Power Engineering Concepts
Power Engineering Concepts
2012
Page 1
Generators
The device converts mechanical energy to electrical energy is called a generator.
Synchronous machines can produce high power reliably with high efficiency, and therefore, are
widely used as generators in power systems. A generator serves two basic functions. The first
one is to produce active power (MW), and the second function, frequently forgotten, is to
produce reactive power (Mvar). The discussion on generators will be limited to the
fundamentals related to these two functions. More details related to the dynamic performance of
generators will be discussed in Module 6. The mechanical structure of generators is out of the
scope of this material.
A simplified turbine-generator-exciter system is shown in Figure 2-1. The turbine, or the
prime mover, controls the active power generation. For instance, by increasing the valve
opening of a steam turbine, more active power can be generated and vice versa. The exciter,
represented as an adjustable DC voltage source, controls the filed current that controls the
internal generated voltage source, E f . Therefore, the generator terminal voltage, V , is
controlled.
jXd
+
+
Vf
-
Rf
Ef
Turbine
Generator
Generator
field
Fig. 2-1. An electrical representation of a simplified turbaine-generator-exciter.
Exciter
Page 2
jXd
+
Ef
Generator
System
Fig. 2-2. A per phase steady-state equivalent circuit of a synchronous generator and the system.
angle. Then, the generator internal voltage can be obtained
E f = I( jX d ) + V = jX d I + V = E f ,
where the angle is called power angle. A graphical representation of these quantities can be
useful and is shown in Figure 2-3.
Ef
jX d I
I
Fig. 2-3. Phasor diagram of E f , V , and I .
The per phase analysis of the complex power injected to the system can be calculated by
*
VE f
E V
E f V
VE f
V2
S = VI = V f
V
sin
j
cos
=
=
+
= P + jQ .
Xd
Xd
jX d
X d 90
Xd
*
Figure 2-4 shows the active power and reactive power versus the power angle. The maximum
value of the active power, Pmax, is referred to as the steady-state stability limit and can be
calculated as
Page 3
Pmax =
VE f
.
Xd
P, Q
VE f
Xd
P
Q
V2
Xd
90
180
Q max = 132Mvar ,
(1) Find P, Q, Ef and in per unit when operated at rated terminal conditions. Set 250MVA
as the power base.
(2) If the active power is reduced by 15%, re-evaluate P, Q, Ef and .
(3) If the exciter is adjusted to reduce Ef by 5.56%, re-evaluate P, Q, Ef and .
Solution:
(1) The complex power at rated conditions can be obtained from its rated MVA and rated
power factor, namely,
S = S3 ,rated cos 1 (pf rated ) = 250 cos 1 (0.85) = 25031.8 = 212.5 + j132 MVA
Its per unit value is
Spu =
S
S Base,3
= 0.85 + j0.527 pu
Therefore,
P = 0.85 pu
and
Q = 0.527 pu
Page 4
= 32
This is the base case for the following parts (2) and (3).
(2) The active power reduced by 15% of the base case,
P = (1 0.15) (0.85) = 0.7225 pu
Assuming the change on the active power does not affect the Ef,
E f = 1.925 pu
Then, the power angle can be calculated by
PX d
(0.7225)(1.2 )
= sin 1
= sin 1
= 26.8
(1.925)(1)
Ef V
The corresponding reactive power can be calculated,
Q=
(1.925) 1 cos(26.8) 12
1.2
1.2
= 0.599 pu
(1.818) 1 cos(34.1) 12
1.2
1.2
= 0.421 pu
Page 5
Table 2-1 tabulates the results from Example 2-1 for a comparison purpose. A decrease
of 15% on active power generation, the power angle is decreased by 14%. A very small decrease
(-5.56%) on the internal generated voltage, it causes a significant decrease (-20%) on generator
reactive power production.
Table 2-1: Comparison of P, Q, Ef and obtained in Example 2-1.
P
Case #
1
2
3
pu
0.85
0.7225
0.85
Q
%
-15%
pu
0.527
0.599
0.421
Ef
%
+14%
-20%
pu
1.925
1.925
1.818
%
-5.56%
Degrees
32
26.8
34.1
%
-14%
+6.6%
Page 6
Transmission Lines
The equipment connecting the generated electrical energy from the generation to the
Distribution system is the transmission line. A transmission system is a massive interconnected
network consists of mainly AC transmission lines with various high/extra high voltage levels.
The main advantage of having higher voltage in transmission system is to reduce the losses in the
grid.
Electrical energy is transported from generating stations to their loads through overhead
lines and cables. Overhead transmission lines are used for long distances in open county and
rural areas, while cables are used for underground transmission in urban areas and for
underwater crossings. Because the cost for cables is much more expensive than the overhead
lines, cables are used in special situations where overhead lines can not be used. Since the
majority of transmission lines are overhead lines, the discussion is limited to overhead lines only.
