Iec 61869 2 2012 09

Download as pdf or txt
Download as pdf or txt
You are on page 1of 144
At a glance
Powered by AI
The document discusses determining the ratio of transformer windings through testing and calculations.

The document discusses testing procedures and calculations to determine the actual ratio of transformer windings, which can be affected by errors from various sources like winding ratios and magnetic circuit excitation currents.

The document describes taking measurements at the rated current and half the rated current while adjusting the secondary loop resistance appropriately. It provides equations to calculate the winding ratio error based on the different measurements.

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

IEC 61869-2
Edition 1.0 2012-09

INTERNATIONAL
STANDARD
NORME
INTERNATIONALE

IEC 61869-2:2012

Transformateurs de mesure
Partie 2: Exigences supplmentaires concernant les transformateurs de courant

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Instrument transformers
Part 2: Additional requirements for current transformers

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

THIS PUBLICATION IS COPYRIGHT PROTECTED


Copyright 2012 IEC, Geneva, Switzerland
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form
or by any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from
either IEC or IEC's member National Committee in the country of the requester.
If you have any questions about IEC copyright or have an enquiry about obtaining additional rights to this publication,
please contact the address below or your local IEC member National Committee for further information.
Droits de reproduction rservs. Sauf indication contraire, aucune partie de cette publication ne peut tre reproduite ni
utilise sous quelque forme que ce soit et par aucun procd, lectronique ou mcanique, y compris la photocopie et les
microfilms, sans l'accord crit de la CEI ou du Comit national de la CEI du pays du demandeur.
Si vous avez des questions sur le copyright de la CEI ou si vous dsirez obtenir des droits supplmentaires sur cette
publication, utilisez les coordonnes ci-aprs ou contactez le Comit national de la CEI de votre pays de rsidence.
IEC Central Office
3, rue de Varemb
CH-1211 Geneva 20
Switzerland

Tel.: +41 22 919 02 11


Fax: +41 22 919 03 00
[email protected]
www.iec.ch

About the IEC

The International Electrotechnical Commission (IEC) is the leading global organization that prepares and publishes
International Standards for all electrical, electronic and related technologies.
The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the
latest edition, a corrigenda or an amendment might have been published.
Useful links:
IEC publications search - www.iec.ch/searchpub

Electropedia - www.electropedia.org

The advanced search enables you to find IEC publications


by a variety of criteria (reference number, text, technical
committee,).
It also gives information on projects, replaced and
withdrawn publications.

The world's leading online dictionary of electronic and


electrical terms containing more than 30 000 terms and
definitions in English and French, with equivalent terms in
additional languages. Also known as the International
Electrotechnical Vocabulary (IEV) on-line.

IEC Just Published - webstore.iec.ch/justpublished

Customer Service Centre - webstore.iec.ch/csc

Stay up to date on all new IEC publications. Just Published


details all new publications released. Available on-line and
also once a month by email.

If you wish to give us your feedback on this publication


or need further assistance, please contact the
Customer Service Centre: [email protected].

A propos de la CEI

La Commission Electrotechnique Internationale (CEI) est la premire organisation mondiale qui labore et publie des
Normes internationales pour tout ce qui a trait l'lectricit, l'lectronique et aux technologies apparentes.

A propos des publications CEI

Le contenu technique des publications de la CEI est constamment revu. Veuillez vous assurer que vous possdez
ldition la plus rcente, un corrigendum ou amendement peut avoir t publi.
Liens utiles:
Recherche de publications CEI - www.iec.ch/searchpub

Electropedia - www.electropedia.org

La recherche avance vous permet de trouver des


publications CEI en utilisant diffrents critres (numro de
rfrence, texte, comit dtudes,).
Elle donne aussi des informations sur les projets et les
publications remplaces ou retires.

Le premier dictionnaire en ligne au monde de termes


lectroniques et lectriques. Il contient plus de 30 000
termes et dfinitions en anglais et en franais, ainsi que
les termes quivalents dans les langues additionnelles.
Egalement
appel
Vocabulaire
Electrotechnique
International (VEI) en ligne.

Just Published CEI - webstore.iec.ch/justpublished


Restez inform sur les nouvelles publications de la CEI.
Just Published dtaille les nouvelles publications parues.
Disponible en ligne et aussi une fois par mois par email.

Service Clients - webstore.iec.ch/csc


Si vous dsirez nous donner des commentaires sur
cette publication ou si vous avez des questions
contactez-nous: [email protected].

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

About IEC publications

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

IEC 61869-2
Edition 1.0 2012-09

INTERNATIONAL
STANDARD
NORME
INTERNATIONALE

Transformateurs de mesure
Partie 2: Exigences supplmentaires concernant les transformateurs de courant

INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE

PRICE CODE
CODE PRIX

ICS 17.220.20

XB

ISBN 978-2-83220-293-7

Warning! Make sure that you obtained this publication from an authorized distributor.
Attention! Veuillez vous assurer que vous avez obtenu cette publication via un distributeur agr.
Registered trademark of the International Electrotechnical Commission
Marque dpose de la Commission Electrotechnique Internationale

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Instrument transformers
Part 2: Additional requirements for current transformers

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012

CONTENTS
FOREWORD ........................................................................................................................... 5
1

Scope ............................................................................................................................... 8

Normative references ....................................................................................................... 8

Terms and definitions ....................................................................................................... 8

3.1 General definitions .................................................................................................. 8


3.3 Definitions related to current ratings ........................................................................ 9
3.4 Definitions related to accuracy .............................................................................. 10
3.7 Index of abbreviations ........................................................................................... 18
Ratings ........................................................................................................................... 20
5.3

6.4

Requirements for temperature rise of parts and components .............................. 27


6.4.1
General ............................................................................................ 27
6.13
Markings ............................................................................................................. 27
6.13.201
Terminal markings ............................................................................ 27
6.13.202
Rating plate markings ....................................................................... 28
Tests .............................................................................................................................. 30
7.1
7.2

7.3

General .............................................................................................................. 30
7.1.2
Lists of tests ..................................................................................... 30
Type tests ........................................................................................................... 31
7.2.2
Temperature-rise test ....................................................................... 31
7.2.3
Impulse voltage withstand test on primary terminals ......................... 33
7.2.6
Tests for accuracy ............................................................................ 33
7.2.201
Short-time current tests .................................................................... 35
Routine tests ...................................................................................................... 36
7.3.1
Power-frequency voltage withstand tests on primary terminals ......... 36
7.3.5
Tests for accuracy ............................................................................ 36
7.3.201
Determination of the secondary winding resistance (R ct ) ................... 38
7.3.202
Determination of the secondary loop time constant (T s ) .................... 38

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Rated insulation levels ........................................................................................ 20


5.3.2
Rated primary terminal insulation level ............................................. 20
5.3.5
Insulation requirements for secondary terminals ............................... 20
5.3.201
Inter-turn insulation requirements ..................................................... 20
5.5
Rated output ....................................................................................................... 20
5.5.201
Rated output values ......................................................................... 20
5.5.202
Rated resistive burden values .......................................................... 20
5.6
Rated accuracy class .......................................................................................... 21
5.6.201
Measuring current transformers ........................................................ 21
5.6.202
Protective current transformers ........................................................ 22
5.6.203
Class assignments for selectable-ratio current transformers ............. 26
5.201 Standard values for rated primary current ........................................................... 26
5.202 Standard values for rated secondary current ....................................................... 27
5.203 Standard values for rated continuous thermal current ......................................... 27
5.204 Short-time current ratings ................................................................................... 27
5.204.1
Rated short-time thermal current (I th ) ............................................... 27
5.204.2
Rated dynamic current (I dyn ) ............................................................ 27
Design and construction ................................................................................................. 27

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012

7.3.203
Test for rated knee point e.m.f. (E k ) and exciting current at E k .......... 39
7.3.204
Inter-turn overvoltage test ................................................................ 39
7.4
Special tests ....................................................................................................... 40
7.4.3
Measurement of capacitance and dielectric dissipation factor ........... 40
7.4.6
Internal arc fault test ........................................................................ 40
7.5
Sample tests ....................................................................................................... 41
7.5.1
Determination of the remanence factor ............................................. 41
7.5.2
Determination of the instrument security factor (FS) of
measuring current transformers ........................................................ 41
Annex 2A (normative) Protective current transformers classes P, PR ................................... 42
Annex 2B (normative) Protective current transformer classes for transient
performance ......................................................................................................................... 47
Annex 2C (normative) Proof of low-leakage reactance type ................................................. 63
Annex 2D (informative) Technique used in temperature rise test of oil-immersed
transformers to determine the thermal constant by an experimental estimation ..................... 64
Annex 2E (informative) Alternative measurement of the ratio error () .................................. 66

Figure 201 Duty cycles ...................................................................................................... 15


Figure 202 Primary time constant T P .................................................................................. 16
Figure 203 Secondary linked flux for different fault inception angles ................................ 17
Figure 2A.1 Vector Diagram ............................................................................................... 42
Figure 2A.2 Error triangle ................................................................................................... 43
Figure 2A.3 Typical current waveforms .............................................................................. 44
Figure 2A.4 Basic circuit for 1:1 current transformer .......................................................... 44
Figure 2A.5 Basic circuit for current transformer with any ratio........................................... 45
Figure 2A.6 Alternative test circuit ..................................................................................... 45
Figure 2B.1 Short-circuit current for two different fault inception angles ............................. 48
Figure 2B.2 max(t) as the curve of the highest flux values, considering all relevant
fault inception angles ......................................................................................................... 48
Figure 2B.3 Relevant time ranges for calculation of transient factor ................................... 49
Figure 2B.4 Determination of K tf in time range 1 at 50 Hz for T s = 1,8 s ........................... 50
Figure 2B.5 Determination of K tf in time range 1 at 60 Hz for T s = 1,5 s ........................... 50
Figure 2B.6 Determination of K tf in time range 1 at 16,7 Hz for T s = 5.5 s ......................... 50
Figure 2B.7 Limiting the magnetic flux by considering core saturation ................................ 52
Figure 2B.8 Basic circuit .................................................................................................... 53
Figure 2B.9 Determination of remanence factor by hysteresis loop .................................... 55
Figure 2B.10 Circuit for d.c. method ................................................................................... 56
Figure 2B.11 Time-amplitude and flux-current diagrams .................................................... 56
Figure 2B.12 Recordings with shifted flux base line ........................................................... 57
Figure 2B.13 Circuit for capacitor discharge method .......................................................... 58
Figure 2B.14 Typical records for capacitor discharge method ............................................ 59
Figure 2B.15 Measurement of error currents ...................................................................... 60
Figure 2D.1 Graphical extrapolation to ultimate temperature rise ....................................... 65
Figure 2E.1 Simplified equivalent circuit of the current transformer .................................... 66

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Annex 2F (normative) Determination of the turns ratio error ................................................. 68

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012

Table 201 Limits of ratio error and phase displacement for measuring current
transformers (classes 0,1 to 1).............................................................................................. 21
Table 202 Limits of ratio error and phase displacement for measuring current
transformers (classes 0,2S and 0,5S) ................................................................................... 22
Table 203 Limits of ratio error for measuring current transformers (classes 3 and 5) .......... 22
Table 204 Characterisation of protective classes ............................................................... 23
Table 205 Error limits for protective current transformers class P and PR .......................... 23
Table 206 Error limits for TPX, TPY and TPZ current transformers..................................... 25
Table 207 Specification Methods for TPX, TPY and TPZ current transformers ................... 26
Table 208 Marking of terminals .......................................................................................... 28
Table 10 List of tests ......................................................................................................... 31

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012

INTERNATIONAL ELECTROTECHNICAL COMMISSION


____________
INSTRUMENT TRANSFORMERS
Part 2: Additional requirements for current transformers
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as IEC
Publication(s)). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and nongovernmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.

3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.

This International Standard IEC 61869-2 Ed.1.0 has been prepared by committee 38:
Instrument transformers.
This first edition of IEC 61869-2 cancels and replaces the first edition of IEC 60044-1,
published in 1996, and its Amendment 1 (2000) and Amendment 2 (2002), and the first edition
of IEC 60044-6, published in 1992. Additionally it introduces technical innovations in the
standardization and adaptation of the requirements for current transformers for transient
performance.
The text of this standard is based on the following documents:
FDIS

Report on voting

38/435/FDIS

38/437/RVD

Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

2) The formal decisions or agreements of IEC on technical matters express, as closely as possible, an
international consensus of opinion on the relevant subjects since each technical committee has representation
from all interested IEC National Committees.

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012

This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.
A list of all the parts in the IEC 61869 series, published under the general title Instrument
transformers, can be found on the IEC website.
This Part 2 is to be used in conjunction with, and is based on, IEC 61869-1:2007, General
Requirements however the reader is encouraged to use its most recent edition.
This Part 2 follows the structure of IEC 61869-1:2007 and supplements or modifies its
corresponding clauses.
When a particular clause/subclause of Part 1 is not mentioned in this Part 2, that
clause/subclause applies as far as is reasonable. When this standard states addition,
modification or replacement, the relevant text in Part 1 is to be adapted accordingly.
For additional clauses, subclauses, figures, tables, annexes or notes, the following numbering
system is used:
clauses, subclauses, tables, figures and notes that are numbered starting from 201 are
additional to those in Part 1;

additional annexes are lettered 2A, 2B, etc.

An overview of the planned set of standards at the date of publication of this document is
given below. The updated list of standards issued by IEC TC38 is available at the website:
www.iec.ch.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012
PRODUCT FAMILY STANDARDS

61869-6

GENERAL
REQUIREMENTS
FOR
INSTRUMENT
TRANSFORMERS

ADDITIONAL
GENERAL
REQUIREMENT
FOR
ELECTRONIC
INSTRUMENT
TRANSFORMERS
AND LOW
POWER STAND
ALONE
SENSORS

PRODUCT
STANDARD

PRODUCTS

OLD
STANDARD

61869-2

ADDITIONAL REQUIREMENTS FOR


CURRENT TRANSFORMERS

60044-1
60044-6

61869-3

ADDITIONAL REQUIREMENTS FOR


INDUCTIVE VOLTAGE TRANSFORMERS

60044-2

61869-4

ADDITIONAL REQUIREMENTS FOR


COMBINED TRANSFORMERS

60044-3

61869-5

ADDITIONAL REQUIREMENTS FOR


CAPACITIVE VOLTAGE TRANSFORMERS

60044-5

61869-7

ADDITIONAL REQUIREMENTS FOR


ELECTRONIC VOLTAGE
TRANSFORMERS

60044-7

61869-8

ADDITIONAL REQUIREMENTS FOR


ELECTRONIC CURRENT
TRANSFORMERS

60044-8

61869-9

DIGITAL INTERFACE FOR INSTRUMENT


TRANSFORMERS

61869-10

ADDITIONAL REQUIREMENTS FOR LOWPOWER STAND-ALONE CURRENT


SENSORS

61869-11

ADDITIONAL REQUIREMENTS FOR LOW


POWER STAND ALONE VOLTAGE
SENSOR

61869-12

ADDITIONAL REQUIREMENTS FOR


COMBINED ELECTRONIC INSTRUMENT
TRANSFORMER OR COMBINED STAND
ALONE SENSORS

61869-13

STAND ALONE MERGING UNIT

60044-7

Since the publication of IEC 60044-6 (Requirements for protective current transformers for
transient performance) in 1992, the area of application of this kind of current transformers has
been extended. As a consequence, the theoretical background for the dimensioning according
to the electrical requirements has become much more complex. In order to keep this standard
as user-friendly as possible, the explanation of the background information will be transferred
to the Technical Report IEC 61869-100 TR, which is now in preparation.
The committee has decided that the contents of this publication will remain unchanged until
the stability date indicated on the IEC web site under "http://webstore.iec.ch" in the data
related to the specific publication. At this date, the publication will be

reconfirmed,
withdrawn,
replaced by a revised edition, or
amended.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

61869-1:2007

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012

INSTRUMENT TRANSFORMERS
Part 2: Additional requirements for Current Transformers

Scope

This part of IEC 61869 is applicable to newly manufactured inductive current transformers for
use with electrical measuring instruments and/or electrical protective devices having rated
frequencies from 15 Hz to 100 Hz.

Normative references

Clause 2 of IEC 61869-1:2007 is applicable with the following additions:

Terms and definitions

For the purposes of this document, the terms and definitions in IEC 61869-1:2007 apply with
the following additions:
3.1

General definitions

3.1.201
current transformer
instrument transformer in which the secondary current, under normal conditions of use, is
substantially proportional to the primary current and differs in phase from it by an angle which
is approximately zero for an appropriate direction of the connections
[SOURCE: IEC 60050-321:1986, 321-02-01]
3.1.202
measuring current transformer
current transformer intended to transmit an information signal to measuring instruments and
meters
[SOURCE: IEC 60050-321:1986, 321-02-18]
3.1.203
protective current transformer
a current transformer intended to transmit an information signal to protective and control
devices
[SOURCE: IEC 60050-321: 1986, 321-02-19)
3.1.204
class P protective current transformer
protective current transformer without remanent flux limit, for which the saturation behaviour
in the case of a symmetrical short-circuit is specified
3.1.205
class PR protective current transformer
protective current transformer with remanent flux limit, for which the saturation behaviour in
the case of a symmetrical short-circuit is specified

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

IEC 61869-1:2007, Instrument Transformers Part 1: General requirements

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012

3.1.206
class PX protective current transformer
protective current transformer of low-leakage reactance without remanent flux limit for which
knowledge of the excitation characteristic and of the secondary winding resistance, secondary
burden resistance and turns ratio, is sufficient to assess its performance in relation to the
protective relay system with which it is to be used
3.1.207
class PXR protective current transformer
protective current transformer with remanent flux limit for which knowledge of the excitation
characteristic and of the secondary winding resistance, secondary burden resistance and
turns ratio, is sufficient to assess its performance in relation to the protective relay system
with which it is to be used
Note 1 to entry: An increasingly number of situations occur where low DC currents are continuously flowing through
current transformers. Therefore, in order to stop the current transformer from saturating, current transformers with
air gaps, but with the same performance as Class PX, are used.
Note 2 to entry: The air gaps for remanence reduction do not necessarily lead to a high-leakage reactance current
transformer (see Annex 2C).

3.1.209
class TPY protective current transformer for transient performance
protective current transformer with remanent flux limit, for which the saturation behaviour in
case of a transient short-circuit current is specified by the peak value of the instantaneous
error
3.1.210
class TPZ protective current transformer for transient performance
protective current transformer with a specified secondary time-constant, for which the
saturation behaviour in case of a transient short-circuit current is specified by the peak value
of the alternating error component
3.1.211
selectable-ratio current transformer
current transformer on which several transformation ratios are obtained by reconnecting the
primary winding sections and / or by means of taps on the secondary winding
3.3

Definitions related to current ratings

3.3.201
rated primary current
I pr
value of the primary current on which the performance of the transformer is based
[SOURCE: IEC 60050-321:1986, 321-01-11, modified title, synonym and definition]
3.3.202
rated secondary current
I sr
value of the secondary current on which the performance of the transformer is based
[SOURCE: IEC 60050-321:1986, 321-01-15, modified title, synonym and definition]

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

3.1.208
class TPX protective current transformer for transient performance
protective current transformer without remanent flux limit, for which the saturation behaviour
in case of a transient short-circuit current is specified by the peak value of the instantaneous
error

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

10

61869-2 IEC:2012

3.3.203
rated short-time thermal current
I th
maximum value of the primary current which a transformer will withstand for a specified short
time without suffering harmful effects, the secondary winding being short-circuited
[SOURCE: IEC 60050-321:1986, 321-02-22]
3.3.204
rated dynamic current
I dyn
maximum peak value of the primary current which a transformer will withstand, without being
damaged electrically or mechanically by the resulting electromagnetic forces, the secondary
winding being short-circuited
[SOURCE: IEC 60050-321:1986, 321-02-24]

[SOURCE: IEC 60050-321:1986, 321-02-25]


3.3.206
rated primary short-circuit current
I psc
r.m.s. value of the a.c. component of a transient primary short-circuit current on which the
accuracy performance of a current transformer is based
Note 1 to entry: While I th is related to the thermal limit, I psc is related to the accuracy limit. Usually, I psc is smaller
than I th .

3.3.207
exciting current
Ie
r.m.s. value of the current taken by the secondary winding of a current transformer, when a
sinusoidal voltage of rated frequency is applied to the secondary terminals, the primary and
any other windings being open-circuited
[SOURCE: IEC 60050-321:1986, 321-02-32]
3.4

Definitions related to accuracy

3.4.3
ratio error

Definition 3.4.3 of IEC 61869-1:2007 is applicable with the addition of the following note:
Note 201 to entry: The current ratio error, expressed in per cent, is given by the formula:

k r I s I p
Ip

100 %

where
kr
is the rated transformation ratio;
Ip
is the actual primary current;
Is
is the actual secondary current when I p is flowing, under the conditions of measurement.
An explicative vector diagram is given in 2A.1.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

3.3.205
rated continuous thermal current
I cth
value of the current which can be permitted to flow continuously in the primary winding, the
secondary winding being connected to the rated burden, without the temperature rise
exceeding the values specified

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012

11

3.4.4
phase displacement

The definition 3.4.4 of IEC 61869-1:2007 is applicable with the addition of the following note:
Note 1 to entry: An explicative vector diagram is given in 2A.1.

3.4.201
rated resistive burden
Rb
rated value of the secondary connected resistive burden in ohms
3.4.202
secondary winding resistance
R ct
actual secondary winding d.c. resistance in ohms corrected to 75 C or such other
temperature as may be specified
Note 1 to entry: R ct is an actual value. It shall not be confused with the upper limit for R ct , which can be specified
otherwise.

a) the instantaneous values of the primary current, and


b) the instantaneous values of the actual secondary current multiplied by the rated
transformation ratio,
the positive signs of the primary and secondary currents corresponding to the convention for
terminal markings
Note 1 to entry: The composite error
current:

is generally expressed as a percentage of the r.m.s. values of the primary

c =

1
( k r i s i p ) 2 dt
T 0
Ip

100 %

where
kr

is the rated transformation ratio;

Ip

is the r.m.s. value of the primary current;

ip

is the instantaneous value of the primary current;

is

is the instantaneous value of the secondary current;

is the duration of one cycle.

For further explanation, refer to 2A.4.

[SOURCE: IEC 60050-321:1986, 321-02-26, modified note to entry]


3.4.204
rated instrument limit primary current
I PL
value of the minimum primary current at which the composite error of the measuring current
transformer is equal to or greater than 10 %, the secondary burden being equal to the rated
burden
[SOURCE: IEC 60050-321:1986, 321-02-27]

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

3.4.203
composite error
c
under steady-state conditions, the r.m.s. value of the difference between

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

12

61869-2 IEC:2012

3.4.205
instrument security factor
FS
ratio of rated instrument limit primary current to the rated primary current
Note 1 to entry: Attention should be paid to the fact that the actual instrument security factor is affected by the
burden. When the burden value is significantly lower than rated one, larger current values will be produced on the
secondary side in the case of short-circuit current.
Note 2 to entry: In the event of system fault currents flowing through the primary winding of a current transformer,
the safety of the apparatus supplied by the transformer is at its highest when the value of the rated instrument
security factor (FS) is at its lowest.

[SOURCE: IEC 60050-321:1986, 321-02-28, modified notes to entry]


3.4.206
secondary limiting e.m.f. for measuring current transformers
E FS
product of the instrument security factor FS, the rated secondary current and the vectorial sum
of the rated burden and the impedance of the secondary winding

E FS = FS I sr ( Rct + Rb ) 2 + X b2
where:

Rb

is the resistive part of the rated burden;

Xb

is the inductive part of the rated burden.

This method will give a higher value than the actual one. It was chosen in order to apply the same test method as
used for protective current transformers. Refer to 7.2.6.202 and 7.2.6.203.

[SOURCE: IEC 60050-321:1986, 321-02-31, modified title, synonym and note to entry]
3.4.207
rated accuracy limit primary current
value of primary current up to which the current transformer will comply with the requirements
for composite error
[SOURCE: IEC 60050-321:1986, 321-02-29]
3.4.208
accuracy limit factor
ALF
ratio of the rated accuracy limit primary current to the rated primary current
[SOURCE: IEC 60050-321:1986, 321-02-30]
3.4.209
secondary limiting e.m.f. for protective current transformers
E ALF
product of the accuracy limit factor, the rated secondary current and the vectorial sum of the
rated burden and the impedance of the secondary winding
Note 1 to entry: The secondary limiting e.m.f for class P and PR protective current transformers E ALF is calculated
as

E ALF = ALF I sr ( Rct + Rb ) 2 + X b2


where:

Rb

is

the resistive part of the rated burden;

Xb

is

the inductive part of the rated burden.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Note 1 to entry: The secondary limiting e.m.f. for measuring current transformers E FS is calculated as

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012

13

3.4.210
saturation flux
sat
maximum value of secondary linked flux in a current transformer, which corresponds to the
magnetic saturation of the core material
Note 1 to entry: The most suitable procedure for the determination of the saturation flux sat is given with the d.c.
saturation method described in 2B.2.3.
Note 2 to entry: In the former standard IEC 60044-6, s was defined as a knee point value, which characterized the
transition from the non-saturated to the fully saturated state of a core. This definition could not gain acceptance
because the saturation value was too low, and led to misunderstandings and contradictions. Therefore, it was
replaced by sat , which defines the condition of complete saturation.

3.4.211
remanent flux
r
value of secondary linked flux which would remain in the core 3 min after the interruption of a
magnetizing current of sufficient magnitude to induce saturation flux ( sat )

3.4.213
secondary loop time constant
Ts
value of the time constant of the secondary loop of the current transformer obtained from the
sum of the magnetizing and the leakage inductances (L s ) and the secondary loop resistance
(R s )
Ts = Ls / Rs
3.4.214
excitation characteristic
graphical or tabular presentation of the relationship between the r.m.s. value of the exciting
current and a sinusoidal voltage applied to the secondary terminals of a current transformer,
the primary and other windings being open-circuited, over a range of values sufficient to
define the characteristics from low levels of excitation up to 1.1 times the knee point e.m.f.
3.4.215
knee point voltage
r.m.s. value of the sinusoidal voltage at rated frequency applied to the secondary terminals of
the transformer, all other terminals being open-circuited, which, when increased by 10 %,
causes the r.m.s. value of the exciting current to increase by 50 %
[SOURCE: IEC 60050-321:1986, 321-02-34]
3.4.216
knee point e.m.f.
e.m.f. of a current transformer at rated frequency, which, when increased by 10 %, causes the
r.m.s. value of the exciting current to increase by 50 %
Note 1 to entry: While the knee point voltage can be applied to the secondary terminals of a current transformer,
the knee point e.m.f. is not directly accessible. The values of the knee point voltage and of the knee point e.m.f.
are deemed as equal, due to the minor influence of the voltage drop across the secondary winding resistance.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

3.4.212
remanence factor
KR
ratio of the remanent flux to the saturation flux, expressed as a percentage

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

14

61869-2 IEC:2012

3.4.217
rated knee point e.m.f.
Ek
lower limit of the knee point e.m.f.
Note 1 to entry: The rated knee point e.m.f. appears in the specifications of class PX and PXR protective current
transformers. It may be calculated as

E k = K x (Rct + Rb ) I sr
3.4.218
rated turns ratio
specified ratio of the number of primary turns to the number of secondary turns
EXAMPLE 1

1/600 (meaning 1 primary turn to 600 secondary turns)

EXAMPLE 2

2/1200 (meaning 2 primary turns to 1200 secondary turns)

Note 1 to entry: The rated turns ratio appears in the specifications of class PX and PXR protective current
transformers.

3.4.219
turns ratio error
difference between the actual turns ratio and the rated turns ratio, expressed as a percentage
of the rated turns ratio
3.4.220
dimensioning factor
Kx
factor to indicate the multiple of rated secondary current (I sr ) occurring under power system
fault conditions, inclusive of safety margins, up to which the transformer is required to meet
performance requirements
Note 1 to entry: See formula under 3.4.217.

3.4.221
instantaneous error current
i
difference between the instantaneous values of the secondary current (i s ) multiplied by the
rated transformation ratio (k r ) and the primary current (i p ):

i = k r is - ip
Note 1 to entry: When both alternating current components (i sac , i pac ) and direct current components (i sdc , i pdc )
are present, the constituent components (i ac , i dc ) are separately identified as follows:

i = iac + idc = (k r isac - i pac ) + (k r isdc - i pdc )


3.4.222
peak instantaneous error

peak value ( ) of instantaneous error current (see 3.4.221) for the specified duty cycle,
expressed as a percentage of the peak value of the rated primary short-circuit current:

i
2 I psc

100 %

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Note 2 to entry: Rated turns ratio and rated transformation ratio are both defined as primary to secondary entities.
If they shall be compared, the value of the rated turns ratio has to be inverted.

