Basic Transformer Notes
Basic Transformer Notes
Basic Transformer Notes
Transformer
Introduction
The transformer is probably one of the most useful electrical devices ever invented. It can
change the magnitude of alternating voltage or current from one value to another. This useful
property of transformer is mainly responsible for the widespread use of alternating currents
rather than direct currents i.e., electric power is generated, transmitted and distributed in the form
of alternating current. Transformers have no moving parts, rugged and durable in construction,
thus requiring very little attention. They also have a very high efficiency as high as 99%. In this
chapter, we shall study some of the basic properties of transformers.
1.Transformer
A transformer is a static device of equipment used either for raising or lowering the
voltage of an a.c. supply with a corresponding decrease or increase in current. It essentially
consists of two windings, the primary and secondary, wound on a common laminated magnetic
core as shown in Fig 1. The winding connected to the a.c. source is called primary winding (or
primary) and the one connected to load is called secondary winding (or secondary). The
alternating voltage V1 whose magnitude is to be changed is applied to the primary.
Depending upon the number of turns of the primary (N1) and secondary
(N2), an alternating e.m.f. E2 is induced in the secondary. This induced e.m.f. E2
in the secondary causes a secondary current I2. Consequently, terminal voltage
V2 will appear across the load.
If V2 > V1, it is called a step up-transformer.
If V2 < V1, it is called a step-down transformer.
Figure 1
Working
Note that magnitudes of E2 and E1 depend upon the number of turns on the secondary and
primary respectively.
If N2 > N1, then E2 > E1 (or V2 > V1) and we get a step-up transformer.
If N2 < N1, then E2 < E1 (or V2< V1) and we get a step-down transformer.
If load is connected across the secondary winding, the secondary e.m.f. E2 will cause a current I2
to flow through the load. Thus, a transformer enables us to transfer a.c. power from one circuit to
another with a change in voltage level.
In practice, these losses are very small so that output power is nearly equal to the input
primary power. In other words, a transformer has very high efficiency.
ϕ=ϕm sinωt
When the primary winding is exited by an alternating voltage V1, it is circulating alternating
current, producing an alternating fluxϕ
3
Φ - Flux
Φm - maximum value of flux
N1 - Number of primary turns
N2 - Number of secondary turns
F - Frequency of the supply voltage
E1 - R.m.s value of the primary induced e.m.f
E2 - R.m.s. value of the secondary induced e.m.f
Φm
Π 2π
ωt
1
2
-ϕm
Sinwave
dϕ = change in flux
dt = time required for change in flux
The flux increases from zero value to maximum value ϕm in 1/4f of the time period
The change of flux that takes place in 1/4f seconds = ϕm-0 = ϕm webers
4
= = 4fϕm wb/sec.
/
Since flux ϕ varies sinusoidally, the R.m.s value of the induced e.m.f is obtained by multiplying
the average value with the form factor
. .
Form factor of a sinwave = = 1.11
= 4.44ϕmf Volts.
VOTAGE RATIO
Voltage transformation ratio is the ratio of e.m.f induced in the secondary winding to the
secondary winding to the e.m.f induced in the primary winding.
.
=
.
= =K
This ratio of secondary induced e.m.f to primary induced e.m.f is known as voltage
transformation ratio
3. If N2=N1 i.e. K=1 we get E2=E1 then the transformer is called isolation transformer or 1:1
transformer.
CURRENT RATIO
Current ratio is the ratio of current flow through the primary winding (I1) to the current
flowing through the secondary winding (I2)
In an ideal transformer
V1I1 = V2I2
= = =K
i) The transformer rating is specified as the products of voltage and current (VA rating).
ii) On both sides, primary and secondary VA rating remains same. This rating is
generally expressed in KVA (Kilo Volts Amperes rating).
