SSR) is a solid state electronic component that provides a
similar function to an electromechanical relay but does not have any moving
components, increasing long-term reliability. With early SSR's, the tradeoff came
from the fact that every transistor has a small voltage drop across it. This voltage
drop limited the amount of current a given SSR could handle. As transistors
improved, higher current SSR's, able to handle 100 to 1,200 Amperes, have become
commercially available. Compared to electromagnetic relays, they may be falsely
triggered by transients.
A solid state contactor is a very heavy-duty solid state relay, including the
necessary heat sink, used for switching electric heaters, small electric motors and
lighting loads; where frequent on/off cycles are required. There are no moving
parts to wear out and there is no contact bounce due to vibration. They are
activated by AC control signals or DC control signals from Programmable logic
controller (PLCs), PCs, Transistor-transistor logic (TTL) sources, or other
microprocessor and microcontroller controls.
9. Buchholz relay:-
A Buchholz relay is a safety device sensing the accumulation of gas in large oil-
filled transformers, which will alarm on slow accumulation of gas or shut down the
transformer if gas is produced rapidly in the transformer oil.
A forced-guided contacts relay has relay contacts that are mechanically linked
together, so that when the relay coil is energized or de-energized, all of the linked
contacts move together. If one set of contacts in the relay becomes immobilized, no
other contact of the same relay will be able to move. The function of forced-guided
contacts is to enable the safety circuit to check the status of the relay. Forced-
guided contacts are also known as "positive-guided contacts", "captive contacts",
"locked contacts", or "safety relays".
Electric motors need over current protection to prevent damage from over-loading
the motor, or to protect against short circuits in connecting cables or internal faults
in the motor windings. [3] One type of electric motor overload protection relay is
operated by a heating element in series with the electric motor. The heat generated
by the motor current heats a bimetallic strip or melts solder, releasing a spring to
operate contacts. Where the overload relay is exposed to the same environment as
the motor, a useful though crude compensation for motor ambient temperature is
provided.
Applications:-
Several 30-contact relays in "Connector" circuits in mid 20th century 1XB switch
and 5XB switch telephone exchanges; cover removed on one
Protective relay:-
Providing the relay is free from dirt, the metal disc and the
spindle with its contact will reach the fixed contact, thus sending a signal to trip and
isolate the circuit, within its designed time and current specifications. Drop off
current of the relay is much lower than its operating value, and once reached the
relay will be reset in a reverse motion by the pressure of the control spring
governed by the braking magnet.
Distance relay:-
CLASSICAL TYPE:-
1. Impedance
2. Reactance
3. Mho or admittance
4. Ohm
5. Offset Mho
6. Modified impedance
NON-CLASSICAL TYPE:-
Buchholz relay
Oil temp relay
DLTC Buchholz relay
17 DTH-32 Transformer differential relay
18 CTL Thermal over load relay
19 GTT Natural displacement relay
20 VDG Phase comparison relay
21 P-40 Static distance protection relay
22 SHNB Static distance protection relay
1) Normal operation
2) Prevention of electrical failure
3) Reduction of damaging caused by electric failure.
Even with most care and also due to unforeseen circumstances it is not always
possible to prevent the electric failure.
The more detailed factors for transmission line protection directly address
dependability and security for a specific application. The protection system selected
should provide redundancy to limit the impact of device failure, and backup
protection to ensure dependability. Reclosing may be applied to keep the line in
service for temporary faults, such as lightning strikes. The maximum load current
level will impact the sensitivity of protection functions, and may require adjustment
to protection functions settings during certain operating circumstances. Single-pole
tripping applications impact the performance requirements of distance elements,
differential elements, and communications schemes. The physical construction of
the transmission line is also a factor in protection system application. The type of
conductor, the size of conductor, and spacing of conductors determines the
impedance of the line, and the physical response to short circuit conditions, as well
as line charging current. In addition, the number of line terminals determines load
and fault current flow, which must be accounted for by the protection system.
Parallel lines also impact relaying, as mutual coupling influences the ground
current measured by protective relays. The presence of tapped transformers on a
line, or reactive compensation devices such as series capacitor banks or shunt
reactors, also influences the choice of protection system, and the actual protection
device settings.