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012

15

3.4.223
peak alternating error component

ac

peak value

iac of the alternating component of the instantaneous error current, expressed as

a percentage of the peak value of the rated primary short-circuit current:

ac =

iac
2 I psc

100 %

3.4.224
specified duty cycle (C-O and / or C-O-C-O)
duty cycle in which, during each specified energization, the primary short circuit current is
assumed to have the worst-case inception angle (see Figure 201)

ip

ip

t
tal

tfr

C-O

tal
t
C-O-C-O

IEC 1547/12

Figure 201 Duty cycles


3.4.225
Specified primary time constant
TP
that specified value of the time constant of the d.c. component of the primary short-circuit
current on which the transient performance of the current transformer is based (see Figure
202)

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

t
tal

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

16

61869-2 IEC:2012

ip

Ipsc 2

Ipsc 2
e
0
t

Tp

Figure 202 Primary time constant T P


3.4.226
duration of the first fault
t
duration of the fault in a C-O duty cycle, or of the first fault in a C-O-C-O duty cycle
Note 1 to entry: See Figure 201.

3.4.227
duration of the second fault
t
duration of the second fault in a C-O-C-O duty cycle
Note 1 to entry: See Figure 201.

3.4.228
specified time to accuracy limit in the first fault
t al
time in a C-O duty cycle, or in the first energization of a C-O-C-O duty cycle, during which the
specified accuracy has to be maintained
Note 1 to entry: See Figure 201. This time interval is usually defined by the critical measuring time of the
associated protection scheme.

3.4.229
specified time to accuracy limit in the second fault
t al
time in the second energization of a C-O-C-O duty cycle during which the specified accuracy
has to be maintained
Note 1 to entry: See Figure 201. This time interval is usually defined by the critical measuring time of the
associated protection scheme.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

IEC 1548/12

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012

17

3.4.230
fault repetition time
t fr
time interval between interruption and re-application of the primary short-circuit current during
a circuit breaker auto-reclosing duty cycle in case of a non-successful fault clearance
Note 1 to entry: See Figure 201.

3.4.231
secondary loop resistance
Rs
total resistance of the secondary circuit

Rs = Rb + Rct
3.4.232
rated symmetrical short-circuit current factor
K ssc
ratio of the rated primary short circuit current to the rated primary current

I psc
I pr

3.4.233
transient factor
K tf
ratio of the secondary linked flux at a specified point of time in a duty cycle to the peak value
of its a.c. component
Note 1 to entry: K tf is calculated analytically with different formulae depending on T P , T S , on the duty cycle and on
the fault inception angle. A determination of K tf is given in Annex 2B.1.
Note 2 to entry: Figure 203 shows possible courses of the secondary linked flux for different fault inception
angles .
10

= 90
=90

=135
= 135
4

=180
= 180

-2
0

0.01

0.02

0.03

0.04

0.05

0.06

0.07

0.08

0.09

tt0.1
IEC 1549/12

Figure 203 Secondary linked flux for different fault inception angles

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

K ssc =

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

18

61869-2 IEC:2012

3.4.234
transient dimensioning factor
K td
dimensioning factor to consider the increase of the secondary linked flux due to a d.c.
component of the primary short circuit current
Note 1 to entry: While K tf is defined as a function of time, K td is the definitive dimensioning parameter. K td is derived
from current transformer requirements given by the relay manufacturer (gained from relay stability type tests) or from worst-case
considerations based on the Ktf curves (see 2B.1).

3.4.235
Low-leakage reactance current transformer
current transformer for which measurements made at the secondary terminals (while primary
open-circuited) are sufficient for an assessment of its protection performance up to the
required accuracy limit

3.4.237
rated equivalent limiting secondary e.m.f.
Eal
that r.m.s. value of the equivalent secondary circuit e.m.f. at rated frequency necessary to
meet the requirements of the specified duty cycle:

Eal = K ssc K td ( Rct + Rb ) I sr


3.4.238
peak value of the exciting secondary current at Eal
al
peak value of the exciting current when a voltage corresponding to Eal is applied to the
secondary terminals while the primary winding is open
3.4.239
factor of construction
Fc
factor reflecting the possible differences in measuring results at limiting conditions between
direct test and indirect test methods
Note 1 to entry: The measuring procedure is given in 2B.3.3.

3.7

Index of abbreviations

3.7 of IEC 61869-1:2007 is replaced by the following table.


AIS

Air-Insulated Switchgear

ALF

Accuracy limit factor

CT

Current Transformer

CVT

Capacitive Voltage Transformer

E al

rated equivalent limiting secondary e.m.f.

E ALF

secondary limiting e.m.f. for class P and PR protective current transformers

E FS

secondary limiting e.m.f for measuring current transformers

Ek

rated knee point e.m.f.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

3.4.236
high-leakage reactance current transformer
current transformer which does not satisfy the requirements of 3.4.235, and for which an
additional allowance is made by the manufacturer to take account of influencing effects which
result in additional leakage flux

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012

19

mechanical load

Fc

factor of construction

fR

rated frequency

F rel

relative leakage rate

FS

instrument security factor

GIS

Gas-Insulated Switchgear

al

peak value of the exciting secondary current at Eal

I cth

rated continuous thermal current

I dyn

rated dynamic current

Ie

exciting current

I PL

rated instrument limit primary current

I pr

rated primary current

I psc

rated primary short-circuit current

I sr

rated secondary current

IT

Instrument Transformer

I th

rated short-time thermal current

instantaneous error current

actual transformation ratio

kr

rated transformation ratio

KR

remanence factor

K ssc

rated symmetrical short-circuit current factor

K td

transient dimensioning factor

K tf

transient factor

Kx

dimensioning factor

Lm

magnetizing inductance

Rb

rated resistive burden

R ct

secondary winding resistance

Rs

secondary loop resistance

Sr

rated output

duration of the first fault

duration of the second fault

t al

specified time to accuracy limit in the first fault

t al

specified time to accuracy limit in the second fault

t fr

fault repetition time

Tp

specified primary time constant

Ts

secondary loop time constant

Um

highest voltage for equipment

U sys

highest voltage for system

VT

Voltage Transformer

phase displacement

ratio error

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

20
c

composite error

peak value of instananeous error

ac

peak value of alternating error component

remanent flux

sat

saturation flux

61869-2 IEC:2012

Ratings

5.3

Rated insulation levels

5.3.2

Rated primary terminal insulation level

Clause 5.3.2 of IEC 61869-1:2007 is applicable with the addition of the following:
For a current transformer without primary winding and without primary insulation of its own,
the value U m = 0,72 kV is assumed.
Insulation requirements for secondary terminals

Clause 5.3.5 of IEC 61869-1:2007 is applicable with the addition of the following:
The secondary winding insulation of class PX and class PXR current transformers having a
rated knee point e.m.f. E k 2 kV shall be capable of withstanding a rated power frequency
withstand voltage of 5 kV r.m.s. for 60 s.
5.3.201

Inter-turn insulation requirements

The rated withstand voltage for inter-turn insulation shall be 4,5 kV peak.
For class PX and class PXR current transformers having a rated knee point e.m.f. of greater
than 450 V, the rated withstand voltage for the inter-turn insulation shall be a peak voltage of
10 times the r.m.s. value of the specified knee point e.m.f., or 10 kV peak, whichever is the
lower.
NOTE 1

Due to the test procedure, the wave shape can be highly distorted.

NOTE 2

In accordance with the test procedure 7.3.204, lower voltage values may result.

5.5

Rated output

5.5.201

Rated output values

The standard values of rated output for measuring classes, class P and class PR are:
2,5 5,0 10 15 and 30 VA.
Values above 30 VA may be selected to suit the application.
NOTE For a given transformer, provided one of the values of rated output is standard and associated with a
standard accuracy class, the declaration of other rated outputs, which may be non-standard values, but associated
with other standard accuracy classes, is not precluded.

5.5.202

Rated resistive burden values

Standard values for rated resistive burden in for class TPX, TPY and TPZ current
transformers are:
0,5 1 2 5

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

5.3.5

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012

21

The preferred values are underlined. The values are based on a rated secondary current of
1 A. For current transformers having a rated secondary current other than 1 A, the above
values shall be adjusted in inverse ratio to the square of the current.
NOTE For a given transformer, provided one of the values of rated resistive burden is standard and associated
with a standard accuracy class, the declaration of other rated resistive burdens, which may be non-standard
values, but associated with other standard accuracy classes, is not precluded.

5.6

Rated accuracy class

5.6.201
5.6.201.1

Measuring current transformers


Accuracy class designation for measuring current transformers

For measuring current transformers, the accuracy class is designated by the highest
permissible percentage of the ratio error () at rated primary current and rated output.
5.6.201.2

Standard accuracy classes

The standard accuracy classes for measuring current transformers are:

5.6.201.3

Limits of ratio error () and phase displacement for measuring current


transformers

For classes 0,1 0,2 0,5 and 1, the ratio error and phase displacement at rated frequency
shall not exceed the values given in Table 201 where the burden can assume any value from
25 % to 100 % of the rated output.
For classes 0,2S and 0,5S the ratio error and phase displacement at the rated frequency shall
not exceed the values given in Table 202 where the burden can assume any value from 25 %
and 100 % of the rated output.
For class 3 and class 5, the ratio error at rated frequency shall not exceed the values given in
Table 203 where the burden can assume any value from 50 % to 100 % of the rated output.
There are no specified limits of phase displacement for class 3 and class 5.
For all classes, the burden shall have a power-factor of 0,8 lagging except that, when the
burden is less than 5 VA, a power-factor of 1,0 shall be used, with a minimum value of 1 VA.
NOTE In general the prescribed limits of ratio error and phase displacement are valid for any given position of an
external conductor spaced at a distance in air not less than that required for insulation in air at the highest voltage
for equipment (U m ).

Table 201 Limits of ratio error and phase displacement for


measuring current transformers (classes 0,1 to 1)
Accuracy
class

Ratio error

Phase displacement

Minutes

at current (% of rated)
5

Centiradians

at current (% of rated)

20

100

120

20

100

at current (% of rated)
120

20

100

120

0,1

0,4

0,2

0,1

0,1

15

0,45

0,24

0,15

0,15

0,2

0,75

0,35

0,2

0,2

30

15

10

10

0,9

0,45

0,3

0,3

0,5

1,5

0,75

0,5

0,5

90

45

30

30

2,7

1,35

0,9

0,9

3,0

1,5

1,0

1,0

180

90

60

60

5,4

2,7

1,8

1,8

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

0,1 0,2 0,2S 0,5 0,5S 1 3 5

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

22

61869-2 IEC:2012

Table 202 Limits of ratio error and phase displacement for


measuring current transformers (classes 0,2S and 0,5S)
Ratio error

Accuracy
class

Phase displacement

Minutes

at current (% of rated)

Centiradians

at current (% of rated)
5
20
100 120

at current (% of rated)

20

100

120

20

100

120

0,2 S

0,75

0,35

0,2

0,2

0,2

30

15

10

10

10

0,9

0,45

0,3

0,3

0,3

0,5 S

1,5

0,75

0,5

0,5

0,5

90

45

30

30

30

2,7

1,35

0,9

0,9

0,9

Table 203 Limits of ratio error for measuring


current transformers (classes 3 and 5)
Class

Ratio error
%
at current (% of rated)
120

Extended burden range

For all measuring classes, an extended burden range can be specified. The ratio error and
phase displacement shall not exceed the limits of the appropriate class given in Table 201,
Table 202 and Table 203 for the range of secondary burden from 1 VA up to rated output. The
power factor shall be 1,0 over the full burden range. The maximum rated output is limited to
15 VA.
5.6.201.5

Extended current ratings

Current transformers of accuracy classes 0.1 to 1 may be marked as having an extended


current rating provided they comply with the following two requirements:
a) the rated continuous thermal current shall be the rated extended primary current.
b) the limits of ratio error and phase displacement prescribed for 120 % of rated primary
current in Table 201 shall be retained up to the rated extended primary current.
The rated extended primary current shall be expressed as a percentage of the rated primary
current.
5.6.201.6

Instrument security factor

An instrument security factor may be specified.


Standard values are:
5.6.202
5.6.202.1

FS 5 and FS 10

Protective current transformers


General

Three different approaches are designated to define protective current transformers (see
Table 204). In practice, each of the three definitions may result in the same physical
realization.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

5.6.201.4

50
3

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012

23

Table 204 Characterisation of protective classes


Designation

Limit for
remanent flux

Explanation

a)

no

PR

yes

PX

no

Defining a current transformer to meet the composite error requirements of a


short-circuit current under symmetrical steady state conditions

a), b)

PXR

yes

TPX

no

TPY

yes

TPZ

yes

Defining a current transformer by specifying its magnetizing characteristic

b)

a)

Defining a current transformer to meet the transient error requirements under


the conditions of an asymmetrical short-circuit current

a)

Although there is no limit of remanent flux, air gaps are allowed, e.g. in split core current transformers.

b)

To distinguish between PX and PXR, the remanent flux criteria is used.

5.6.202.2

Class P protective current transformers


Standard accuracy limit factors (ALF)

The standard ALF values are:


5 10 15 20 30
5.6.202.2.2

Accuracy class designation

The accuracy class is designated using the highest permissible percentage of the composite
error, followed by the letter P (standing for protection) and the ALF value.
5.6.202.2.3

Standard accuracy classes

The standard accuracy classes for protective current transformers are:


5P and 10P
5.6.202.2.4

Error limits for class P protective current transformers

At rated frequency and with rated burden connected, the ratio error, phase displacement and
composite error shall not exceed the limits given in Table 205.
The rated burden shall have a power-factor of 0,8 inductive except that, when the rated output
is less than 5 VA a power-factor of 1,0 shall be used.
Table 205 Error limits for protective current transformers class P and PR
Accuracy class

Ratio error at rated


primary current

Phase displacement at
rated primary current

Composite error at rated


accuracy limit primary
current
%

Minutes

Centiradians

5P and 5PR

60

1,8

10P and 10PR

10

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

5.6.202.2.1

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

24
5.6.202.3
5.6.202.3.1

61869-2 IEC:2012

Class PR protective current transformers


Standard accuracy limit factors (ALF)

The standard ALF values are:


5 10 15 20 30
5.6.202.3.2

Accuracy class designation

The accuracy class is designated by the highest permissible percentage of the composite
error, followed by the letters "PR" (indicating protection low remanence) and the ALF value.
5.6.202.3.3

Standard accuracy classes

The standard accuracy classes for low remanence protective current transformers are:
5PR and 10PR
Error limits for class PR protective current transformers

At rated frequency and with rated burden connected, the ratio error, phase displacement and
composite error shall not exceed the limits given in Table 205.
The rated burden shall have a power-factor of 0,8 inductive except that, when the rated output
is less than 5 VA a power-factor of 1,0 shall be used.
5.6.202.3.5

Remanence factor (K R )

The remanence factor (K R ) shall not exceed 10 %.


NOTE

The insertion of one or more air gaps in the core is a method for limiting the remanence factor.

5.6.202.3.6

Secondary loop time constant (T s )

The secondary loop time constant may be specified.


5.6.202.3.7

Secondary winding resistance (R ct )

The upper limit of the secondary winding resistance may be specified.


5.6.202.4

Class PX and class PXR protective current transformers

The performance of class PX protective current transformers shall be specified in terms of the
following:
rated primary current (I pr );
rated secondary current (I sr );
rated turns ratio;
rated knee point e.m.f. (E k );
upper limit of exciting current (I e ) at the rated knee point e.m.f. and/or at a stated
percentage thereof;
upper limit of secondary winding resistance (R ct ).
Instead of specifying the rated knee point e.m.f. (E k ) explicitly, E k may be calculated as
follows:

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

5.6.202.3.4

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012

25

Ek = K x (Rct + Rb ) I sr
In this case, the rated resistive burden (R b ) and the dimensioning factor (K x ) shall be
specified, and the choice of R ct is left to the manufacturer.
For class PX, the turns ratio error shall not exceed 0,25 %.
For class PXR, the turns ratio error shall not exceed 1 %.
For class PXR, the remanence factor shall not exceed 10 %.
NOTE 201

To ensure a remanence factor <= 10 %, class PXR current transformers may comprise air gaps.

NOTE 202 For large class PXR cores with low ampere-turns, it may be difficult to meet the remanence factor
requirement. In such cases, a remanence factor higher than 10 % may be agreed.

5.6.202.5

Protective current transformers for transient performance

5.6.202.5.1

Error limits for TPX, TPY and TPZ current transformers

When the specified duty cycle (or a duty cycle corresponding to the specified transient
dimensioning factor K td ) is applied to the current transformer connected to the rated resistive
burden, the transient errors (for TPX and TPY) or ac (for TPZ) shall not exceed the limits
given in Table 206.
All error limits are based on a secondary winding temperature of 75C.
Table 206 Error limits for TPX, TPY and TPZ current transformers
Class

At rated primary current


Ratio error

Phase displacement

Transient error limits


under specified duty
cycle conditions

Minutes

Centiradians

TPX

0,5

30

0,9

=10 %

TPY

1,0

60

1,8

=10 %

TPZ

1,0

18018

5,30,6

ac =10 %

NOTE 1 In some cases, the absolute value of the phase displacement may be of less importance than achieving
minimal deviation from the average value of a given production series.
NOTE 2 For TPY cores, the following formula can be used under the condition that the appropriate E al value
does not exceed the linear part of the magnetizing curve:

5.6.202.5.2

K td
100 %
2fR Ts

Limits for remanence factor (K R )

TPX:

no limit

TPY:

K R 10 %

TPZ:

K R 10 %

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

With rated resistive burden connected to the current transformer, the ratio error and the phase
displacement at rated frequency shall not exceed the error limits given in Table 206.

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

26

61869-2 IEC:2012

NOTE For TPZ cores, a remanence factor << 10 % is given by the design. Therefore, the remanent flux can be
neglected.

5.6.202.5.3

Specification Methods

The two specification methods are illustrated in Table 207.


In some cases, the choice of one specific duty cycle cannot describe all protection
requirements. Therefore, the alternative definition offers the possibility to specify overall
requirements, which cover the requirements of different duty cycles. The specifications shall
not be mixed, otherwise the current transformer may be over-determined.
Table 207 Specification Methods for TPX, TPY and TPZ current transformers
Alternative specification

Class designation (TPX, TPY or TPZ)

Class designation (TPX, TPY or TPZ)

Rated symmetrical
short-circuit current factor K ssc

Rated symmetrical
short-circuit current factor K ssc

Duty cycle, consisting of


for C-O cycle:

t al

Rated value of transient dimensioning factor


K td

for C-O-C-O cycle:

t al , t, t fr , t al

Rated value of secondary loop time constant


T S (for TPY cores only)

Rated primary time constant T p


Rated resistive burden R b

Rated resistive burden R b

NOTE 1 For current transformers with tapped secondary windings, the given accuracy requirements can be
fulfilled for one ratio only.
Note 2 For current transformers with primary reconnection, the accuracy requirements may be fulfilled for
different ratios. In this case, attention should be paid to the factor of construction F c which may be influenced by
the configuration of the primary conductors.
NOTE 3 In the alternative specification, K td is usually given by the supplier of the protection devices. T S has also
to be specified, because it is the only parameter of the current transformer which is used in the calculation of K td .

5.6.203
5.6.203.1

Class assignments for selectable-ratio current transformers


Accuracy performance for current transformers with primary reconnection

For all accuracy classes, the accuracy requirements refer to all specified reconnections.
5.6.203.2

Accuracy performance for current transformers with tapped secondary


windings

For all accuracy classes, the accuracy requirements refer to the highest transformation ratio,
unless specified otherwise.
When required by the purchaser, the manufacturer shall give information about the accuracy
performance at lower ratios.
5.201

Standard values for rated primary current

The standard values for rated primary current are:

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Standard specification

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012

27
10 12,5 15 20 25 30 40 50 60 75 A,

and their decimal multiples or fractions.


The preferred values are those underlined.
5.202

Standard values for rated secondary current

The standard values for rated secondary current are 1 A and 5 A.


For protective current transformers for transient performance, the standard value of the rated
secondary current is 1 A.
5.203

Standard values for rated continuous thermal current

The standard value for rated continuous thermal current is the rated primary current.
When a rated continuous thermal current greater than the rated primary current is specified,
the preferred values are 120 %, 150 % and 200 % of rated primary current.
Short-time current ratings

5.204.1

Rated short-time thermal current (I th )

A rated short-time thermal current (I th ) shall be assigned to the transformer.


The standard value for the duration of the rated short-time thermal current is 1 s.
5.204.2

Rated dynamic current (I dyn )

The standard value of the rated dynamic current (I dyn ) is 2,5 times the rated short-time
thermal current (I th ).

6
6.4

Design and construction


Requirements for temperature rise of parts and components

6.4.1

General

This clause of IEC 61869-1:2007 is applicable with the addition of the following:
The temperature rise in a current transformer when carrying a primary current equal to the
rated continuous thermal current, with a unity power-factor burden corresponding to the rated
output, shall not exceed the appropriate value given in Table 5 of IEC 61869-1:2007. These
values are based on the service conditions given in Clause 4.
6.13

Markings

6.13.201
6.13.201.1

Terminal markings
General rules

The terminal markings shall identify:


a) the primary and secondary windings;
b) the winding sections, if any;
c) the relative polarities of windings and winding sections;

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

5.204

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

28

61869-2 IEC:2012

d) the intermediate taps, if any.


6.13.201.2

Method of marking

The marking shall consist of letters followed, or preceded where necessary, by numbers. The
letters shall be in block capitals.
6.13.201.3

Markings to be used

The markings of current transformer terminals shall be as indicated in Table 208.


Table 208 Marking of terminals

Primary terminals

P1

P2

P1

P2

Secondary terminals
S2

S1

Single-ratio transformer

C1

Secondary terminals

P1

P2

P2

S1

S2

Transformer with primary winding in


2 sections intended for connections
either in series or in parallel

6.13.201.4

S3

Transformer with an intermediate tapping


on secondary winding

C2

P1

Primary terminals

S2

1S1

1S2

2S1

2S2

1
S1

1
S2

2
S1

S2

Transformer with 2 secondary windings;


each with its own magnetic core (two
alternative markings for the secondary
terminals)

Indication of relative polarities

All the terminals marked P1, S1 and C1 shall have the same polarity at the same instant.
6.13.202
6.13.202.1

Rating plate markings


General

In addition to those markings defined in IEC 61869-1:2007, Clause 6.13, all current
transformers shall carry the general rating plate markings as defined in this clause. The
markings related to the particular accuracy classes are given in Subclauses 6.13.202.2 to
6.13.202.6.
a) the rated primary and secondary current (e.g. 100/1 A);
b) the rated short-time thermal current (I th ), (e.g. Ith = 40 kA);
c) the rated dynamic current (I dyn ) if it differs from 2,5 I th (e.g. I dyn = 85 kA);
d) on current transformers with two or more secondary windings, the use of each winding and
its corresponding terminals;
e) the rated continuous thermal current if different from the rated primary current.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

S1

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012

29

EXAMPLE 1
For single core current transformer with secondary taps: I cth = 150 %
(meaning 150 % of the rated primary current for each tap)
EXAMPLE 2
For current transformers with several cores of different ratios
(e.g. 300/5 A and 4000/1 A): I cth = 450 A
(meaning 450 A as the maximum continuous thermal current through all cores of the current transformer)
EXAMPLE 3
For current transformers with primary reconnection (4x300/1 A): I cth = 4450 A
(meaning continuous thermal current of 450, 900 or 1800 A, depending on the primary reconnection)

A current transformer satisfying the requirements of several combinations of output and


accuracy class may be marked according to all of them.
EXAMPLE 4
EXAMPLE 5
EXAMPLE 6

6.13.202.2

5 VA cl. 0,5;

10 VA cl. 5P20

15 VA cl. 1;

7 VA cl. 0,5

5 VA cl.1 & 5P20

Specific marking of the rating plate of a measuring current transformer

EXAMPLE 1

15 VA cl. 0,5

EXAMPLE 2

15 VA cl. 0,5 FS 10

Current transformers having an extended current rating (see 5.6.201.5) shall have this rating
indicated immediately following the class designation.
EXAMPLE 3

15 VA cl. 0,5 ext.150 % FS 10

For current transformers having an extended burden range (see 5.6.201.4), this rating shall
directly precede the class indication.
EXAMPLE 4

1-10 VA class 0,2 (meaning burden range from 1 to 10 VA at class 0,2)

NOTE The rating plate may contain information concerning several combinations of ratios, burdens and accuracy
classes that the transformer can satisfy at the same ratio. In this case, non-standard values of burden may be
used.
EXAMPLE

6.13.202.3

15 VA class 1; 7 VA class 0,5

Specific marking of the rating plate of a class P protective current


transformer

The rated accuracy limit factor shall be indicated following the corresponding rated output and
accuracy class.
EXAMPLE

6.13.202.4

30 VA class 5P10

Specific marking of the rating plate of class PR protective current


transformers

The rated accuracy limit factor shall be indicated following the corresponding rated output and
accuracy class.
EXAMPLE 1

10 VA class 5PR10

If specified, the following parameters shall also be indicated:

the secondary loop time constant (T s );


the upper limit of the secondary winding resistance (R ct );

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

The accuracy class and instrument security factor (if any) shall be indicated following the
indication of the corresponding rated output.

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

30
EXAMPLE 2

10 VA class 5PR10,

6.13.202.5

Ts = 200 ms,

61869-2 IEC:2012

Rct <= 2,4

Specific marking of the rating plate of class PX and PXR protective


current transformers

The class requirements may be indicated as follows:

the rated turns ratio

the rated knee point e.m.f. (E k );


the upper limit of exciting current (I e ) at the rated knee point e.m.f. and/or at the stated
percentage thereof;

the upper limit of secondary winding resistance (R ct ).

EXAMPLE 1

class PX, Ek = 200 V, Ie <= 0,2A,

Rct <= 2,0

If specified, the following parameters shall also be indicated:

the dimensioning factor (K x );


the rated resistive burden (R b ).

EXAMPLE 2

Ek = 200 V, Ie <= 0,2 A,

Rb = 3,0

Specific marking of the rating plate of current transformers for transient


performance

The class marking consists of the following 2 elements:


a) Definition part (compulsory)
The definition part contains the essential information which is necessary to determine
whether the current transformer fulfils given requirements (consisting of duty cycle and
T p ).
EXAMPLE 1 applying K ssc = 20 and K td = 12,5:
Rb = 5,

class TPX 20x12,5,

Rct <= 2,8

Rb = 5,

class TPY 20x12,5,

Rct <= 2,8,

Rb = 5,

class TPZ 20x12,5,

Rct <= 2,8

NOTE

Ts = 900 ms

For R ct , its maximum value within the batch may be stated.

b) Complementary part (compulsory only if a duty cycle is specified by the customer)


The complementary part represents one of many possible duty cycles which lead to the
K td value specified in a).
EXAMPLE 2
T p = 100 ms

Cycle 100 ms,

meaning t al =100 ms, T p =100 ms

Cycle (40-100)-300-40 ms, T p = 100 ms


Cycle (100-100)-300-40 ms,

7
7.1
7.1.2

T p = 75 ms

meaning t al =40 ms, t=100 ms, t fr =300 ms, t al =40 ms, T p =100 ms
meaning t = t al =100 ms, t fr =300 ms, t al =40 ms, T p = 75 ms

Tests
General
Lists of tests

Table 10 of IEC 61869-1:2007 is replaced by new Table 10.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

6.13.202.6

Rct <= 2,0 , Kx = 40,

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012

31
Table 10 List of tests
Tests

Subclause

Type tests

7.2

Temperature-rise test

7.2.2

Impulse voltage withstand test on primary terminals

7.2.3

Wet test for outdoor type transformers

7.2.4

Electromagnetic Compatibility tests

7.2.5

Tests for accuracy

7.2.6

Verification of the degree of protection by enclosures

7.2.7

Enclosure tightness test at ambient temperature

7.2.8

Pressure test for the enclosure

7.2.9

Short-time current tests

7.2.201
Routine tests

7.3
7.3.1

Partial discharge measurement

7.3.2

Power-frequency voltage withstand tests between sections

7.3.3

Power-frequency voltage withstand tests on secondary terminals

7.3.4

Tests for accuracy

7.3.5

Verification of markings

7.3.6

Enclosure tightness test at ambient temperature

7.3.7

Pressure test for the enclosure

7.3.8

Determination of the secondary winding resistance

7.3.201

Determination of the secondary loop time constant

7.3.202

Test for rated knee point e.m.f. and exciting current at rated knee point e.m.f.

