GeoSource Ultra Hydronic
GeoSource Ultra Hydronic
GeoSource Ultra Hydronic
Installation
and
Operating Instructions
Hydronic
GW 37 Thru 57 Series
Transformer
Hydronic
Pump Relay
Contactor
Controller
Reversing
Valve
Expansion Valve
Low Pressure
Switch
Desuperheater
(Optional)
Scroll
Compressor
Desuperheater
Pump
High Pressure
Switch
Air Pad
TABLE OF CONTENTS
Section
I.
Title
Page
Introduction to ECONAR Heat Pumps . . . . . . . . . . . . . . . . . . . . . . 2
II.
Unit Location/Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
III.
IV.
V.
VI.
Unit Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
A.
B.
C.
D.
VII.
Electrical Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
VIII.
IX.
Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
X.
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
A.
Lockout Lights
XI.
Thermostat Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
XII.
XIII.
XIV.
XV.
Desuperheater (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
17
I. INTRODUCTION TO
ECONAR HEAT PUMPS
** IMPORTANT**
heat pump, which pulls heat out of the solution, and then
back through the ground to extract more heat from the
earth.
2.5 to 3.0 gallons per minute (GPM) per ton are required
for proper operation of the heat pump and the earth
coupled heat exchanger.
4.
5.
6.
7.
8.
9.
1.
2.
B. Fan Coils
Fan coils can be used with ECONAR's hydronic heat
pumps in the heating and cooling mode. In many cases,
radiant floor heating and fan coil cooling are used
together. Fan coils also provide dehumidification in the
cooling mode. The rate of dehumidification can be
adjusted by varying the fan coil operating temperature.
D. Other Applications
High static pressure fan coils have recently come onto the
market, which work well with ECONAR's hydronic heat
pumps. These systems provide heating and cooling for
houses without ductwork. They use a high static pressure
blower to supply air through small tubes, which run
through chaseways to the living space. The blower passes
air though a water-to-air coil that is coupled to a hydronic
heat pump to provide heating and cooling. These systems
work nicely on retrofit applications where ductwork isn't
available or wanted. Fan coil data is available in Table 5.
C. Baseboard Heating
Another application of hydronic heating is finned tube
baseboard heating. This is the same tubing used with
boilers with one major difference. The discharge
temperature of a boiler is much higher than geothermal
heat pumps. The heat pump system should be sized at
115oF hydronic leaving water temperature to maintain
efficiency. At a 125oF hydronic leaving water
temperature, the heat pump is at a maximum operating
temperature and may start to trip off on high head
pressures. Standard 3/4" finned tube baseboard
conductors have an average output of 230 Btuh/ft at
V. APPLICATIONS OF
HYDRONIC HEAT
EXCHANGERS
This section deals with some common practices used
when coupling the ECONAR GeoSource Ultra hydronic
heat pumps to the space conditioning heat exchanger.
There are so many possible applications for hydronic
systems that they cannot all be covered in this text.
Hopefully these ideas can help in many of your system
designs.
)Note: Actual systems must be constructed to all
appropriate codes and according to accepted plumbing
practices.
7
A. Storage Tanks
Coupling the heat pump to the space conditioning heat
exchanger through a water storage tank is very common.
In fact, the only instance where these storage tanks are not
recommended is when the heat pump is coupled to a large
heat exchanger capable of absorbing the entire heating or
cooling capacity of the heat pump (see Figure 5). In
applications that use multiple smaller zones, storage tanks
absorb the relatively large amount of energy supplied by
the heat pump, in order to provide longer run times and
less compressor cycling for the heat pump. Storage tanks
also serve to dispense energy in small amounts so that the
conditioned zones have time to absorb heat without
requiring high discharge water temperatures. Insulated
hot water heaters are commonly used for storage tanks.
)Note: While all hot water tanks are insulated on the
top and sides, many do not have insulation on the bottom.
An insulated pad beneath uninsulated tanks will reduce
energy loss to the floor.
When properly sized, a storage tank eliminates many
problems with multiple zone hydronic systems. These
problems include excessive leaving water temperature if a
single zone cannot dissipate heat quickly enough, and
hydronic flow reduction through the heat pump when only
one zone is calling. This may occur because the hydronic
circulating pump is normally sized to provide the heat
pumps required flow with all zones calling. When sizing
storage tanks to the heat pump, a good rule of thumb is
ten gallons of storage tank per ton of hydronic capacity.