Particular at the SOJA substation there are three lines of 400 KV. Each line is
provided with its main protection and back up protection.
There is several method of protection of transmission lines.
The first group is of non-unit type of protection which includes:-
Such non unit type of protection of lines is unit type of protection. The
discrimination is obtained by conditioning the relay settings.
The other group of protection of line is unit type of protection. Such as pilot wire
is differential protection carrier protection etc.
through relay coil and the relay pick up. The relay contacts close, there by the trip
circuit is closed and the circuit breaker operates.
Phase comparison method compares the phase relation between current in the
protected zone and current leaving the protected zone.
At SOJA S/S, this type of protection made English electric know as P-40
scheme.
In this method single are send from each end of line and received at other end. The single
are relate to the current flow in mainline as they are derived from CT secondary current
when there is no fault the single is send for alternate ½ cycle form one end remaining half
from the other. The same condition holds good for external fault. As shown in fig. during
internal fault the current in one of the lines reverses in phase or differs in phase and
remains below the fault detector setting. So that carrier is sent only for half the time. The
relay is arranged to sense absence of single in the lines. Depending upon the setting the
tripping occurs when the phase angle between two single reaches a certain value normally
at 30.
Such protection is providing as primary protection only when no other primary bus
zone protection is applied. If other primary bus zone protection acts as back up
protection to the bus bar. Fig. shown principal on which it is acts.
The fault on bus can be sensed by over current of the incoming circuit and is
disconnected by opening of incoming circuit. The over current is protection of
incoming feeder gives protection to the bus.
DISADVANTAGES:-
Delayed action disconnection of more circuit in case there are two or more
incoming lines.
Zone not clearly be used so exact discrimination is not possible.
Referring to fig. again the bus. A is covered in second step of distance relay at
station B. thus foe a fault F on bus A the distance protection B will operate. The
operating time of the second step can be order of 0.4 second. Distance protection is
widely used in protection of transmission is widely used in protection of
transmission lines; hence it is often economical to use same as for bus protection.
LIMITATIONS:-
Protection is slow.
There can be unwanted disconnection of oil incoming paralleled circuits.
Due to the above limitation it is not desirable to use it as main protection for
important buses.
A Through fault is one which is beyond the protected zone of the transformer but
fed through the transformer. The unit protection of transformer should not operate
of through fault. The overload relaying may be provided to operate with a time lag
to provide backup protection. Internal fault are those in the proceed zone of the
transformer. These faults can be between phase to phase and phase to ground.
Transformers are a critical and expensive component of the power system. Due to
the long lead time for repair of and replacement of transformers, a major goal of
transformer protection is limiting the damage to a faulted transformer. Some
protection functions, such as over excitation protection and temperature-based
protection may aid this goal by identifying operating conditions that may cause
transformer failure. The comprehensive transformer protection provided by
multiple function protective relays is appropriate for critical transformers of all
applications.
The type of protection for the transformers varies depending on the application and
the importance of the transformer. Transformers are protected primarily against
faults and Overloads. The type of protection used should minimize the time of
disconnection for faults within the transformer and to reduce the risk of
catastrophic failure to simplify eventual repair. Any extended operation of the
transformer under abnormal condition such as faults or overloads compromises
the life of the transformer, which means adequate protection should be provided
for quicker isolation of the transformer under such conditions.
Transformer Failures:-
• winding failures due to short circuits (turn-turn faults, Phase-phase faults, phase-
ground, open winding)
• Core faults (core insulation failure, shorted laminations)
• Terminal failures (open leads, loose connections, short Circuits)
• On-load tap changer failures (mechanical, electrical, short Circuit, overheating)
• Abnormal operating conditions (over fluxing, overloading, overvoltage)
• External faults
LIMITATIONS:-
The relay is slow minimum operating time is 0.1 sec. average time 0.2 sec.
It is not economical to provide relay below 500 KVA.
This does not respond to a small arcing.
Earth fault protection senses earth current following are methods of earth fault
protection:-
Rusticated earth fault portion on differential protection.
Additional separate restricted earth fault protection.
Leakage to frame protection.
Neutral current relays.