7.3.203

Inter-turn overvoltage test

7.3.204
Special tests

7.4

Chopped impulse voltage withstand test on primary terminals

7.4.1

Multiple chopped impulse test on primary terminals

7.4.2

Measurement of capacitance and dielectric dissipation factor

7.4.3

Transmitted overvoltage test

7.4.4

Mechanical tests

7.4.5

Internal arc fault test

7.4.6

Enclosure tightness test at low and high temperatures

7.4.7

Gas dew point test

7.4.8

Corrosion test

7.4.9

Fire hazard test

7.4.10
Sample Tests

7.5

Determination of the remanence factor

7.5.1

Determination of the instrument security factor (FS) of measuring current transformers

7.5.2

Table 11 of IEC 61869-1:2007 is applicable with the addition of the following text:
For GIS current transformers, the accuracy tests may be performed without insulating gas.
7.2
7.2.2

Type tests
Temperature-rise test

IEC 61869-1:2007, 7.2.2 is applicable with the following additions:

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Power-frequency voltage withstand tests on primary terminals

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

32
7.2.2.201

61869-2 IEC:2012

Test set up

The current transformer shall be mounted in a manner representative of the mounting in


service and the secondary windings shall be loaded with the burdens according to 6.4.1.
However, because the position of the current transformer in each switchgear installation can
be different, the test setup arrangement is left to the manufacturer.
For current transformers in three phase gas-insulated metal enclosed switchgear, all three
phases have to be tested at the same time.
7.2.2.202

Measurement of the ambient temperature

The sensors to measure the ambient temperature shall be distributed around the current
transformer, at an appropriate distance according to the current transformer ratings and at
about half-height of the transformer, protected from direct heat radiation.
To minimise the effects of variation of cooling-air temperature, particularly during the last test
period, appropriate means should be used for the temperature sensors such as heat sinks
with a time-constant approximately equal to that of the transformer.

7.2.2.203

Duration of test

The test can be stopped when both of the following conditions are met:
the test duration is at least equal to three times the current transformer thermal time
constant;

the rate of temperature rise of the windings (and of the top oil of oil-immersed current
transformers) does not exceed 1 K per hour during three consecutive temperature rise
readings.

The manufacturer shall estimate the thermal time constant by one of the following methods:
before the test, based on the results of previous tests on a similar design. The thermal time
constant shall be confirmed during the temperature rise test.
during the test, from the temperature rise curve(s) or temperature decrease curve(s)
recorded during the course of the test and calculated according to Annex 2D.
during the test, as the point of intersection between the tangent to the temperature rise
curve originating at 0 and the maximum estimated temperature rise.
during the test, as the time elapsed until 63 % of maximum estimated temperature rise.
7.2.2.204

Temperatures and temperature rises

The purpose of the test is to determine the average temperature rise of the windings and, for
oil-immersed transformers, the temperature rise of the top oil, in steady state when the losses
resulting from the specified service conditions are generated in the current transformer.
The average temperature of the windings shall, when practicable, be determined by the
resistance variation method, but for windings of very low resistance, thermometers,
thermocouples or other appropriate temperature sensors may be employed.
Thermometers or thermocouples shall measure the temperature rise of parts other than
windings. The top-oil temperature shall be measured by sensors applied to the top of metallic
head directly in contact with the oil.
The temperature rises shall be determined by the difference with respect to the ambient
temperature measured as indicated in 7.2.2.202.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

The average readings of two sensors shall be used for the test.

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012
7.2.2.205

33

Test modalities for current transformers having U m <550 kV

The test shall be performed by applying the rated continuous thermal current to the primary
winding.
NOTE Subject to an agreement between manufacturer and purchaser the test current may also be applied by
energizing one or more secondary windings, if the voltages at the secondary terminals of the energizing cores are
at least as high as if connected to rated burden, with the primary winding short-circuited and the non-supplied
secondary winding(s) connected to the rated burden(s).

7.2.2.206

Test modalities for oil-immersed current transformers having U m 550 kV

The test shall be performed by simultaneously applying the following to the current
transformer:

the rated continuous thermal current to the primary winding;


The test current may also be applied by energizing one or more secondary windings, if the
voltages at the secondary terminals of the energizing cores are at least as high as if
connected to rated burden, with the primary winding short-circuited and the non-supplied
secondary winding(s) connected to the rated burden(s).
the highest voltage of the equipment divided by 3 between the primary winding and earth.
One terminal of each secondary winding shall be connected to earth.

7.2.3
7.2.3.1

Impulse voltage withstand test on primary terminals


General

IEC 61869-1:2007, 7.2.3.1 is applicable with the addition of the following:


The test voltage shall be applied between the terminals of the primary winding (connected
together) and earth. The frame, case (if any), and core (if intended to be earthed) and all
terminals of the secondary winding(s) shall be connected to earth.
For three-phase current transformers for gas insulated substations, each phase shall be
tested, one by one. During the test on each phase, the other phases shall be earthed.
For the acceptance criteria of gas-insulated metal enclosed transformers, refer to
IEC 62271-203:2011, Clause 6.2.4.
7.2.6
7.2.6.201

Tests for accuracy


Test for ratio error and phase displacement of measuring current
transformers

To prove compliance with 5.6.201.3, 5.6.201.4 and 5.6.201.5, accuracy measurements shall
be made at each value of current given in Table 201, Table 202 and Table 203 respectively,
at the highest and at the lowest value of the specified burden range.
Transformers having an extended current rating shall be tested at the rated extended primary
current instead of 120 % of rated current.
7.2.6.202

Determination of the instrument security factor (FS) of measuring current


transformers

This test may be performed using the following indirect test method:
With the primary winding open-circuited, the secondary winding is energized at rated
frequency by a substantially sinusoidal voltage. The voltage shall be increased until the
exciting current I e reaches I sr FS 10 % .

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

34

61869-2 IEC:2012

The r.m.s. value of the obtained terminal voltage shall be less than the secondary limiting
e.m.f. E FS (see 3.4.206).
The exciting voltage shall be measured with an instrument which has a response proportional
to the average of the rectified signal, but calibrated in r.m.s.. The exciting current shall be
measured using an r.m.s measuring instrument having a minimum crest factor of 3.
If the measurement result should be put to question, a further measurement shall be
performed with the direct test (see 2A.5, 2A.6). Then the result of the direct test is the
reference.
NOTE The great advantage of the indirect test is that high currents are not necessary (for instance 30 000 A at a
primary rated current 3 000 A and an instrument security factor 10) and also that no burdens have to be made
available for 50 A. The effect of the return primary conductors is not physically effective during the indirect test.
Under service conditions the effect can only increase the composite error, which is desirable for the safety of the
apparatus supplied by the measuring current transformer.

7.2.6.203

Test for composite error of class P and PR protective current


transformers

a) Compliance with the limits of composite error given in Table 205 shall be demonstrated by
a direct test in which a substantially sinusoidal current equal to the rated accuracy limit
primary current is passed through the primary winding with the secondary winding
connected to a burden of magnitude equal to the rated burden but having, at the
discretion of the manufacturer, a power factor between 0,8 inductive and unity (see 2A.4,
2A.5, 2A.6, 2A.7.
The test may be carried out on a transformer similar to the one being supplied, except that
reduced insulation may be used, provided that the same geometrical arrangement is
retained.
As far as very high primary currents and single-bar primary winding current transformers
are concerned, the distance between the return primary conductor and the current
transformer should be taken into account from the point of view of reproducing service
conditions.
b) For low-leakage reactance current transformers according to Annex 2C, the direct test
may be replaced by the following indirect test.
With the primary winding open-circuited, the secondary winding is energized at rated
frequency by a substantially sinusoidal voltage having an r.m.s. value equal to the
secondary limiting e.m.f. E ALF .
The resulting exciting current, expressed as a percentage of
the composite error limit given in Table 205.

I sr ALF shall not exceed

The exciting voltage shall be measured with an instrument which has a response
proportional to the average of the rectified signal, but calibrated in r.m.s.. The exciting
current shall be measured using an r.m.s measuring instrument having a minimum crest
factor of 3.
In determining the composite error by the indirect method, a possible correction of the
turns ratio need not be taken into account.
7.2.6.204

Test for error at limiting conditions for class TPX, TPY and TPZ protective
current transformers

The purpose of the type test is to prove the compliance with the requirements at limiting
conditions. For test methods refer to Annex 2B.
If the current transformer is a low-leakage reactance type according to Annex 2C, an indirect
type test may be performed according to 2B.2, otherwise a direct test shall be performed
according to 2B.3.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

The following two test procedures are given:

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012

35

The test can be performed on a full-scale model of the active part of the current transformer
assembly inclusive of all metal housings but without insulation.
7.2.6.205

Test of low-leakage reactance type for class PX and PXR protective


current transformers

The proof of low-leakage reactance shall be made according to Annex 2C.


7.2.6.206

Determination of the remanence factor class PR, TPY, and PXR protective
current transformers

To prove compliance with


5.6.202.3.5 for class PR,
5.6.202.5.2 for class TPY,
5.6.202.4 for class PXR,

7.2.201

Short-time current tests

To verify the requirements of rated short-time thermal current and of rated dynamic current
given in 5.204, the two following tests are specified.
The thermal test shall be made with the secondary winding(s) short-circuited, and at a
current I for a time t, so that

I ' 2 t ' I th2 t


where t is the specified duration of the short-time thermal current.
t' shall have a value between 0,5 s and 5 s.
The dynamic test shall be made with the secondary winding(s) short-circuited, and with
a primary current the peak value of which is not less than the rated dynamic current
(I dyn ) for at least one peak.
The dynamic test may be combined with the thermal test above, provided the first major peak
current of that test is not less than the rated dynamic current (I dyn ).
The transformer shall be deemed to have passed these tests if, after cooling to ambient
temperature (between 10 C and 40 C), it satisfies the following requirements:
a) it is not visibly damaged;
b) its errors after demagnetization do not differ from those recorded before the tests by more
than half the limits of error appropriate to its accuracy class;
c) it withstands the dielectric tests specified in 7.3.1, 7.3.2, 7.3.3 and 7.3.4 but with the test
voltages or currents reduced to 90 % of those given;
d) on examination, the insulation next to the surface of the conductor does not show
significant deterioration (e.g. carbonization).
The examination d) is not required if the current density in the primary winding, corresponding
to the rated short-time thermal current (I th ), does not exceed:

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

the remanence factor ( K R ) shall be determined. For test methods, refer to 2B.2.

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

36

61869-2 IEC:2012

180 A/mm where the winding is of copper of conductivity not less than 97 % of the value
given in IEC 60028;
2

120 A/mm where the winding is of aluminium of conductivity not less than 97 % of the
value given in IEC 60121.
NOTE Experience has shown that in service the requirements for thermal rating are generally fulfilled in the case
of class A insulation, provided that the current density in the primary winding, corresponding to the rated short-time
thermal current, does not exceed the above-mentioned values.

7.3

Routine tests

7.3.1

Power-frequency voltage withstand tests on primary terminals

This clause of IEC 61689-1 is applicable with the addition of the following:
The test voltage shall be applied between the short-circuited primary winding and earth. The
short-circuited secondary winding(s), the frame, case (if any) and core (if there is a special
earth terminal) shall be connected to earth.
7.3.5

Tests for ratio error and phase displacement of measuring current


transformers

The routine test for accuracy is in principle the same as the type test in 7.2.6.201, but routine
tests at a reduced number of currents and/or burdens are permissible provided it has been
shown by type tests on a similar transformer that such a reduced number of tests are
sufficient to prove compliance with 5.6.201.3.
7.3.5.202

Tests for ratio error and phase displacement of class P and PR protective
current transformers

Tests shall be made at rated primary current and rated burden to prove compliance with
5.6.202.2 and 5.6.202.3 respectively, with respect of ratio error and phase displacement.
7.3.5.203

Test for composite error of class P and PR protective current


transformers

For low-leakage reactance current transformers (see Annex 2C), the routine test is the same
as the indirect type test described in item b) of 7.2.6.203.
For other transformers, the indirect test described in item b) of 7.2.6.203 may be used, but a
correction factor for the exciting current shall be applied to the results. This factor is obtained
from a comparison between the results of direct and indirect tests applied to a transformer of
the same type as the one under consideration, the accuracy limit factor and the conditions of
loading being the same. In such cases, the manufacturer should hold test reports available.
NOTE 1 The correction factor is equal to the ratio of the composite error obtained by the direct method, and the
exciting current expressed as a percentage of I sr x ALF, as determined by the indirect method.
NOTE 2 The expression transformer of the same type implies that the ampere turns are similar irrespective of
ratio, and that the materials and the geometrical arrangements of the iron core and the secondary windings are
identical.

7.3.5.204

Test for ratio error and phase displacement for class TPX, TPY and TPZ
protective current transformers

The ratio error and the phase displacement shall be measured at rated current to prove
compliance with 5.6.202.5.1.
The results shall correspond to a secondary winding temperature of 75 C.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

7.3.5.201

Tests for accuracy

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012

37

Therefore, the actual value of the secondary winding temperature shall be measured and the
difference to its value corrected to 75 C shall be determined. The error measurement shall be
made with the burden R b increased by the above mentioned difference of winding resistance.
Alternatively, for TPY and TPZ cores the phase displacement at 75 C ( 75 ) may be
determined by measuring at ambient temperature ( amb ) and calculating as follows:

75 = amb
where

Rct + Rb
Rct amb + Rb

Rct amb is the winding resistance at the ambient temperature. The influence of this

resistance correction on the ratio error can be neglected.

7.3.5.205

Test for error at limiting conditions for class TPX, TPY and TPZ protective
current transformers

The purpose of the routine test is to prove compliance with the requirements at limiting
conditions.
If the current transformer is a low-leakage reactance type according to Annex 2C, an indirect
test shall be performed according to 2B.2.
If compliance with the requirements of low-leakage reactance design cannot be established,
but a type test report of a current transformer of the same type is available, an indirect test
shall be performed according to 2B.2. In this case, a possibly available factor of construction
F c shall be considered if the factor is greater than 1,1. If such a type test is not available, one
unit of the batch shall be type-tested and used as reference for the indirect testing of the
remaining units.
NOTE 1 When determining the factor of construction F C , laboratories have to cope with a high measuring
uncertainty due to the necessity of integrating the e.m.f. and due to nonlinear parameters at accuracy limiting
conditions. Furthermore, only few laboratories are in the position to provide the required duty cycles, and these
with limited precision only. As a consequence, the results of direct and indirect tests usually do not match nicely,
and unreliable F C values may result. Therefore, little experience exists in this field.
NOTE 2 The expression transformer of the same type implies that the ampere turns are similar irrespective of
ratio, and that the materials and the geometrical arrangements of the iron core and the secondary windings are
identical.

7.3.5.206

Test for turns ratio error for class PX and PXR protective current
transformers

For class PX and class PXR, the turns ratio error shall be determined in accordance with
Annex 2F.
The test may be substituted by performing the measurement of the ratio error with a zero-
burden connected, subject to an agreement between manufacturer and purchaser.
The turns ratio error shall not exceed the limits given in 5.6.202.4.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

For type and routine testing, a direct test method (using a primary current source and a
reference current transformer) has to be applied. For low-leakage reactance current
transformers, an indirect test method is given in Annex 2E. It may be applied for on-site
measurements and for monitoring purposes.

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

38
7.3.201

61869-2 IEC:2012

Determination of the secondary winding resistance (R ct )

The secondary winding resistance (R ct ) shall be measured for current transformers of the
following classes, to prove compliance with the appropriate clauses:
class PR:

clauses 5.6.202.3.7 and 6.13.202.4 (if parameter specified)

class PX, PXR:

clauses 5.6.202.4 and 6.13.202.5

class TPX, TPY, TPZ:

clause 6.13.202.6

An appropriate correction shall be made to meet 75C or other such temperature as may have
been specified.
For classes PR, PX and PXR, the value obtained when corrected to 75 C shall not exceed
the specified upper limit (if any).
7.3.202

Determination of the secondary loop time constant (T s )

class PR:

clause 5.6.202.3.6 (if parameter specified)

class TPY

clause 5.6.202.5.3

The measured value shall not differ from any specified value by more than 30 %.
For the determination of T s , the following formula shall be used (For the determination of L m :
see 2B.2):

TS =

Lm
( Rct + Rb )

In cases where the burden is defined as rated output, given in VA, R b is taken as being equal
to the resistive part of the burden.
Alternatively, T s may be determined according to the following equation:

TS =
If the phase displacement
may be applied:

1
2f R tan( )

is expressed in minutes, the following approximate formula

TS [s] =

3438
2f R [min]

NOTE 1 The method using may cause difficulties for current transformers with high transformation ratio and
small phase displacement due to uncertainty of the measurement of low phase displacement.
NOTE 2 For class TPZ cores, T s has not to be stated explicitly. The accuracy requirement of = (180 18) min
is verified as routine test. T s is then provided by the above mentioned formula.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

The secondary loop time constant (T s ) shall be determined at current transformers with the
following classes, to prove compliance with the appropriate clauses:

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012
7.3.203

39

Test for rated knee point e.m.f. (E k ) and exciting current at E k

The rated knee point e.m.f. shall be verified and the exciting current I e at rated knee point
e.m.f. E k shall be measured for current transformers with the following classes, to prove
compliance with the appropriate clause:
class PX, PXR:

clause 5.6.202.4

A suitable sinusoidal exciting voltage with rated frequency shall be applied to the secondary
terminals of the full winding of the transformer, all other terminals being open-circuited, and
the exciting current shall be measured.
The exciting voltage shall be measured with an instrument which has a response proportional
to the average of the rectified signal, but calibrated in r.m.s.. The exciting current shall be
measured using an r.m.s measuring instrument having a minimum crest factor of 3.
The excitation characteristic shall be plotted at least up to a voltage equal to 1.1 x E k .
At a voltage equal to E k , the knee point condition according to 3.4.215 shall be fulfilled.

NOTE 1 For selectable-ratio current transformers with tapped secondary windings, the excitation characteristic for
other than the maximum ratio may be calculated. For every measuring point, the following equations can be
applied:

E 2 = E1

k r2
k r1

I e2 = I e1
where

k r1
k r2

k r1 , k r2

are the two rated transformation ratios;

E1, E2

are the two appropriate secondary e.m.f values;

I e1 , I e2

are the two appropriate exciting current values.

NOTE 2

The number of measurement points may be agreed between the manufacturer and the purchaser.

NOTE 3
Ek.

Usually, the actual knee point e.m.f. is determined, which must be higher than the rated knee point e.m.f

7.3.204

Inter-turn overvoltage test

Tests shall be performed to demonstrate compliance with 5.3.201.


The inter-turn overvoltage test shall be performed at the full winding in accordance with one
of the following procedures. If not otherwise agreed, the choice of the procedure is left to the
manufacturer.
Procedure A: with the secondary windings open-circuited (or connected to a high impedance
device which reads peak voltage), a substantially sinusoidal current at a frequency between
40 Hz and 60 Hz and of r.m.s. value equal to the rated primary current (or rated extended
primary current if specified) shall be applied for 60 s to the primary winding.
The applied current shall be limited if the test voltage given in 5.3.201 is obtained before
reaching the rated primary current (or rated extended primary current).

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

The exciting current I e at a voltage equal to E k (or at any stated percentage), shall not exceed
the specified limit.

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

40

61869-2 IEC:2012

If the test voltage given in 5.3.201 is not reached at maximum primary current, the obtained
voltage shall be regarded as the test voltage.
Procedure B: with the primary winding open-circuited, the test voltage given in 5.3.201 (at
some suitable test frequency) shall be applied for 60 s to the terminals of each secondary
winding.
The r.m.s. value of the secondary current shall not exceed the rated secondary current (or the
appropriate extended value if specified).
The test frequency shall be chosen in order to reach the test voltage, but it shall not exceed
400 Hz.
If the test voltage given in 5.3.201 is not reached at maximum secondary current and
maximum test frequency, the obtained voltage shall be regarded as the test voltage.
When the test frequency exceeds twice the rated frequency, the duration of the test t shall be
reduced as below:

f
= 120 s R
f
T

where
fR

is the rated frequency;

fT

is the test frequency;

with a minimum t of 15 s.
NOTE The inter-turn overvoltage test is not a test carried out to verify the suitability of a current transformer to
operate with the secondary winding open-circuited. Current transformers should not be operated with the
secondary winding open-circuited because of the potentially dangerous overvoltage and overheating which can
occur.

7.4

Special tests

7.4.3

Measurement of capacitance and dielectric dissipation factor

This clause of IEC 61869-1:2007 is applicable with the addition of the following:
The test voltage shall be applied between the short-circuited primary winding terminals and
earth. Generally, the short-circuited secondary winding(s), any screen, and the insulated
metal casing shall be connected to the measuring device. If the current transformer has a
special terminal suitable for this measurement, the other low-voltage terminals shall be shortcircuited and connected together with the metal casing to the earth or the screen of the
measuring device.
The test shall be performed with the current transformer at ambient temperature, the value of
which shall be recorded.
7.4.6

Internal arc fault test

This clause of IEC 61869-1:2007 is applicable with the addition of the following note:
NOTE For top-core oil-immersed current transformers, the area in which in-service failure occurs, the incept is, in
many cases, located in the upper part of the main insulation. For hair-pin oil-immersed current transformers this
area is generally located in the bottom part of the main insulation.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012
7.5
7.5.1

41

Sample tests
Determination of the remanence factor

Usually, as sample test for each production series, the type test given in 7.2.6.206 is
repeated.
7.5.2

Determination of the instrument security factor (FS) of measuring current


transformers

Usually, as sample test for each production series, the type test given in 7.2.6.202 is repeated
using the indirect method.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

42

61869-2 IEC:2012

Annex 2A
(normative)
Protective current transformers classes P, PR

2A.1 Vector diagram


If consideration is given to a current transformer which is assumed to contain only linear
electric and magnetic components in itself and in its burden, then, under the further
assumption of sinusoidal primary current, all the currents, voltages and magnetic fluxes will
be sinusoidal, and the performance can be illustrated by a vector diagram as shown in Figure
2A.1.
Im
Ia
Is

Ip

Ie
0

IEC 1550/12

Figure 2A.1 Vector Diagram


In Figure 2A.1, I s represents the secondary current. It flows through the impedance of the
secondary winding and the burden which determines the magnitude and direction of the
necessary induced e.m.f. E s and of the secondary linked flux which is perpendicular to the
e.m.f. vector. This flux is maintained by the exciting current I e , having a magnetizing
component I m parallel to the secondary linked flux , and a loss (or active) component I a
parallel to the e.m.f.. The vector sum of the secondary current I s and the exciting current I e is
the vector I p representing the primary current multiplied by the actual turns ratio (number of
primary turns to number of secondary turns).
Thus, for a current transformer with the inverse of the actual turns ratio equal to the rated
transformation ratio, the difference in the lengths of the vectors I s and I p, related to the
length of I p, is the ratio error () according to the definition of 3.4.3, and the angular
difference is the phase displacement according to 3.4.4.

2A.2 Turns correction


When the inverse of the actual turns ratio is different from (usually less than) the rated
transformation ratio, the current transformer is said to have turns correction. Thus, in
evaluating performance, it is necessary to distinguish between I p, the primary current
multiplied by the actual turns ratio, and I p, the primary current divided by the rated
transformation ratio. Absence of turns correction means I p = I p. If turns correction is present,
I p is different from I p, and since I p is used in the vector diagram and I p is used for the
determination of the ratio error (), it can be seen that turns correction has an influence on the
ratio error () (and may be used deliberately for that purpose). However, the vectors I p and
I p have the same direction, so turns correction has no influence on phase displacement.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Es

Ie

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012

43

It will also be apparent that the influence of turns correction on composite error is less than its
influence on ratio error ().

2A.3 The error triangle


In Figure 2A.2, the upper part of Figure 2A.1 is re-drawn to a larger scale and under the
further assumption that the phase displacement is so small that for practical purposes the two
vectors I s and I p can be considered to be parallel. Assuming again that there is no turns
correction, it will be seen by projecting I e to I p that to a good approximation the in-phase
component (I) of I e can be used instead of the arithmetic difference between I p and I s to
obtain the ratio error (). Similarly, the quadrature component (I q ) of I e can be used to
express the phase displacement.
Im
Ie

Ia

Is

Ip

IEC 1551/12

Figure 2A.2 Error triangle


It can further be seen that under the given assumptions the exciting current I e divided by I p
is equal to the composite error according to 3.4.203.
Thus, for a current transformer without turns correction and under conditions where a vector
representation is justifiable, the ratio error (), phase displacement and composite error form a
right-angled triangle.
In this triangle, the hypotenuse representing the composite error is dependent on the
magnitude of the total burden impedance consisting of burden and secondary winding, while
the division between ratio error () and phase displacement depends on the power factors of
the total burden impedance and of the exciting current. Zero phase displacement will result
when these two power factors are equal, i.e. when I s and I e are in phase.

2A.4 Composite error


The most important application, however, of the concept of composite error is under
conditions where a vector representation cannot be justified because non-linear conditions
introduce higher harmonics in the exciting current and in the secondary current (see
Figure 2A.3).

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Iq

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

44

61869-2 IEC:2012

Ip
Is
Ie

IEC 1552/12

Figure 2A.3 Typical current waveforms


It is for this reason that the composite error is defined as in 3.4.203 and not in the far simpler
way as the vector sum of ratio error () and phase displacement as shown in Figure 2A.2.

2A.5 Direct test for composite error


The standard method is given by recording and digitizing the waveforms of the primary
current and of the secondary current, and by calculating the composite error using numerical
integration according to its definition in 3.4.203.
Nevertheless, in this annex, the traditional methods for the determination of the composite
error with analogue instruments are described.
Figure 2A.4 shows a current transformer having a turns ratio of 1:1. It is connected to a
source of primary (sinusoidal) current, a secondary burden Z B with linear characteristics and
to an ammeter in such a manner that both the primary and secondary currents pass through
the ammeter but in opposite directions. In this manner, the resultant current through the
ammeter will be equal to the exciting current under the prevailing conditions of sinusoidal
primary current, and the r.m.s. value of that current related to the r.m.s. value of the primary
current is the composite error according to 3.4.203, the relation being expressed as a
percentage.

P1

S1

P2

S2

ZB

A
IEC 1553/12

Figure 2A.4 Basic circuit for 1:1 current transformer


Figure 2A.4 therefore represents the basic circuit for the direct measurement of composite
error.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Thus, in the general case, the composite error also represents the deviations from the ideal
current transformer that are caused by the presence in the secondary winding of higher
harmonics which do not exist in the primary. (The primary current is always considered
sinusoidal for the purposes of this standard.)

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012

45

Figure 2A.5 represents the basic circuit for the direct measurement of composite error for
current transformers having rated transformation ratios differing from unity. It shows two
current transformers of the same rated transformation ratio. The current transformer marked N
is assumed to have negligible composite error under the prevailing conditions (minimum
burden), while the current transformer under test and marked X is connected to its rated
burden.
P1

S1

P2

P1

S2

S1

P2

S2
ZB

A1

A2
IEC 1554/12

They are both fed from the same source of primary sinusoidal current, and an ammeter is
connected to measure the difference between the two secondary currents. Under these
conditions, the r.m.s. value of the current in the ammeter A 2 related to the r.m.s. value of the
current in ammeter A 1 is the composite error of transformer X, the relation being expressed as
a percentage.
With this method, it is necessary that the composite error of transformer N is truly negligible
under the conditions of use. It is not sufficient that transformer N has a known composite error
since, because of the highly complicated nature of composite error (distorted waveform), any
composite error of the reference transformer N cannot be used to correct the test results.

2A.6 Alternative method for the direct measurement of composite error


Alternative means may be used for the measurement of composite error and one method is
shown in Figure 2A.6.
P1
S1

P2

P1

S2

P2
S2

S1
ZB
P1
S1

A1

A2

S2

ZB
N

P2
IEC 1555/12

Figure 2A.6 Alternative test circuit


Whilst the method shown in Figure 2A.5 requires a special reference transformer N of the
same rated transformation ratio as the transformer X and having negligible composite error at

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Figure 2A.5 Basic circuit for current transformer with any ratio

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

46

61869-2 IEC:2012

the accuracy limit primary current, the method shown in Figure 2A.6, enables standard
reference current transformers N and N to be used at or around their rated primary currents.
It is still essential, however, for these reference transformers to have negligible composite
errors but the requirement is easier to satisfy.
In Figure 2A.6, X is the transformer under test. N is a standard reference transformer with a
rated primary current of the same order of magnitude as the rated accuracy limit primary
current of transformer X (the current at which the test is to be made). N is a standard
reference transformer having a rated primary current of the order of magnitude of the
secondary current corresponding to the rated accuracy limit primary current of transformer X.
It should be noted that the transformer N constitutes a part of the burden Z B of transformer X
and must therefore be taken into account in determining the value of the burden Z B . A 1 and
A 2 are two ammeters and care must be taken that A 2 measures the difference between the
secondary currents of transformers N and N.
If the rated transformation ratio of transformer N is k r , of transformer X is k rx and of
transformer N is k r, the ratio k r must equal the product of k r and k rx :
k r = k r k rx

NOTE When using the methods shown in Figure 2A.5 and Figure 2A.6, care should be taken to use a low
impedance instrument for A 2 since the voltage across this ammeter (divided by the ratio of transformer N in the
case of Figure 2A.6) constitutes part of the burden voltage of transformer X and tends to reduce the burden on this
transformer. Similarly, this ammeter voltage increases the burden on transformer N.

