T8@7"C/C 4 T12: Schedule of Footings

1) The document provides notes and specifications for a structural drawing of column details, including dimensions for elements like beams, slabs, footings, and reinforcement. 2) Key specifications include concrete grades of M30 for roof beams and reinforcement bars of grade Fe500. Minimum cover for reinforcement is specified for different elements. 3) Development lengths for reinforcement bars are provided for different bar diameters and concrete grades. A schedule of footings provides dimensions and reinforcement details.

Uploaded by

Mohammed Sumer
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
597 views1 page

T8@7"C/C 4 T12: Schedule of Footings

1) The document provides notes and specifications for a structural drawing of column details, including dimensions for elements like beams, slabs, footings, and reinforcement. 2) Key specifications include concrete grades of M30 for roof beams and reinforcement bars of grade Fe500. Minimum cover for reinforcement is specified for different elements. 3) Development lengths for reinforcement bars are provided for different bar diameters and concrete grades. A schedule of footings provides dimensions and reinforcement details.

Uploaded by

Mohammed Sumer
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

NOTES & SPECIFICATIONS :

7'

9"

2) DO NOT SCALE THE DRAWING. FOLLOW THE FIGURED


DIMENSIONS ONLY.
3) ANY DISCREPANCY SHOULD BE BROUGHT TO THE
NOTICE OF THE CONSULTANTS.

4 T12
T8@7"C/C

9"

6'-3"

1) ALL DIMENSIONS ARE IN MILLIMETERS.

4) GRADE OF CONCRETE SHALL BE :


a) ROOF BEAMS : M30
5) FINE AND COARSE AGGREGATE SHALL CONFIRM ING
TO IS 383 : 1987
6) ALL REINFORCEMENT SHALL HYSD BARS OF GRADE Fe500
CONFORMING TO IS:1786 WITH A MINIMUM YIELD STRENGTH
7) CLEAR COVER REINFORCEMENT SHALL BE :

C1

d) SLABS
: 15-20mm
e) FLOOR BEAMS : 25mm
8) LAP / DEVELOPMENT LENGTH REPRESENTED BY
SHALL BE EQUAL TO 50 TIMES THE DIA OF BAR
(UNLESS NOTED OTHERWISE)

5'

4'-3"

C1

a) FOOTINGS
: 40mm
b) COLUMNS
: 25mm
c) PLINTH BEAMS : 25mm

C1

9) COLUMNS AND FOOTINGS ARE DESIGNED FOR


G+5
10) BUILDING SHALL BE USED FOR HOSPITAL PURPOSE
AS MENTIONED IN DESIGN BASIS REPORT

CLEAR COVER

11) CONTRACTOR'S SITE ENGINEERS TO CHECK AND VERIFY


ALL DIMENSIONS & CORRECTNESS OF DRAWING.
INTIMATE DISCREPANCIES, IF ANY BEFORE EXECUTION
OF WORK.

SLAB TOP LVL.

C1

DEVELOPMENT LENGTH OF BARS FOR Fe-415 GRADE


CJ

IN TENSION

FLOOR BEAM BOTTOM LVL.

IN COMPRESSION

GRADE OF CONCRETE

DIA M-20 M-25 M-30

M-35

300 260

250

215

375

325 10 mm 375 325

300

265

485

450

400 12 mm 450 390

360

320

16 mm 750

645

600

530 16 mm 600 520

480

425

20 mm 945

800

750

665 20 mm 750 645

600

530

25 mm 1175 1010 940

830 25 mm 940 800

750

665

965

850

DIA

COLUMN REINFORCEMENT
COLUMN TIES

M-20 M-25 M-30 M-35

GRADE OF CONCRETE

8 mm 375

325

300

275 8 mm

10 mm 475

400

12 mm 565

32 mm 1500 1290 1200 1060 32 mm 1200 1035

APPROVAL SIGNATORY & STAMP:

G.FLOOR SLAB TOP LVL.

CJ

8'

BEAM AT MID LVL OF COLUMN

PROJECT :
COLUMN REINFORCEMENT
COLUMN TIES

TITLE :

STRUCTURAL DRAWINGS
COLUMN DETAILS

TOP OF PLINTH BEAM


PLINTH
BEAM

CLIENT :

COLUMN REINFORCEMENT

ARCHITECTURAL & STRUCTURAL CONSULTANTS

COLUMN TIES

FOOTING

b
a

PROGRESSIVE

6'

RF

ENGINEERING CONSULTANT
Quality works with in the affordable budget

M10 PCC LEVELLING


COURSE

6"

M A S A B T A N K , H Y D E R A B A D - 28
Ph : +9 5 5 0 8 9 9 6 5 2 , 7 7 9 9 5 3 6 2 2 5
Email: [email protected]

TYPICAL ELEVATION OF COLUMN

REVISIONS :

6"

6'

5'

COLUMN

SCHEDULE OF FOOTINGS
REINFORCEMENT

DIMENSIONS
S.NO. TYPE
1

RF

REMARKS
L

7'-0"

5'-0"

Along L(a)

24"

10 @ 6"c/c

Along B(b)
10 @ 6"c/c

Along L(c)

Along B(d)

10 @ 6"c/c

10 @ 6"c/c

RAFT FOOTING

DATE :

02-01-2016

SCALE :

NTS

DEALT BY :

B.Akshay

Sr. DESIGN ENGG :

Mohd Sumer

PRINCIPAL CONSULTANT :

Md. Taufiq

DRG.NO : PEC/STR/SD-01