TEST REPORT

FOR
AIR CIRCUIT BREAKERS

AT

M/S Miot Hospitals Ltd.,


4 / 112, Mount poonamalle Road,
Manapakkam, Chennai 600 089
Carried out
On
12th December 2010

DURGA SWITCHGEARS (98843 20732)


EA 2616 A-Grade Contractors
No. 8/5, John Vasu Street,
Madhavaram Milk Colony,
Chennai 600 051

DURGA SWITCHGEARS

TIN 33251085384

A-Grade Contractors -------- EA 2616


CST 872774/08-01-08
(Servicing, Repairing Testing of all kinds of LT/HT Circuit Breakers,
AREA CODE 0 5 5
Protective relays, Transformer oil filtration and High pot Test)
Branch:
Door No. 14, Anand Nagar First Street,
Anand Nagar,
Mobile: 9884320732 Office; 044 25550453
Tiruchirappalli 620 021
Mail : [email protected]

PAGE 1a

HO : 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI 600 051

DATE OF TEST : 12TH DECEMBER 2010


ACB
TO

Breaker Sl. No.

M/S Miot Hospitals


Ltd.,Make /
Breaker
4 / 112, Mount poonamalle
Road,
Type/ Rating
Feeder
Name
Manapakkam, Chennai
600
089
Voltage
Location

S.NO
.

DESCRIPTION

TEST

REPORT

MR 173186
L&T / CN-CS 1600C /
1600 Amps
LT Incomer from TFR. 1
440 volts
MV PANEL ROOM

TYPE OF CHECK

CHECKED

REMARKS

PHYSICAL INSPECTION

VISUAL

FOR DAMAGE

OK

INSTALLATION/CONNECTION

VISUAL/MECHANICAL

FOR
CORRECTNESS

OK

OPERATIONS
a)Manual Closing / Tripping

MECHANICAL

CORRECTNESS

OK

b) Normal Closing/Tripping

MECHANICAL

CORRECTNESS

OK

c) tripping at 60% U a

ELECTRICAL

FOR
PERFORMANCE

OK

d) Closing time

ELECTRICAL

FOR
PERFORMANCE

OK

e) Opening time

ELECTRICAL

FOR
PERFORMANCE

OK

f) Under Voltage Coil

ELECTRICAL

FOR
PERFORMANCE

OK

g) Tripping of ACB through Shunt


Trip Coil

ELECTRICAL

FOR
PERFORMANCE

OK

VISUAL

FOR ABNORMALITY

OK

MECHANICAL

FOR LUBRICATION
AND
PERFORMANCE

LUBRICATED
OK

CONTACT PENETRATION /
ALIGNMENT FOR ACB

CLOSING & TRIPPING


MECHANISM FUNCTIONAL
CHECK

TIN 33251085384

DURGA SWITCHGEARS
A-Grade Contractors -------- EA 2616

CST 872774/08-01-08 (Servicing, Repairing Testing of all kinds of LT/HT Circuit Breakers,
AREA CODE 0 5 5
Protective relays, Transformer oil filtration and High pot Test)
Branch:
Door No. 14, Anand Nagar First Street,
Anand Nagar,
Mobile: 9884320732 Office; 044 25550453 PAGE 1b
Tiruchirappalli 620 021
Mail
: [email protected]
HO : 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI 600 051

DATE OF TEST : 12TH DECEMBER 2010

S.NO
.