= =K
V1I1 = V2I2
KVA Rating of a transformer = = (1000 is to convert KVA to VA)
V1 and V2 are the Vt of primary and secondary by using KVA rating we can calculate I1 and I2
Full load current and it is safe maximum current.
TRANSFORMER ON NO LOAD
Ideal Transformer
Although ideal transformer cannot be physically realized, yet its study provides a very powerful
tool in the analysis of a practical transformer. In fact, practical transformers have properties that
approach very close to an ideal transformer.
Figure
Fig. (2 (ii)) shows the phasor diagram of an ideal transformer on no load. Since flux ϕ is
common to both the windings, it has been taken as the reference phasor. The primary e.m.f. E1
and secondary e.m.f. E2 lag behind the flux ϕ by 90°. Note that E1 and E2 are inphase. But E1 is
equal to V1 and 180° out of phase with it.
= =K
PHASOR DIAGRAM
i) Φ(flux) is reference
ii) Im produce ϕ and it is in phase with ϕ V1 Leads Im by 90˚
7
iii) E1 and E2 are inphase and both opposing supply voltage V1, winding is purely
inductive so current has to lag voltage by 90˚.
iv) The power input to the transformer
A practical transformer differs from the ideal transformer in many respects. The practical
transformer has (i) iron losses (ii) winding resistances and (iii) Magnetic leakage
(i) Iron losses. Since the iron core is subjected to alternating flux, there occurs eddy current and
hysteresis loss in it. These two losses together are known as iron losses or core losses. The iron
losses depend upon the supply frequency, maximum flux density in the core, volume of the core
etc. It may be noted that magnitude of iron losses is quite small in a practical transformer.
(ii) Winding resistances. Since the windings consist of copper conductors, it immediately
follows that both primary and secondary will have winding resistance. The primary resistance R1
and secondary resistance R2 act in series with the respective windings as shown in Fig. When
current flows through the windings, there will be power loss as well as a loss in voltage due to
IR drop. This will affect the power factor and E1 will be less than V1 while V2 will be less than
E2.
As seen from the phasor diagram in Fig., the no-load primary current I0
8
(i) The component Ic in phase with the applied voltage V1. This is known as active or working or
iron loss component and supplies the iron loss and a very small primary copper loss.
Ic= I0 cos ϕ0
The component Im lagging behind V1 by 90° and is known as magnetizing component. It is this
component which produces the mutual flux ϕ in the core.
Im = Io sin ϕ0
Clearly, Io is phasor sum of Im and Ic,
Io = √ +
V1 V2 V1
(i) (ii)
Φ ϕ2 ϕ2’ ϕ
V1 v1
(III) (iv)
9
Note. At no load, there is no current in the secondary so that V2 = E2. On the primary side, the
drops in R1 and X1, due to I0 are also very small because of the smallness of I0. Hence, we can
say that at no load, V1 = E1.
vi) Φ2 opposes the main flux ϕ, the total flux in the core reduced. It is called de-
magnetising ampere-turns due to this E1 reduced.
vii) To maintain the ϕ constant primary winding draws more current(I2’) from the
supply(load component of primary) and produce ϕ2’ flux which is oppose ϕ2(but
in same direction as ϕ), to maintain flux constant flux constant in the core
fig (iii).
viii) The load component current I2’ always neutralizes the changes in the load.
ix) Whatever the load conditions, the net flux passing through the core is
approximately the same as at no-load. An important deduction is that due to the
constancy of core flux at all loads, the core loss is also practically the same under
all load conditions fig (iv).
I1 = Io + I2’
I1 = + 2′
a) If load is Inductive, I2 lags E2 by ϕ2, shown in phasor diagram (a).
b) If load is resistive, I2 inphase with E2 shown in phasor diagram (b).
c) If load is capacitive load, I2 leads E2 by ϕ2 shown in phasor diagram (c).
10
Note:
For easy understanding at this stage E2 is assumed equal to V2 neglecting various drops.