6.1 INTRODUCTION:-
BATTERY 220 V D.C.:-
The storage batteries are installed in special room. The battery
room should have adequate ventilation and lighting. The floor and walls should be
acid resistance tiles. The battery cells are places on racks. The racks are placed on
porcelain insulators. The D.C. bus bars are flat copper sections or tabular copper
sections. The connections are made by soldering or brazing. The conductors are
covered by grease or electrolyte resistant varnish. The positive leads are painted
red and negative leads blue. Only acid-proof cables must be used upon D.C.
switchboard.
Without battery the relay will not operate and also C.B. the D.C. supply
is used for automatic control telemetering equipment, communication equipments,
interlocking equipment and emergency lightening system.
P.L.C.C.
STATION BATTERY
1. SUBSTATION BATTERY:-
MAKE: - Auto bat
CAP.:- 250 A.H.
VOLTAGE: - 220 V
NO. OF CELL: - 108*2
2. P.L.C.C.:-
MAKE: - Standard
CAP.:- 600A.H.
VOLTAGE: - 220 V
NO. OF CELL: - 25*2
Battery Set:-
► Battery is considered as the heart of sub-station.
220 V DC
► Single or double
110 V DC
► Single or double
48 V DC
Battery specifications:-
► Generally.. Telecom DC source.. 48 V dc.
► 50 V - 200 AH means Battery set is having 25 nos. of 2-Volts cells that can deliver…
Battery structure:-
► Hard rubber container
► Vent plug
► Electrolyte…H2SO4
Chemical Reaction:-
Pb + PbO2 + H2SO4
Discharge Charge
2 PbSO4 + H2O
Battery Charger:-
MAIN PARTS:-
1. FLOAT CHARGER
2. BOOTS CHARGER
Unless the UPS has protection for excess discharge, 1.75V per cell should
be selected to prevent battery damage. Battery discharge rates in kw at 25 0C are
given in table.
1. Rate of Discharge:-
AH rating decreases with increase in the rate of discharge. Due to rapid rate
of discharge cell potential falls significantly, due to internal losses. Weakling of acid
at higher discharge rate in porous plate is also greater at higher discharge rates.
This also affects the capacity adversely.
2. Temperature:-
Capacity of a battery is increase with increase in temperature.
3. Density of Electrolyte:-
As the density of electrolyte affects the internal resistance and the vigor of the
chemical reaction, it has an important effect on the capacity. Capacity is increase
with density.
1. Ampere-hour efficiency
2. Watt-hour efficiency.
1. AH Efficiency:-
The typical value of A-H efficiency is 90 to 95%.5 to 10% reduction is due to the
losses taking place in the battery. The ampere hour efficiency takes into account
only the current and time but it does not consider the battery terminal voltage at
all.
= 70-80% usually.
If the changing volts increases or discharge volts decrease then WH-efficiency will
also decrease. High charging and discharging rates will usually do this and hence
are not recommended.
6.3 MAINTENANCE:-
Do not adjust factory preset potentiometers in the printed circuit board.
Remove the dust collected inside the panel using blower or any other
suitable machine.
Check for any white/black/red tap opening on the capacitor. Replace the
blown capacitor (once in six months).
Check contactor power contact for wearing. Replace with spare kit (once in
year).
Maintain input AC voltage with it specified band. Normally it should be
around 415 V AC +/- 10 % /230 V AC +/- 10 %.
6.4 DO’S:-
Read “installation and operating manual” prior to installation of the
batteries.
Clean the batteries as and when dust accumulates.
The batteries if places in cubical, provide sufficient ventilation.
The terminal bolt connection to be torque in 10 Nm.
Re-torque the connection once every six month.
Keep the batteries away from heat source, sparks, etc.
Charge the batteries once every six months, if stored for long periods.
After a discharge recharge the batteries immediately.
Note down module voltage readings once, every one mouth.
Charge the batteries only at 13.5 v per module.
6.6 DONT’S:-
► Do not add water or acid
► Do not attempt to dismantle the battery
► Do not tamper with safety valves
► Do not over tighten the terminal bolts
► Do not allow any metal object to rest on the battery or fall across the
battery terminals
► Do not mix the batteries of different capacities of makes
► Do not install physically damaged cell
► Do not boots charge the batteries for more than 12 hours
The diagram of main connection are given on the front face of the panel, there
diagrams indicate the positions of the circuit breakers and isolators. The control
operator gets the ides as to which breaker open or closed. The controls of centrally
is in front of main control board. Separate control desks are provided for prime
movers and boilers.