2A.7 Use of composite error


The numeric value of the composite error will never be less than the vector sum of the ratio
error () and the phase displacement (the latter being expressed in centiradians).
Consequently, the composite error always indicates the highest possible value of ratio error
() or phase displacement.
The ratio error () is of particular interest in the operation of overcurrent relays, and the phase
displacement in the operation of phase sensitive relays (e.g. directional relays).
In the case of differential relays, it is the combination of the composite errors of the current
transformers involved, which must be considered.
An additional advantage of a limitation of composite error is the resulting limitation of the
harmonic content of the secondary current, which is necessary for the correct operation of
certain types of relays.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Under these conditions, the r.m.s. value of the current in ammeter A 2 , related to the current in
ammeter A 1 , is the composite error of transformer X, the relation being expressed as a
percentage.

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012

47

Annex 2B
(normative)
Protective current transformer classes
for transient performance

2B.1 Basic theoretical equations for transient dimensioning


2B.1.1

Short-circuit

The following equations refer to a C-O duty cycle. C-O-C-O duty cycles are treated in 2B.1.3.
The general expression for the instantaneous value of a short-circuit current may be defined:

t/Tp

cos( ) cos( t + )

i (t ) =
k

2 I psc e

(2B.1)

is the r.m.s. value of primary symmetrical shortcircuit current I psc = K ssc I pr ;

I psc

Tp =

Lp

is the primary time constant;

Rp

= arctan

is the switching or fault inception angle;

Xp
Rp

= arctan Tp

is the phase angle of the system short-circuit


impedance;
is the angular frequency 2f R ;

when the equivalent voltage source in the short-circuit with Rp and X p is

u (t ) = U max cos( t + )

(2B.2)

For simplification purposes the fault inception angle and system impedance angle can be
summed up to one single angle which makes the calculation easier to understand from the
mathematical point of view.

=
i (t ) =
k

t/Tp

cos( ) cos( t + )

2 I psc e

(2B.3)
(2B.4)

The angles and both describe the possibility of varying the fault inception angle and
therefore can be applied alternatively as suitable but according to their definition.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

where

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

48

61869-2 IEC:2012

Figure 2B.1 shows two typical primary short-circuit currents. The first one occurs with a fault
inception angle of = 90 which leads to the highest peak current and the highest peak of
secondary linked flux for long t al (Figure 2B.2) whereas the second one occurs with = 140,
which leads to a lower asymmetry. Cases like the latter one are important for short t al ,
because, during the first half cycle, the current and flux are temporarily higher than in the
case of = 90.
ik(t)
ik( = 140)

ik,dc( = 90)
ik( = 90)

ik,dc( = 140)
t

IEC 1556/12

== 90
90
==100
100
==110
110
==120
120

max

m ax

==130
130
==140
140
==150
150
==160
160
==170
170

0.005

0.01

0.015

0.02

-2

0.025

0.03

0.035

180
0.04 ==180
0.045

tt

IEC 1557/12

Figure 2B.2 max (t) as the curve of the highest flux values, considering
all relevant fault inception angles
A possibly reduced range of fault inception angle can be used to define a reduced asymmetry
which may lead to a reduced factor K td in some special cases.
NOTE The possibility of restricting the current inception angle is not covered in this standard, but will be
discussed in the Technical Report IEC 61869-100.

2B.1.2

Transient dimensioning factor K td

The transient dimensioning factor K td is the final parameter for the core dimensioning and is
given on the rating plate. It can be calculated from different functions of the transient factor
K tf as given in the equations below and as shown in Figure 2B.3.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Figure 2B.1 Short-circuit current for two different fault inception angles

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012

49

In some cases, the protection system may require a t al value which is not constant and
depends on various parameters of the short-circuit current. Therefore the transient
dimensioning factor K td can also be obtained from relay stability type tests and given by the
manufacturer of the protection system.
The transient factor K tf given in this section is derived from the differential equation of the
equivalent circuit with a constant inductivity of the current transformer core, with an ohmic
burden and without consideration of remanence. In this annex, the solutions of the differential
equation are given either as curve diagrams or as simplified formulas.
NOTE

The differential equation and the exact solution is given in the Technical Report IEC 61869-100 TR.

K tf and the secondary linked flux depend likewise on time and, in the end, on the time to
accuracy limit t al required by the protection system. By calculating with the linear inductivity,
the solution is only valid up to the first saturation of the current transformer.

K
Ktfp,max
tfp,max

K
Ktftf

K
Ktf,max
tf,max

KKtf,max
tf,max

(1)
(1)

(2)
(2)

(3)
(3)

tttf,max
tf,max

t tfp,max
tfp,max

tt
IEC 1558/12

Figure 2B.3 Relevant time ranges for calculation of transient factor


In Figure 2B.3, the curve K tf,max is built as follows:
For every time point of the max curve (Figure 2B.2), the K tf value is calculated according its
definition in 3.4.233. Ktfp is the appropriate envelope curve. Three ranges have to be
distinguished, defined by three functions of K tf :
Range 1:

0 t al < t tf,max :

In the first time range, the K tf curve follows the K tf,max curve. The time range begins at zero
time and ends when the curve of K tf,max touches its envelope curve of peaks K tfp at the time

tf,max

(2B.5)

Eqn (2B.5) is simplified with = 90 from a more general formula, but it is suitable for practical
application.
Within this time range, K tf,max considers the worst-case switching angle (t al ) which leads to
the highest flux at the time to accuracy limit t al . Figure 2B.4 to Figure 2B.6 show the K tf
curves versus the primary time constant T p for different values of t al . A high secondary time
constant T s was chosen in the calculation. Lower T s values lead to slightly lower K tf values.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

K
Ktfp
tfp

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

50
NOTE

61869-2 IEC:2012

A larger variety of curves is given in the Technical Report IEC 61869-100 TR.

Ktf,
tf,max
max

ttalal

14 ms
13 ms
12 ms

Figure 2B.4
Determination of K tf
in time range 1
at 50 Hz
for T s = 1,8 s

11 ms

10 ms
9 ms

8 ms
7 ms

6 ms
5 ms

4 ms
3 ms
2 ms

10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200

(ms)
Tpp [ms]

Ktf,max
tf,max

IEC 1559/12

tal
tal

11 ms

10 ms
9 ms

Figure 2B.5
Determination of K tf
in time range 1
at 60 Hz
for T s = 1,5 s

8 ms
3

7 ms
6 ms

5 ms
4 ms

3 ms
2 ms

0
0

10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200
Tp (ms)
IEC 1560/12

Tp [ms]

K
Ktf,max
tf, max

ttalal

42 ms
39 ms
36 ms

Figure 2B.6
Determination of K tf
in time range 1
at 16,7 Hz
for T s = 5,5 s

33 ms
30 ms
27 ms

24 ms
2

21 ms

15 ms

18 ms
12 ms
9 ms
6 ms

0
0

10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200

TTpp[ms]
(ms)

IEC 1561/12

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012

51

Range 2: t tf,max t al < t tfp,max


In the second time range, the K tf curve follows the envelope curve K tfp for = 90, which leads
to the highest peak flux, therefore = 90- .

tfp

TsTp
Tp Ts

t / T
tal / Tp tal / TS
+ sin( )e al S + 1
e

cos( ) e

(2B.6)

The time range ends at the maximum of the K tfp curve at the time

Tp

Range 3:

tfp,max

Tp Ts
Tp Ts

ln

Ts

(2B.7)

t tfp,max t al

In the third time range, K tf assumes the constant value K tfp,max , given in eqn. (2B.8). It is
defined as the maximum value of the K tfp curve.

Tp
Ts Tp

Ts Tp
Tp
sin( )
cos( ) +
2
Tp + Ts

Ts
Ts

T cos( ) +
K
sin( )
tfp,max = p

Ts
cos( )

2B.1.3

+1

(2B.8)

C-O-C-O duty cycles

The transient dimensioning for auto-reclosure duty cycles has to be done separately for each
cycle according to the equations given above.
For cores having a high secondary time constant (typically TPX cores), there is no significant
flux declination after t.

K td,(COCO) = K td (t ' ) + K td (t al" )

(2B.9)

For cores having a low secondary time constant (typically TPY and TPZ cores), the secondary
linked flux declines exponentially with the secondary time constant T S during the fault
repetition time t fr . In this case, no analytical formula exists for the time argument t in the term
for the first cycle, and several case differentiations may be necessary.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Ts Tp
sin( )
2
Ts
cos( )

cos( ) +

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

52

61869-2 IEC:2012

1(t)
sat

2(t)

tsat

0
tal

t
tfr

IEC 1562/12

Figure 2B.7 Limiting the magnetic flux by considering core saturation


Fig. 2B.7 shows a typical case where saturation is reached after t al . The flux ( 2 (t)) is limited
to saturation flux( sat ) before t is reached. During t fr , it declines to a value which is low
enough to remain below saturation up to t al . Ignoring saturation (shoved by curve 1 (t)), the
declined flux starts from a higher level at the beginning of the second cycle. This example
demonstrates the interdependency between the core dimensioning in the first and in the
second cycle, and the determination of K td .
NOTE 1 The formula for the C-O-C-O-cycle, which was given in the preceding standard IEC 60044-6, ignores
saturation within the first cycle and leads in many cases to unnecessarily high K td values. See Fig. 2B.7.

It is therefore recommended to draw a graph similar to the one in Fig. 2B.7, in order to make
oneself familiar with the actual situation. The following equation provides an upper limit for
Ktd :

K td,(COCO)max = max K td (t 'al ) , K td (t ' )e (tfr +t ''al ) / Ts + K td (t al" )

(2B.10)

NOTE 2 In Technical Report IEC 61869-100 TR calculation methods are given which may be used to determine
the K td value.

2B.2 Measurement of the core magnetization characteristic


2B.2.1

General

Measuring the core magnetization characteristic implies

the measurement of the magnetizing inductance L m;


the measurement of the remanence factor K R ;

the determination of the error at limiting conditions using an indirect method.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

tal

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012

53

All of these are based on the following relationship. If an arbitrary voltage u(t) is applied to the
secondary terminals (see Figure 2B.8), the flux (t) linked through the secondary winding at
time t is related to this voltage through the equation:
t

(t ) = (u (t ) Rct im (t ))dt

(2B.11)

where i m is the instantaneous value of the magnetizing current.


NOTE As the term exciting current is reserved for the r.m.s. value using a.c. quantities (see 3.3.207), i m and the
term magnetizing current are used for instantaneous values in the d.c. method and capacitor discharge method.

The methods described in the following clauses take advantage of this relationship.
The effect of the voltage drop across the secondary winding resistance shall be estimated. If
it exceeds 2 %, this drop shall be deduced from the voltage measured.

Rct

u(t)

IEC 1563/12

Figure 2B.8 Basic circuit


For TPX current transformers, it is necessary to demagnetize the core before each test,
because of the high remanence factor. For TPY current transformers the remanent flux is
often so low that it can be neglected. Demagnetization requires additional means by which the
core can be subjected to slowly decreasing hysteresis loops starting from saturation. A direct
current source will normally be provided when the d.c. test method has to be used.
Either of the three methods (a.c. method, d.c. method, capacitor discharge method) may be
applied.
2B.2.2
2B.2.2.1

A.C. method
Determination of the magnetizing inductance L m

A substantially sinusoidal a.c. voltage is applied to the secondary terminals and the
corresponding value of the exciting current is measured. The test may be performed at
reduced frequency f to avoid unacceptable voltage stressing of the winding and secondary
terminals. Effects of undue eddy current losses in the core and capacitive currents between
the winding layers will be less likely to cause false readings at lower frequencies. The result
shall be shown as a saturation curve.
The exciting voltage shall be measured with an instrument whose response is proportional to
the average of the rectified signal, but calibrated in r.m.s. The exciting current shall be
measured using a peak reading instrument.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

im

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

54

61869-2 IEC:2012

The peak value of the secondary linked flux may be derived from the measured r.m.s. value
of the applied voltage U at the frequency f as follows:

2U
2f '

Accordingly, the saturation voltage U sat corresponds with the saturation flux sat as follows:

sat =

2 U sat
2f '

NOTE 201 U sat shall be estimated as the voltage value where the curve is practically horizontal. The influence of
the uncertainty in the determination of U sat on L m is practically negligible.

Lm =

0,5 U sat 2
(i70 i20 ) 2f '

where
20
70

is the peak value of the exciting current at 20 % U sat ;


is the peak value of the exciting current at 70 % U sat .

NOTE 202 This formula differs slightly from the formula given in the preceding standard IEC 60044-6 (B4) due to
the improved definition of saturation.

2B.2.2.2

Determination of the error at limiting conditions

The test arrangement of 2B.2.2.1 shall be used.


The voltage shall be increased up to the voltage equal to E al given as

Eal = K ssc K td ( Rct + Rb ) I sr


The appropriate exciting current al shall not exceed the following limits:
For classes TPX and TPY:

Ial 2 I sr K ssc

For class TPZ:

K td 1

+ ac
Ial 2 I sr K ssc
2f R TS

NOTE For TPZ current transformers, the accuracy is specified only for the a.c. component while, in the
determination of the permissible value of I al during indirect tests, it is also necessary to take the d.c. component of
the exciting current into account. In the above equation, the d.c. component is represented by (K td 1).

2B.2.2.3

Determination of the remanence factor K R

Other than in 2B.2.2.1 and 2B.2.2.2, the waveforms of the a.c. signals have to be detected.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Considering this equation, the curve gives the required relationship between the peak value of
the exciting current and the peak value of the secondary linked flux . The magnetizing
inductance L m is defined as the mean slope of this curve between 20 % and 70 % of the
saturation flux sat . It is calculated as

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012

55

In determining the remanence factor K R by the a.c. test method, it is necessary to integrate
the exciting voltage according to equation (1) given in 2B.2.1. The integrated voltage with the
corresponding current i e will display a hysteresis loop, showing the saturation flux sat . The
secondary linked flux value at zero crossing of current is deemed to represent the remanent
flux r . See Figure 2B.9. The remanence factor K R is then calculated as

KR =

r
sat

(2B.12)

At lower frequencies, effects of undue eddy current losses in the core and capacitive currents
between the winding layers will be less likely to cause false readings.
NOTE

sat shall be estimated as the secondary linked flux value where the curve is practically horizontal.

sat

ie

IEC 1564/12

Figure 2B.9 Determination of remanence factor by hysteresis loop


2B.2.3
2B.2.3.1

D.C. method
General

The d.c. saturation method applies a d.c. voltage u(t) of such duration that saturation flux is
reached. The flux measurement is derived according to equation (2B.11) given in 2B.2.1,
where u(t) is the voltage across the terminals. See Figure 2B.10.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

56

61869-2 IEC:2012

im

Rct

u(t)

um(t)

Rd

(t)

im(t)
IEC 1565/12

Figure 2B.10 Circuit for d.c. method


The applied voltage source shall be suitable to drive the current transformer into saturation.

2B.2.3.2

Determination of the remanence factor K R

The test circuit according to 2B.2.3.1 shall be used.


Sometime after the switch S has been closed, the magnetizing current will be deemed to have
reached its maximum value ( m ) at which the secondary linked flux would remain constant.
Before reaching the constant value, the i m curve must show a significant increase of the
gradient, indicating saturation. The d.c. source shall be able to drive the transformer core into
saturation without influencing the test results due to its limitations. This condition is fulfilled if
the secondary linked flux achieves a stable value earlier than the magnetizing current.
The rising values of the magnetizing current and of the flux shall be recorded up to the time at
which the values become constant, then the switch S will be opened.
Typical test records of the flux and of the magnetizing current i m are shown in Figure 2B.11.

im

im

im
IEC 1566/12

Figure 2B.11 Time-amplitude and flux-current diagrams


At the opening of switch S, a decreasing current flows through the secondary winding and the
discharging resistor R d . The corresponding flux value decreases, but may not fall to zero.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

The discharge resistor R d shall be connected; otherwise the magnetizing inductance of the
core may cause very high overvoltage when switch S is opened and the inductive current
interrupted.

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012

57

When a suitable magnetizing current i m has been chosen to achieve the saturation flux sat ,
the remaining flux value at the zero current shall be deemed to be the remanent flux r .
For a current transformer whose core has not been demagnetized before, the saturation flux
and the remanent flux may be determined by an additional test in which the secondary
terminals have been interchanged. The curve of secondary linked flux obtained hereby
contains an offset of half of the apparently measured remanent flux value. Therefore, the zero
line has to be shifted correspondingly, leading to corrected values of saturation flux and
remanent flux. See figure 2B.12.

IImm

IImm

t
IEC 1567/12

Figure 2B.12 Recordings with shifted flux base line


The remanence factor K R is determined

KR =
2B.2.3.3

r
sat

Determination of the magnetizing inductance L m

The test procedure of 2B.2.3.2 shall be used.


The magnetizing inductance (L m ) may be deduced according to the following equation:

Lm =

0,5 sat
i70 i20

where
i 20

is the peak value of the magnetizing current at 20 % sat ;

i 70

is the peak value of the magnetizing current at 70 % sat .

NOTE This formula differs slightly from the definition given in the preceding standard IEC 60044-6 (B4) due to the
improved definition of saturation.

2B.2.3.4

Determination of the error at limiting conditions

The test circuit according to 2B.2.3.1 shall be used.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

0
0

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

58

61869-2 IEC:2012

For determination of the error at limiting conditions, the magnetizing current im at the
secondary linked flux al shall be measured while increasing the flux.

al is given as

al =

2 Eal
=
2f R

2 K td K ssc I sr ( Rb + Rct )
2f R

The magnetizing current i m shall not exceed the following limits:


For classes TPX and TPY:

im 2 I sr K ssc

For class TPZ:

K td 1

+ ac
im 2 I sr K ssc
2f R TS

2B.2.4

Capacitor discharge method

The capacitor discharge method uses the charge of a capacitor for energizing the current
transformer core from the secondary. The flux measurement is derived according to equation
(1) given in 2B.2.1, where u(t) is the voltage across the terminals. See Figure 2B.13.
The capacitor is charged with a voltage sufficiently high to produce a secondary linked flux
equal to or greater than the flux al corresponding to E al . See Figure 2B.13 and Figure 2B.14.

al =

u(t)

2 Eal
2f R

udt

CT

i(t)
IEC 1568/12

Figure 2B.13 Circuit for capacitor discharge method


At the time when al is reached, the peak value of the secondary exciting current i m shall be
measured and shall not exceed the peak value of the exciting secondary current al .
The secondary time constant T s shall be determined by applying a voltage with a voltage-time
integral corresponding to 90 % of E al . The corresponding exciting current i m is measured and
the secondary time constant calculated as follows:

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

NOTE For TPZ current transformers, the accuracy is specified only for the a.c. component while, in the
determination of the permissible value of im during indirect tests, it is also necessary to take the d.c. component of
the exciting current into account. In the above equation, the d.c. component is represented by (K td 1).

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012

59

Ts =
NOTE

2 0,9 Eal
2f R ( Rct + Rb ) i 'm

This definition of T s does not conform with the definition in the above mentioned d.c. and a.c. methods.

In determining the remanence factor K R , the integrated voltage with the corresponding current
will determine a hysteresis loop. If the exciting current has been such that the saturation flux
is reached, the flux value at zero crossing of the current is deemed to represent the remanent
flux r .
The remanence factor K R is determined:

KR =

r
sat

im

im

r
t

td

im
IEC 1569/12

Figure 2B.14 Typical records for capacitor discharge method

2B.3 Direct test for determination of the error at limiting conditions


2B.3.1

General

The instantaneous error current can be measured in different ways. In all cases, the errors of
the measuring system shall not exceed 10 % of the error limit corresponding to the class of
the tested current transformer during the whole of the duty cycle.
2B.3.2

Direct test

Class TPX current transformers shall be demagnetized before the direct test because of the
high remanence factor. It may be necessary to demagnetize class TPY current transformers if
the remanence factor K R is not negligible.
Two direct tests shall be performed at rated frequency and with rated secondary burden:
a)

The rated primary short-circuit current at rated frequency is applied without any offset.
The a.c. component of the instantaneous error is measured and shall be in accordance
with the theoretical value 1/T s .

b)

To verify that the current transformer meets the accuracy requirements of the specified
duty cycle, the following test shall be performed:
The rated primary short-circuit current at rated frequency is applied with the required
offset. For specified values of primary time constant up to 80 ms, the test is performed in
the specified accuracy limiting condition (specified duty cycle). The primary time constant
shall not deviate by more than 10 % from the specified value.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

sat

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

60

61869-2 IEC:2012

For specified values of primary time constant above 80 ms, the tests can be performed in
equivalent accuracy limiting conditions (by modifying duty cycle and/or burden),
subjected to agreement between manufacturer and purchaser.
During the energization period, the first peak of the primary current shall be not less than
the value corresponding to the specified conditions.
In laboratory practice, it may be difficult to reproduce the exact duty cycle specification.
In this case, the calculated K td value of the applied duty cycle shall not be less than the
calculated K td value of the specified duty cycle. To meet this requirement, the duration of
the energization(s) and/or the secondary burden may be adjusted.
NOTE As the calculation of K td is based on worst-case formulas (formula 6 in 2B.1.2 may deliver K td values
which are 30 % higher than necessary), the current transformer may satisfy the duty cycle without reaching
the flux corresponding to the calculated K td value.

For class TPX and TPY current transformers, the instantaneous error current i is
measured as i = is k r ip . The error value according to 3.4.222 shall be
determined. Its value shall not exceed the limit given in Table 206.

to 3.4.223 shall be determined. Its value shall not exceed the limit given in Table 206.
NOTE It is possible that the class definition does not contain a duty cycle. In this case, for test purposes, a
duty cycle leading to the given K td value shall be agreed between manufacturer and purchaser.
i

bb

cc
aa

tt
IEC 1570/12

Where:
a= idc
b=

2iac

c= iac

+ idc

for TPY: i

=c

for TPZ: i

= iac =

b
2
Figure 2B.15 Measurement of error currents

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

For class TPZ current transformers, the a.c. component of the error current is measured
as one half of the peak-to-peak value (see Figure 2B.15). The error value ac according

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012

61

If the real K td value of the current transformer has to be determined, the duration of the
energization and/or secondary burden shall be increased so that the measured instantaneous
error current reaches the limiting value for the accuracy class concerned (Table 206). For
class TPZ, linear interpolation is used to determine the instant at which the limiting value of
the a.c. component of the error current is reached.
The secondary linked flux dir shall be determined as

(t ) =

Rct + Rb t
Rb is (t )dt
Rb
0

where t is the time point when the error limit or ac is reached.


The total dimensioning factor K td of the current transformer is the ratio of dir to the peak
value of the a.c. component of under steady-state conditions. This a.c. component can be
derived from a secondary linked flux measurement in the test a), which has to be related to
the exact (theoretical) value of the short circuit current K ssc x I sr . The measurement shall be
made using the abovementioned formula.

2B.3.3

Determination of the factor of construction

If compliance with the requirements of low-leakage reactance design cannot be established to


the mutual satisfaction of the manufacturer and purchaser by reference to drawings, then the
factor of construction F c shall be determined as follows:
The secondary linked flux values in both a direct test and an indirect test have to be
determined, in both cases for the magnetizing current at accuracy limiting conditions. If a
transient performance class is specified by the alternative definition, the appropriate duty
cycle and burden shall be chosen in order to achieve the specified K SSC x K td value.
The secondary linked flux dir , which is obtained in the direct test according to 2B.3.2, shall
be determined.
In the indirect test, the secondary linked flux

ind shall be determined with one of the following

methods:
a.c. method:
The test arrangement according to 2B.2.2.1 shall be applied.
The voltage shall be increased until the appropriate limit of the exciting current al given
in 2B.2.2.2 is reached. The voltage U obtained hereby shall be noted. The secondary
linked flux ind is given by

ind =
where f is the applied frequency.
d.c. or capacitor discharge method:

2 U
2f

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

The error in flux measurement shall not exceed 5 %.

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

62

61869-2 IEC:2012

The test circuit according to 2B.2.3.1 (d.c. method) or 2B.2.4 (capacitor discharge
method) shall be used.
The flux

ind

is the secondary linked flux which corresponds to the limit of the

magnetizing current i m given in 2B.2.3.4.


F c is then calculated as

Fc =

ind
dir

In the tests, the error in flux measurement shall not exceed 5 %.


If F c is greater than 1,1, it shall be considered when dimensioning the core.
NOTE The value of primary current required to perform direct tests on certain transformer types may be beyond
the capability of facilities normally provided by manufacturers. Tests at lower levels of primary current may be
agreed between the manufacturer and purchaser.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012

63

Annex 2C
(normative)
Proof of low-leakage reactance type
It shall be demonstrated that:

the current transformer has a substantially continuous ring core, with air gaps
uniformly distributed, if any;

the current transformer has uniformly distributed secondary winding;

the current transformer has a primary conductor symmetrical with respect to rotation;

the influences of conductors of the adjacent phase outside of the current transformer
housing and of the neighbouring phases are negligible.

If compliance with the requirements of low-leakage reactance design cannot be established to


the mutual satisfaction of manufacturer and purchaser by reference to drawings, then the
results of a direct test and of an indirect test shall be compared as follows:

For all other protection classes, the composite errors of the full winding obtained with a direct
test method and with the indirect test method shall be compared.
For the direct test, either of the methods given in 2A.5 and 2A.6 may be applied. The primary
test current shall be:
ALF x I pr
K x x I pr

for class P and class PR;


for class PX and class PXR.

For the indirect test, the method given in 7.2.6.203 b) shall be applied. The voltage applied to
the secondary terminals shall be equal to:
E ALF

for class P and class PR;

Ek

for class PX and class PXR.

Proof of low-leakage reactance design shall be considered to have been established if the
value of composite error from the direct method is less than 1,1 times that deduced from the
indirect method.
NOTE According to its definition (3.4.235), the term low-leakage reactance current transformer is not universal,
but related to its protection performance, e.g. protection class.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

For class TPX, TPY and TPZ current transformers, the factor of construction F c shall be
determined according to 2B.3.3. If F c is less than 1,1, the current transformer shall be
regarded as low-leakage reactance current transformer.

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

64

61869-2 IEC:2012

Annex 2D
(informative)
Technique used in temperature rise test of oil-immersed transformers
to determine the thermal constant by an experimental estimation
List of symbols:

Temperature in C

(t)

Oil temperature, varying with time (this may be the temperature of the oil at the
top, or average oil temperature)

External cooling medium temperature (ambient air or water) assumed to be


constant

Oil temperature rise above a


Ultimate values in steady state

To

Remaining deviation from steady-state value u


Time constant for exponential variation of bulk oil temperature rise

Time interval between readings

1 , 2 , 3

Three successive temperature readings with time interval h between them.

In principle, the test should continue until the steady-state temperature rise (of the oil) is
ascertained.
u = a + u

(2D.1)

(t) = a + u (1 e t/To )

(2D.2)

The remaining deviation from steady state is then:

(t) = u (t) = u e t/To

(2D.3)

It is considered that:

the ambient temperature is kept as constant as possible;

the oil temperature (t) will approach an ultimate value u along an exponential
function with a time constant of T o ;

the equation (2D.2) is a good approximation of the temperature curve (see Figure
2D.1).

Given three successive readings 1 , 2 and 3 , the exponential relation of equation


(2D.2), is a good approximation of the temperature curve, then the increments will have the
following relation:

2 1
= e h/To
3 2
To =

h
1
ln 2
3 2

The readings also permit a prediction of the final temperature rise:

(2D.4)

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

u , u
(t)

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012

65

u =

( 2 )2 1 3

(2D.5)

2 2 1 3

Successive estimates are to be made and they should converge. In order to avoid large
random numerical errors the time interval h should be approximately T o and 3 / u should be
not less than 0,95.
A more accurate value of steady-rate temperature rise is obtained by a least square method
of extrapolation of all measured points above approximately 60 % of u ( u estimated by the
three point method).
A different numerical formulation is:

u = 2 +

ln

(2D.6)

2 1

3 2

3
2

2
1

(t)

h
IEC 1571/12

Figure 2D.1 Graphical extrapolation to ultimate temperature rise

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

( 2 1 ) ( 3 2 )

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

66

61869-2 IEC:2012

Annex 2E
(informative)
Alternative measurement of the ratio error ()
For low-leakage reactance current transformers, the following indirect test will lead to results
which are very close to the results obtained in the direct test.
Nevertheless, routine tests for ratio error determination shall always be performed as a direct
test, as this method gives the highest evidence of the low-leakage reactance property of a
core, including magnetic homogeneity of the iron core. On the other hand, the alternative
method is suitable for on-site measurements, and for monitoring purposes.
In this case, it shall be noted that this method never considers the influence of current flow in
the neighborhood of the current transformer.