Before discussing the model for transmission lines, some related terms need to be clearly
defined. The parameters for modeling of overhead transmission lines are:
(1)
(2)
(3)
Then, the series (line) impedance of the transmission line can be expressed as
Z = R + jX L = R + jL ,
and the shunt admittance of the transmission line can be expressed as
Y = jB c = jC Siemen.
The characteristic impedance of a transmission line is defined as
Zc =
Z
=
Y
R + j L
.
j C
If the resistance of the transmission line is neglected, the characteristic impedance can be
simplified as
Page 7
Zc = Z c =
j L
=
j C
L
,
C
which is a real number in this case. It is commonly referred to as the surge impedance. The
power delivered by a transmission line when it is terminated by its surge impedance is known as
the surge impedance load (SIL),
SIL =
VL,2 rated
Zc
MW.
When the loading of a transmission line is heavier than its SIL, the voltage will be decreasing
along the line. This implies that the reactive power generated from the line charging is less than
the reactive power consumption of the line impedance. Therefore, the transmission line acts as
an inductor. When the loading of the line is light, less than its SIL, the line reactive charging is
greater than the line reactive consumption. At light loading conditions, a transmission line acts
like a capacitor, and the voltage along the line will be increasing. The voltage profile along the
line is the same, as shown in Figure 2-6, when the loading of the line is at its SIL.
V
Light Load (<SIL)
SIL
Heavy Load (>SIL)
Sending
End
Receiving
End
Line length
Fig. 2-6. Voltage profiles with various loading conditions on the transmission line.
The model commonly used for AC overhead transmission lines is called Pi () network
and is shown in Figure 2-7. Please note that the shunt admittance has been even divided into two
shunt elements connecting to both ends of a pi equivalent network. By KVL:
ZY
Y
Vr + ZI r ,
Vs = Z I r + Vr + Vr = 1 +
2
2
By KCL:
Is =
ZY
Y
Y
ZY 2
Vr + 1 +
I r ,
Vs + I r + Vr = Y +
2
2
4
2
where
Page 8
jXL
Ir
Vs
+
Y
2
jBc
2
jBc Y
2 2
Vr
-
ZY
Vs 1 + 2
=
2
I s Y + ZY
4
The two
Vr A B Vr
,
=
ZY I r C D I r
1+
2
Z
where
A = 1+
and
ZY
= D,
2
B = Z,
C=Y+
ZY 2
.
4
Example 2-2: A transmission line has a series impedance and a shunt admittance as follows
Z = 8.8 + j46.54 and Y = j0.3524 mS, find:
(1) The characteristic impedance of the transmission line.
Page 9
(2) The model of the transmission line by a pi equivalent network with its actual
impedance/admittance values.
(3) If S3 ,Base = 100MVA and VL,Base = 230kV , re-evaluate part (2) with per unit values
and calculate transmission parameters, A , B , C and D in per unit values.
Solution:
8.8 + j46.54
=
j0.3524 10 3
(1) Z c =
47.364579.3
10.7
= 134405.98
= 366.6 5.35
0.000352490
2
Zc =
8.8
Ir
j46.54
+
j0.0001762S
j0.0001762S
Vs
Vr
Fig. 2-8. The pi equivalent model in actual values for the given transmission line.
(3) Z Base =
Z pu =
VL,2 Base
S Base,3
230 2
=
= 529
100
8.8 + j46.54
= 0.016635 + j0.087977 pu
529
Y
j0.0001762
=
= j0.09321 pu
1 529
2 pu
Page 10
Is
0.016635pu j0.087977pu
Ir
Vs
+
j0.09321pu
j0.09321pu
Vr
-
Fig. 2-9. The pi equivalent model in per unit values for the given transmission line.
For the transmission parameters, A , B , C and D :
A = D = 1 + (0.016635 + j0.087977 )( j0.09321) = 0.99178340.084 pu
B = 0.016635 + j0.087977 = 0.089535879.95 pu
C = 2 ( j0.09321) + (0.089535879.95 )( j0.09321)2 = 0.18565490.04 pu
Transformers
The main functions of transformers are stepping up voltages from the lower generation
levels to the higher transmission voltage levels and stepping down voltages from the higher
transmission voltage levels to the lower distribution voltage levels. The main advantage of
having higher voltage in transmission system is to reduce the losses in the grid. Since
transformers operate at constant power, when the voltage is higher, then the current has a lower
value. Therefore, the losses, a function of the current square, will be lower at a higher voltage.
The output power of an ideal two winding transformer equals the input power while
having two different voltage levels on its input and output terminals, namely,
S1 = S2 .