CONSTRUCTION:-
The constructional features vary with the manufacturer and applications. However,
a general pattern can be described. The control and relay board are built of self
contained sheet steel cubicles. These cubicles are assembled on common channel
iron base plates according to the needs.
The cubicles are fabricated as follows: the angle ions or channel irons are cut
according to drawings. The pieces are welded to form the frame. Sheets are cut on
shearing machine to required sizes. They are placed on the frame at appropriate
position and are welded. The sheets of thickness 3 to 5 mm are used. The wiring is
suitable for 250 V and is generally of grade 7/0.029 cable. The standard color code
is generally used. Terminal blocks are used for connecting the wires.
SYNCHROINSING ARRANGEMENTS:-
The panel for synchronizing can be conveniently arranged on the upper portion of
the cubicle. The indicating instrument are show “incoming volts”, and “slow or fast”.
CUBICLE ARRENGMENTS:-
The cubicles are arranged in a line, side by side. Sometimes, the relay cubicles are
arranged back to back with their respective control cubicles, with a corridor on
between. The corridor is roofed and troughs are provided for wiring which run
between the control and relay panes. the operator’s control desk, personal
computer and video display screen. Event recorders are usually located at the
center of the control room. Mimic diagram boras is at the front.
PANEL TYPES:-
These are illustrated in figs. There are a variety of patterns. The dimensions of
cubicles are standardized.
(H)SCADA
Control Panel:-
► Semaphores
► Annunciation schemes
► TNC Switch
► DAS meter
► Annunciation Relay
Relay Panel:-
► Relays for:-
► Relays:-
Induction type
Static type
Thermal type
Numerical type
Metering Panel:-
PLCC Panel:-
PLCC Speech
Protection Coupler
RTU Panel
8.1 INTRODUTIONS:-
These functions can only be performed provided all the equipment
involved gives continuous all the equipment involved gives continuous troubles
free services under specified operating condition to meet this requirements, the
equipment has to be checked, attended to, trouble shooter, Operated under
specified conditions etc.
MANAGEMENT STRUCTRE:-
The staff engaged in operating the substation and power network is divided into
shift operators and maintenance men.
OPERATION:-
The shift operators keep watch on and attend to the electrical equipment in
operation, perform the switching operations, take out equipment for repair and put
it back into service after repair , adjust and record thr operation condition, quickly
find remind for any abnormal conditions, eliminate and emergency etc.
MAINTENANCE:-
Maintenance may be defined as the up keeping of any equipment in healthy or
working condition so as to get the following:
Reliable and effective operation
Optimum utilization
Availability
Reduced down time
Finding pre matured faults.
Minimization of revenue loss
EXECUTIVE:-
Substation in charge – 1
Shift operation – 4
Maintenance – 2
Total – 7
JUNIOR ENGINEER:-
Maintenance – 2
Total – 2
WORKMEN:-
Operation – 4
Maintenance – 4
Total – 8
BREAKDOWN MAINTENANCE:-
For low value and less important items only.
PREVENTIVE MAINTENANCE:-
Planned in advance.
Based on previous experience.
Based on guidance from equipment manufacturer.
Development of equipment maintenance schedules.
Preparation of annual maintenance plan.
MAINTENANCE SCHEDULES:-
A large percentage of failures of electrical equipments are due to a deteriorated
condition of the insulation, loose connection etc. many of these failures can be
anticipated by regular application of simple tests and timely maintenance. If the
failures are detected in the early stage it. The extent of damage can be reduced and
the equipment can be reconditioned put back into service.
In general the electrical equipment is capacity to communicate with
their ‘well –wishers’ through signals like heat, sound, vibration, etc.
The detection of incipient faults in electrical equipment depends upon
the possession of proper diagnostic tools, its effective use, correlation and proper
8.4 MAINTENANCE:-
DIFFERENT PERIODIC MAINTENANCE DONE AT SOJA
SUBSTATON:-
Following are the different types of maintenance taking place at the S/S. these
maintenance can be classified according to the periods in which they are done
DAILY MAINTENANCE:-
The readings of the pilot cell are taken.