Ip x Np / N s = Is + I e
IsRCT
Re
P1

Ip

RCT

Np : Ns
Ixm
Xm

S1

Us

IRm
Rm

e.m.f

Is

e.m.f

Is

Rb

Ip(Isr/Ipr)

Us

E0

Xb

P2

Im

S2

Ixm

IRm
IEC 1572/12

Figure 2E.1 Simplified equivalent circuit of the current transformer


A substantially sinusoidal voltage is applied to the secondary terminals S 1 S 2 of the current
transformer. The test voltage across the terminals U s Test and the current I s Test are
measured. The injected voltage should generate an e.m.f. across the main inductivity with the
same amplitude as during operation with a certain current and the actual burden. The e.m.f.
can be calculated from the test results by subtracting the voltage drop across the winding
resistance R ct from the test voltage U s Test across the S 1 S 2 terminals. This subtraction has
to be done in the complex plane. The measured current I s Test is equal the error current I .
The ratio error can be expressed as:

Is Ip

I sr
I pr

I
I p sr
I pr

I s I pr
I p I sr

(2E.1)

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

For the determination of the ratio error, the simplified equivalent circuit diagram shown in
Figure 2E.1 is used:

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 IEC:2012

67

with:

I p Np
Ns

= Ie + I

Ip =

(I e + I s )N s
Np

(2E.2)

the ratio error can be expressed as:

I s N p I pr

(I e + I s ) N s I sr

(2E.3)

To determine the ratio error for a certain secondary current I s the following test procedure is
proposed:

Calculation of the secondary voltage across S 1 S 2 :

U s = I s (Rb + jX b )

Measurement of the secondary winding resistance R (value at the actual temperature)

Calculation of the corresponding e.m.f.


E0 = I sR + U s

Injection of

U s Test = E 0 + I s Test R

( with I s Test = I s )

into the secondary terminals S 1 S 2

Measurement of the voltage U p Test across P 1 - P 2


Calculation of the turns ratio

Np
Ns

U p Test
E0

Calculation of the corresponding I p

IP =

( I s + I s Test ) N s
Np

The ratio error can be calculated as:

(I

I s N p I pr
s Test

+ I s ) I sr

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

68

61869-2 IEC:2012

Annex 2F
(normative)
Determination of the turns ratio error
The actual transformation ratio is affected by errors from three sources:
a) the difference between the inverse of the turns ratio and the rated transformation ratio;
b) the core exciting current (I e );
c) the currents which flow in the stray capacitances associated with the windings.

given by

I ' S ( R + R 'b ) = E S = I ' ' S ( R + R ' 'b )


where R is the actual resistance of the secondary winding.
Assuming that the measured ratio errors are c and c , the turns ratio error is denoted as t ,
and the combined magnetization and stray currents are given by I x . The respective error
currents will be given by:

( 'c t ) k r I ' s = I x = ( ' 'c t ) k r I ' ' s


whence:

t =

'c I ' s ' 'c I ' ' s


I 's I ' 's

If I S = 2I S , the turns ratio error is given by 2 c c .


A test at rated current with minimum secondary connected burden, followed by a test at half
rated current and suitable increase in secondary loop resistance, will usually give satisfactory
results.

___________

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

In most cases, it is reasonable to assume that for a given secondary winding induced e.m.f.
(E s ), the error currents due to stray capacitances and core magnetization will maintain a
constant value irrespective of the value of the primary energizing current. E s can theoretically
be maintained at a constant value for a range of energizing currents, provided that the
secondary loop impedance can be appropriately adjusted. For current transformers designed
to be of the low-leakage reactance type, the secondary leakage reactance can be ignored and
only the secondary winding resistance has to be considered. Thus, for any two currents l' s
and I" s the basic equation defining the test requirement is

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

70

61869-2 CEI:2012

SOMMAIRE
AVANT-PROPOS .................................................................................................................. 73
1

Domaine dapplication .................................................................................................... 77

Rfrences normatives ................................................................................................... 77

Termes et dfinitions ...................................................................................................... 77

3.1 Dfinitions gnrales ............................................................................................. 77


3.3 Dfinitions relatives aux caractristiques assignes de courant ............................. 79
3.4 Dfinitions relatives la prcision ......................................................................... 80
3.7 Index des abrviations .......................................................................................... 88
Caractristiques assignes ............................................................................................. 90
5.3

6.4

Exigences relatives lchauffement des parties et des composants .................. 98


6.4.1
Gnralits ......................................................................................... 98
6.13
Marquage ........................................................................................................... 98
6.13.201 Marquage des bornes ......................................................................... 98
6.13.202 Marquage des plaques signaltiques .................................................. 99
Essais .......................................................................................................................... 102
7.1
7.2

7.3

Gnralits ....................................................................................................... 102


7.1.2
Liste des essais ................................................................................ 102
Essais de type .................................................................................................. 103
7.2.2
Essai dchauffement........................................................................ 103
7.2.3
Essai de tenue la tension de choc sur les bornes primaires ........... 104
7.2.6
Essais concernant la prcision .......................................................... 105
7.2.201 Essais de tenue aux courants de courte dure .................................. 106
Essais individuels de srie ................................................................................ 107
7.3.1
Essais de tenue la tension frquence industrielle sur les
bornes primaires ............................................................................... 107
7.3.5
Essais concernant la prcision .......................................................... 107
7.3.201 Dtermination de la rsistance de lenroulement secondaire (R ct ) ..... 109

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Niveaux disolement assigns ............................................................................. 90


5.3.2
Niveau disolement assign des bornes primaires ............................... 90
5.3.5
Exigences disolement pour les bornes secondaires ........................... 90
5.3.201 Exigences disolement entre spires ..................................................... 90
5.5
Puissance de sortie assigne ............................................................................. 90
5.5.201 Valeurs de la puissance de sortie assigne ........................................ 90
5.5.202 Valeurs de charge rsistive assigne .................................................. 90
5.6
Classe de prcision assigne ............................................................................. 91
5.6.201 Transformateurs de courant pour mesure ........................................... 91
5.6.202 Transformateurs de courant pour protection........................................ 92
5.6.203 Spcification de classe pour les transformateurs de courant
rapports de transformation slectionnables ......................................... 97
5.201 Valeurs normales du courant primaire assign .................................................... 97
5.202 Valeurs normales du courant secondaire assign ............................................... 98
5.203 Valeurs normales du courant thermique permanent assign ............................... 98
5.204 Courants de court-circuit assigns ...................................................................... 98
5.204.1 Courant de court-circuit thermique assign (I th ) .................................. 98
5.204.2 Courant dynamique assign (I dyn ) ...................................................... 98
Conception et construction ............................................................................................. 98

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012

71

Dtermination de la constante de temps de la boucle


secondaire (T s ) ................................................................................. 109
7.3.203 Essai pour la force lectromotrice de coude assigne (E k ) et le
courant dexcitation E k ................................................................... 110
7.3.204 Essai de surtension entre spires ....................................................... 111
7.4
Essais spciaux ................................................................................................ 112
7.4.3
Mesure de la capacit et du facteur de dissipation dilectrique ......... 112
7.4.6
Essai de dfaut darc interne ............................................................ 112
7.5
Essais sur prlvements ................................................................................... 112
7.5.1
Dtermination du facteur de rmanence ........................................... 112
7.5.2
Dtermination du facteur de scurit (FS) pour les
transformateurs de courant pour mesure .......................................... 112
Annexe 2A (normative) Transformateurs de courant pour protection de classes P
et PR .................................................................................................................................. 113
7.3.202

Annexe 2B (normative) Classes de transformateurs de courant pour protection pour


rponse en rgime transitoire ............................................................................................. 118
Annexe 2C (normative) Preuve de type faible ractance de fuite ..................................... 135

Annexe 2E (informative) Mthode alternative pour la mesure de lerreur de rapport () ...... 138
Annexe 2F (normative) Dtermination du rapport des nombres de spires ........................... 140
Figure 201 Cycles de fonctionnement ................................................................................ 85
Figure 202 Constante de temps du primaire T p .................................................................. 85
Figure 203 Flux embrass par lenroulement secondaire pour des diffrents angles
dapparition du courant de court-circuit ............................................................................... 87
Figure 2A.1 Diagramme vectoriel ..................................................................................... 113
Figure 2A.2 Triangle derreur ........................................................................................... 114
Figure 2A.3 Forme donde typique ................................................................................... 115
Figure 2A.4 Circuit de base pour transformateur de courant 1: 1 ...................................... 115
Figure 2A.5 Circuit de base pour transformateur de rapport quelconque .......................... 116
Figure 2A.6 Variante de circuit dessai ............................................................................. 116
Figure 2B.1 Courants de court-circuit prsentant la crte la plus leve ( = 90) et
prsentant une asymtrie infrieure ( = 140) .................................................................... 119
Figure 2B.2 La courbe max (t), compose des valeurs de flux les plus leves,
considrant tous les angles d'enclenchement apprciables .............................................. 119
Figure 2B.3 Plages de temps appropries pour le calcul du facteur transitoire ................. 120
Figure 2B.4 Dtermination de K tf pour la plage 1 50 Hz et T s = 1,8 s .......................... 121
Figure 2B.5 Dtermination de K tf pour la plage 1 60 Hz et T s = 1,5 s ......................... 121
Figure 2B.6 Dtermination de K tf pour la plage 1 16,7 Hz et T s = 5.5 s ....................... 122
Figure 2B.7 Limitation du flux magntique considrant la saturation du noyau ................. 123
Figure 2B.8 Circuit de base .............................................................................................. 124
Figure 2B.9 Dtermination du facteur de rmanence par cycle dhystrsis ..................... 127
Figure 2B.10 Circuit pour la mthode en courant continu ................................................. 127
Figure 2B.11 Diagrammes temps-amplitude et flux-courrant ............................................ 128
Figure 2B.12 Diagramme avec la ligne de zro dplace ................................................. 129

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Annexe 2D (informative) Technique utilise dans lessai dchauffement des


transformateurs immergs dans lhuile pour dterminer la constante thermique par
estimation exprimentale .................................................................................................... 136

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

72

61869-2 CEI:2012

Figure 2B.13 Circuit utilis dans la mthode par dcharge dun condensateur ................. 130
Figure 2B.14 Enregistrements types de la mthode par dcharge dun condensateur ...... 131
Figure 2B.15 Mesure des courants derreur ..................................................................... 133
Figure 2D.1 Extrapolation graphique de lchauffement final ............................................ 137
Figure 2E.1 Circuit quivalent simplifi du transformateur de courant .............................. 138
Tableau 201 Limites de lerreur de rapport et du dphasage des transformateurs de
courant pour mesure (classes de 0,1 1) ............................................................................. 91
Tableau 202 Limites de lerreur de rapport () et du dphasage des transformateurs
de courant pour mesure pour applications particulires......................................................... 92
Tableau 203 Limites de lerreur de rapport des transformateurs de courant pour
mesure (classes 3 et 5)......................................................................................................... 92
Tableau 204 Caractristiques des classes de protection .................................................... 93
Tableau 205 Limites derreur des transformateurs de courant pour protection
des classes P et PR .............................................................................................................. 94

Tableau 207 Mthodes de spcification des transformateurs de courant de


classes TPX, TPY et TPZ...................................................................................................... 97
Tableau 208 Marquage des bornes .................................................................................... 99
Tableau 10 Liste des essais ............................................................................................. 102

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Tableau 206 Limites derreur pour les transformateurs de courant de classes TPX,
TPY et TPZ ........................................................................................................................... 96

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012

73

COMMISSION LECTROTECHNIQUE INTERNATIONALE


____________
TRANSFORMATEURS DE MESURE
Partie 2: Exigences supplmentaires concernant
les transformateurs de courant
AVANT-PROPOS

2) Les dcisions ou accords officiels de la CEI concernant les questions techniques reprsentent, dans la mesure
du possible, un accord international sur les sujets tudis, tant donn que les Comits nationaux de la CEI
intresss sont reprsents dans chaque comit dtudes.
3) Les Publications de la CEI se prsentent sous la forme de recommandations internationales et sont agres
comme telles par les Comits nationaux de la CEI. Tous les efforts raisonnables sont entrepris afin que la CEI
sassure de lexactitude du contenu technique de ses publications; la CEI ne peut pas tre tenue responsable
de lventuelle mauvaise utilisation ou interprtation qui en est faite par un quelconque utilisateur final.
4) Dans le but dencourager luniformit internationale, les Comits nationaux de la CEI sengagent, dans toute la
mesure possible, appliquer de faon transparente les Publications de la CEI dans leurs publications
nationales et rgionales. Toutes divergences entre toutes Publications de la CEI et toutes publications
nationales ou rgionales correspondantes doivent tre indiques en termes clairs dans ces dernires.
5) La CEI elle-mme naccorde aucune attestation de conformit. Des organismes de certification indpendants
proposent des services dvaluation de conformit et, dans certains domaines, un accs aux marques de
conformit de la CEI. La CEI nest responsable daucun des services effectus par les organismes de
certification indpendants.
6) Il convient que tous les utilisateurs sassurent quils sont en possession de la dernire dition de cette
publication.
7) Aucune responsabilit ne doit tre impute la CEI, ses administrateurs, employs, auxiliaires ou
mandataires, y compris ses experts particuliers et les membres de ses comits dtudes et des Comits
nationaux de la CEI, pour tout prjudice caus en cas de dommages corporels et matriels, ou de tout autre
dommage de quelque nature que ce soit, directe ou indirecte, ou pour supporter les cots (y compris les frais
de justice) et les dpenses dcoulant de la publication ou de lutilisation de cette Publication de la CEI ou de
toute autre Publication de la CEI, ou au crdit qui lui est accord.
8) Lattention est attire sur les rfrences normatives cites dans cette publication. Lutilisation des publications
rfrences est obligatoire pour une application correcte de la prsente publication.
9) Lattention est attire sur le fait que certains des lments de la prsente Publication de la CEI peuvent faire
lobjet de droits de brevet. La CEI ne doit pas tre tenue pour responsable de ne pas avoir identifi de tels
droits de brevets et de ne pas avoir signal leur existence.

Cette Norme Internationale CEI 61869-2 Ed. 1.0 a t tablie par le comit 38:
Transformateurs de mesure.
La prsente premire dition de la CEI 61869-2 annule et remplace la premire dition de la
CEI 60044-1, publie en 1996, et son Amendement 1 (2000) et Amendement 2 (2002), et la
premire dition de la CEI 60044-6 (1992). De plus, elle introduit des innovations techniques
dans la normalisation et ladaptation des exigences des transformateurs de courant pour
rponse en rgime transitoire.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

1) La Commission Electrotechnique Internationale (CEI) est une organisation mondiale de normalisation


compose de lensemble des comits lectrotechniques nationaux (Comits nationaux de la CEI). La CEI
a pour objet de favoriser la coopration internationale pour toutes les questions de normalisation dans les
domaines de llectricit et de llectronique. A cet effet, la CEI entre autres activits publie des Normes
internationales, des Spcifications techniques, des Rapports techniques, des Spcifications accessibles au
public (PAS) et des Guides (ci-aprs dnomms Publication(s) de la CEI). Leur laboration est confie des
comits dtudes, aux travaux desquels tout Comit national intress par le sujet trait peut participer. Les
organisations internationales, gouvernementales et non gouvernementales, en liaison avec la CEI, participent
galement aux travaux. La CEI collabore troitement avec lOrganisation Internationale de Normalisation (ISO),
selon des conditions fixes par accord entre les deux organisations.

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

74

61869-2 CEI:2012

Le texte de la prsente norme est issu des documents suivants:


FDIS

Rapport de vote

38/435/FDIS

38/437/RVD

Le rapport de vote indiqu dans le tableau ci-dessus donne toute information sur le vote ayant
abouti lapprobation de cette norme.
La prsente publication a t rdige selon les Directives ISO/CEI, Partie 2.
Une liste de toutes les parties de la srie CEI 61869, publies sous le titre gnral
Transformateurs de mesure, peut tre consulte sur le site web de la CEI.
La prsente Partie 2 doit tre utilise conjointement avec la CEI 61869-1:2007, Exigences
gnrales, sur laquelle elle est base. Le lecteur est toutefois encourag utiliser ldition la
plus rcente de la norme.

Lorsquun article/paragraphe particulier de la Partie 1 nest pas mentionn dans cette


Partie 2, cet article/paragraphe sapplique. Lorsque la prsente norme indique un
complment, une modification ou un remplacement, le texte correspondant de la
Partie 1 doit tre adapt en consquence.
Pour les articles, paragraphes, figures, tableaux, annexes ou notes supplmentaires, le
systme de numrotation suivant est utilis:

les articles, paragraphes, tableaux, figures et notes numrots partir de 201 sajoutent
ceux de la Partie 1;

les annexes supplmentaires sont dsignes 2A, 2B, etc.

Une vue globale de l'ensemble planifi de normes la date de publication du prsent


document est indique ci-dessous. La liste jour des normes publies par le TC 38 de la CEI
est disponible sur le site Web: www.iec.ch.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Cette Partie 2 suit la structure de la CEI 61869-1:2007 et complte ou modifie ses articles
correspondants.

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012
NORMES DE FAMILLES DE PRODUITS

61869-1:2007

61869-6
EXIGENCES
GNRALES
ADDITIONNELLE
S POUR LES
TRANSFORMATEURS DE
MESURE
LECTRONIQUE
S ET POUR LES
CAPTEURS BAS
NIVEAUX

NORME DE
PRODUITS

PRODUITS

ANCIENNE
NORME

61869-2

EXIGENCES SUPPLEMENTAIRES
CONCERNANT LES
TRANSFORMATEURS DE COURANT

60044-1
60044-6

61869-3

EXIGENCES SUPPLEMENTAIRES
CONCERNANT LES
TRANSFORMATEURS INDUCTIFS DE
TENSION

60044-2

61869-4

EXIGENCES SUPPLEMENTAIRES
CONCERNANT LES
TRANSFORMATEURS COMBINES

60044-3

61869-5

EXIGENCES SUPPLEMENTAIRES
CONCERNANT LES
TRANSFORMATEURS CONDENSATEURS
DE TENSION

60044-5

61869-7

EXIGENCES SUPPLEMENTAIRES
CONCERNANT LES
TRANSFORMATEURS DE TENSION
ELECTRONIQUES

60044-7

61869-8

EXIGENCES SUPPLEMENTAIRES
CONCERNANT LES
TRANSFORMATEURS DE COURANT
ELECTRONIQUES

60044-8

61869-9

INTERFACE NUMERIQUE POUR LES


TRANSFORMATEURS DE MESURE

61869-10

EXIGENCES SUPPLEMENTAIRES
CONCERNANT LES CAPTEURS DE
COURANT AUTONOMES DE FAIBLE
PUISSANCE

61869-11

EXIGENCES SUPPLEMENTAIRES
CONCERNANT LES CAPTEURS DE
TENSION AUTONOMES DE FAIBLE
PUISSANCE

61869-12

EXIGENCES SUPPLEMENTAIRES
CONCERNANT LES
TRANSFORMATEURS DE MESURE
LECTRONIQUES COMBINS OU LES
CAPTEURS AUTONOMES COMBINS

61869-13

UNIT D'INTERFACE NUMRIQUE


INDEPENDANTE

60044-7

Depuis la publication de la Norme internationale CEI 60044-6 (Prescriptions concernant les


transformateurs de courant pour protection pour la rponse en rgime transitoire) en 1992, le
domaine dapplication de ce type de transformateurs de courant sest dvelopp. De ce fait, le
contexte thorique du dimensionnement selon les exigences lectriques est devenu bien plus
complexe. Pour des raisons de lisibilit de la prsente norme, lexplication du contexte sera
effectue dans le Rapport technique CEI 61869-100 TR, qui est en cours de rdaction.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

EXIGENCES
GENERALES
CONCERNANT
LES
TRANSFORMATEURS DE
MESURE

75

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

76

61869-2 CEI:2012

Le comit a dcid que le contenu de cette publication ne sera pas modifi avant la date de
stabilit indique sur le site web de la CEI sous http://webstore.iec.ch dans les donnes
relatives la publication recherche. A cette date, la publication sera

reconduite,
supprime,
remplace par une dition rvise, ou
amende.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012

77

TRANSFORMATEURS DE MESURE
Partie 2: Exigences supplmentaires concernant
les transformateurs de courant

Domaine dapplication

La prsente Norme internationale sapplique aux transformateurs inductifs de courant


fabriqus rcemment et destins tre utiliss avec des appareils de mesure lectriques
et/ou des dispositifs lectriques de protection prsentant une frquence assigne comprise
entre 15 Hz et 100 Hz.

Rfrences normatives

CEI 61869-1:2007, Transformateurs de mesure Partie 1: Exigences gnrales.

Termes et dfinitions

Pour les besoins du prsent document, les termes et dfinitions fournis dans la
CEI 61869-1:2007 sappliquent conjointement avec les ajouts suivants:
3.1

Dfinitions gnrales

3.1.201
transformateur de courant
transformateur de mesure dans lequel le courant secondaire est, dans les conditions
normales demploi, pratiquement proportionnel au courant primaire et dphas par rapport
celui-ci dun angle voisin de zro, pour un sens appropri des connexions
[SOURCE: CEI 60050-321:1986, 321-02-01]
3.1.202
transformateur de courant pour mesure
transformateur de courant destin transmettre un signal dinformation des appareils
de mesure ou des compteurs
[SOURCE: CEI 60050-321:1986, 321-02-18]
3.1.203
transformateur de courant pour protection
transformateur de courant destin transmettre un signal dinformation des dispositifs
de protection ou de commande
[SOURCE: CEI 60050-321:1986, 321-02-19)
3.1.204
transformateur de courant pour protection de classe P
transformateur de courant pour protection sans limite de flux rmanent, pour lequel est
spcifi un comportement de saturation en cas de court-circuit symtrique

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

LArticle 2 de la CEI 61869-1:2007 sapplique, avec les complments suivants:

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

78

61869-2 CEI:2012

3.1.205
transformateur de courant pour protection de classe PR
transformateur de courant pour protection avec limite de flux rmanent, pour lequel est
spcifi un comportement de saturation en cas de court-circuit symtrique
3.1.206
transformateur de courant pour protection de classe PX
transformateur de courant pour protection faible ractance de fuite sans limite de flux
rmanent, pour lequel la connaissance de la caractristique dexcitation, et de la rsistance
de lenroulement secondaire, de la rsistance de charge secondaire et du rapport des
nombres de spires est suffisante pour valuer ses performances dans le systme de relais de
protection auquel il est connect
3.1.207
transformateur de courant pour protection de classe PXR
transformateur de courant pour protection avec limite de flux rmanent, pour lequel la
connaissance de la caractristique dexcitation, et de la rsistance de lenroulement
secondaire, de la rsistance de charge secondaire et du rapport des nombres de spires est
suffisante pour valuer ses performances dans le systme de relais de protection auquel il est
connect

Note 2 larticle: Les entrefers pour la rduction de la rmanence ne conduisent pas forcment crer un
transformateur de courant forte ractance de fuite (voir Annexe 2C)

3.1.208
transformateur de courant pour protection de classe TPX pour rponse en rgime
transitoire
transformateur de courant pour protection sans limite de flux rmanent, pour lequel le
comportement en cas de saturation au cours dun court-circuit transitoire est spcifi par la
valeur de crte de lerreur instantane
3.1.209
transformateur de courant pour protection de classe TPY pour rponse en rgime
transitoire
transformateur de courant pour protection avec limite de flux rmanent, pour lequel le
comportement en cas de saturation au cours dun court-circuit transitoire est spcifi par la
valeur de crte de lerreur instantane
3.1.210
transformateur de courant pour protection de classe TPZ pour rponse en rgime
transitoire
transformateur de courant pour protection avec une constante de temps secondaire spcife,
pour lequel le comportement en cas de saturation au cours dun court-circuit transitoire est
spcifi par la valeur de crte de la composante alternative de lerreur
3.1.211
transformateur de courant rapport de transformation slectionnable
transformateur de courant qui permet dobtenir plusieurs rapports de transformation en
reconnectant des sections de lenroulement primaire ou au moyen de prises sur lenroulement
secondaire

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Note 1 larticle: On relve de plus en plus de cas o de faibles courants continus traversent constamment les
transformateurs de courant. Pour viter toute saturation, il est recommand dutiliser des transformateurs de
courant entrefers, qui offrent les mmes performances que les transformateurs de courant de classe PX.

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012
3.3

79

Dfinitions relatives aux caractristiques assignes de courant

3.3.201
courant primaire assign
I pr
valeur du courant primaire daprs laquelle sont dtermines les caractristiques de
fonctionnement dun transformateur
[SOURCE: CEI 60050-321:1986, 321-01-11, titre, synonyme et dfinition modifis]
3.3.202
courant secondaire assign
I sr
valeur du courant secondaire daprs laquelle sont dtermines les caractristiques de
fonctionnement dun transformateur
[SOURCE: CEI 60050-321:1986, 321-01-15, titre, synonyme et dfinition modifis]

[SOURCE: CEI 60050-321:1986, 321-02-22]


3.3.204
courant dynamique assign
I dyn
valeur de crte maximale du courant primaire quun transformateur supporte sans subir de
dommages lectriques ni mcaniques du fait des efforts lectromagntiques qui en rsultent,
le secondaire tant mis en court-circuit
[SOURCE: CEI 60050-321:1986, 321-02-24]
3.3.205
courant thermique permanent assign
I cth
valeur du courant qui peut circuler indfiniment dans lenroulement primaire, lenroulement
secondaire tant connect la charge assigne, sans que lchauffement dpasse les limites
spcifies
[SOURCE: CEI 60050-321:1986, 321-02-25]
3.3.206
courant primaire de court-circuit assign
I psc
valeur efficace de la composante alternative dun court-circuit transitoire sur laquelle est
base la performance de prcision assigne dun transformateur de courant
Note 1 l'article: Bien que I th soit li la limite thermique, la valeur I psc est relative la limite de prcision.
Gnralement, I psc est plus petit que I th .

3.3.207
courant dexcitation
Ie
valeur efficace du courant qui traverse lenroulement secondaire dun transformateur de
courant lorsquon applique entre les bornes secondaires une tension sinusodale de
frquence assigne, lenroulement primaire et tous les autres enroulements tant en circuit
ouvert

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

3.3.203
courant de court-circuit thermique assign
I th
valeur maximale du courant primaire quun transformateur supporte sans subir de dommages
pendant une courte dure spcifie, le secondaire tant mis en court-circuit

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

80

61869-2 CEI:2012

[SOURCE: CEI 60050-321:1986, 321-02-32]


3.4

Dfinitions relatives la prcision

3.4.3
erreur de rapport

La dfinition 3.4.3 de la CEI 61869-1:2007 sapplique, avec la note suivante:


Note 201 larticle: Lerreur de rapport de courant, exprime en pourcentage, est donne par la formule:

k r I s I p
Ip

100 %

o
kr
Ip
Is

est le rapport de transformation assign;


est le courant primaire rel;
est le courant secondaire correspondant I p dans les conditions de la mesure.

3.4.4
dphasage

La dfinition 3.4.3 de la CEI 61869-1:2007 sapplique, avec la note suivante:


Note 1 l'article:

Un diagramme vectoriel explicatif est donn dans lAnnexe 2A.1.

3.4.201
charge rsistive assigne
Rb
valeur assigne de la charge rsistive connecte au secondaire, exprime en ohms
3.4.202
rsistance de lenroulement secondaire
R ct
rsistance relle en courant continu de lenroulement secondaire, exprime en ohms,
ramene 75 C ou toute autre temprature qui peut tre spcifie
Note 1 l'article: R ct est une valeur relle. Elle ne doit pas tre confondue avec la limite suprieure de R ct , quil
est possible de spcifier.

3.4.203
erreur compose
c
en rgime permanent, la valeur efficace de la diffrence entre:
a) les valeurs instantanes du courant primaire, et
b) le produit du rapport de transformation assign par les valeurs instantanes du
courant secondaire,
les sens positifs des courants primaire et secondaire correspondant aux conventions admises
pour le marquage des bornes
Note 1 l'article: L'erreur compose c est exprime en gnral en pourcent de la valeur efficace du courant
selon la formule suivante:

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Un diagramme vectoriel explicatif est donn dans lAnnexe 2A.1

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012

81
T

c =

1
( k r i s i p ) 2 dt
T 0
Ip

100 %

o
kr
Ip
ip
is
T

est
est
est
est
est

le
la
la
la
la

rapport de transformation assign;


valeur efficace du courant primaire;
valeur instantane du courant primaire;
valeur instantane du courant secondaire;
valeur de la priode des courants.

Pour plus dinformations, se rfrer lAnnexe 2A.4.

[SOURCE: CEI 60050-321:1986, 321-02-26, note l'article modifi]

[SOURCE: CEI 60050-321:1986, 321-02-27]


3.4.205
facteur de scurit
FS
rapport entre le courant limite primaire assign et le courant primaire assign
Note 1 l'article: Il convient de prter attention au fait que le facteur de scurit rel pour les appareils est
affect par la charge. Lorsque la valeur de la charge est significativement infrieure la valeur assigne, des
valeurs de courant plus leves sont produites ct secondaire en cas de courant de court-circuit.
Note 2 l'article: Dans le cas o des courants de dfaut du systme circulent dans lenroulement primaire dun
transformateur de courant, la scurit des appareils aliments par le transformateur est son maximum lorsque le
facteur de scurit (FS) est son minimum.