The equivalent circuit of an ideal transformer is shown in Figure 2-10. This is assumed to be a
generator step-up transformer (GSU) that will step-up the voltage at the primary side (or low
side) from a lower level to a higher voltage at the secondary side (high side). It is commonly
assumed that power flows from the primary side to the secondary side of transformers. The
primary/secondary voltages and currents have the following relationship:
E1 I1 = E 2 I 2 ,
E1 E 2
,
=
N1 N 2
and
N1 I1 = N 2 I 2 ,
Page 11
where
E1 = primary voltage,
I1 = primary current,
N1 = number of primary turns,
E 2 = secondary voltage,
I 2 = secondary current,
and
N 2 = number of secondary turns.
I2
I1
+
+
N1
E1
N2
E2
r1
Ic
+
V1
N1 : N 2
I1'
jx1
rc
jxm
r2
jx2
I2
E1
E2
V2
Ideal Transformer
Page 12
V2 = E 2 I 2 (r2 + jx 2 ) .
By KCL,
I1' = I1 I c .
where
r1 = primary winding resistance,
x 1 = primary leakage reactance,
V1 = applied primary voltage,
I c = exciting current,
rc = resistance representing core losses,
x m = reactance representing magnetizing current,
N
n = 1 , turn ratio, rated primary voltage/rated secondary voltage,
N2
r2 = secondary winding resistance,
x 2 = secondary leakage reactance,
and
V2 = applied secondary voltage.
The exciting current is small as compared to rated current. Since rc and xm are very large
in comparison to other ohmic values, they are generally ignored in circuit calculation. Under this
condition, if secondary values are referred to the primary side, the equivalent circuit can be
simplified and redrawn as shown in Figure 2-12. The equivalent resistance and reactance can be
calculated as follows
req = r1 + n 2 r2 ,
and
x eq = x 1 + n 2 x 2 .
I1
req
jxeq
V1
nV2
Fig. 2-12. The transformer equivalent circuit with impedances referred to primary.
Page 13
Similarly, one can refer all impedances to the secondary side. (Relations refer from primary to
secondary in inverse order)
Two quantities that help describe the operation of a transformer are its voltage regulation and
efficiency. Voltage regulation is defined as the change in the voltage from no load to full load as
a percentage of the full-load voltage. Efficiency is defined as power output divided by power
input and is usually given as a percent quantity as well. The voltage regulation (VR) and
efficiency () can be expressed as
VR =
Vnl Vfl
100% ,
Vfl
and
Pout
Pout
100% =
100% ,
Pin
Pout + Plosses
where
Vfl = full-load voltage,
Vnl = no-load voltage,
Pout = output power,
Pin = input power,
and
Plosses = power losses including core losses and copper losses.
Sometimes the impedances of a transformer are not given. Instead, the results from a
short circuit test and open circuit test are given. However, the details on the short circuit and
open circuit tests are out of the scope of this material. The following example should be
sufficient for readers to review these tests and to understand the material presented so far in this
section.
Example 2-3: Short circuit and open circuit tests in the usual way are conducted on a 75 kVA
7600:240 volt single-phase transformer. The data are listed below:
Type of Test
S-C
O-C
Volts
380 (VS-C)
240 (VO-C)
Amperes
9.87 (IS-C)
11.1 (IO-C)
Watts
750 (PS-C)
600 (PO-C)
Find:
(1) The transformer equivalent circuit with all quantities referred to the high side.
(2) The exciting current taken by the transformer when energized with rated voltage on the
high side of the transformer.
(3) The voltage regulation and efficiency of the transformer when delivering rated kVA at
0.8 power factor lagging at rated voltage.
(4) Express req + jx eq in per unit on the transformer rating.
Page 14
Solution:
(1) The short circuit test is commonly performed on the high side of the transformer. The
equivalent winding impedance can be calculated.
PSC
req =
I S2C
Z eq =
750
= 7.7
9.87 2
VSC 380
=
= 38.5
I SC 9.87
2
x eq = Z eq
req2 = 38.5 2 7.7 2 = 37.72
The open circuit test is commonly performed on the low side of the transformer. The
conversion from the low side to the high side is necessary to calculate the rc and xm. The
turn ratio
n=
7600
= 31.66667
240
Since
POC =
VO2 C
rc
n2
Therefore,
rc =
Then,
1
1 I OC
=
n 2 +
rc jx m VOC
xm =
n2
I OC
VOC
n2
rc
(31.66667 )2
2
2
11.1 31.66667
240 96267
= 22253
The equivalent circuit for the given transformer with all impedances referred to the high
side is shown in Figure 2-13.
Page 15
7.7
j37.72
+
V1
+
j22253
96267
nV2
-
(2) I c =
1 1
96267 22253
= 0.35 amps
2
or,
Ic =
I OC
11.1
=
= 0.35 amps
n
31.66667
75000
cos 1 (0.8) = 9.868 36.87 amps
7600
Assuming the voltage at the terminals on the right hand side is 7600 volts, the voltage at
the left hand side can be calculated.