The tank temperature can be controlled with a simple
aquastat or a setpoint controller. The setpoint controller
senses tank water temperature and outside air temperature
to increase the tank temperature as the outside air
temperature goes down. This control scheme provides the
highest heating efficiencies by requiring the lowest
possible water temperature to heat the space. Setting the
optimal design temperatures in the controller is difficult,
and the simple aquastat does have its advantages. To help
in setpoint control, the following equation can be used.
Reset Ratio = Design Water Temp Indoor Design Temp
Indoor Design Temp Outdoor Design Temp
C. Circulation Fluid
The fluid circulating through the hydronic side of the
geothermal heat pump system is the transfer medium for
the heating and cooling being supplied to the conditioned
space. Selection of this fluid is very important. Water is
the most readily available fluid but has the drawback of
expansion during freezing which can damage the system.
System operation in the cooling mode, extended power
interruption to a structure, or disabling of an outside zone
(such as a garage floor) provides the opportunity for
freezing the circulating fluid.
Antifreeze must be used whenever the possibility of
freezing exists from the environment or from use of the
unit in the cooling mode. A propylene glycol based
antifreeze (readily available through HVAC wholesalers)
and water solution is recommended. Methanol based
antifreeze is not recommended for use on any hydronic
system where heat is being added to the system for
structural heating purposes. Freeze protection for the
hydronic side fluid down to 20oF (20% propylene glycol
by volume in water) is recommended for most indoor
applications (see Chart 1). Forty percent propylene glycol
in water (-5oF freeze protection) is recommended by
radiant tubing manufactures for snow melt applications, in
order to protect the tubing from expansion in outdoor
applications. Using over 40% in hydronic side
applications can cause pumping problems due to high
viscosity.
The water being added to the system should have 100PPM grain hardness or less. If poor water conditions
exist on the site, softened water is recommended, or
acceptable water should be brought in. Bacteria or algae
growth in the water is a possibility, especially bacteria or
algae that thrive at the particular temperatures produced in
the heating system. This growth can cause buildup on
hydronic side heat exchanger surfaces, reducing the
efficiency of the system or causing the heat pump to run
at higher head pressures and possibly lock out. Adding a
gallon of bleach or boiler system conditioner can reduce
the possibility of growth and clean up visual flow meters
and other components in the system.
D. Expansion Tanks
Expansion tanks must be used in the hydronic side of the
water-to-water system to absorb the change in pressure of
the closed system due to the change in temperature when
heat is supplied to the system. Diaphragm-type expansion
tanks should be used. The diaphragm in these tanks is
filled with pressurized air which expands or contracts to
maintain a constant overall system pressure as the fluid in
the system expands with increasing temperature. Use
EPDM diaphragm tanks because they are compatible with
glycol-based antifreeze fluids (butyl rubber diaphragms
will slowly dissolve with glycol-based antifreezes).
Tanks from 1 to 10 gallons are generally used with heat
pump systems in residential and light commercial
applications. Expansion tanks should be installed in the
system near the suction of the circulator pump whenever
possible. This maintains positive pressure at the
circulator pump and reduces the highest working pressure
of the system. A pressure gauge near the inlet of the
expansion tank gives a good indication of how the system
is operating.
Pressure relief valves are required on all hydronic
applications. A 30 psi relief is adequate if the system is
operated at 12 to 15 psi pressure. If a hot water heater is
used for a storage tank, the 150 psi pressure relief may be
acceptable (check local codes).
E. Application Diagrams
Figures 3 through 6 show the components of a hydronic
heat pump system discussed above used in some common
applications. These figures by no means represent all the
possible hydronic heat pump applications, but they do
show some important principals that can be applied to any
system.
Figure 4 ECONAR Hydronic Heat Pump Radiant Floor Heating and Fan Coil Cooling
10
Figure 5 ECONAR Hydronic Heat Pump Single Zone Hydronic Heating Heat Exchanger
)Note: Expect a 10F temperature differential between supply tank and receiving tank when transferring heat with intermediate heat exchanger.