The yard is observed daily if the inspector gets any abnormal smell then
that portion is attended.
Tree cutting the portion of trees touching the lines of very near to line are
cut so as to prevent short circuit.
The reading of certain meters which show critical factors such as
transformers temp. Are taken daily.
WEEKLY MAINTENANCE:-
The charger is switched off and voltage of each cell is measured.
The temp. And gravity of each cell is also noted with the voltage.
The solution in the cell has to be filled. This solution used is the distilled
water.
The contacts and terminals are cleared and petroleum Jelly is applied on
the contacts. This jelly helps in removing the products accumulated on contacts due
to acid in solution. Maintenance of compressor used for maintain pressure in ABCB
SF6 C.B. D.G. set is run every week for a check. The reading of the counter of lighting
arrestor is taken.
MOTHLY MAINTENNANCE:-
Compressors are used to maintain pressure in ABCB & SF 6 C.B. the oil used in
compressor for its functioning is replaced every three mouths.
YEARLY MAINTENCNANE:-
There are many type of relay used in substation.
The proper working of each and every relay is checked once in year.
9.1.2. Under earthing system measures, the metal covering body and enclosure of
all the equipments are connected to each other as a grid by means of appropriate
conductors to establish an equal zero level potential among all the points which
may come in contact with the operators. Zero potential, which is built-up and
applied to the earthing conductor grid, is produced by special earth wells and their
associated accessories.
9.1.4. Lightning, with its high electrical potential, is one of the most serious and
Dangerous environmental threats, which could cause severe damages to both
human Life and the installations. Lightning arresters, as part of the earthing system
in an Installation, are the protective devices, which avert the risks of lightings.
EARTHING:-
“The process of connecting the metallic frame of electrical
equipment or some electrical parts of the system to earth is called Earthing.”
1. Equipment Earthing:-
The process of connecting non-carrying metal parts of the electrical equipment to
earth in such a way that in case of insulation failure, the enclosure effectively
remains at earth potential is called equipment earthing.
The equipment earthing also helps in the earth fault protection. The earth fault
current from the equipment flows through the earthing system to the earth and is
sensed by proteation system and CB are opened. The fault equipment is then
repaied and recommission system earthed parts remain at approximatery earth
potential even during flow of fault current. The equipment earth ing ensures safety
to personnel.
2. System Earthing:-
“The process of connectimg some electrical part of the power system to earth is
called system Earthing.”
1. Earth Rods:-
Depending on the design for an specific earth well, a number of rods are driven into
the ground by means of hammering to form the main earthing electrode in the
earth well. In cases where two or more earth rods are to be driven, the individual
rods are coupled to each other by means of “earth rod coupling”.
1. During the driving of rod into the ground, and to protect the earth rod against
Impact of hammering, a “driving head” is screwed onto the top of the rod.
2. For easy and convenient driving of the earth rod into the ground an earth rod tip
With sharp point is screwed to the first rod.
3. Earth rods are used in installation of plain earthing well where, based on design
Specification of the earthing system the carbon bedding is not necessary and
Applicable.
2. Earthing Clamp:-
Earthing grid conductors are connected to the earth rods, already driven into
the ground, by means of earthing clamps. Connection is essentially made by tightly
Clamping of the grid conductor to the rod using the bolt and nut assembly of the
earthing clamp. Earthing clamps and associated bolts nuts, washers, etc. are made
of either brass or copper.
4. Electromagnetic interference:-
The earthing system ensure freedom from electromagnetic interference in
communication and data processing equipment in the substation .the control room
are provided with earthed screen in the walls and window to ensure ferrdom from
electromagnetic disturbances.
V/ I where V is measured voltage between the electrode and the voltage spike and
injected current during the earth resistance measurement through the electrode.
The desirable values of earth resistance measurement are:-
- For installation rated below 1000 V and earth fault current less than 500 A.
the earth resistance shall be less than 125/Is.
- For installation rated less than 2000kVA and 1000V the earth resistance
should not exceed 2 ohms.
Soil Resistivity
1. Based on the specification and location of the fault point, the fault current value
can be calculated and therefore predicted. Four factors are influential with respect
to the fault current value.
