MV Capacitor Banks Brochure
MV Capacitor Banks Brochure
MV Capacitor Banks Brochure
Catalogue
2000
Contents
Schneider Electric
Presentation
Propivar capacitors
MV capacitor banks
10
11
469E1315.fm/1
Presentation
MV capacitors and banks
E29121
E62610
469E1320.fm/2
Schneider Electric
Presentation
MV capacitors and banks (cont.)
Gh y Scc/120
Gh y 0.15 Sn
Standard equipment
Gh > Scc/30
Gh > 0.6 Sn
Harmonic filters
E62611
Filtering harmonics
To improve electrical power quality, Merlin Gerin proposes HV or MV filters which
reduce or eliminate the harmonics flowing in the electrical installation.
These filters are made up of capacitors associated with reactors. They reduce the
distortion rate to a value permissible to or recommended by the electricity board or
clients system as well as compensate reactive power.
Merlin Gerin will conduct all compensation and filtering studies.
Schneider Electric
469E1320.fm/3
052312
Propivar capacitors
Presentation
A Propivar medium voltage capacitor is a steel case or tank provided with resin
insulators. The tank comprises an assembly of capacitor elements having a
maximum permissible rated voltage of 2250 V.
When connected in series-parallel groups, they provide high power units for elevated
system voltages.
There are two types of capacitors:
b with internal fuses (single-phase capacitor)
b without internal fuses (three-phase or single-phase capacitor).
Each capacitor is normally provided with discharge resistors to bring the residual
voltage down to 75 V 10 minutes after the capacitor has been switched off.
If requested, the capacitors can be supplied without discharge resistors.
Construction
The Propivar capacitors are composed of elements which include:
b aluminium foil electrodes;
b a non-chlorinated biodegradable dielectric liquid and a polypropylene film.
The dielectric solely made up of plastic films helps to greatly reduce dielectric losses.
E14591
Main characteristics
E14445A
E14445B
Fig. 1
Fig. 2
469E2325.fm/4
Schneider Electric
Propivar capacitors
3.6
7.2
12
17.5
24
36
20
60
28
75
38
95
50
125
70
170
Insulation level
Other characteristics
The rated reactive power of the unit capacitors is 100 to 600 kvar, according to rated
voltage (see tables opposite).
The capacitance of the capacitors is always between 0.95 and 1.15 times rated
capacitance. Other intermediate powers can be offered on request.
Service frequency
50 Hz - (60 Hz if requested)
Temperature range
-25 to +45 C (other ranges, if requested)
Average loss factor at 20 C
0.16 W/kvar with internal fuses
after stabilisation
0.12 W/kvar without internal fuses
Capacitance variation C/C
-3.5 . 10-4/C
Connection to porcelain or resin insulators for cables with a section y 50 mm2
Tank
welded steel
thickness
1.5 mm
paint
vinyl
colour
grey RAL 7038
anticorrosion treatment indoor type
wash-primer, thickness 5 m
paint, thickness 20 m
outdoor type sanding
metallisation, 80 m of zinc
wash-primer and paint: thickness 20 m
Fixing
2 perforated brackets for M10 screw
system
Choice
The three tables opposite present the range of Propivar capacitors.
Single-phase capacitors without internal fuses
for Um voltages 7.2 - 12 - 17.5 - 24 - 36 kV/50 Hz (*)
Nota : Um = highest network voltage
Power
(kvar)
100 to 150
150 to 200
200 to 250
250 to 300
300 to 350
350 to 400
400 to 450
450 to 500
500 to 550
550 to 600
3.5
4.5
5.5
6.8
9.1
11.4 13.8
5.5
6.8
9.1
11.4 13.8
5.5
6.8
9.1
11.4 13.8
3.5
4.5
3.5
4.5
469E2325.fm/5
052314
052323
MV capacitor banks
Presentation
Composition of capacitor banks
Merlin Gerin designs all types of capacitor banks whatever:
b the complexity of the system (calculation of the filter)
b the desired reactive power
b the rated insulating voltages.