Figure 6 ECONAR Hydronic Heat Pump Supplying Radiant Floor Heating, Fan Coil Cooling, and Car Wash
Water Heating for a Service Station
11
12
D. Temperature Limitations
Be aware of the operating range of the geothermal system
when sizing the particular heat pump. An operating range
of 15oF (minimum for heating) to 110oF (maximum for
cooling) is required for the earth loop side. These limits
have been established based on efficiency limitations and
safety pressure switch limits (50-psi low-pressure cutout
and 580-psi high-pressure cutout). Hydronic side
limitations in heating have a minimum of 50oF HYD
entering water temperature and a maximum of 125oF
HYD leaving water temperature range (entering water to
the hydronic side below 50oF gives low head pressures
B. Thermostat/Aquastat
A. Transformer
Electrical diagrams are provided in Figure 7, and also on
the electrical box cover panel of the heat pump. An
internal 24-volt, 55 VA transformer is provided to operate
13
C. Controller
The controller receives a signal from the thermostat and
initiates the correct sequence of operations for the heat
pump. The controller performs the following functions:
1) Earth Loop Pump Initiation
2) Compressor Operation
3) 4-Way Valve Control
4) Compressor Lockouts
5) Compressor Anti-Short-Cycle
6) System Diagnostics
2. Compressor Operation
A Y signal from the thermostat will ask the controller to
initiate heating or cooling. The controller then decides,
based on lockout and anti-short-cycle periods, when to
bring the compressor on. The M1 output of the controller
energizes the compressor. This compressor stays on until
on the thermostat is satisfied.
4. Compressor Lockouts
A compressor lockout occurs if the high-pressure, low
pressure, or freeze protection pressure switches open.
The controller blocks the signal from the thermostat to the
contactor that normally would energize the compressor. In
the event of a compressor lockout the controller will send
a signal from L on the terminal strip to an LED on the
thermostat to indicate a lockout condition. This lockout
condition means that the unit has shut itself down to
protect itself, and will not come back on until power has
been disconnected (via the circuit breaker) to the heat
pump for one minute. Problems that could cause a
lockout situation include:
1. Water flow or temperature problems
2. Internal heat pump operation problems
3. Cold ambient air temperature conditions
If a lockout condition exists, the heat pump should not
be reset more than once; a service technician should be
called immediately.
,The cause of the lockout must be determined. Repeated
reset may cause damage to the system.
5. Compressor Anti-Short-Cycle
An anti-short-cycle is a delay period between the time a
compressor shuts down and when it is allowed to come on
again. This protects the compressor and avoids nuisance
lockout conditions. Anti-short-cycles occur after these
two conditions;
1. A 30 second to one minute time-out period occurs
on the compressor before it will start after its last
shutdown.
2. A 4 minute 35 second delay is incorporated into
the timing function immediately after power is
applied to the heat pump. This occurs only after
reapplying power to the unit. To avoid this
timeout while servicing the unit, apply power,
disconnect and reapply power very quickly. This
can sometimes eliminate the waiting period.
6. System Diagnostics
The controller is equipped with diagnostic LED lights,
which indicate the system status at any particular time.
The lights indicate the following conditions:
1. 24 Volt system power
GREEN
2. Fault or Lockout
YELLOW
3. Anti-short-cycle mode
RED
IX. STARTUP
Before applying power to the heat pump, check the
following items:
- Water supply plumbing to the heat pump is
completed and operating. Manually open the water
valve on well systems to check flow. Make sure all
valves are open and air has been purged from a loop
system. Never operate the system without correct
water supply.
- Low voltage wiring of the thermostat and any
additional control wiring is complete. Set
thermostat to the OFF position.
- All high voltage wiring is correct including fuses,
breakers, and wire sizes.
- The heat pump is located in a warm area (above
45oF). Starting the system with low ambient
temperature conditions is more difficult; do not
X. SERVICE
Regular service to a GeoSource Ultra hydronic heat
pump is very limited. Setting up regular service checkups
with your ECONAR dealer could be considered. Any
major problems with the heat pump system operation will
be indicated on the thermostat lockout light.
A. Lockout Lights
A lockout light on the thermostat will light to indicate
major system problems. If lockout occurs, follow the
procedure below:
1) Check for correct water supply from the earth loop or
well water system.
2) Reset the system by disconnecting power at the
circuit breaker for one minute and then reapplying
power.
3) If shutdown reoccurs, check the indicator lights on
the controller in the unit and review the lockout
troubleshooting guide in section XI of this manual.
4) If lockouts persist, call your ECONAR dealer. Do
not continuously reset the lockout condition or
damage may occur.
XI. THERMOSTAT
OPERATION
This section covers basic operation of the standard 2-heat
1-cool thermostat that ECONAR carries. This thermostat
is ECONAR part number 70-2002, Honeywell part
number T8511G. If your thermostat is a different style,
please refer to the instructions supplied with that
thermostat.
The settings of the thermostat are controlled with the
System, Fan, i, up key, and down key buttons. The
System and Fan buttons are located behind the flip-down
panel.