V1 = 76000 + (9.868 36.87)(7.7 + j37.72 ) = 7884.1 + j252.15 = 7888.131.83 V
The voltage regulation can be calculated as
VR =
240
240
7600
100% = 3.79%
240
7888.13
The power output is the product of the rated kVA and the load power factor, namely,
Pout = 75 0.8 = 60 kW
The efficiency is
60000
100% = 97.8%
60000 + 750 + 600
(4) Z Base =
7600 2
= 770.1
75000
Page 16
req =
7.7
= 0.01 pu
770.1
x eq =
37.72
= 0.049 pu
770.1
rP
IS
jxS
jxP
+
rT
jxT
VS
IT
+
VP
VT
Fig. 2-14. An equivalent circuit of a three winding transformer in per unit values.
Table 2-2. Method of testing for a three winding transformer.
Winding
Energized
Primary (P)
Winding
Short-circuited
Secondary (S)
Winding
Open
Tertiary (T)
Impedance
Measured
Z PS
Primary (P)
Tertiary (T)
Secondary (S)
Z PT
Secondary (S)
Tertiary (T)
Primary (P)
ZST
Three impedances are obtained from the three short circuit tests. To calculate the three
individual winding impedances, Z P , ZS , and Z T , the following three equations can be used.
1
Z P = (Z PS + Z PT ZST ),
2
1
ZS = (Z PS + ZST Z PT ),
2
and
1
Z T = (Z PT + ZST Z PS ) .
2
Page 17
It is worth mentioning that although the real and imaginary parts of the three measured
impedances ( Z PS , ZST , and Z PT ) are all positive, but some of the real and imaginary parts of the
individual winding impedances ( Z P , ZS , and Z T ) may have negative values.
Example 2-4: Three impedances are measured from three short circuit tests:
Z PS = 0.015 + j0.07 pu; ZST = 0.05333 + j0.02446 pu; Z PT = 0.025 + j0.08507 pu
Calculate three individual winding impedances, Z P , ZS , and Z T .
Solution:
ZP =
1
[(0.015 + 0.025 0.05333) + j(0.07 + 0.08507 0.02446)] = 0.006665 + j0.065305
2
ZS =
1
[(0.015 + 0.05333 0.025) + j(0.07 + 0.02446 0.08507 )] = 0.021665 + j0.004695
2
ZT =
1
[(0.05333 + 0.025 0.015) + j(0.02446 + 0.08507 0.07 )] = 0.031665 + j0.019765
2
The discussions so far are for single-phase transformers. Three single-phase transformers
(usually identical) can be used for three-phase applications, either in a delta or wye
configuration. The properties discussed in Module #1 for delta and wye configurations can be
applied for transformers. Also, some transformers are built as three-phase transformers.
Example 2-5: Given a system as shown below:
50MVA
13.2 kV
Xd"=20%
X2=20%
G
12.47:138 kV
50MVA
X=10%
Load
138:13.8 kV
40MVA
X=10%
ZL=10+j0
(ohms/phase)
Y connected
Compute three-phase (3) fault currents in kA at the load, transmission line and generator
terminal.
Select S Base,3 = 50MVA and VBase,L = 138kV at the transmission line.
Solution:
Use per phase analysis for this problem:
At transmission line section,
S Base =
S Base,3
3
50
= 16.66667 MVA
3
Page 18
VBase =
I Base =
VBase,L
3
138
3
= 79.6743 kV
16.66667
= 0.209185 kA
79.6743
Z Base =
79.6743
= 380.88
0.209185
Similarly, the base values at the generator section and load section can be obtained and
tabulated in Table 2-3.
Table 2-3. Base values at different sections of the given system.
Location
Generator
Transmission Line
Load
SBase
(MVA)
16.66667
16.66667
16.66667
VBase
(kV)
7.1996
79.6743
7.96743
IBase
(kA)
2.31494
0.209185
2.09185
ZBase
()
3.11
380.88
3.8088
13.2
X G = (0.2 )
= 0.2241016 pu
12.47
X T1 = 0.1 pu
50
X T2 = (0.1) = 0.125 pu
40
X TL =
20
= 0.05251 pu
380.88
The generator voltage at pre-fault is 13.2 kV, and its per unit value is
VG =
13.20
= 1.058540 pu
12.47
The equivalent circuit for the given system with a three-phase fault at load terminals is
shown in Figure 2-15.
Page 19
j0.2241016
j0.1
j0.05251
j0.125
+
1.05854
IS-C
Fig. 2-15. The equivalent circuit in per unit values for the given system.
1.05854
= j2.11028 pu
j(0.2241016 + 0.1 + 0.05251 + 0.125)
The three-phase fault current at the load terminals:
I S C =
Page 20