2. The value of voltage applied to the fault point.
3. The pure ohmic resistance of the fault point with respect to the ground, which
Includes the ohmic resistance of each individual well, as well as the earthing grid
Conductors and earthing is wires and earthing cables.
4. The number of rotating machineries (motors and generators) and their rated
power at the time of fault.
5. The distance between the fault point and the rotating machineries.
1. Earthing resistance for each individual earth well is measured by means of the
earth tester once the earth rods are driven into the ground or once the earthing
plates are positioned inside the carbon beddings.
2. The earthing resistance value measured for each earth well should not be lower
than the prescribed value in the design specifications.
3. In the event of greater earthing resistance that that of deemed and prescribed in
the design specification, the number of earth rods should be inevitably increased
and more rods shall be driven into the ground.
4. To drive the additional earth rods into the ground, following alternative ways
could be implemented depending on the existing condition of the earthing well
due improved.
4.1. Coupling of additional earth rods to the existing rods already driven, and
driving the new arrangement into the ground by means of hammering.
4.2. In cases where coupling of additional rods to the existing (already driven)
earth rods is not practically possible, the additional rods could be driven
somewhere in the close vicinity of the existing earth well to form a separate but
interconnected earth well. The overall earthing resistance is actually lower as a
result of two earth wells now in parallel.
4.3. To achieve a low earthing resistance, the normal practice in design of the
earthing system is to introduce three separate earth wells of similar specification in
form of a triangle configuration. Actually the overall earth resistance (with the
Wells interconnected) shall be one third of the value for each individual well.
5. Earthing resistance for the lightning protection system shall not exceed 5 OHM.
6. Earthing resistance for the power system earthing in power station and power
Plants shall not exceed 5 OHM.
7. Earthing resistance for the electrical earthing (equipment earthing) shall not
Exceed 4 OHM.
8. Earthing resistance for the electronic devices and instrumentations shall not
Exceed 1 OHM.
FIG. OF MAGGER
(a) : The neutral point of the transformer is connected to the Earth / Ground.
(b) : Earth connection due to poor / broken-down insulation
(c) : Line capacitance with respect to the ground
(d) : Transformer’s neutral point connected to the earth / ground
(e) : The floor of the area is wet and conductive
(f) : The floor of the area is insulated, but the connection is made by other
conductive material
10.1 Introduction:-
PLCC is commonly used for voice communication, telemetry,
telecontrolling purposes. Each end of the transmission line is provided with
identical carrier current equipment with frequency range 30 to 500 ks/s. the high
frequency signals are transmitted through the power lines.
The communication flow of today is very high. Many applications are operating at
high speed and a fixed connection is often preferred. If the power utilities could
supply communication over the power-line to the costumers it could make a
tremendous breakthrough in communications. Every household would be
connected at any time and services being provided at real-time. Using the power-
line as a communication medium Could also be a cost-effective way compared to
other systems because it uses an existing infrastructure, wires exists to every
household connected to the power-line network. The deregulated market has
forced the power utilities to explore new markets to find new business
opportunities, which have increased the research in power-line communications
the last decade. The research has initially been focused on providing services
related to power distribution such as load control, meter reading, tariff control,
remote control and smart homes. These value-added services would open up new
markets for the power utilities and hence increase the profit. The moderate
demands of these applications make it easier to obtain reliable communication.
Firstly, the information bit rate is low; secondly, they do not require real-time
performance. During the last years the use of Internet has increased. If it would be
possible to supply this kind of network communication over the power-line, the
utilities could also become communication providers, a rapidly growing market. On
the contrary to power related applications, network communications require very
high bit rates and in some cases real time responses are needed (such as video and
TV). This complicates the design of a communication system but has been the focus
of many researchers during the last years. Systems under trial exist today that
claim a bit rate of 1 Mb/s, but most commercially available systems use low bit
rates, about 10-100 kb/s, and provides low-demanding services such as meter
reading. The power-line was initially designed to distribute power in an efficient
way, hence it is not adapted for communication and advanced communication
methods are needed. Today’s research is mainly focused on increasing the bit rate
to support high-speed network Applications.