I1 ≅ I2 ’
Balancing the ampere – turns
= =K
In practical transformer it process its own winding resistance causes power loss and also
the voltage drop.
The current flow in primary winding make voltage drop across it is denoted as I1R1 here supply
voltage V1 has to supply this drop primary induced e.m.f E1 is the vector difference between V1
and I1R1
E1 = V1 – I1R1
Similarly the induced e.m.f in secondary E2, The flow of current in secondary winding makes
voltage drop across it and it is denoted as I2R2 here E2 has to supply this drop.
11
V2 = E2 – I2R2
Note:
Assumed as purely resistive drop here.
EQUIVALENT RESISTANCE
1) It would now be shown that the resistances of the two windings can be transferred to
any one of the two winding.
2) The advantage of concentrating both the resistances in one winding is that it makes
calculations very simple and easy because one has then to work in one winding only.
3) Transfer to any one side either primary or secondary without affecting the
performance of the transformer.
R2’ =
²
R1e = R1 + R2’ = R1 + ²
R1 R2
V1 V2
I1 I2
(i)
12
(ii)
(iii)
²
Total copper loss = I1²R1 + I2²R2 = I2² [ R1 + R2]
²
= I2²[K²R1 + R2]
K²R1 is primary resistance referred to secondary denoted as R1’.
R1’ = K²R1
Equivalent resistance of transformer referred to secondary, denoted as R2e
Note:
i) It has been assumed that all the flux linked with primary winding also links the
secondary winding. But, in practice, it is impossible to realize this condition.
ii) However, primary current would produce flux ϕ which would not link the secondary
winding. Similarly, current would produce some flux ϕ that would not link the
primary winding.
iii) The flux ϕL1 complete its magnetic circuit by passing through air rather than around
the core, as shown in fig. This flux is known as primary leakage flux and is
proportional to the primary ampere – turns alone because the secondary turns do not
links the magnetic circuit of ϕL1. It induces an e.m.f eL1 in primary but not in
secondary.
iv) The flux ϕL2 complete its magnetic circuit by passing through air rather than around
the core , as shown in fig. This flux is known as secondary leakage flux and is
proportional to the secondary ampere – turns alone because the primary turns do not
links the magnetic circuit of ϕL2. It induces an e.m.f eL2 in secondary but not in
primary.
eL1 eL2
ϕL1 ϕL2
Similarly to the resistance, the leakage reactance also can be transferred from primary to
secondary. The relation through K² remains same for the transfer of reactance as it is studied
earlier for the resistance
X1e = X1 + X2’
X2’ = ²
The total leakage reactance referred to secondary is X2e given by
X2e = X2 + X1’
X1’ = K²X1
X1e = X1 + X2’
X2e = X2 + X1’
EQUIVALENT IMPEDANCE
The transformer winding has both resistance and reactance (R1, R2, X1,X2)
Thus we can say that the total impedance of primary winding isZ1 which is,
Z1 = R1 + jX1 ohms
15
On secondary winding
Z2 = R2 + jX2 ohms
Z1 = √ 1 + 1
Z2 = √ 2 + 2
Similar to resistance and reactance, the impedance also can be referred to any one side
Z1 = √ 1 + 1
Z2 = √ 2 + 2
16
Ro = , Xo =
i) Im produces the flux and is assumed to flow through reactance Xo called no load
reactance while Ic is active component representing core losses hence is assumed to
flow through the resistance R0
ii) Equivalent resistance is shown in fig.
iii) When the load is connected to the transformer then secondary current I2 flows causes
voltage drop across R2 and X2. Due to I2, primary draws an additional current.
I2 ’ =
I1 is the phasor addition of Io and I2’. This I1 causes the voltage drop across primary
resistance R1 and reactance X1
To simplified the circuit the winding is not taken in equivalent circuit while transfer to one side.