By pressing the System button, you can control the
mode that the thermostat operates in. The five system
settings are:
1. Em. Heat Controls backup heating. In this mode,
the heat pumps compressor is locked out, and only
the backup heating elements (if installed) operate.
2. Heat Controls normal heating operation.
3. Off Both heating and cooling are off.
4. Cool Controls normal cooling operation.
5. Auto The thermostat automatically changes
between heating and cooling operation, depending
on the indoor temperature.
Note: When the thermostat is set to Auto, there must be
at least a 2oF difference between the Heating setpoint
temperature and the Cooling setpoint temperature.
The Fan button controls the operation of the heat
pumps blower. The Fan button has two settings:
1. On The blower operates continuously.
2. Auto The blower operates with either a heating or
cooling call.
By pressing the i, or information, key, you can cycle
through your temperature setpoints. If you wish to
change a temperature setting, press either the up key or
down key when the appropriate mode is displayed. For
example, you wish to change the heating setpoint from
68oF to 70oF. Push the i key until the heating setpoint
appears on the LCD display. Then, press the up key until
the desired setpoint is reached. The thermostat will
automatically switch back to the room temperature
display after a few seconds.
If the LED on the bottom of the thermostat is lit, your
heat pump has locked itself out to protect itself. If this
occurs, please see the Compressor Lockout section of this
manual.
If you have additional questions about your thermostat,
please see the installation manual that was sent with the
thermostat.
16
LOCKOUT CONDITION
High Pressure
(Condenser/Hydronic Side)
Heating
Low Pressure
(Evaporator/Earth Coupled Side)
High Pressure
(Condenser/Earth Coupled Side)
Cooling
Low Pressure (Anti-Short Cycle)
(Evaporator/Hydronic Side)
POSSIBLE CAUSE
-Loss/lack of flow through hydronic heat exchanger
-High fluid temperature operation in the hydronic loop
-Overcharged refrigerant circuit
-Loss/lack of flow through earth coupled coil
-Low fluid temperature operation in the earth loop
-Freezing fluid in heat exchanger (lack of antifreeze)
-Undercharged/overcharged refrigerant circuit
-Expansion valve/sensing bulb malfunction
-Loss/lack of flow in earth loop
-High fluid temperature operation in the earth loop
-Dirty (fouled) condenser coil
-Overcharged refrigerant circuit
-Loss/lack of flow through hydronic heat exchanger
-Low fluid temperature operation in the hydronic loop
-Freezing fluid in hydronic heat exchanger (lack of antifreeze)
-Undercharged/overcharged refrigerant circuit
-Expansion valve/sensing bulb malfunction
POSSIBLE CAUSE
Blown Fuse/Tripped Circuit
Breaker
Blown Fuse on Controller
Broken or Loose Wires
Voltage Supply Low
Low Voltage Circuit
Thermostat
17
PROBLEMS
POSSIBLE CAUSE
Thermostat
Wiring
Blown Fuse
High or Low Pressure Controls
Defective Capacitor
Hydronic pump runs Voltage Supply Low
but compressor does
not, or compressor Low Voltage Circuit
short cycles.
Compressor Overload Open
Compressor Overload
Aquastat
Wiring and Controls
Thermostat Improperly Set
Defective Thermostat
Incorrect Wiring
Aquastat set Too High
Reversing Valve does not Shift
Reversing Valve does not Shift,
the Valve is Stuck
Aquastat set Too Low
Insufficient Antifreeze
Compressor
Contactor
Noisy Operation
Rattles and Vibrations
Water and Airborne Noises
Cavitating Pumps
18
Figure 7 - Electrical Diagram for GeoSource Ultra Hydronic Series Heat Pump (GWxxx-x-UxOx)
19
Model
CFM
3 HBC-3
310
4 HBC-3
510
5 HBC-3
600
6 HBC-3
730
8 HBC-3
870
10 HBC-3
1070
13 HBC-3
1400
Heating
dP
Capacity (1000 BTU/hr)
(Ft. of Head)
120oF EWT
140oF EWT
3.0
12.0
12.2
17.4
2.0
6.0
11.7
16.7
1.0
1.9
10.5
14.9
3.5
18.0
16.1
22.9
2.5
10.0
15.7
22.3
1.5
4.5
14.5
20.6
4.0
10.0
19.7
28.0
3.0
5.9
19.1
27.1
2.0
2.9
17.9
25.4
5.5
17.0
24.1
34.3
4.0
10.0
23.4
33.3
2.5
4.2
21.9
31.2
6.0
11.0
29.2
41.5
4.5
6.5
28.3
40.2
3.0
3.0
26.3
37.4
8.0
14.0
34.9
49.7
6.0
8.1
34.2
48.6
4.0
3.9
32.0
45.6
10.0
22.0
45.9
65.3
7.5
13.0
44.8
63.7
5.0
6.2
41.9
59.5
Ratings at 70oF entering air temperature
GPM
Cooling
Model
CFM
GPM
2.8
2.1
1.6
3.6
510
2.8
4 HBC-3
2.1
4.5
600
3.3
5 HBC-3
2.6
5.7
730
4.3
6 HBC-3
3.3
6.4
870
4.7
8 HBC-3
3.7
8.4
1070
6.0
10 HBC-3
4.6
10.8
1400
7.8
13 HBC-3
6.0
TH = Total Heating Capacity
3 HBC-3
310
CONDITION
AC power applied
"
"
INDICATOR LIGHTS
PWR ASC LP
HP
FP
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
COMMENTS
Blown fuse or power removed.