A. Coupling capacitor
B. Line trap unit
C. Tuning unit
D. Transmitter receiver etc.
A. Coupling capacitor:-
The carrier equipment is connected to the transmission line
through coupling capacitor which is such a capacitance that it offers low reactance
to the carrier frequency but high reactance power frequency. For example, 2000 pf
capacitor offers 1.5 mega ohms to 50 Hz and 150 ohms to 500 KHz.
B. LINE TRAP:-
Line trap unit is inserted between bus bar and connection of coupling
capacitor to the line. It is parallel turned circuit comprising L and C. it has low
impedance to 50 HZ and high impedance to carrier frequencies.
C. RUNING UNIT:-
The tuning unit is mounted inside the main coil on the tension rod. The tuning unit
is designed for one of the following:-
Single wave
Wide band
Double wave
Adjustable tuning
High frequency singles are transmitted through the transmission line conductor for
the purpose of communication, protection, signaling and monitoring. Carrier
current equipments are installed at the sending end and receiving end of
transmission line sections.
The power line carrier equipment can be used for the following:-
Wave trap is a parallel tuned inductor - capacitor 'tank' circuit made to be resonant at
the desired communication frequency. It is the effort to utilize the same transmission line
between two substations for the purpose of communications. At this communication
frequency the tank ckt provides high impedance and does not allow passing through them
& onto the substation bus & into transformers.
A wave trap is a special case of a band stop filter. It notches out one frequency, and
passes all others. Series tuned wave traps are placed across the transmission line, so that
its low impedance at the resonant frequency short-circuits the undesired frequencies,
while passing all others. The parallel resonant variety is placed in series with the
transmission line, and uses its high impedance at resonance to block further transmission
of the undesired signal.
Some wave trap circuits use both series and parallel forms. If the two wave traps are
tuned to the same frequency, then the attenuation at that frequency is increased. If the two
wave traps are tuned to two different frequencies, then the two traps will work
independently of each other with minimum mutual interference. The wave trap has the
same advantages as other filters. It also has the added advantage of taking out a single
strong signal that is causing most of the problem. For example, if you live close to an AM or
FM broadcast station, or a commercial land mobile radio station, then you might
experience various forms of interference due solely to that signal. A wave trap to notch out
the offending signal will work wonders for your reception on other frequencies.
The wave trap also has most of the disadvantages of the other forms of
filter. In addition, they must be tuned to the frequency of the undesired signal.
[Note: Half wavelength shorted transmission line stubs are often used as wave traps.]
Important points for wave trap:-
Line traps are either suspended from gantry or placed on pedestal
insulators.
For 400 KV, 220 KV, 132 KV & 66 KV.
Allows passing 50 Hz power frequency signal in to the switch-yard.
Low impedance to LF.
Blocks HF (50 kHz – 500 kHz) signals to enter into S/Y. High
impedance to HF.
Normal blocking band is 150 – 500 kHz.
INTRODUCTION:-
The use of Infrared Thermograph to evaluate the operating
condition of electrical, mechanical and process equipment for early warning signs
of impending failure has increased dramatically over the past few years. The
industry is forecast to continue growing at unprecedented rates, driven by the
following catalysts:-
Infrared cameras provide the means for which trained and qualified technicians can
examine the temperature distribution of plant equipment. Once a problem is
identified a decision is made based on the operating condition of equipment, to
either resolve the problem immediately, or continue to monitor the condition The
latter may involve using another monitoring technique to provide additional
information. Infrared condition monitoring techniques offer an objective way of
assessing the condition of plant equipment in order to predict the need for
maintenance.
BENEFITS OF THERMOGRAPHY:-
APPLICATIONS:-
SIGNIFICANT ADVANCES:-
The greatest single benefit of an FPA is its ability to generate high quality
images (Figure 1). In mechanically scanned single-element detectors, 14,000 to
26,000 picture elements make up the field-of-view. An FPA covering the same field-
of-view will comprise 65,000 to 262,000 pixels. This means the FPA will have 3 – 10
times more image detail. An image with higher resolution allows problems to be
identified without the camera operator having to change lenses, it enhances
analysis procedures and it provides an image that is easier to read and understand.
The FPA detector may be a significant breakthrough in technology but without
advancements in the optics, electronics and microprocessor technology it would
not have been the possible to develop these cameras. The interaction between
these components is important and it determines the diversity and quality of the
instruments available today.
