4-20ma Input Wiring

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Walchem Webmaster 4-20ma Input Wiring Guide

Walchem Corporation, Holliston, MA

CJ 6/14/07
1. The (-) Minus terminal is the signal input. The 4-20ma signal goes here.
2. The (+) Plus terminal is a +24vdc power supply for the transmitters.
3. The GND terminal is the return for completing the circuits, both signal and power.
4. The +24 terminal at the top, middle of the board is the same supply as the (+) Plus terminal.

A. Two-Wire Loop-Powered Transmitter


Input 1 Input 1 +
Input 2 Input 2 +
Input 3 Input 3 +
Input 4 Input 4 +

- Signal
+24
Notes The - Signal wire is the actual 4-20ma signal and
is also the GND return wire to complete the circuit.
Input - is internally connected to GND via 25 ohm resistor

B. Two-Wire Externally-Powered Transmitter


GND

Notes This transmitter gets it's power from it's own dedicated
power supply.

+24

Input 1 Input 1 +
Input 2 Input 2 +
Input 3 Input 3 +
Input 4 Input 4 +

Power +
Power - Signal
+ Signal

+24 V
GND

Connecting a powered transmitter to the Input + terminal


of the WebMaster will permanently damage the input!

C. Three-Wire Transmitter
GND

Notes The Red and Black wires are the 4-20ma signal.
The Yellow and Black wires are the +24vdc
power supply wires.

+24

Input 1 Input 1 +
Input 2 Input 2 +
Input 3 Input 3 +
Input 4 Input 4 +

+24
- Signal
+ Signal

D. Four-Wire Transmitter
GND

Notes The Red and Black wires are the 4-20ma signal.
The Yellow and Green wires are the +24vdc
power supply wires.

+24

Input 1 Input 1 +
Input 2 Input 2 +
Input 3 Input 3 +
Input 4 Input 4 +

+24
GND
- Signal
+ Signal

E. Non-Isolated Two-Wire Externally-Powered Transmitter


GND
Input 1 Input 1 +
Input 2 Input 2 +
Input 3 Input 3 +
Input 4 Input 4 +

+24

Isolator
OUT IN OUT + IN +

Power +
Power - Signal
+ Signal

Notes The analog inputs share their negative terminals.


They are all isolated from earth ground but not isolated
from each other.
One non-isolated device may be connected without
problems.
If more than one non-isolated transmitter is connected
they must be installed with an isolator.

F. Non-Isolated Four-Wire Externally-Powered Transmitter


GND
Input 1 Input 1 +
Input 2 Input 2 +
Input 3 Input 3 +
Input 4 Input 4 +

Notes The analog inputs share their negative terminals.


They are all isolated from earth ground but not isolated
from each other.
One non-isolated device may be connected without
problems.
If more than one non-isolated transmitter is connected
they must be installed with an isolator.

+24

Isolator
OUT IN OUT + IN +

+24
GND
- Signal
+ Signal

ADDING AN ISOLATED RECEIVER TO THE LOOP (PLC, Chart Recorder, etc.)


The WebMaster GND must always be at the bottom of the loop
Maximum total loop resistance 1000 ohms
A. Two-Wire Loop-Powered Transmitter
Input 1 Input 1 +
Input 2 Input 2 +
Input 3 Input 3 +
Input 4 Input 4 +

PLC

- Signal
+24
Notes The - Signal wire is the actual 4-20ma signal and
is also the GND return wire to complete the circuit.
Input - is internally connected to GND via 25 ohm resistor

B. Two-Wire Externally-Powered Transmitter


GND
Input 1 Input 1 +
Input 2 Input 2 +
Input 3 Input 3 +
Input 4 Input 4 +

Notes This transmitter gets it's power from it's own dedicated
power supply.

+24

PLC

Power +
Power - Signal
+ Signal

+24 V
GND

Connecting a powered transmitter to the Input + terminal


of the WebMaster will permanently damage the input!

C. Three-Wire Transmitter
GND
Input 1 Input 1 +
Input 2 Input 2 +
Input 3 Input 3 +
Input 4 Input 4 +

Notes The Red and Black wires are the 4-20ma signal.
The Yellow and Black wires are the +24vdc
power supply wires.

+24

+24

PLC

- Signal
+ Signal

D. Four-Wire Transmitter
GND
Input 1 Input 1 +
Input 2 Input 2 +
Input 3 Input 3 +
Input 4 Input 4 +

Notes The Red and Black wires are the 4-20ma signal.
The Yellow and Green wires are the +24vdc
power supply wires.

+24

PLC

+24
GND
- Signal
+ Signal