ASC indicator on for 4' 35" on power initialization.
Power applied - unit running or waiting for a call to run.
ASC indicator ON for 30 to 60 seconds after compressor shutdown.
X
X
X
X
7)
8)
9)
10)
11)
12)
13)
14)
15)
16)
17)
Initial BTU's to Heat the Pool Water with no Surface Heat Loss
Hours Allowed to Heat the Pool Water to Desired Temperature
Initial BTU/hr Needed to Heat Pool Water in Time Allowed
Average Wind Speed Factor (see below)
Heat Loss from Pool Surface in BTU/hr
======>
======>
Initial
80
Maintain
80
120
18) Total BTU/hr Required to Heat & Maintain Pool Water Temperature
A)
B)
C)
D)
E)
F)
G)
H)
I)
J)
K)
L)
XV. DESUPERHEATER
(OPTIONAL)
METHOD 1
Using a desuperheater tee installed in the drain at the
bottom of the water heater (See Figure 9). This is the
preferred method for ease of installation, comfort and
efficiency. The tee eliminates the need to tap into the
domestic hot water lines and eliminates household water
supply temperature variations that could occur from
connecting to the hot water pipes.
METHOD 2
Taking hot water from the bottom drain and returning it
to the cold water supply line (See Figure 10). This
method maintains the same comfort and efficiency levels
but increases installation time and costs. This method
requires a check valve in the return line to the cold water
supply to prevent water from flowing backwards through
the desuperheater when the tank is filling. Water passing
through the pump backwards damages the rotor's bearing,
22
NOTES
24
Years 1 through 2, ECONAR Energy Systems Corp. will provide a free replacement part upon prepaid return of all defective parts, F.O.B.
Appleton, MN for any part which fails to function properly due to defective material, or workmanship. * During this period, ECONAR will
provide a free relacement part F.O.B. Appleton, MN for any part which fails to function properly due to defective material, or workmanship.
**First year, ECONAR will provide a free replacement upon prepaid return of all defective parts, F.O.B. Appleton, MN for any part which
fails to function properly due to defective material or workmanship. During this period, ECONAR will cover the cost of labor for the
replacement of parts found to be defective; not to exceed ECONARs published Labor Schedule.
All Applications:
Limitations:
Begins the date of original purchase as recorded by ECONAR with the return of the warranty registration card. (If warranty card is not
submitted, warranty begins the date of original manufacture based on serial number).
Applies to original installation and normal use of the heat pump only and does not include any other component of a system as a whole.
All ECONAR labeled and manufactured accessories carry a 2 year part warranty for residential duty and 1 year for commerical duty. All
other accessories carry the manufacturers warranty only. Labor is excluded on all accessories.
Service must be performed by an ECONAR authorized service person.
Replacement parts shall be warranted for 90 days. After the 90 days, the parts will be covered by the remaining warranty of the unit.
Under no circumstances will ECONAR be liable for incidental, or consequential expenses, losses or damages.
Owners Responsibilites:
Warranty Performance:
The installing contractor will provide the warranty service for the owner. If the installing contractor is not available, contact:
ECONAR Energy Systems, Corp., Customer Support, at 33 West Veum, Appleton, MN 56208 or call toll free 1-800-4-ECONAR.
*Determination of the defect is the sole discretion of ECONAR Energy Systems, Corp.
**Limited Commercial Warranty covers all non-residential applications.
***Energy Star rated products include parts and labor.
This warranty supersedes any and all previously written or implied warranty documentation.
ECONAR Energy Systems Corporation 7/03
25
NRTL/C
90-1050 Rev. 4/04
26