FUTURE DEVELOPMENTS:-
The simplicity, flexibility, high performance and low cost will guarantee
the development of this technology.Initially, this technology will be used for
military, surveillance and process monitoring and control, but, watch this
technology as it is going to be a very interesting one. The interaction between these
components is important and it determines the diversity and quality of the
instruments available today.
Figure 1 - The image resolution of the two FPA images (right) are clearly superior
to the single element detector image (left), making identification and analysis easier.
INFRARED PROGRAM:-
Education:- The very first step is to find out some more about the products and
technology that are available and how they can be used.
CONCLUSION:-
1. CIRCUIT BREAKER:-
No of C.B : 8
Make : ABB
Capacity : 2000A
2. ISOLATOR:-
A. CENTER BREAK:-
No. of Isolator : 6
Make : S&S
Rating : 2000A
Type : RC 500 HGB
B. PENTOGRAPH:-
No. of Isolator : 60
Make : S&S
Rating : 2000A
Type : RP 700 GM-2
3. EARTH SWITCH:-
No. of Switch : 6
Make : S&S
Rating : 2000A
Type : VLC
4. CURRENT TRANSFORMER:-
Total : 16
No. of units : 16*3= 48 (3-phase)
Make : W.S.I
CTR : 2000-100-500A
Total :4
Make : WSI (2)
CTR Connected : 400 W/ 110V/3
Type : CVBA
6. LIGHTENING ARRESTOR:-
Total : 6
No. of units : 16
Make : ELPRO (3)
WSI (3)
Type : CPL QL 11 ZMO 90
7. BUS REACTOR:-
No. of Reactor : 3
Make : Crompton Greaves
Capacity : 16.67 MVAR
Rated Voltage : 420/3 KV
Date of Commissioning: 26-11-1991
1. CIRCUIT BREAKER:-
No of C.B : 30 { 220 KV - 16 , 11 KV – 1}
Make : ABB, Crompton Greaves, Siemens
Capacity : 2000A
2. ISOLATOR:-
No. of Isolator : 6
Make : Wigman, S & S
Rating : 1600A
Type : RC 500 HGB, RP 500
3. CURRENT TRANSFORMER:-
Total : 16
No. of units : 16*3= 48 (3-phase)
Make : W.S.I., ABB, AE
CTR : 1500-750-375/1 A, 1200-600-300-150/1 A
Total : 10
Make : WSI, ABB, Crompton Greaves
CTR Connected : 245 KV/ 220 0KV/110 KV/3
5. LIGHTING ARRESTOR:-
Total : 14
No. of units : 14*3=42
Make : ELPRO, WSI
Capacity : 198 KV
6. POTENTIAL TRANSFORMER:-
Total : 2
No. of Units : 2*3=6
PT Ratio : 245 KV/110 KV/3
Make : BHEl
FOR 66 KV:-
Total :2
No. of Units : 2*3=6
PT Ratio : 66 KV/110KV/3
Make : Hivlotran Elect.
Total :6
Make : Johnson Elect. Company, NEL, Apex, Ashok
Capacity :5 MVA
%Impedance : 5.93/5.6,
5/4.59
7. D.G. SET:-
Total :1
Make :Jyoti Kirlosker
Capacity : 275 KVA
Type : NTA 855 G2
8. COPRESSOR:-
Total :4
Make : Ingersoll
Capacity : 60 kg/cm 2
Type : 30/15-t-2
SF6 CB:-
Total :5
Make : EIGI
Capacity : 20-5 kg/cm 2
Type : 234s000
14. BIBLIOGRAPHY:-
1) ELECTRICAL POWER BY
S.L. UPPAL –KHANNA PUBLISHERS
4) BROCHURE
400 KV SOJA SUBSTATIONS
ROHIT MEHTA
S.R. BHIDE
7) WEBSITES:-
1. www.electronicsforyou.com
2. www.Getco.com
3. www.allcircuitabout.com
4. www.efu.com
5. www.en.wikipedia.org
6. www.1000electricalproject.com
8) SOURCES OF COMPUTER:-
1. CIRCUIT MAKER.
2. PAINT