17
Note :
High voltage winding low current high impedance
low voltage winding high current low impedance
Now as long as no load branch i.e. exciting branch is in between Z1 and Z2 ’, the impedances
cannot be combined. So further simplification of the circuit can be done. Such circuit is called
approximate equivalent circuit.
i) To get approximate equivalent circuit, shift the no load branch containing Ro and Xo
to the left of R1 and X1.
ii) By doing this we are creating an error that the drop across R1 and X1 to Io is neglected
due to this circuit because more simple
iii) This equivalent circuit is called approximate equivalent circuit.
In this circuit new R1 and R2’ can be combined to get equivalent circuit referred to primary
R1e,similarly X1 and X2’ can be combined to get X1e.
19
R1e = R1 + R2’ = R1 +
²
X1e = X1 + X2’ = X1 +
²
Z1e = R1e + jX1E, Ro = , and Xo =
Ic = Io cosϕo, and Im = Io sinϕo
Primary parameter is referred to secondary there are no voltage drop in primary. When there is
no load, I2 = 0 and we get no load terminal voltage drop in
iv) Draw the circle with O as center and OC as radius cutting extended OA at M. as OA
= V2 and now OM = E2.
v) The total voltage drop is AM = I2Z2e.
vi) The angle α is practically very small and in practice M&N are very close to each
other. Due to this the approximate voltage drop is equal to AN instead of AM
I2 leads V2 by angle ϕ2
%R= x100
The ratio ( 2 − 2)/ 2) is called per unit regulation.
Note:
The regulation can be further expressed in terms of I1, V1, R1e and X1e
= =K
In above regulation we had seen about the positive and negative regulation. But as load
becomes capacitive, V2 starts increasing as load increases. At a certain leading power factor we
get E2 = V2 and the regulation becomes zero. If the load is increased further, E2 > V2 and we get
negative regulation.
E2 = V2
E2 – V2 = 0
VR cosϕ – VX sinϕ = 0
VR = = and VX = =
23
VR cosϕ = VX sin ϕ
tan ϕ =
Losses in a Transformer
These losses appear in the form of heat and produce (i) an increase in
Temperature and (ii) a drop in efficiency.
Iron or Core losses, Pi = Hysteresis loss + Eddy current loss = Constant losses (Pi)
The hysteresis loss can be minimized by using steel of high silicon content
Whereas eddy current loss can be reduced by using core of thin laminations.
24
These losses occur in both the primary and secondary windings due to their
ohmic resistance. These can be determined by short-circuit test. The copper loss depends on the
magnitude of the current flowing through the windings.
Total copper loss = I1²R1 + I22R2 = I12(R1 + R2’) = I22 (R2 + R1’)
Efficiency of a Transformer
Like any other electrical machine, the efficiency of a transformer is defined as the ratio of output
power (in watts or kW) to input power (watts or kW) i.e.,
Power output = power input – Total losses
Power input = power output + Total losses
= power output + Pi + Pcu
Efficiency =
Efficiency =
Efficiency =
²
V2I2 = VA rating of a transformer
( )
Efficiency =
( ) ²
( )
% Efficiency = X 100
( ) ²
( )
Full load Efficiency =
( ) ²
Also for any load equal to n x full-load,
Corresponding total losses = Pi + n2PCu
( )
n= = = 0.5
( )
Corresponding (n) % Efficiency = X 100
( ) ²
Voltage and frequency supply to the transformer is constant the efficiency varies with the
load. As load increases, the efficiency increases. At a certain load current, it loaded further the
efficiency start decreases as shown in fig.
The load current at which the efficiency attains maximum value is denoted as I2m and maximum
efficiency is denoted as max
1) condition for maximum efficiency
2) load current at which max occurs
3) KVA supplied at maximum efficiency
Considering primary side,
Load output = V1I1 cosϕ1
Copper loss = I12 R1e or I22 R2e
Iron loss = hysteresis + eddy current loss = Pi
26
²
Efficiency = =
=1– =
Differentiating both sides with respect to I2, we get
=0– =
²
= or Pi = I12R1e
²
( ) .