For easier selection, Merlin Gerin has standardised its capacitor equipment and
offers two versions:
b in open rack IP 00
b in cubicle IP 23, with or without control devices.
The capacitor banks are designed according to two capacitor connection modes:
delta connection or double star connection.
Cubicles increase:
b safety of operating personnel by protecting them from contact with live parts and
integrating the switching and protection functions
b continuity of service by reducing electrical faults by isolation of live parts.
The capacitor bank control equipment is incorporated into the cubicles containing the
capacitors when:
b compensation is on an individual basis, for each machine consuming large
quantities of reactive power
b the capacitor banks in the system are separate and distributed throughout the
installation
b multi stage automatic compensation is required.
Capacitor protection
Capacitors must be protected against short-circuits and earth faults.
Current and voltage overload protection is also recommended.
Bank with delta-connected capacitors (fig. 3)
These capacitors must be protected by a device that trips quickly should an internal
fault occur. Only limiting HBC fuses can provide such protection. Their rating must
be at least 1.8 lN. The exact determination of the rating requires knowledge of
installation data. A circuit-breaker alone does not provide sufficient protection.
469E2330.fm/6
Schneider Electric
MV capacitor banks
The fitness of the devices to switch capacitive currents must be checked with the
manufacturer.
Current sizing
Breaking and protection devices must withstand a continuous current of 1.43 times
rated bank current.
E29128
Connection mode
The equipment can have different forms:
b delta connection:
v three-phase capacitors (without internal fuse) connected in parallel
v single-phase capacitors (without internal fuse).
b double star connection: from 6 to 48 single-phase capacitors (with or without
internal fuse)
b single star connection (special for EHV) 36 single-phase capacitors
(12 per branch) if requested.
The selection depends on:
b the following characteristics: network voltage and capacitor bank power
b the type of compensation, fixed or controlled (switched steps)
b the type of protection:
v capacitor with or without internal fuse
v unbalance current with MV fuses.
b economic requirements. In response to this last point, it should be noted that the
cost of a capacitor bank is a direct function of the number of elements: with identical
operating characteristics, a system composed of three capacitors with a delta
connection is therefore cheaper than a system composed of six single-phase
capacitors with a double star connection.
Standard assemblies
Aside from the capacitors, the banks standardised by Merlin Gerin include the
elements mentioned in the opposite table. Any power available on request.
Rated voltage Un (kV)
Highest voltage Um (kV)
Connection mode delta
double star
Fixed bank, open rack
Maximum power (kvar)
Protection against internal faults
MV fuses
unbalance measurement
Fixed bank, cubicle
Maximum power (kvar)
Protection against internal faults
MV fuses
unbalance measurement
"switched steps" bank, cubicle
Maximum power (kvar)
control device
contactor
switch or CB
Protection against internal faults
MV fuses
unbalance measurement
Schneider Electric
y 6.6
7.2
6.6 to 11
12
11 to 15.6
17.5
1500
4200
1500
21000
36000
36000
36000
1500
4200
1500
7200
7200
7200
7200
1500
4200
1500
7200
7200
7200
7200
all powers
469E2330.fm/7
MV capacitor banks
Characteristics
CP 210 (*)
fixed
Type of bank
Capacitors
CP210
numbers
type
1, 2 or 3
three-phase
Connection
delta
Rack
open with terminal cover
Protection index
IP 23
Indoor
yes
Outdoor
yes
Maximum insulating voltage
12 kV
Max. power
1500 kvar
(*) capacitor protection is ensured using HBC fuses (not supplied)
Characteristics
Type of bank
Capacitors
E29128
CP212
numbers
type
CP212
fixed
CP225
fixed
CP229
fixed
CP230
fixed
1, 2 or 3
three-phase
delta
open
yes
no (1)
12 kV
1500 kvar
6, 9 or 12
single-phase
double star
open
yes
yes
36 kV
7200 kvar
60 maxi
single-phase
double star
open
yes
yes
36 kV
36000 kvar
as required
single-phase
double star
open
yes
yes
> 36 kV
all powers
Connection
Equipment
on rack
Indoor
Outdoor
max. insulating voltage
Max. power (2)
Additional equipment
Inrush current reactor
Rapid discharge reactor
HBC fuses
Unbalance protection relay (supplied separately)
(1) the equipment can be used outdoor if the fuse option is not chosen.