[SOURCE: CEI 60050-321:1986, 321-02-28, notes l'article modifis]


3.4.206
force lectromotrice limite secondaire
E FS
produit du facteur de scurit par le courant secondaire assign et par la somme vectorielle
de la charge de prcision et de limpdance de lenroulement secondaire
Note 1 l'article: La force lectromotrice limite secondaire pour les transformateurs de courant pour mesure E FS
se calcule comme suit:

E FS = FS I sr ( Rct + Rb ) 2 + X b2
o:

Rb

est le part rsistive de la charge assigne;

Xb

est le part inductive de la charge assigne.

La mthode de calcul de la force lectromotrice limite secondaire donne une valeur suprieure la valeur relle.
Elle a t choisie en vue dappliquer la mme mthode dessai que pour les transformateurs de courant pour
protection. Se rfrer aux paragraphes 7.2.6.202 et 7.2.6.203.

[SOURCE: CEI 60050-321:1986, 321-02-31, note l'article modifi]

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

3.4.204
courant limite primaire assign
I PL
valeur du courant primaire minimum pour lequel l'erreur compose du transformateur de
courant pour mesures est gale ou suprieure 10%, la charge secondaire tant gale la
charge de prcision

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

82

61869-2 CEI:2012

3.4.207
courant limite de prcision assign
valeur la plus leve du courant primaire pour laquelle le transformateur de courant doit
satisfaire aux prescriptions concernant l'erreur compose
[SOURCE: CEI 60050-321:1986, 321-02-29]
3.4.208
facteur limite de prcision
ALF
rapport entre le courant limite de prcision assign et le courant primaire assign
[SOURCE: CEI 60050-321:1986, 321-02-30]
3.4.209
force lectromotrice limite secondaire pour les transformateurs de courant pour
protection
E ALF
produit du facteur limite de prcision par le courant secondaire assign et par la somme
vectorielle de la charge assigne et de limpdance de lenroulement secondaire

E ALF = ALF I sr ( Rct + Rb ) 2 + X b2


o:

Rb

est le part rsistive de la charge assigne;

Xb

est le part inductive de la charge assigne.

3.4.210
flux de saturation
sat
valeur maximale du flux embrass par l'enroulement secondaire dun transformateur de
courant qui correspond la saturation magntique du matriau du noyau
Note 1 l'article: La procdure la plus approprie pour dterminer le flux de saturation sat est donne par la
mthode de saturation en courant continu dcrite lAnnexe 2B.2.3 .
Note 2 l'article: Dans lancienne norme CEI 60044-6, s tait dfini comme valeur du coude de saturation, qui
caractrisait la transition de ltat non-satur ltat satur du noyau. Cette dfinition na pas t bien accepte
car la valeur de saturation tait trop basse, ce qui entranait des confusions. En consquence, la dfinition est
remplace par sat , qui dfinit la condition de saturation complte.

3.4.211
flux rmanent
r
valeur du flux embrass par lenroulement secondaire qui subsisterait dans le circuit
magntique, 3 min aprs linterruption dun courant dexcitation de grandeur suffisante pour
produire le flux de saturation ( sat )
3.4.212
facteur de rmanence
KR
Rapport du flux rmanent sur le flux de saturation, exprim en pourcentage

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Note 1 l'article: La force lectromotrice limite secondaire E ALF pour les transformateurs de courant pour
protection de classe P et PR se calcule comme suit:

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012

83

3.4.213
constante de temps assigne de la boucle secondaire
Ts
valeur de la constante de temps de la boucle secondaire du transformateur de courant,
dtermine par le rapport de la somme (L s ) des inductances de magntisation et de fuite la
rsistance totale (R s ) de la boucle secondaire
Ts = Ls / Rs
3.4.214
caractristique dexcitation
prsentation, sous forme de graphique ou de tableau, de la relation entre la valeur efficace du
courant dexcitation et la tension sinusodale applique aux bornes secondaires dun
transformateur de courant, le primaire et les autres enroulements tant en circuit ouvert, sur
une plage de valeurs permettant de dfinir la caractristique depuis les bas niveaux
dexcitation jusqu 1,1 fois la force lectromotrice de coude

[SOURCE: CEI 60050-321: 1986, 321-02-34]


3.4.216
force lectromotrice du point de coude
force lectromotrice dun transformateur de courant la frquence assigne, telle que son
augmentation de 10 % entrane une augmentation de 50 % de la valeur efficace du courant
dexcitation
Note 1 l'article: Alors que la tension du point de coude peut tre applique aux bornes secondaires du
transformateur de courant, la force lectromotrice du point de coude nest pas accessible directement. La tension
du point de coude et la force lectromotrice de coude sont considres comme identiques, par le fait que la chute
de tension lie la rsistance de lenroulement secondaire peut tre considre comme ngligeable.

3.4.217
force lectromotrice de coude assigne
Ek
limite infrieure de la force lectromotrice de coude
Note 1 l'article: La force lectromotrice de coude figure sur la spcification des classes de protection PX et
PXR. Elle peut tre calcule comme suit:

E k = K x (Rct + Rb ) I sr
3.4.218
rapport des nombres de spires assign
rapport spcifi entre le nombre de spires de lenroulement primaire et le nombre de spires de
lenroulement secondaire
EXEMPLE 1

1/600 (signification: 1 spire primaire avec 600 spires secondaires)

EXEMPLE 2

2/1200 (signification: 2 spires primaires avec 1 200 spires secondaires)

Note 1 l'article: Le rapport des nombres de spires assign est donn pour un transformateur de courant pour
protection de classe PX ou PXR.
Note 2 l'article: Le rapport des nombres de spires assign et le rapport de transformation assign sont dfinis
comme des entits du primaire au secondaire. Pour les comparer, la valeur du rapport des nombres de spires
assign doit tre inverse.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

3.4.215
tension du point de coude
valeur efficace de la tension sinusodale la frquence assigne qui, applique aux bornes
secondaires du transformateur, tous les autres enroulements tant circuit ouvert, provoque
une augmentation du courant d'excitation de 50% lorsqu'elle augmente de 10%

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

84

61869-2 CEI:2012

3.4.219
erreur sur le rapport des nombres de spires
diffrence entre les valeurs relle et assigne du rapport des nombres de spires exprime en
pourcentage du rapport des nombres de spires assign
3.4.220
facteur de dimensionnement
Kx
facteur indiquant le multiple du courant secondaire assign (I sr ) apparaissant lors de
conditions de dfaut au primaire, compte tenu des marges de scurit, et jusquauquel le
transformateur doit satisfaire aux performances exiges
Note 1 l'article:

Voir la formule sous 3.4.217.

3.4.221
courant derreur instantan
i
diffrence entre les valeurs instantanes du courant secondaire (i s ) multipli par le rapport de
transformation assign (k r ) et du courant primaire (i p ):

Note 1 l'article: Lorsque le courant comporte deux composantes, lune alternative (i sac , i pac ) et lautre
continue (i sdc , i pdc ), ces composantes (i ac , i dc ) sont identifies sparment comme suit:

i = iac + idc = (k r isac - i pac ) + (k r isdc - i pdc )


3.4.222
valeur de crte de lerreur instantane

valeur maximale ( ) du courant derreur instantan (voir 3.4.221) pour le cycle de


fonctionnement spcifi, exprime en pourcentage de la valeur de crte du courant primaire
de court-circuit assign:

i
2 I psc

100 %

3.4.223
valeur de crte de la composante alternative de lerreur

ac

valeur

maximale iac

de

la

composante

alternative

du

courant

derreur

instantan

(voir 3.4.221) exprime en pourcentage de la valeur de crte du courant primaire de courtcircuit assign:

ac =

iac
2 I psc

100 %

3.4.224
cycle de fonctionnement spcifi (C-O et/ou C-O-C-O)
cycle de fonctionnement pendant lequel, pour chaque excitation spcifie, on considre que
le courant de court-circuit primaire rsulte de l'angle dapparition le plus dfavorable (voir
Figure 201)

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

i = k r is - ip

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012

85

ip

ip

t
tal

t
tal

tfr

tal
t
C-O-C-O

C-O

IEC 1547/12

3.4.225
constante de temps du primaire spcifie
TP
valeur spcifie de la constante de temps de la composante continue du courant primaire de
court-circuit sur laquelle est base la rponse du transformateur de courant en rgime
transitoire (voir Figure 202)

ip

Ipsc 2

Ipsc 2
e
0
Tp

IEC 1548/12

Figure 202 Constante de temps du primaire T p

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Figure 201 Cycles de fonctionnement

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

86

61869-2 CEI:2012

3.4.226
dure de premier dfaut
t
dure du dfaut dans un cycle de fonctionnement C-O, ou dure du premier dfaut dans un
cycle de fonctionnement C-O-C-O
Note 1 l'article:

Voir Figure 201.

3.4.227
dure de deuxime dfaut
t
dure du deuxime dfaut dans un cycle de fonctionnement C-O-C-O
Note 1 l'article:

Voir Figure 201.

Note 1 l'article: Voir Figure 201. Cette dure est habituellement dfinie par le temps critique de mesure du
systme de protection associ.

3.4.229
dure spcifie jusqu la limite de prcision dans le deuxime dfaut
t al
dure de la deuxime excitation dun cycle de fonctionnement C-O-C-O pendant laquelle la
prcision spcifie doit tre maintenue
Note 1 l'article: Voir Figure 201. Cette dure est habituellement dfinie par le temps critique de mesure du
systme de protection associ.

3.4.230
temps de rptition de dfaut
t fr
intervalle de temps coul, au cours dun cycle de renclenchement automatique de
disjoncteur, entre la coupure du courant primaire de court-circuit et sa seconde application en
cas dchec de la suppression de dfaut
Note 1 l'article:

Voir Figure 201.

3.4.231
rsistance de la boucle secondaire
Rs
rsistance totale du circuit secondaire

Rs = Rb + Rct
3.4.232
facteur de courant de court-circuit symtrique assign
K ssc
rapport entre le courant primaire de court-circuit assign et le courant primaire assign

K ssc =

I psc
I pr

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

3.4.228
dure spcifie jusqu la limite de prcision dans le premier dfaut
t al
dure dun cycle de fonctionnement C-O, ou de la premire excitation dun cycle de
fonctionnement C-O-C-O, pendant laquelle la prcision spcifie doit tre maintenue

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012

87

3.4.233
facteur de rgime transitoire
K tf
rapport du flux embrass par lenroulement secondaire un temps spcifi dun cycle de
fonctionnement et de la valeur de crte de sa composante alternative
Note 1 l'article: K tf est calcul analytiquement selon diffrentes formules en fonction de T P , de T S , du cycle de
fonctionnement et de l'angle dapparition du courant de court-circuit. Une dtermination de K tf est donne
lAnnexe 2B.1
Note 2 l'article: Figure 203 montre des volutions possibles du flux embrass par lenroulement secondaire pour
des diffrents angles dapparition du courant de court-circuit.
10

= 90
=90

=180
= 180

-2
0

0.01

0.02

0.03

0.04

0.05

0.06

0.07

0.08

0.09

tt0.1
IEC 1549/12

Figure 203 Flux embrass par lenroulement secondaire pour des diffrents angles
dapparition du courant de court-circuit
3.4.234
facteur de dimensionnement pour le rgime transitoire
K td
facteur de dimensionnement permettant de prendre en compte laugmentation du flux
embrass par lenroulement secondaire sous leffet dune composante continue du courant
primaire de court-circuit
Note 1 l'article: Alors que K tf est dfini comme fonction du temps, K td est le paramtre de dimensionnement
final. K td est driv des exigences du transformateur de courant indiques par le constructeur du relais (et bases sur les
essais de type de stabilit du relais) ou des considrations les plus pessimistes, bases sur les courbes de Ktf (voir
Annexe 2B.1).

3.4.235
transformateur de courant faible ractance de fuite
transformateur de courant pour lequel la mesure aux bornes secondaires (le primaire tant en
circuit ouvert) suffit pour dterminer sa conformit aux limites de prcision requises pour la
classe protection

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

=135
= 135

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

88

61869-2 CEI:2012

3.4.236
transformateur de courant forte ractance de fuite
transformateur de courant qui ne rpond pas aux exigences du paragraphe 3.4.235 et pour
lequel le constructeur prvoit une marge supplmentaire afin de tenir compte des effets
dinfluence qui produisent un flux de fuite supplmentaire
3.4.237
force lectromotrice secondaire limite quivalente assigne
E al
valeur efficace de la force lectromotrice quivalente du circuit secondaire la frquence
assigne ncessaire pour satisfaire les exigences du cycle de fonctionnement spcifi:

Eal = K ssc K td ( Rct + Rb ) I sr


3.4.238
valeur de crte du courant secondaire dexcitation E al
al
valeur de crte du courant dexcitation lorsque une tension correspondant Eal est applique
aux bornes secondaire et que lenroulement primaire est ouvert

Note 1 l'article:

3.7

La procdure de mesure est donne lAnnexe 2B.3.3.

Index des abrviations

Le paragraphe 3.7 de la norme CEI 61869-1:2007 est remplac par ce qui suit:
AIS

Appareillage isolation par air

ALF

Facteur limite de prcision

CT

transformateur de courant

CVT

transformateur capacitif de tension

E al

force lectromotrice secondaire limite quivalente assigne

E ALF

force lectromotrice limite secondaire pour les transformateurs de courant pour


protection

E FS

force lectromotrice limite secondaire pour les transformateurs de courant pour


mesure

Ek

force lectromotrice de coude assigne

charge mcanique

Fc

facteur de construction

fR

frquence assigne

F rel

taux de fuite relatif

FS

facteur de scurit pour les appareils

GIS

appareillage isolation gazeuse

al
I cth

valeur de crte du courant secondaire dexcitation Ual


courant thermique permanent assign

I dyn

courant dynamique assign

Ie

courant dexcitation

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

3.4.239
facteur de construction
Fc
facteur reprsentant les diffrences de rsultats de mesure entre la mthode dessai direct et
la mthode dessai indirect, susceptibles dapparatre dans les conditions limites

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012

89

courant limite assign pour les appareils

I pr

courant primaire assign

I psc

courant primaire de court-circuit assign

I sr

courant secondaire assign

IT

transformateur de mesure

I th

courant de court-circuit thermique assign

courant derreur instantan

rapport de transformation rel

kr

rapport de transformation assign

KR

facteur de rmanence

K ssc

facteur de courant de court-circuit symtrique assign

K td

facteur de dimensionnement pour le rgime transitoire

K tf

facteur transitoire

Kx

facteur de dimensionnement

Lm

inductance de magntisation

Rb

charge rsistive assigne

R ct

rsistance de lenroulement secondaire

Rs

rsistance de la boucle secondaire

Sr

puissance de sortie assigne

dure de premier dfaut

dure de deuxime dfaut

t al

dure spcifie jusqu la limite de prcision dans le premier dfaut

t al

dure spcifie jusqu la limite de prcision dans le deuxime dfaut

t fr

temps de rptition de dfaut

Tp

constante de temps du primaire spcifie

Ts

constante de temps de la boucle secondaire

Um

tension la plus leve pour le matriel

Usys

tension la plus leve du rseau

VT

transformateur de tension

dphasage

erreur de rapport

erreur compose

valeur de crte de lerreur instantane

ac

valeur de crte de la composante alternative de lerreur

flux rmanent

sat

flux de saturation

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

I PL

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

90

61869-2 CEI:2012

Caractristiques assignes

5.3
5.3.2

Niveaux disolement assigns


Niveau disolement assign des bornes primaires

LArticle 5.3.2 de la CEI 61869-1:2007 sapplique avec le complment suivant:


Pour un transformateur de courant sans enroulement primaire et sans isolation primaire
propre, la valeur U m = 0,72 kV est considre.
5.3.5

Exigences disolement pour les bornes secondaires

LArticle 5.3.5 de la CEI 61869-1:2007 sapplique avec le complment suivant:


Lisolation de lenroulement secondaire de transformateurs de courant de classe PX ou PXR
ayant une force lectromotrice de coude assigne E k 2 kV doit tre capable de supporter
une tension de tenue assigne frquence industrielle de 5 kV (valeur efficace) pendant
60 s.
Exigences disolement entre spires

La tension de tenue assigne de lisolation entre spires doit tre de 4,5 kV en valeur de crte.
Pour les transformateurs de classe PX ou PXR prsentant une force lectromotrice de coude
assigne suprieure 450 V, la tension de tenue assigne de lisolation entre spires doit tre
une tension de crte gale 10 fois la valeur efficace de la force lectromotrice de coude
spcifie limite 10 kV (valeur crte).
NOTE 1

Il est possible que la forme donde soit fortement dforme par suite de la procdure dessai.

NOTE 2

En accord avec la mthode d'essai 7.3.204, des valeurs de tension plus faibles peuvent apparatre.

5.5
5.5.201

Puissance de sortie assigne


Valeurs de la puissance de sortie assigne

Les valeurs normales de la puissance de sortie assigne pour les classes de mesure
(P et PR) sont les suivantes:
2,5 5,0 10 15 et 30 VA
Des valeurs suprieures 30 VA peuvent tre choisies afin de rpondre aux besoins.
NOTE Pour un transformateur donn, pourvu qu'une des valeurs de puissance de sortie assigne soit normale et
associe une classe de prcision normale, lindication dautres valeurs de puissance de sortie assigne qui
peuvent ne pas tre normales, mais associes dautres classes de prcision normales, nest pas exclue.

5.5.202

Valeurs de charge rsistive assigne

Les valeurs normales de la charge rsistive assigne, exprime en ohms,


transformateurs de courant des classes TPX, TPY et TPZ, sont les suivantes:

des

0,5 1 2 5 Ohm
Les valeurs prfrentielles sont soulignes. Les valeurs sont bases sur un courant
secondaire assign de 1 A. Pour les transformateurs de courant ayant un courant secondaire
assign diffrent de 1 A, les valeurs indiques ci-dessus doivent tre adaptes en raison
inverse du carr du courant.
NOTE Pour un transformateur donn, pourvu quune des valeurs de charge rsistive assigne soit normalise et
associe une classe de prcision normale, lindication dautres valeurs de charge rsistive assigne qui peuvent
ne pas tre normales, mais associes dautres classes de prcision normales, nest pas exclue.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

5.3.201

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012
5.6

91

Classe de prcision assigne

5.6.201

Transformateurs de courant pour mesure

5.6.201.1

Dsignation de la classe de prcision dun transformateur de courant


pour mesure

La classe de prcision des transformateurs de courant pour mesure est dsigne par le plus
haut pourcentage admissible derreur de rapport () au courant primaire assign et la
puissance de sortie assigne.
5.6.201.2

Classes de prcision normales

Les classes de prcision normales des transformateurs de courant pour mesure sont les
suivantes:
0,1 0,2 0,2S 0,5 0,5S 1 3 5
5.6.201.3

Limites de lerreur de rapport () et du dphasage pour les


transformateurs de courant pour mesure

Pour les classes 0,2S et 0,5S, lerreur de rapport et le dphasage, la frquence assigne,
ne doivent pas dpasser les valeurs donnes dans le Tableau 202, pour toute valeur de
charge comprise entre 25 % et 100 % de la puissance de sortie assigne.
Pour les classes 3 et 5, lerreur de rapport, la frquence assigne, ne doit pas dpasser les
valeurs donnes dans le Tableau 203, pour toute valeur de charge comprise entre 50 % et
100 % de la puissance de sortie assigne. Il nest spcifi aucune limite de dphasage pour
les classes 3 et 5.
Pour toutes les classes, la charge doit tre inductive avec un facteur de puissance de 0,8
sauf si elle absorbe une puissance infrieure 5 VA; dans ce cas, son facteur de puissance
sera 1,0.
NOTE En gnral, les limites prescrites de lerreur de rapport et du dphasage sont valables pour toute position
donne dun conducteur externe plac une distance dans lair non infrieure la distance requise pour
lisolement dans lair la tension la plus leve pour le matriel (U m ).

Tableau 201 Limites de lerreur de rapport et du dphasage


des transformateurs de courant pour mesure (classes de 0,1 1)
Classe de
prcision

Erreur de rapport

Dphasage

Minutes ()

Centiradians ()

au courant (% de la valeur
assigne)

au courant (% de la valeur
assigne)

au courant (% de la valeur
assigne)

20

100

120

20

100

120

20

100

120

0,1

0,4

0,2

0,1

0,1

15

0,45

0,24

0,15

0,15

0,2

0,75

0,35

0,2

0,2

30

15

10

10

0,9

0,45

0,3

0,3

0,5

1,5

0,75

0,5

0,5

90

45

30

30

2,7

1,35

0,9

0,9

3,0

1,5

1,0

1,0

180

90

60

60

5,4

2,7

1,8

1,8

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Pour les classes 0,1 0,2 0,5 et 1, lerreur de rapport et le dphasage, la frquence
assigne, ne doivent pas dpasser les valeurs donnes dans le Tableau 201, pour toute
valeur de charge comprise entre 25 % et 100 % de la puissance de sortie assigne.

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

92

61869-2 CEI:2012

Tableau 202 Limites de lerreur de rapport () et du dphasage


des transformateurs de courant pour mesure pour applications particulires
Erreur de rapport

Classe de
prcision

Dphasage

Minutes ()

au courant (% de la valeur
assigne)

Centiradians ()

20

100

120

au courant (% de la valeur
assigne)
1
5
20
100 120

0,2S

0,75

0,35

0,2

0,2

0,2

30

15

10

10

0,5S

1,5

0,75

0,5

0,5

0,5

90

45

30

30

au courant (% de la valeur
assigne)
1

20

100

120

10

0,9

0,45

0,3

0,3

0,3

30

2,7

1,35

0,9

0,9

0,9

Tableau 203 Limites de lerreur de rapport des


transformateurs de courant pour mesure (classes 3 et 5)
Classe

Erreur de rapport
%
au courant (% de la valeur assigne)
120

Gamme de charge tendue

Pour toutes les classes de mesure, il est possible de spcifier une gamme de charge
tendue. Lerreur de rapport et le dphasage ne doivent pas dpasser les limites de la classe
correspondante, dfinies dans le Tableau 201, le Tableau 202 et le Tableau 203 pour la
gamme de charge secondaire comprise entre 1 VA et la charge assigne. Le facteur de
puissance doit tre de 1,0 dans toute la gamme de charge. La charge assigne maximale est
limite 15 VA.
5.6.201.5

Transformateurs gamme tendue

Des transformateurs de courant de classes de prcision 0,1 1 seront considrs comme


possdant une gamme tendue en courant, sils satisfont aux deux conditions suivantes:
a) le courant thermique permanent assign doit tre gal au courant primaire tendu
assign;
b) les limites derreur de rapport et de dphasage prescrites pour 120 % du courant primaire
assign dans le Tableau 201 doivent tre conserves jusquau courant primaire tendu
assign.
Le courant primaire tendu assign doit tre exprim en pourcentage du courant primaire
assign.
5.6.201.6

Facteur de scurit

Un facteur de scurit peut tre spcifi pour les appareils.


Les valeurs normales sont:
5.6.202
5.6.202.1

FS 5 et FS 10

Transformateurs de courant pour protection


Gnralits

Trois mthodes diffrentes sont prvues pour dfinir les transformateurs de courant pour
protection (voir Tableau 204). Chacune des trois dfinitions peut conduire en pratique la
mme ralisation physique.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

5.6.201.4

50
3

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012

93

Tableau 204 Caractristiques des classes de protection


Dsignation

Limite de flux
rmanent

non a

PR

oui

PX

non a,b

PXR

oui

TPX

non a

TPY

oui

TPZ

oui

Explication
Dfinition dun transformateur de courant satisfaisant aux exigences derreur
compose dans des conditions de courant de court-circuit symtrique en
rgime tabli
Dfinition dun transformateur de courant par spcification de ses
caractristiques de magntisation

Dfinition dun transformateur de courant satisfaisant aux exigences d'erreur


en rgime transitoire dans des conditions de courant de court-circuit
asymtrique

Bien quil nexiste aucune limite de flux rmanent, des entrefers sont autoriss, par exemple dans les
transformateurs de courant circuit magntique ouvrant.

Pour distinguer les classes PX et PXR, le critre de flux de rmanence doit tre utilis.

5.6.202.2.1

Transformateur de courant pour protection de classe P


Valeurs normales des facteurs limites de prcision (ALF)

Les valeurs normales des facteurs limites ALF sont les suivantes:
5 10 15 20 30
5.6.202.2.2

Dsignation de la classe de prcision

La classe de prcision est dsigne par la limite suprieure de lerreur compose, exprime
en pourcentage, suivie de la lettre P (pour protection) et de la valeur ALF.
5.6.202.2.3

Classes de prcision normales

Les classes de prcision normales des transformateurs de courant pour protection sont les
suivantes:
5P et 10P
5.6.202.2.4

Limites derreur des transformateurs de courant pour protection


de classe P

A la frquence assigne et la charge assigne tant connecte, lerreur de rapport, le


dphasage et lerreur compose ne doivent pas dpasser les limites donnes dans
le Tableau 205.
La charge assigne doit avoir un facteur de puissance de 0,8 (circuit inductif) sauf si la
charge assigne absorbe une puissance infrieure 5 VA; dans ce cas, on doit utiliser un
facteur de puissance de 1,0.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

5.6.202.2

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

94

61869-2 CEI:2012

Tableau 205 Limites derreur des transformateurs de courant


pour protection des classes P et PR
Classe de
prcision

Erreur de rapport au
courant primaire
assign

Dphasage
au courant primaire assign

Erreur compose au courant


limite de prcision assign
%

Minutes ()

Centiradians ()

5P et 5PR

60

1,8

10P et 10PR

10

5.6.202.3
5.6.202.3.1

Transformateurs de courant pour protection de classe PR


Valeurs normales des facteurs limites de prcision

Les valeurs normales des facteurs limites ALF sont les suivantes:
5 10 15 20 30
5.6.202.3.2

Dsignation de la classe de prcision

5.6.202.3.3

Classes de prcision normales

Les classes de prcision normales des transformateurs de courant de classe PR sont les
suivantes:
5PR et 10PR
5.6.202.3.4

Limites derreur des transformateurs de courant pour protection de


classe PR

A la frquence assigne et la charge assigne tant connecte, lerreur de rapport, le


dphasage et lerreur compose ne doivent pas dpasser les limites donnes dans le
Tableau 205.
La charge assigne doit avoir un facteur de puissance de 0,8 (circuit inductif) sauf si la
charge assigne absorbe une puissance infrieure 5 VA; dans ce cas, on doit utiliser un
facteur de puissance de 1,0.
5.6.202.3.5

Facteur de rmanence (K R )

Le facteur de rmanence (K R ) ne doit pas tre suprieur 10 %.


NOTE Linsertion dun ou de plusieurs entrefers dans le circuit magntique constitue une mthode de limitation du
facteur de rmanence.

5.6.202.3.6

Constante de temps de la boucle secondaire (T s )

Il est permis de spcifier la constante de temps de la boucle secondaire.


5.6.202.3.7

Rsistance de lenroulement secondaire (R ct )

Il est permis de spcifier la limite suprieure de rsistance de lenroulement secondaire.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

La classe de prcision est dsigne par la limite suprieure de lerreur compose, exprime
en pourcentage, suivie des lettres "PR" (pour protection et faible rmanence) et de la valeur
ALF.

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012
5.6.202.4

95

Transformateurs de courant pour protection des classes PX et PXR

Les caractristiques des transformateurs de courant des classes PX et PXR doivent tre
spcifies dans les termes suivants:

courant primaire assign (I pr );

courant secondaire assign (I sr );


rapport des nombres de spires assign;

force lectromotrice de coude assigne (E k );


limite suprieure du courant dexcitation (I e ) la force lectromotrice de coude assigne
et/ou un pourcentage donn de celle-ci;

limite suprieure de la rsistance de lenroulement secondaire (R ct ).

Au lieu de donner explicitement la force lectromotrice de coude assigne, E k peut tre


calcul comme suit:

E k = K x (Rct + Rb ) I sr

Pour la classe PX, lerreur sur le rapport des nombres de spires ne doit pas dpasser la limite
de 0,25 %.
Pour la classe PXR, lerreur sur le rapport des nombres de spires ne doit pas dpasser la
limite de 1 %.
Pour la classe PXR, le facteur de rmanence ne doit pas tre suprieur 10 %.
NOTE 201 Pour garantir un facteur de rmanence <= 10 %, les transformateurs de courant de classe PXR
peuvent comporter des entrefers.
NOTE 202 Pour les circuits magntiques de grande dimension et faible ampre-tour de classe PXR, il peut tre
difficile de satisfaire lexigence du facteur de rmanence. Dans de tels cas, un facteur de rmanence suprieur
10 % peut tre accept.