=( )
= =
( ) . [(I2)F.L]² [ ]F.L
Substituting condition for max in the expression of efficiency, we can write expression for
max as ,
as Pcu = Pi
% max = X 100
% max =
Testing of Transformer
This method is also called as direct loading test on transformer because the load is
directly connected to the transformer. We required various meters to measure the input and
28
output reading while change the load from zero to full load. Fig shows the connection of
transformer for direct load test.
The primary is connected through the variac to change the input voltage as we required. Connect
the meters as shown in the figure
The load is varied from no load to full load in desired steps. All the time, keep primary
voltage V1 constant at its rated value with help of variac and tabulated the reading
Calculation
From the observed reading
W1 = input power to the transformer
W2 = output power delivered to the load
29
% = X 100
%R= X 100
The graph of % and % R on each load against load current IL is plotted as shown in fig
Advantages:
1) This test enables us to determine the efficiency of the transformer accurately at any
load.
2) The results are accurate as load is directly used
Disadvantages:
1) There are large power losses during the test
2) Load not avail in lab while test conduct for large transformer
This test is conducted to determine the iron losses (or core losses) and parameters R0 and
X0 of the transformer. In this test, the rated voltage is applied to the primary (usually low-voltage
winding) while the secondary is left open circuited. The applied primary voltage V1 is measured
by the voltmeter, the no load current I0 by ammeter and no-load input power W0 by wattmeter as
shown in Fig. As the normal rated voltage is applied to the primary, therefore, normal iron losses
will occur in the transformer core. Hence wattmeter will record the iron losses and small copper
loss in the primary. Since no-load current I0 is very small (usually 2-10 % of rated current). Cu
30
losses in the primary under no-load condition are negligible as compared with iron losses. Hence,
wattmeter reading practically gives the iron losses in the transformer. It is reminded that iron
losses are the same at all loads. Fig.
Ro = Ω, Xo = Ω
Thus open-circuit test enables us to determine iron losses and parameters R0 and
X0 of the transformer.
31
This test is conducted to determine R1e (or R2e), X1e (or X2e) and full-load copper losses
of the transformer. In this test, the secondary (usually low-voltage winding) is short-circuited by
a thick conductor and variable low voltage is applied to the primary as shown in Fig. The low
input voltage is gradually raised till at voltage VSC, full-load current I1 flows in the primary.
Then I2 in the secondary also has full-load value since I1/I2 = N2/N1. Under such conditions, the
copper loss in the windings is the same as that on full load.
There is no output from the transformer under short-circuit conditions. Therefore, input power is
all loss and this loss is almost entirely copper loss. It is because iron loss in the core is negligibly
small since the voltage VSC is very small. Hence, the wattmeter will practically register the full-
load copper losses in the transformer windings.
Commercial efficiency =
There are certain types of transformers whose performance cannot be judged by this
efficiency. For instance, distribution transformers used for supplying lighting loads have their
primaries energized all the 24 hours in a day but the secondary’s supply little or no load during
the major portion of the day. It means that a constant loss (i.e., iron loss) occurs during the whole
day but copper loss occurs only when the transformer is loaded and would depend upon the
magnitude of load. Consequently, the copper loss varies considerably during the day and the
commercial efficiency of such transformers will vary from a low value (or even zero) to a high
value when the load is high. The performance of such transformers is judged on the basis of
energy consumption during the whole day (i.e., 24 hours). This is known as all-day or energy
efficiency.
The ratio of output in kWh to the input in kWh of a transformer over a 24-hour period is known
as all-day efficiency i.e.
ηall-day =
All-day efficiency is of special importance for those transformers whose primaries are never
open-circuited but the secondary carry little or no load much of the time during the day. In the
design of such transformers, efforts should be made to reduce the iron losses which continuously
occur during the whole day.