DESCRIPTION

TYPE OF CHECK

DRAW-OUT MECHANISM
FUNCTIONAL CHECK

MECHANICAL

INSULATION RESISTANCE

CHECKED BY 1000V
MEGGER
BREAKER CLOSED
CONDITION
R-E
Y-E
B-E
N-E

>
>
>
>

100
100
100
100

M
M
M
M

R-N > 100 M OHMS


Y-N > 100 M OHMS
B-N > 100 M OHMS

CHECKED

FOR LUBRICATION
AND
PERFORMANCE

BREAKER OPEN
CONDITION
R I/CO/G
100 M
Y I/CO/G
100 M
B I/CO/G
100 M

R-Y > 100 M


Y-B > 100 M
B-R > 100 M

TIN 33251085384

DURGA SWITCHGEARS

REMARKS

LUBRICATED
OK

A-Grade Contractors -------- EA 2616


CST 872774/08-01-08
(Servicing, Repairing Testing of all kinds of LT/HT Circuit Breakers,
AREA CODE 0 5 5
Protective relays, Transformer oil filtration and High pot Test)
Branch:
Door No. 14, Anand Nagar First Street,
Anand Nagar,
Mobile: 9884320732 Office; 044 25550453
Tiruchirappalli 620 021
Mail : [email protected]

PAGE 2a

HO : 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI 600 051

DATE OF TEST : 12TH DECEMBER 2010


ACB
TO

Breaker Sl. No.

M/S Miot Hospitals


Ltd.,Make /
Breaker
4 / 112, Mount poonamalle
Road,
Type/ Rating
Feeder
Name
Manapakkam, Chennai 600
089
Voltage
Location

S.NO
.

DESCRIPTION

TEST

REPORT

MR 173181
L&T / CN-CS 1600C /
1600 Amps
LT Incomer from TFR. 2
440 volts
MV PANEL ROOM

TYPE OF CHECK

CHECKED

REMARKS

PHYSICAL INSPECTION

VISUAL

FOR DAMAGE

OK

INSTALLATION/CONNECTION

VISUAL/MECHANICAL

FOR
CORRECTNESS

OK

OPERATIONS
a)Manual Closing / Tripping

MECHANICAL

CORRECTNESS

OK

b) Normal Closing/Tripping

MECHANICAL

CORRECTNESS

OK

c) tripping at 60% U a

ELECTRICAL

FOR
PERFORMANCE

OK

d) Closing time

ELECTRICAL

FOR
PERFORMANCE

OK

e) Opening time

ELECTRICAL

FOR
PERFORMANCE

OK

f) Under Voltage Coil

ELECTRICAL

FOR
PERFORMANCE

OK

g) Tripping of ACB through Shunt


Trip Coil

ELECTRICAL

FOR
PERFORMANCE

OK

VISUAL

FOR ABNORMALITY

OK

MECHANICAL

FOR LUBRICATION
AND
PERFORMANCE

LUBRICATED
OK

CONTACT PENETRATION /
ALIGNMENT FOR ACB

CLOSING & TRIPPING


MECHANISM FUNCTIONAL
CHECK

TIN 33251085384

DURGA SWITCHGEARS
A-Grade Contractors -------- EA 2616

CST 872774/08-01-08 (Servicing, Repairing Testing of all kinds of LT/HT Circuit Breakers,
AREA CODE 0 5 5
Protective relays, Transformer oil filtration and High pot Test)
Branch:
Door No. 14, Anand Nagar First Street,
Anand Nagar,
Mobile: 9884320732 Office; 044 25550453 PAGE 2b
Tiruchirappalli 620 021
Mail
: [email protected]
HO : 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI 600 051

DATE OF TEST : 12TH DECEMBER 2010

S.NO
.

DESCRIPTION

TYPE OF CHECK

DRAW-OUT MECHANISM
FUNCTIONAL CHECK

MECHANICAL

INSULATION RESISTANCE

CHECKED BY 1000V
MEGGER
BREAKER CLOSED
CONDITION
R-E
Y-E
B-E
N-E

>
>
>
>

100
100
100
100

M
M
M
M

R-N > 100 M OHMS


Y-N > 100 M OHMS
B-N > 100 M OHMS
R-Y > 100 M
Y-B > 100 M
B-R > 100 M

CHECKED

FOR LUBRICATION
AND
PERFORMANCE

BREAKER OPEN
CONDITION
R I/CO/G
100 M
Y I/CO/G
100 M
B I/CO/G
100 M

REMARKS

LUBRICATED
OK