(2) please consult us for higher powers.
E29127
CP225
E29129
CP229
CP230
469E2330.fm/8
Schneider Electric
MV capacitor banks
Characteristics
Type of battery
Capacitors
E29127
CP214
number
type
CP214
fixed
CP227
fixed
1, 2 or 3
three-phase
delta
in cubicle
yes
yes
12 kV
1500 kvar
6, 9 or 12
single-phase
double star
in cubicle
yes
yes
36 kV
7200 kvar
Connection
Equipment
Indoor
Outdoor
Max. insulating voltage
Max. power (2)
Additional equipment
Inrush current reactors
rapid discharge reactor
HBC fuses
Unbalance protection relay (supplied separately)
CP227
Characteristics
Type of battery
Capacitors
E29133
CP253
number
type
Connection
Equipment
Indoor
Outdoor
Max. insulating voltage
Max. power
Additional equipment
MV equipment: Inrush current reactors
Rapid discharge reactor
Earthing switch
Control device with
- Rollarc with HBC fuses
- Fluarc SF1 circuit breaker
LV equipment:
CP253
modulable steps
CP254
modulable steps
1, 2 or 3
three-phase
three-phase
in cubicle
yes
yes
12 kV
1500 kvar
6, 9 or 12
single-phase
double star
in cubicle
yes
yes
36 kV
7200 kvar
CP254
Schneider Electric
469E2330.fm/9
Propivar capacitors
E62612
Single-phase capacitors
with internal fuses
without internal fuses
Three-phase capacitors
without internal fuses
H
320
390
460
530
610
650
710
780
770
840
900
H
280
370
460
530
620
640
700
760
760
P
130
135
140
145
145
155
165
165
185
185
185
masse
25
31
36
42
48
54
62
68
74
80
86
H
270
360
430
510
590
630
670
760
740
810
870
P
130
130
140
140
140
150
160
160
180
180
180
masse
21
27
34
39
45
51
57
64
69
75
80
P
130
130
135
140
140
150
160
160
180
masse
24
30
37
43
49
53
61
65
72
E62613
Fixing system
469E3340.fm/10
Schneider Electric
H (mm)
1300
L (mm)
D (mm)
Weight (kg)
750
600
10
Nota : the dimensions and weight (not including the capacitor) are shown with the most complete
equipment.
CP210
Model
CP212
CP225
CP229
CP230
H (mm)
L (mm)
D (mm)
Weight (kg)
1600
2000
1950
3000
1500
2300
3100
3100
700
1200
2200
2200
150
200
400
450
Nota : the dimensions and weights (not including the capacitor) are shown with the most
complete equipment of this type of bank.
E62616
CP212
E62617
CP225
E62618
CP229
CP230
Schneider Electric
469E3345.fm/11
Model
CP214
CP227
H (mm)
L (mm)
D (mm)
Weight (kg)
1800
2000
1550
2350
950
1400
340
350
Nota : the dimensions and weights (not including the capacitor) are shown with the most
complete equipment of this type of bank.
E62621
CP214
CP227
Model
H (mm)
L (mm)
D (mm)
Weight (kg)
CP253
2000
3200
1400
280
CP254
2100
2700
1400
650
Nota : the dimensions and weights (not including the capacitor) are shown with the most
complete equipment of this type of bank.
E62622
CP253
CP254
469E3345.fm/12
Schneider Electric
As standards, specifications and designs develop from time to time, always ask for confirmation
of the information given in this publication.
This document has been printed on ecological paper
04-2000