Expansion Vessel Sizing To Upload
Expansion Vessel Sizing To Upload
Project
Project Consultant
Client
Contractor
Subject
Design By
Reference
Calculation
Output
References
[1]
2000 ASHRAE systems and equipment handbook
[2]
2003 ASHRAE journal - Annex 02
[3]
Pg.15, Installation and Maintenance Manual (IM 1044-1)-Models
WSC,WDC,WCC,HSC - May 2010 Annex 03
[4]
Table 3, pg.6.5, 1997 ASHRAE fundermentals handbook - Annex 04
[1]
chapter 12
eq.14
[(2 1 ) 1] 3
(1 1 2 )
System volume
See Annex 01
System volume
50 m
[2]
[2]
[3]
=
1034 kPa
The critical pressure point (CPP) in the system is lowest point in the system on discharge
side of the secondary pump
2. Pressure relief valve (PRV) is installed near the expansion tank
3. The static pressure difference between CPP and
Pressure relief valve (Ps,CPP-PRV)
=
0 kPa
Because there is no height difference between expansion tank and CPP
4. The frictional pressure drop is secondary pump head
(Pf,CPP-PRV)
255.06 kPa
Frictional pressure loss from CPP to PRV is roughly the head of secondary pump
5. Pressure relief valve set point (Prv) = Pma+ Ps,CPP-PRV Pf,CPP-PRV
778.94 kPa
0 kPa
1 of 2
Calculation sheet
Reference
Calculation
7. Frictional pressure drop from PRV to tank ( Pf,PRV-tank)
Output
=
0 kPa
778.94 kPa
Vs
Minimum temperature
t1
Value
Unit
50 m3
7 C
Maximum temperature
t2
32 C
Atmospheric pressure
Pa
101.33 kPa
Minimum pressure
P1
505.82 kPa
Maximum pressure
P2
[4]
v1
778.94 kPa
3
0.001 m /kg
[4]
v2
Symbol
3
0.001005 m /kg
1.17E-05 m/mK
25 C
Vt >=
Vt >=
0.66 m3
664.33 ltrs
eq.14
Vt >=
664.33
ltrs
Conclusion
Expansion vessel volume (ie. 1000 l) requested by the employer's requirement of
tender document is acceptable.
2 of 2
Calculation sheet
Reference
Calculation
Output
3 of 2
Calculation sheet
4 of 2
Calculation sheet
5 of 2
Calculation sheet
6 of 2