5.6.202.5

Transformateurs de courant pour protection en rgime transitoire

5.6.202.5.1

Limites derreur pour les transformateurs de courant de


classes TPX, TPY et TPZ

La charge rsistive assigne tant connecte au transformateur de courant et la frquence


assigne, lerreur de rapport et le dphasage ne doivent pas dpasser les limites donnes
dans le Tableau 206.
Lorsque le cycle de fonctionnement spcifi (ou un cycle de fonctionnement qui correspond
au facteur de dimensionnement pour le rgime transitoire K td ) est appliqu au transformateur
de courant branch sur la charge rsistive assigne, les erreurs transitoires (pour classes
TPX et TPY) ou

ac

(pour classe TPZ) ne doivent pas dpasser les limites donnes dans le

Tableau 206.
Toutes les limites derreur sont donnes pour une temprature de lenroulement secondaire
de 75C.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Dans ce cas, la charge rsistive assigne (R b ) et le facteur de dimensionnement (K x ) doivent


tre spcifis, et la choix de la valeur R ct est laisse au constructeur.

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

96

61869-2 CEI:2012

Tableau 206 Limites derreur pour les transformateurs de courant


de classes TPX, TPY et TPZ
Classe

Au courant primaire assign


Dphasage a

Erreur de rapport

Limite derreur transitoire


sous la condition du
cycle de fonctionnement
spcifi

Minutes

Centiradians

TPX

0,5

30

0,9

=10 %

TPY

1,0

60

1,8

=10 % b

TPZ

1,0

18018

5,30,6

ac =10 %

NOTE 1 Dans certains cas, la valeur absolue du dphasage peut prsenter moins dimportance que le fait de
minimiser son cart-type dans une srie de fabrication donne
NOTE 2 Pour les circuits magntiques de classe TPY, il est possible demployer la formule suivante la
condition que la valeur correspondante de E al ne dpasse pas la zone linaire de la courbe de magntisation:

K td
100 %
2f R Ts

TPY:

K R 10 %

TPZ:

K R 10 %

NOTE Pour la classe TPZ, un facteur de rmanence << 10 %, est donn par la construction. Par consquent, le
flux rmanent peut tre nglig.

5.6.202.5.3

Mthodes de spcification

Les deux mthodes de spcification sont illustres dans le Tableau 207.


Dans certains cas, le choix dun cycle de fonctionnement spcifique ne peut pas dcrire
toutes les exigences de protection. En consquence, la spcification alternative donne la
possibilit de spcifier des exigences globales qui couvrent les exigences de diffrents
cycles de fonctionnement. Les deux mthodes de spcifications ne doivent pas tre
combines, sinon le transformateur de courant pourrait tre indtermin.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

TPX:

Limites du facteur de rmanence (K R )


aucune limite

5.6.202.5.2

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012

97

Tableau 207 Mthodes de spcification des transformateurs de courant


de classes TPX, TPY et TPZ

Spcification normale

Spcification alternative

Dsignation de la classe du
transformateur de courant
(TPX, TPY ou TPZ)

Dsignation de la classe du transformateur


de courant (TPX, TPY ou TPZ)

Facteur de courant
de court-circuit symtrique assign K ssc

Facteur de courant
de court-circuit symtrique assign K ssc

Cycle de fonctionnement,
dfini par
t al

Facteur de dimensionnement pour le rgime


transitoire assign K td

pour le cycle C-O-C-O:

t al , t, t fr , t al

Constante de temps assigne de la boucle


secondaire T S
(pour circuits magntiques TPY uniquement)

Constante de temps du
primaire assigne T p
Charge rsistive assigne R b

Charge rsistive assigne R b

NOTE 1 Pour les transformateurs de courant avec prises au secondaire, les exigences de prcision donnes
peuvent tre satisfaites pour un rapport seulement.
NOTE 2 Pour les transformateurs de courant avec couplage primaire, les exigences de prcision peuvent tre
satisfaites pour plusieurs rapports. Dans ce cas, il convient de prter attention au facteur de construction F c , qui
peut tre influenc par la configuration des conducteurs primaires.
NOTE 3 Si la spcification alternative est utilise, K td est normalement donn par le fournisseur du dispositif de
protection. Dans ce cas, T S doit aussi tre spcifie, car cest le seul paramtre du transformateur de courant qui
est utilis pour le calcul de K td .

5.6.203

Spcification de classe pour les transformateurs de courant rapports de


transformation slectionnables

5.6.203.1

Performance de prcision pour transformateurs de courant avec couplage


primaire

Pour toutes les classes de prcision, la performance de prcision doit tre respecte pour
tous les couplages spcifis.
5.6.203.2

Performance de prcision pour transformateurs de courant avec prises au


secondaire

Pour toutes les classes de prcision, la performance de prcision doit tre respecte au
rapport le plus lev, sauf indication contraire.
Lorsque lacheteur en fait la demande, le constructeur doit donner des informations sur la
performance de prcision aux rapports infrieurs.
5.201

Valeurs normales du courant primaire assign

Les valeurs normales du courant primaire assign sont les suivantes:

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

pour le cycle C-O:

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

98

61869-2 CEI:2012

10 12,5 15 20 25 30 40 50 60 75 A
et leurs multiples ou sous-multiples dcimaux.
Les valeurs prfrentielles sont soulignes.
5.202

Valeurs normales du courant secondaire assign

Les valeurs normales du courant secondaire assign sont de 1 A et 5 A.


Pour les transformateurs de courant pour protection pour rponse en rgime transitoire,
la valeur normale du courant secondaire assign est de 1 A.
5.203

Valeurs normales du courant thermique permanent assign

La valeur normale du courant thermique permanent assign est le courant primaire assign.

5.204

Courants de court-circuit assigns


Courant de court-circuit thermique assign (I th )

5.204.1

Un courant de court-circuit thermique assign (I th ) doit tre assign au transformateur


(voir 3.3.203).
La valeur normale de la dure du courant de court-circuit thermique assign est de 1 s.
Courant dynamique assign (I dyn )

5.204.2

La valeur normale du courant dynamique assign (I dyn ) est de 2,5 fois le courant de courtcircuit thermique assign (I th ).

Conception et construction

6.4

Exigences relatives lchauffement des parties et des composants

6.4.1

Gnralits

Le prsent article de la CEI 61869-1:2007 sapplique avec le complment suivant:


Lchauffement dun transformateur de courant parcouru par un courant primaire gal au
courant thermique permanent assign, avec une charge de facteur de puissance unit
correspondant la puissance de sortie assigne, ne doit pas dpasser la valeur approprie,
donne dans le Tableau 5 de la CEI 61869-1:2007. Ces valeurs sont bases sur les
conditions de service de lArticle 4.
6.13

Marquage

6.13.201
6.13.201.1

Marquage des bornes


Rgles gnrales

Le marquage des bornes doit identifier:


a) les enroulements primaires et secondaires;

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Lorsquun courant thermique permanent assign suprieur au courant primaire assign est
spcifi, les valeurs prfrentielles sont de 120 %, 150 % et 200 % du courant primaire
assign.

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012

99

b) les sections de chaque enroulement, lorsquil est divis en sections;


c) les polarits relatives des enroulements et des sections denroulements;
d) les prises intermdiaires, le cas chant.
6.13.201.2

Mode de marquage

Le marquage doit tre constitu de lettres suivies ou prcdes si ncessaire de chiffres. Les
lettres doivent tre en majuscules dimprimerie.
6.13.201.3

Marquage employer

Le marquage des bornes dun transformateur de courant doit tre tel quindiqu dans le
Tableau 208:
Tableau 208 Marquage des bornes

P2

P1

P1

P2

Bornes secondaires
S1

S2

S1

Transformateur simple rapport

C1

Bornes primaires

C2

P1

S3

Transformateur prise intermdiaire sur


lenroulement secondaire

P1

P2

P2

Bornes secondaires
S1

S2

Transformateur enroulement primaire


2 sections, pour couplage en srie ou
parallle

6.13.201.4

S2

1S1

1S2

2S1

2S2

1
S1

1
S2

2
S1

S2

Transformateurs 2 enroulements
secondaires; chacun ayant son circuit
magntique propre (deux variantes pour
le marquage des bornes secondaires)

Indication des polarits relatives

Les bornes marques P1, S1 et C1 doivent avoir, tout instant, la mme polarit.
6.13.202
6.13.202.1

Marquage des plaques signaltiques


Gnralits

En plus des marquages dfinis dans lArticle 6.13 de la CEI 61869-1:2007, tous les
transformateurs de courant doivent porter le marquage de plaques signaltiques gnral
dfini dans le prsent article. Le marquage relatif aux classes de prcisions particulires est
donn dans les Paragraphes 6.13.202.2 6.13.202.6.
a) Le courant primaire et secondaire assigns (par exemple: 100/1 A);

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Bornes primaires

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

100

61869-2 CEI:2012

b) le courant de court-circuit thermique assign (I th ), (par exemple: Ith = 40 kA);


c) le courant dynamique assign (I dyn ), sil diffre de 2,5 x I th (par exemple: Idyn = 85 kA);
d) pour les transformateurs deux enroulements secondaires ou plus, lutilisation de chacun
de ces enroulements et des bornes correspondantes;
e) le courant thermique permanent assign, sil diffre du courant primaire assign.
EXEMPLE 1
Pour un transformateur de courant circuit magntique unique avec prises au secondaire: I cth = 150 %
(signifie 150 % du courant primaire assign pour chaque prise)
EXEMPLE 2
Pour un transformateur de courant comportant plusieurs circuits
magntiques de rapports diffrents (par exemple, 300/5 A et 4000/1 A): Icth = 450 A
(signifie 450 A comme courant thermique permanent maximal pour tous les circuits magntiques du
transformateur de courant)
EXEMPLE 3
Pour un transformateur de courant avec couplage primaire (4x300/1 A): Icth = 4x450 A
(signifie courant thermique permanent de 450, 900 ou 1 800 A, en fonction de la couplage primaire)

Un transformateur de courant satisfaisant plusieurs combinaisons de charges et de classes


de prcision peut tre marqu suivant chacune d'elles.
5 VA cl. 0,5;

10 VA cl. 5P20

EXEMPLE 5

15 VA cl. 1;

7 VA cl. 0,5

EXEMPLE 6

5 VA cl.1 & 5P20

6.13.202.2

Marquage spcifique de la plaque signaltique dun transformateur de


courant pour mesure

La classe de prcision et le facteur de scurit (le cas chant) doivent tre mentionns
aprs lindication de la puissance de sortie assigne correspondante.
EXEMPLE 1

15 VA cl. 0,5

EXEMPLE 2

15 VA cl. 0,5 FS 10

Pour les transformateurs de courant gamme tendue (voir 5.6.201.5), cette indication doit
figurer immdiatement aprs la classe de prcision.
EXEMPLE 3

15 VA cl. 0,5 ext.150 % FS 10

Pour les transformateurs de courant gamme de charge tendue (voir 5.6.201.4), cette
indication doit figurer immdiatement avant lindication de la classe.
EXEMPLE 4

1-10 VA classe 0,2 (gamme de charge de 1 10 VA de la classe 0,2)

NOTE La plaque signaltique peut contenir des indications concernant diverses combinaisons de rapport de
transformation, de puissance de sortie et de classe de prcision auxquelles le transformateur peut satisfaire pour
le mme rapport de transformation. Dans ce cas, des valeurs de puissance de sortie non normales peuvent tre
utilises.
EXEMPLE

6.13.202.3

5 VA classe 1;

7 VA classe 0,5

Marquage spcifique de la plaque signaltique dun transformateur de


courant pour protection de classe P

Le facteur limite de prcision assign doit tre indiqu aprs la puissance de sortie assigne
et la classe de prcision correspondantes.
EXEMPLE

30 VA classe 5P10

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

EXEMPLE 4

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012
6.13.202.4

101

Marquage spcifique de la plaque signaltique des transformateurs de


courant pour protection de classe PR

Le facteur limite de prcision assign doit tre indiqu aprs la puissance de sortie assigne
et la classe de prcision correspondantes.
EXEMPLE 1

10 VA classe 5PR10

Si spcifis, les valeurs suivantes doivent tre indiques:

la constante de temps de la boucle secondaire (T s );


la limite suprieure de la rsistance de lenroulement secondaire (R ct ).

EXEMPLE 2

6.13.202.5

10 VA classe 5PR10, Ts = 200 ms,

Rct <= 2,4

Marquage spcifique de la plaque signaltique des transformateurs de


courant pour protection de classes PX et PXR

Les exigences de classe peuvent tre indiques comme suit:


le rapport des nombres de spires assign;

la force lectromotrice de coude assigne (E k );


la limite suprieure du courant dexcitation (I e ) la force lectromotrice de coude
assigne et/ou au pourcentage donn de celle-ci;

la limite suprieure de la rsistance de lenroulement secondaire (R ct ).

EXEMPLE 1

classe PX, Ek = 200 V, Ie <= 0,2A,

Rct <= 2,0

Si spcifis, les paramtres suivants doivent galement tre indiqus:

le facteur de dimensionnement (K x );
la charge rsistive assigne (R b ).

EXEMPLE 2

6.13.202.6

Ek = 200 V, Ie <= 0,2 A,

Rct <= 2,0 , Kx = 40,

Rb = 3,0

Marquage spcifique de la plaque signaltique des transformateurs de


courant pour protection en rgime transitoire

Le marquage de la classe est constitu des deux lments suivants:


a) La partie dfinition (obligatoire)
contient les informations essentielles ncessaires pour dterminer si le transformateur de
courant satisfait aux exigences donnes (constitues du cycle de fonctionnement et
de T p ).
EXEMPLE 1

Application avec K ssc = 20 et K td = 12,5:

Rb = 5,

classe TPX 20x12,5,

Rct <= 2,8

Rb = 5,

classe TPY 20x12,5,

Rct <= 2,8,

Rb = 5,

classe TPZ 20x12,5,

Rct <= 2,8

NOTE

Ts = 900 ms

Pour R ct , la valeur maximale du lot de fabrication peut tre indique.

b) Partie complmentaire (obligatoire seulement si un cycle de fonctionnement est spcifi


par lacheteur): La partie complmentaire reprsente un des nombreux cycles de
fonctionnement possibles, conduisant la mme valeur de K td spcifi dans larticle a).
EXEMPLE 2
Cycle 100 ms,

Tp = 100 ms

Cycle (40-100)-300-40 ms, Tp = 100 ms

signifie t al =100 ms, T p =100 ms


signifie t al =40 ms, t=100 ms, t fr =300 ms, t al =40 ms, T p =100 ms

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

102
Cycle (100-100)-300-40 ms,

Tp = 75 ms

61869-2 CEI:2012

signifie t = t al =100 ms, t fr =300 ms, t al =40 ms, T p = 75 ms

Essais

7.1

Gnralits

7.1.2

Liste des essais

Le Tableau 10 de CEI 61869-1:2007 est remplac par le nouveau Tableau 10.


Tableau 10 Liste des essais
Essais
Essais de type
Essai dchauffement
Essai de tenue la tension de choc sur les bornes primaires
Essai sous pluie pour les transformateurs de type extrieur
Essais de compatibilit lectromagntique
Essais concernant la prcision

Paragraphe
7.2
7.2.2
7.2.3
7.2.4
7.2.5
7.2.6
7.2.7

Essai dtanchit de lenveloppe temprature ambiante


Essai de pression sur lenveloppe
Essais de tenue aux courants de courte dure
Essais individuels de srie

7.2.8
7.2.9
7.2.201
7.3

Essais de tenue la tension frquence industrielle sur les bornes primaires


Mesure des dcharges partielles
Essais de tenue la tension frquence industrielle entre les sections
Essais de tenue la tension frquence industrielle sur les bornes secondaires
Essais concernant la prcision
Vrification des marquages
Essai dtanchit de lenveloppe temprature ambiante
Essai de pression sur lenveloppe
Dtermination de la rsistance de lenroulement secondaire
Dtermination de la constante de temps de la boucle secondaire
Essai pour la force lectromotrice de coude assigne et courant dexcitation E k
Essai de surtension entre spires
Essais spciaux

7.3.1
7.3.2
7.3.3
7.3.4
7.3.5
7.3.6
7.3.7
7.3.8
7.3.201
7.3.202
7.3.203
7.3.204
7.4

Essai de tenue la tension de choc coupe sur les bornes primaires


Essai de chocs coups multiples sur les bornes primaires
Mesure de la capacit et du facteur de dissipation dilectrique
Essai de surtension transmise
Essais mcaniques
Essai de dfaut darc interne
Essai dtanchit de lenveloppe basse et haute temprature
Essai de point de rose du gaz
Essai de corrosion
Essai relatif au danger dincendie
Essais sur prlvements

7.4.1
7.4.2
7.4.3
7.4.4
7.4.5
7.4.6
7.4.7
7.4.8
7.4.9
7.4.10
7.5

Dtermination du facteur de rmanence


Dtermination du facteur de scurit (FS) pour les appareils des transformateurs de courant
pour mesure

7.5
7.5.2

Le Tableau 11 de la CEI 61869-1:2007 sapplique, en y ajoutant la note suivante:


Pour les transformateurs de courant GIS, les essais de prcision peuvent tre raliss sans
isolant gazeux.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Vrification du degr de protection fourni par les enveloppes

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012
7.2

103

Essais de type

7.2.2

Essai dchauffement

Le paragraphe 7.2.2 de la CEI 61869-1:2007 sapplique avec les complments suivants:


7.2.2.201

Montage dessai

Le transformateur de courant doit tre mont dune manire reprsentative du montage en


service et les enroulements secondaires doivent tre raccords des charges selon 6.4.1.
Toutefois, puisque la position du transformateur de courant dans chaque poste peut tre
diffrente, le choix de lagencement du montage dessai est laiss lapprciation du
constructeur.
Pour les transformateurs de courant destins des postes triphass sous enveloppe
mtallique isolation gazeuse, les trois phases doivent tre soumises lessai en mme
temps.
7.2.2.202

Mesure de la temprature ambiante

Pour minimiser les effets de la variation de la temprature de lair de refroidissement, en


particulier pendant la dernire priode dessai, il convient dutiliser des moyens appropris
pour les capteurs de temprature, tels que des dissipateurs de chaleur ayant une constante
de temps approximativement gale celle du transformateur.
La moyenne des relevs des deux capteurs doivent tre utiliss pour lessai.
7.2.2.203

Dure de lessai

Il est possible de mettre fin lessai lorsque les deux conditions suivantes sont satisfaites:
la dure de lessai est au moins gale trois fois la constante de temps thermique du
transformateur de courant;

la variation dchauffement des enroulements (et de lhuile en tte des transformateurs


immergs dans lhuile) ne doit pas dpasser 1 K par heure, pendant trois relevs
dchauffement conscutifs.

Le constructeur doit estimer la constante de temps thermique par lune des mthodes
suivantes:
avant lessai, en se basant sur les rsultats dessais prcdents, raliss sur un dispositif
similaire. La constante de temps thermique doit tre confirms pendant lessai
dchauffement;
pendant lessai, daprs la ou les courbes dchauffement ou la ou les courbes de
diminution de temprature enregistres au cours de lessai et calcules selon lAnnexe 2D;
pendant lessai, en tant que point dintersection entre la tangente la courbe
dchauffement partant de 0 et lchauffement maximal estim;
pendant lessai, 63 % de lchauffement maximal estim.
7.2.2.204

Tempratures et chauffements

Lobjectif de lessai est de dterminer lchauffement moyen des enroulements et, pour les
transformateurs immergs dans lhuile, lchauffement de lhuile en tte, en rgime tabli,

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Les capteurs destins mesurer la temprature ambiante doivent tre rpartis autour du
transformateur de courant, une distance approprie eu gard aux caractristiques
assignes du transformateur et environ mi-hauteur de ce dernier. Ils doivent tre protgs
du rayonnement thermique direct.

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

104

61869-2 CEI:2012

lorsque les pertes rsultant des conditions de service spcifies sont gnres dans le
transformateur de courant.
La temprature moyenne des enroulements doit tre dtermine si possible par la mthode
de variation de rsistance; pour les enroulements de trs faible rsistance, il est toutefois
permis dutiliser un thermomtre, un thermocouple ou dautres capteurs de temprature.
Des thermomtres ou thermocouples doivent mesurer lchauffement des parties autres que
les enroulements. La temprature de lhuile en tte doit tre mesure au moyen de capteurs
placs sur le haut de la tte mtallique, qui est en contact direct avec lhuile.
Lchauffement doit tre dtermin en tant que diffrence par rapport la temprature
ambiante, mesure comme indiqu au paragraphe 7.2.2.202.
7.2.2.205

Modalits dessai pour les transformateurs de courant avec U m < 550 kV

Lessai doit tre effectu en appliquant lenroulement primaire le courant thermique


permanent assign.

7.2.2.206

Modalits dessai pour les transformateurs de courant immergs dans


lhuile avec U m 550 kV

Lessai doit tre effectu en appliquant simultanment au transformateur de courant:

le courant thermique permanent assign lenroulement primaire;


Le courant dessai peut galement tre appliqu par excitation de un ou plusieurs
enroulements secondaires si les tensions aux bornes secondaires des noyaux aliments
sont aussi grandes que les tensions apparaissant lorsqu'ils sont branchs sur la charge
assigne, lenroulement primaire tant mis en court-circuit et le ou les enroulements
secondaires non aliments tant connects leurs charges assignes.

la tension la plus leve du matriel divise par 3 entre lenroulement primaire et la


terre. Une borne de chaque enroulement secondaire doit tre connecte la terre.

7.2.3
7.2.3.1

Essai de tenue la tension de choc sur les bornes primaires


Gnralits

Le paragraphe 7.2.3.1 de la CEI 61869-1:2007 sapplique avec les complments suivants:


La tension dessai doit tre applique entre les bornes de lenroulement primaire, mises en
court-circuit, et la terre. Le chssis, la cuve (le cas chant), le circuit magntique (sil est
prvu de le mettre la terre) et toutes les bornes du ou des enroulements secondaires
doivent tre relis la terre.
Pour les transformateurs de courant triphas destins des sous-stations isolation
gazeuse, chaque phase doit tre soumise lessai individuellement. Lors de lessai de
chaque phase, les autres phases doivent tre relies la terre.
Pour les critres dacceptation des transformateurs sous enveloppe mtallique isolation
gazeuse, se rfrer lArticle 6.2.4 de la CEI 62271-203:2011.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

NOTE Sous rserve daccord entre le constructeur et lacheteur, le courant dessai peut galement tre appliqu
en alimentant un ou plusieurs enroulements secondaires, si les tensions aux bornes secondaires des noyaux
aliments sont aussi grandes que les tensions apparaissant lorsqu'ils sont branchs sur la charge assigne,
lenroulement primaire tant mis en court-circuit et le ou les enroulements secondaires non aliments tant
connects leurs charges assignes.

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012
7.2.6
7.2.6.201

105

Essais concernant la prcision


Essai derreur de rapport et de dphasage des transformateurs de courant
pour mesure

Pour prouver la conformit avec les paragraphes 5.6.201.3, 5.6.201.4 et 5.6.201.5, des
mesures de la prcision doivent tre effectues chaque valeur de courant donne
respectivement dans le Tableau 201, le Tableau 202 et le Tableau 203, la valeur la plus
leve et la valeur la plus basse de la gamme de charge spcifie.
Les transformateurs de courant gamme de courant tendue doivent tre soumis lessai
avec le courant primaire tendu assign au lieu de 120 % du courant assign.
7.2.6.202

Dtermination du facteur de scurit (FS) pour les transformateurs de


courant pour mesure

Il est permis deffectuer un essai en utilisant la mthode dessai indirect suivante:

La valeur efficace de la tension obtenue aux bornes doit tre infrieure la force
lectromotrice limite secondaire E FS (voir 3.4.206).
La tension dexcitation doit tre mesure avec un appareil qui donne une rponse
proportionnelle la valeur moyenne du signal redress, mais est gradu en valeur efficace.
Le courant dexcitation doit tre mesur laide dun appareil de mesure de valeur efficace
ayant un facteur de crte de 3.
Sil convient de mettre en doute le rsultat de la mesure, une mesure plus approfondie doit
tre effectue par le biais dun essai direct (voir Annexes 2A.5 et 2A.6) pour vrifier le
rsultat. Le rsultat de lessai direct devient alors la rfrence.
NOTE Lessai indirect prsente le grand avantage de ne ncessiter ni courants levs (par exemple, 30 000 A
pour un courant primaire assign de 3 000 A et un facteur de scurit pour les appareils de 10), ni charges
conues pour supporter un courant de 50 A. Lors de lessai indirect, leffet d aux conducteurs primaires de retour
nintervient pas physiquement. En service, cet effet peut seulement majorer lerreur compose, ce qui est
souhaitable pour la scurit de lappareil aliment par le transformateur de courant pour mesure.

7.2.6.203

Essai derreur compose des transformateurs de courant pour protection


de classes P et PR

Les deux procdures dessai suivantes sont donnes:


a) La conformit avec les limites de lerreur compose indiques dans le Tableau 205 doit
tre prouve par un essai direct pendant lequel on fait passer dans lenroulement primaire
un courant pratiquement sinusodal, gal au courant limite de prcision assign, le
secondaire tant connect une charge de valeur gale la charge assigne. Le facteur
de puissance de la charge dessai doit tre choisi par le constructeur entre 0,8 (circuit
inductif) et 1,0, quelle que soit la charge assigne (voir Annexes 2A.4, 2A.5, 2A.6
et 2A.7).
Il est permis deffectuer lessai sur un transformateur similaire au transformateur fourni,
lisolation pouvant tre rduite, pourvu que la disposition gomtrique soit la mme dans
les deux cas.
Dans le cas de courants primaires trs levs et de transformateurs de courant barre
primaire, il convient de tenir compte de la distance entre le conducteur de retour du
primaire et le transformateur de courant afin de reproduire autant que possible les
conditions de service.
b) Pour les transformateur de courant faible ractance de fuite selon lAnnexe 2C, il est
permis de remplacer lessai direct par lessai indirect suivant:

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Lenroulement primaire tant en circuit ouvert, lenroulement secondaire est excit la


frquence assigne par une tension pratiquement sinusodale. La tension doit tre augmente
jusqu ce que le courant dexcitation I e atteigne Isr FS 10 % .

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

106

61869-2 CEI:2012

Lenroulement primaire tant en circuit ouvert, lenroulement secondaire est excit la


frquence assigne par une tension pratiquement sinusodale de valeur efficace gale la
force lectromotrice limite secondaire E ALF .
Le courant dexcitation ainsi obtenu, exprim en pourcentage de
dpasser la limite de lerreur compose indique au Tableau 205.

I sr ALF ne doit pas

La tension dexcitation doit tre mesure avec un appareil qui donne une rponse
proportionnelle la valeur moyenne du signal redress, mais est gradu en valeur
efficace. Le courant dexcitation doit tre mesur laide dun appareil de mesure de
valeur efficace ayant un facteur de crte de 3.
Lors de la dtermination de lerreur compose par la mthode indirecte, il nest pas
ncessaire de tenir compte dune ventuelle correction du rapport des nombres de spires.
7.2.6.204

Dtermination de lerreur aux conditions limites des transformateurs de


courant pour protection de classes TPX, TPY et TPZ

Lobjectif de cet essai de type est de prouver la conformit avec les exigences aux conditions
limites. Pour les mthodes dessai, se rfrer lAnnexe 2B.

Lessai peut tre effectu sur un modle en grandeur relle de la partie active du
transformateur de courant, avec toutes les enveloppes mtalliques, mais sans isolation.
7.2.6.205

Essai des transformateurs de courant du type faible ractance de fuite


pour classes de protection PX et PXR

La preuve qu'il s'agit d'un transformateur de courant faible ractance de fuite doit tre
tablie selon l'Annexe 2C.
7.2.6.206

Dtermination du facteur de rmanence des transformateurs de courant


pour classes de protection PR, TPY et PXR

Le facteur de rmanence ( K R ) doit tre dtermin pour les transformateurs de courant des
classes suivantes, afin de prouver leur conformit avec les articles correspondants:
Classe PR:

Article 5.6.202.3.5,

Classe PXR: Article 5.6.202.5.2,


Classe TPY:

Article 5.6.202.4.

Pour les mthodes dessai, se rfrer lAnnexe 2B.2.


7.2.201

Essais de tenue aux courants de courte dure

Pour vrifier la conformit avec les exigences de courant de court-circuit thermique assign et
de courant dynamique assign donnes au paragraphe 5.204, les deux essais suivants sont
spcifis.
Lessai thermique doit tre ralis avec le ou les enroulements secondaires mis en
court-circuit, un courant I et pendant un temps t tels que

I ' 2 t ' I th2 t


o

t est est la valeur de la dure du courant de court-circuit thermique.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Si le transformateur de courant est du type faible ractance de fuite selon lAnnexe 2C, un
essai indirect peut tre effectu selon 2B.2, sinon un essai direct doit tre effectu selon
2B.3.

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012

107

La valeur de t soit comprise entre 0,5 s et 5 s.


Lessai dynamique doit tre effectu aussi avec le ou les enroulements secondaires mis
en court-circuit et avec un courant primaire dont la valeur de crte est suprieure ou
gale au courant dynamique assign (I dyn ), pendant au moins une crte.
Il est permis de combiner lessai dynamique avec lessai thermique ci-dessus, condition que
le premier courant de crte principal soit suprieur ou gal au courant dynamique
assign (I dyn ).
On doit considrer que le transformateur a russi ces essais si, une fois revenu temprature
ambiante (entre 10 C et 40 C), il satisfait aux exigences suivantes:
a) il nest pas endommag de manire apparente;
b) ses erreurs aprs dmagntisation ne diffrent pas de celles releves avant les essais de
plus de la moiti des limites derreur correspondant sa classe de prcision;
c) il supporte les essais dilectriques spcifis aux paragraphes 7.3.1, 7.3.2, 7.3.3 et 7.3.4,
mais avec des tensions ou des courants dessai rduits 90 % de ceux qui sont indiqus;

Lexamen d) nest pas requis si la densit du courant dans lenroulement primaire,


correspondant au courant de court-circuit thermique assign (I th ), ne dpasse pas:
180 A/mm 2 , lorsque lenroulement est en cuivre de conductivit suprieure ou gale
97 % de la valeur indique dans la CEI 60028;
120 A/mm 2 , lorsque lenroulement est en aluminium de conductivit suprieure ou gale
97 % de la valeur indique dans la CEI 60121.
NOTE Lexprience montre quen service, les exigences concernant le courant thermique sont gnralement
satisfaites pour une isolation de classe A, condition que la densit du courant dans lenroulement primaire,
correspondant au courant de court-circuit thermique assign, ne dpasse pas les valeurs susmentionnes.

7.3

Essais individuels de srie

7.3.1

Essais de tenue la tension frquence industrielle sur les bornes


primaires

Le prsent article de la CEI 61689-1 sapplique avec les complments suivants:


La tension dessai doit tre applique entre lenroulement primaire mis en court-circuit et la
terre. Le ou les enroulements secondaires mis en court-circuit, le chssis, la cuve (le cas
chant) et le circuit magntique (sil y a une borne spciale de mise la terre) doivent tre
relis la terre.
7.3.5
7.3.5.201

Essais concernant la prcision


Essais derreur de rapport et de dphasage des transformateurs de
courant pour mesure

Lessai individuel de srie visant dterminer la prcision est en principe le mme que lessai
de type dcrit au paragraphe 7.2.6.201; cependant, des essais individuels de srie avec un
nombre rduit de courants et/ou de charges sont autoriss, sous rserve que des essais de
type sur un transformateur analogue aient montr que ce nombre dessais rduit suffit pour
prouver la conformit avec le paragraphe 5.6.201.3.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

d) lexamen de lisolation proximit de la surface du conducteur ne rvle aucune


dtrioration sensible (par exemple, une carbonisation).

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

108
7.3.5.202

61869-2 CEI:2012

Essais derreur de rapport et de dphasage des transformateurs de


courant pour protection de classes P et PR

Des essais doivent tre effectus au courant primaire assign, la charge secondaire tant
gale la charge assigne, afin de prouver la conformit avec les paragraphes 5.6.202.2
et 5.6.202.3, respectivement, en ce qui concerne lerreur de rapport et le dphasage.
7.3.5.203

Essai derreur compose des transformateurs de courant pour protection


de classes P et PR

Pour les transformateur de courant faible ractance de fuite (voir lAnnexe 2C), lessai
individuel de srie est le mme que lessai indirect de type spcifi au point b) du
paragraphe 7.2.6.203.
Pour les autres transformateurs, lessai indirect spcifi au point b) du paragraphe 7.2.6.203
peut tre utilis, mais on doit appliquer au courant dexcitation un facteur de correction. Ce
facteur est obtenu par comparaison entre les rsultats des essais direct et indirect raliss
sur un transformateur de mme type que le transformateur lessai, avec le mme facteur
limite de prcision et les mmes conditions de charge. Dans ces cas, il convient que le
constructeur tienne disposition un certificat dessai.

NOTE 2 Lexpression transformateur du mme type implique que la force magntomotrice (ampres-tours) soit
la mme, indpendamment du rapport de transformation, et que les enroulements secondaires ainsi que les
agencements gomtriques et les matriaux du circuit magntique soient identiques.

7.3.5.204

Essai derreur de rapport et de dphasage des transformateurs de courant


pour protection de classes TPX, TPY et TPZ

Lerreur de rapport et le dphasage doivent tre mesurs au courant assign pour prouver la
conformit avec le paragraphe 5.6.202.5.1.
Les rsultats doivent correspondre une temprature de lenroulement secondaire de 75 C.
La valeur relle de la temprature de lenroulement secondaire doit donc tre mesure et la
diffrence par rapport sa valeur ramene 75 C doit tre dtermine. La mesure de
lerreur doit tre effectue avec la charge R b majore de la diffrence de rsistance
denroulement mentionne ci-dessus.
En variante, pour les circuits magntiques TPY et TPZ, il est permis de dterminer le
dphasage 75 C ( 75 ) par une mesure temprature ambiante ( amb ) et le calcul
suivant:

75 = amb
o

Rct + Rb
Rct amb + Rb

Rct amb est la rsistance de lenroulement temprature ambiante. Lerreur de rapport

nest pas affecte par cette correction de rsistance.


Pour lessai de type et lessai individuel de srie, une mthode dessai directe (utilisant une
source de courant primaire et un transformateur de courant de rfrence) doit tre applique.
Pour les transformateurs de courant faible ractance de fuite, une mthode dessai indirecte
est donne lAnnexe 2E. Il est permis dappliquer cette mthode aux mesures sur site et
la surveillance.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

NOTE 1 Le facteur de correction est gal au rapport entre lerreur compose obtenue par la mthode directe et le
courant dexcitation, exprim en pourcentage de I sr x ALF dtermin par la mthode indirecte.

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012
7.3.5.205

109

Dtermination de lerreur dans les conditions limites des transformateurs


de courant pour protection de classes TPX, TPY et TPZ

Lobjectif de cet essai individuel de srie est de prouver la conformit avec les exigences aux
conditions limites.
Si le transformateur de courant est du type faible ractance de fuite selon lAnnexe 2C, un
essai indirect doit tre effectu selon 2B.2.
Si la conformit avec les exigences de limites de type faible ractance de fuite ne peut tre
tablie, mais si un essai de type du mme type est disposition, un essai indirect doit tre
effectu selon 2B.2. Dans ce cas, on doit prendre en compte le facteur de construction
ventuellement disponible F c sil est suprieur 1,1. Si un tel essai de type nest pas
disponible, un essai de type doit tre effectu avec une pice du lot de fabrication. Le rsultat
de cet essai devient alors la rfrence pour lessai indirect des autres pices.

NOTE 2 Lexpression transformateur du mme type implique que la force magntomotrice (ampres-tours) soit
similaire, indpendamment du rapport de transformation, et que les matriaux et larrangement du noyau et de
lenroulement secondaire sont identiques.

7.3.5.206

Dtermination du rapport du nombre de spires des transformateurs de


courant pour protection de classes PX et PXR

Pour les classes PX et PXR, le rapport du nombre de spires doit tre dtermin
conformment lAnnexe 2F.
Il est permis de remplacer cet essai par une mesure de lerreur de rapport avec une charge
nulle, sous rserve daccord entre le constructeur et lacheteur.
Le rapport du nombre de spires ne doit pas dpasser la limite selon 5.6.202.4.
7.3.201

Dtermination de la rsistance de lenroulement secondaire (R ct )

La rsistance de lenroulement secondaire (R ct ) doit tre mesure sur les transformateurs de


courant des classes suivantes, afin de prouver leur conformit avec les articles
correspondants:
Classe PR:
spcifi)

Articles 5.6.202.3.7 et 6.13.202.4 (si le paramtre est

Classe PX, PXR:

Articles 5.6.202.4 et 6.13.202.5

Classes TPX, TPY, TPZ:

Article 6.13.202.6

La valeur mesure doit tre corrige une temprature de 75C ou la temprature qui est
spcifie.
Pour les classes PR, PX et PXR, la valeur rsultante aprs la correction 75C ne doit pas
dpasser la limite maximale spcifie (si dfinie).
7.3.202

Dtermination de la constante de temps de la boucle secondaire (T s )

La constante de temps de la boucle secondaire (T s ) doit tre dtermine pour les


transformateurs de courant des classes suivantes, afin de prouver leur conformit avec les
articles correspondants:

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

NOTE 1 Pour dterminer le facteur F C , les laboratoires doivent prendre en compte une grande incertitude de
mesure cause de la ncessit dintgrer la force lectromotrice, et cause des paramtres non-linaires aux
conditions limites. De plus, seulement quelques laboratoires peuvent raliser les cycles de fonctionnement
demands. En consquence, les rsultats des essais directs et indirects ne correspondent pas bien, et peut
rsulter en des valeurs de F c non fiables. Cependant, une petite exprience existe dans ce domaine.

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

110

61869-2 CEI:2012

Classes PR:

Article 5.6.202.3.6 (si le paramtre est spcifi)

Classes TPY:

Article 5.6.202.5.3

Sa valeur ne doit pas diffrer de quelconque valeur spcifie de plus de 30 %.


T s sera dtermine selon la lquation suivante (Dtermination de L m : voir 2B.2):

TS =

Lm
( Rct + Rb )

Dans les cas o la charge correspond la puissance de sortie assigne, exprime en VA, R b
est considre comme tant gal la partie rsistive de la charge.
Il est galement permis de dterminer T s selon lquation suivante:

TS =

Si le dphasage est exprim en minutes, on peut appliquer la formule dapproximation


suivante:

TS [s] =

3438
2f R [min]

NOTE 1 La mthode utilisant peut provoquer des difficults pour les transformateurs rapport lev et faible
dphasage en raison de lincertitude de la mesure dun faible dphasage.
NOTE 2 Pour les noyaux de la classe TPZ, il nest pas ncessaire dindiquer T s . Lexigence de prcision
= (180 18) min est vrifie comme essai individuel de srie. La formule susmentionne fournit la valeur de T s .

7.3.203

Essai pour la force lectromotrice de coude assigne (E k ) et le courant


dexcitation E k

La force lectromotrice de coude assigne (E k ) doit tre vrifie et le courant dexcitation I e


doit tre mesur sur les transformateurs de courant des classes suivantes, afin de prouver
leur conformit avec les articles correspondants:
Classe PX, PXR:

Article 5.6.202.4

Une tension dexcitation sinusodale adquate, la frquence assigne, doit tre applique
aux bornes secondaires de lenroulement secondaire complet du transformateur, toutes les
autres bornes tant en circuit ouvert, et le courant dexcitation doit tre mesur.
La tension dexcitation doit tre mesure avec un appareil qui donne une rponse
proportionnelle la valeur moyenne du signal redress, mais est gradu en valeur efficace.
Le courant dexcitation doit tre mesur laide dun appareil de mesure de valeur efficace
ayant un facteur de crte de 3.
La caractristique dexcitation doit tre trace au moins jusqu 1.1 x E k .
La condition du point de coude dfinie en 3.4.215 doit tre satisfaite une tension gale la
force lectromotrice de coude E k .
Le courant dexcitation I e une tension gale E k (ou tout pourcentage donn), ne doit pas
dpasser la valeur spcifie.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

1
2f R tan( )

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012

111

NOTE 1 Pour les transformateurs de courant rapport de transformation slectionnable par des prises sur
lenroulement secondaire, il est permis de calculer la caractristique dexcitation pour les rapports diffrents du
rapport maximal. Pour chaque point de mesure, les quations suivantes peuvent tre appliques:

E 2 = E1

k r2
k r1

I e2 = I e1
o

NOTE 2

k r1
k r2

k r1 , k r2

sont les deux rapports de transformation;

E1, E2

sont les deux forces lectromotrices adquates;

I e1 , I e2

sont les deux courants dexcitation adquates.

Le nombre de points de mesure peut tre convenu entre le constructeur et lacheteur.

NOTE 3 Normalement, la force lectromotrice du point de coude rel est dtermine et doit tre suprieure la
force lectromotrice de coude assigne.

Essai de surtension entre spires

Des essais doivent tre effectus afin de prouver la conformit avec le paragraphe 5.3.201.
Lessai de surtension entre spires doit tre effectu sur lenroulement secondaire complet
selon lune des procdures suivantes. Sauf convention contraire, le choix de la procdure est
laiss au constructeur.
Procdure A: les enroulements secondaires tant en circuit ouvert (ou connects un
dispositif haute impdance qui mesure la tension de crte), un courant pratiquement
sinusodal, de frquence comprise entre 40 Hz et 60 Hz et de valeur efficace gale au
courant primaire assign (ou au courant primaire tendu assign, si spcifi), doit tre
appliqu pendant 60 s lenroulement primaire.
Le courant appliqu doit tre limit si lon obtient la tension dessai donne au paragraphe
5.3.201 avant datteindre le courant primaire assign (ou le courant primaire tendu assign).
Si la tension dessai donne au paragraphe 5.3.201 nest pas atteinte au courant primaire
maximum, la tension obtenue doit tre considre comme la tension dessai.
Procdure B: lenroulement primaire tant en circuit ouvert, la tension dessai donne au
paragraphe 5.3.201 ( une frquence dessai adquate) doit tre applique pendant 60 s aux
bornes de chaque enroulement secondaire.
La valeur efficace du courant secondaire ne doit pas dpasser le courant secondaire assign
(ou la valeur tendue correspondante, si spcifi).
La frquence dessai choisie doit permettre datteindre la tension dessai, mais ne doit pas
dpasser 400 Hz.
Si la tension dessai donne au paragraphe 5.3.201 nest pas atteinte au courant secondaire
maximum et la frquence dessai maximum, la tension obtenue doit tre considre comme
la tension dessai.
Lorsque la frquence dessai dpasse deux fois la frquence assigne, la dure de lessai t
doit tre rduite comme suit:

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

7.3.204

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

112

61869-2 CEI:2012

f
= 120 s R
f
T

o
fR
fT

est la frquence assigne;


est la frquence dessai;

avec un t minimum de 15 s.
NOTE Lessai de surtension entre spires nest pas destin vrifier ladquation dun transformateur de courant
au fonctionnement avec lenroulement secondaire en circuit ouvert. Il convient de ne pas faire fonctionner les
transformateurs de courant avec lenroulement secondaire en circuit ouvert en raison des surtensions et des
chauffements potentiellement dangereux qui peuvent apparatre.

7.4
7.4.3

Essais spciaux
Mesure de la capacit et du facteur de dissipation dilectrique

La tension dessai doit tre applique entre les bornes de lenroulement primaire mis en
court-circuit et la terre. En gnral, les bornes de lenroulement ou des enroulements
secondaires mis en court-circuit, tout cran et la carcasse mtallique isole doivent tre relis
lappareil de mesure. Si le transformateur de courant comporte une borne spciale adapte
cette mesure, les autres bornes basse tension doivent tre mises en court-circuit et
relies, de mme que la carcasse mtallique, la terre ou lcran de lappareil de mesure.
Lessai doit tre effectu avec le transformateur de courant temprature ambiante, et la
valeur de cette temprature doit tre enregistre.
7.4.6

Essai de dfaut darc interne

L'article de la CEI 61869-1:2007 sapplique, en y ajoutant la note suivante:


NOTE Pour les transformateurs de courant immergs dans lhuile avec partie active en tte, la zone dorigine des
dfauts en service se situe souvent dans la partie suprieure de lisolation principale. Pour les transformateurs de
courant de type pingle cheveux immergs dans lhuile, cette zone se situe gnralement dans la partie
infrieure de lisolation principale.

7.5
7.5.1

Essais sur prlvements


Dtermination du facteur de rmanence

Normalement, un essai sur prlvement est rpt pour chaque srie de production, selon
lessai de type 7.2.6.206.
7.5.2

Dtermination du facteur de scurit (FS) pour les transformateurs de


courant pour mesure

Normalement, un essai sur prlvement est rpt pour chaque srie de production, selon
lessai de type 7.2.6.202.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

L'article de la CEI 61869-1:2007 sapplique avec les complments suivants:

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012

113

Annexe 2A
(normative)
Transformateurs de courant pour protection de classes P et PR

2A.1 Diagramme vectoriel


Si lon admet que le transformateur de courant ainsi que sa charge puissent tre assimils
un systme lectromagntique linaire, un courant primaire de forme sinusodale dterminera
des courants, tensions et flux magntique qui seront galement sinusodaux, et le
fonctionnement du transformateur pourra se reprsenter par le diagramme vectoriel de
la Figure 2A.1.
Im
Ia
Is

Ip

Ie
0

IEC 1550/12

Figure 2A.1 Diagramme vectoriel


Dans la Figure 2A.1, I s reprsente le courant secondaire. Il traverse lenroulement et la
charge secondaire et dtermine en grandeur et phase la force lectromotrice E s qui doit tre
induite dans lenroulement secondaire, laquelle son tour dtermine le flux embrass par
l'enroulement secondaire en quadrature sur E s . Le flux est produit par les ampres-tours
rsultant des enroulements primaire et secondaire ou de faon quivalente par le courant
dexcitation secondaire I e , lui-mme somme vectorielle dun courant magntisant I m parallle
et dune composante active I a , (rpondant aux pertes) parallle E s . La somme
vectorielle des courants I s et I e est le vecteur I p qui reprsente le courant primaire multipli
par le rapport denroulement rel (cest--dire par le rapport entre les nombres de spires
primaires et secondaires).
Il en rsulte que pour un transformateur dont le rapport du nombre de spires est inverse au
rapport de transformation assign, la diffrence entre les longueurs des vecteurs I s et I p
rapportes I p fournit lerreur de courant (telle que dfinie en 3.4.3) tandis que lcart
angulaire entre les vecteurs I s et I p est le dphasage (dfini en 3.4.4).

2A.2 Correction de spires


Lorsque linverse du rapport du nombre de spires est diffrent du rapport de transformation
assign (le premier est gnralement plus petit) on dit quil y a une correction de spires. Il
importe alors dtablir une distinction entre I p , le courant primaire multipli par le rapport
denroulement rel et I p , le courant primaire divis par le rapport de transformation assign.
Labsence dune correction de spires signifie que I p = I p . Sil existe une correction de spires,
I p est diffrent de I p et on voit facilement que la correction de spires influe sur lerreur de
courant (et peut tre utilise cet effet), tant donn que I p figure dans le diagramme

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Es

Ie

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

114

61869-2 CEI:2012

vectoriel et I p intervient pour la dtermination de lerreur de courant. Cependant, les vecteurs


I p et I p ayant la mme direction, la correction de spires naffecte pas le dphasage.
Il apparat aussi que linfluence de la correction de spires est plus faible sur lerreur
compose que sur lerreur de rapport ().

2A.3 Triangle derreur


Sur la Figure 2A.2, la partie suprieure de la Figure 2A.1 est redessine plus grande
chelle et avec l'hypothse que l'angle de phase est assez petit pour que l'on puisse
considrer que les deux vecteurs I s et I p sont parallles. Supposant aussi l'absence de
correction de spires, on obtient l'erreur de rapport () avec une bonne approximation en
projetant I e sur I p et en utilisant la composante (I) de I e en phase avec I p au lieu de la
diffrence arithmtique entre I p et I s. De mme, la composante (I q ) de I e en quadrature
peut tre utilise pour exprimer l'erreur de phase.
Im

Ia

Iq
Is

Ip

IEC 1551/12

Figure 2A.2 Triangle derreur


On peut en outre voir quavec les mmes hypothses, le courant dexcitation I e divis par I p
est gal lerreur compose selon le paragraphe 3.4.203.
En dfinitive, pour un transformateur de courant sans correction de spires, pourvu que la
reprsentation vectorielle soit valable, lerreur de rapport (), le dphasage et lerreur
compose peuvent tre reprsents par les trois cts dun triangle rectangle.
Dans ce triangle, lhypotnuse qui reprsente lerreur compose et dpend de limpdance
totale constitue de la charge et de l'enroulement secondaire (somme vectorielle), tandis que
la dcomposition en erreur de rapport () et en dphasage dpend du facteur de puissance de
cette impdance totale et de celui du courant dexcitation. On obtient une erreur de phase
nulle lorsque ces deux facteurs de puissance sont gaux, i.e. quand I s et I e sont en phase.

2A.4 Erreur compose


La considration de lerreur compose est surtout intressante dans le cas o la
reprsentation vectorielle nest pas applicable du fait de la prsence dharmoniques dans le
courant secondaire et dans le courant dexcitation (voir Figure 2A.3).

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Ie

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012

115

Ip
Is
Ie

IEC 1552/12

Figure 2A.3 Forme donde typique


Cest la raison pour laquelle lerreur compose est dfinie au paragraphe 3.4.203 et non, de
manire bien plus simple, par la somme vectorielle de lerreur de rapport () et du dphasage,
comme illustr la Figure 2A.2.

2A.5 Mthode directe de mesure de lerreur compose


La mthode normale est donne par lenregistrement numrique des formes donde des
courants primaire et secondaire, suivi par le calcul de lerreur compose, utilisant la mthode
dintgration numrique selon la dfinition donne en 3.4.203.
Nanmoins, dans cette annexe, les mthodes traditionnelles pour la dtermination de lerreur
compose avec des instruments analogiques sont dcrites.
La Figure 2A.4 reprsente le schma de principe de la mthode de mesure directe pour un
transformateur dont le rapport denroulement est gal lunit. La source est suppose
fournir un courant primaire sinusodal et lenroulement secondaire (reli la charge Z B qui a
des caractristiques linaires) est raccord de telle manire que lampremtre A est travers
par la diffrence des courants primaire et secondaire. La valeur efficace que cet appareil
mesure est donc celle du courant dexcitation, et son rapport (exprim en pour-cent) la
valeur efficace du courant primaire fournit lerreur compose telle que dfinie au
paragraphe 3.4.203, compte tenu des conditions actuelles.

P1

S1

P2

S2

ZB

A
IEC 1553/12

Figure 2A.4 Circuit de base pour transformateur de courant 1:1

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Il en rsulte galement que lerreur compose englobe leffet propre de la prsence


dharmoniques dans le courant secondaire, alors que le courant primaire en est exempt,
prsence dharmoniques qui constitue dj par elle-mme un cart dans le comportement de
lappareil par rapport un transformateur de courant idal (le courant primaire est toujours
suppos sinusodal dans la prsente norme).

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

116

61869-2 CEI:2012

La Figure 2A.4 reprsente donc le schma de principe pour la mesure directe de lerreur
compose.
La Figure 2A.5, reprsente le schma de principe de la mthode de mesure directe tendu au
cas dun transformateur de rapport de transformation diffrent de lunit. Dans ce schma, N
est un transformateur de mme rapport de transformation assign que le transformateur X
essay. Ce transformateur N doit avoir une erreur compose ngligeable dans les conditions
de lessai (sa charge se rduit pratiquement lampremtre A 1 ). Le transformateur X est
raccord sa charge assigne Z B et les enroulements secondaires de N et de X sont
branchs de telle sorte que lampremtre A 2 mesure la diffrence de leurs courants.
P1

S1

P2

P1

S2

S1

P2

S2
ZB

A2
IEC 1554/12

Figure 2A.5 Circuit de base pour transformateur de rapport quelconque


Les deux circuits primaires sont aliments par la mme source de courant sinusodal. Dans
ces conditions, le rapport (exprim en pour-cent) de la valeur efficace du courant mesur par
lampremtre A 2 celle mesure par lampremtre A 1 fournit lerreur compose du
transformateur X.
Il est remarquer que le caractre ngligeable de lerreur compose de N est requis dans
cette mthode. Il nest en effet pas suffisant que cette erreur compose soit connue car du
fait mme de sa complexit (notamment du fait des dformations donde) les corrections
voulues ne pourraient pas tre apportes.

2A.6 Autre mthode de mesure directe de lerreur compose


Dautres mthodes directes de dtermination de lerreur compose peuvent tre utilises pour
mesurer lerreur compose et une mthode est illustre la Figure 2A.6.
N

P1

P2
S2

S1

P1
S1

P2
S2

ZB
P1
S1
A1

A2

S2

ZB
N

P2
IEC 1555/12

Figure 2A.6 Variante de circuit dessai

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

A1

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012

117

La mthode schmatiquement reprsente par la Figure 2A.6 , prsente sur celle illustre par
la Figure 2A.5 lavantage de ne pas exiger lemploi dun transformateur de prcision spcial.
Dans cette mthode en effet, le transformateur N, de mme rapport que X, doit prsenter une
erreur compose ngligeable sous le courant limite de prcision assign du transformateur X
tandis que la mthode reprsente par la Figure 2A.6 ne soumet les transformateurs de
prcision N et N qu des courants de lordre de leurs courants assigns. Il reste bien
entendu essentiel que leurs erreurs composes soient ngligeables dans les conditions de
lessai mais lexigence devient plus facile satisfaire.
Dans la Figure 2A.6, X est le transformateur sous essai. N est un transformateur de prcision
dont le courant primaire assign est choisi voisin du courant limite de prcision assign du
transformateur X (cest--dire de la valeur du courant primaire sous lequel lessai doit tre
entrepris). Lappareil N est un transformateur de prcision dont le courant primaire assign
doit tre de lordre de grandeur du courant secondaire de X correspondant au courant
(primaire) limite de prcision assign. Il ne faut pas perdre de vue que ce transformateur N
fait partie intgrante de la charge Z B du transformateur X et quil faut donc en tenir compte
lors de la dtermination de limpdance Z B . A 1 et A 2 sont deux ampremtres et il y a lieu de
sassurer que A 2 mesure bien la diffrence des courants secondaires des transformateurs N
et N.

k r = k r k rx
Dans ces conditions, le rapport (exprim en pour-cent) des valeurs efficaces des courants
mesurs par les ampremtres A 1 et A 2 fournit lerreur compose du transformateur X.
NOTE Lors de lutilisation des circuits de mesure illustrs par les Figure 2A.5 et Figure 2A.6, il y a lieu de veiller
ce que la puissance absorbe par lampremtre A 2 reste suffisamment faible. La chute de tension sur cet
ampremtre (divise par le rapport de transformation du transformateur N dans le cas de la Figure 2A.6) vient en
effet se composer avec la tension sur la charge Z B et modifie en consquence la charge effective du
transformateur X (elle tend en fait la rduire). Par ailleurs, cette mme chute de tension sur A 2 reprsente un
accroissement de la charge effective du transformateur N.

2A.7 Emploi de lerreur compose


Lerreur compose sera toujours suprieure ou gale la racine carre de la somme des
carrs de lerreur de de rapport () et du dphasage (ce dernier tant exprim en
centiradians).
Il en rsulte que lerreur compose est toujours une limite suprieure aussi bien de lerreur de
rapport () que du dphasage.
Lerreur de rapport () intresse surtout les relais de surcharge; les dphasages intressent
surtout les relais sensibles la phase (exemple: les relais directionnels).
Dans le cas des relais diffrentiels, cest la combinaison des erreurs composes des
transformateurs de courant qui doit tre prise en considration.
Un avantage supplmentaire de la limitation de lerreur compose rside dans la limitation
rsultante de la teneur en harmoniques du courant secondaire, qui est ncessaire pour le bon
fonctionnement de certains types de relais.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Si les rapports de transformation assigns des transformateurs N, N et X sont


respectivement dsigns par k r , k rx et k r , le rapport k r doit tre gal au produit de k r par k rx :

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

118

61869-2 CEI:2012

Annexe 2B
(normative)
Classes de transformateurs de courant pour protection
pour rponse en rgime transitoire

2B.1 Equations thoriques fondamentales relatives au dimensionnement pour


le rgime transitoire
2B.1.1

Court-circuit

Les quations suivantes correspondent au cycle de fonctionnement C-O. Pour les cycles de
fonctionnement C-O-C-O voir 2B.1.3
Lexpression gnrale de la valeur instantane dun courant de court-circuit peut s'crire:

2 I psc e

(2B.1)

o
est le courant alternatif de court-circuit initial la
limite
de
prcision
du
transformateur
de
courant I psc = K ssc I pr ;

I psc

Tp =

Lp

est la constante de temps du primaire;

Rp

= arctan

est l angle d'enclenchement ou dapparition du


dfaut;

Xp
Rp

= arctan Tp

est l angle de phase de limpdance de courtcircuit du systme;

est la pulsation 2f R ;

lorsque la source de tension quivalente dans le court-circuit avec Rp et X p est

u (t ) = U max cos( t + )

(2B.2)

Pour simplifier, langle dapparition du dfaut et langle dimpdance du systme peuvent tre
additionns en un seul angle, ce qui rend le calcul plus facile comprendre du point de vue
mathmatique.

=
i (t ) =
k

t/Tp

cos( ) cos( t + )

2 I psc e

(2B.3)
(2B.4)

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

t/Tp

cos( ) cos( t + )

i (t ) =
k

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012

119

Les angles et dcrivent tous les deux la possibilit de la variation de langle


d'enclenchement. Ils peuvent donc tre galement utiliss lorsquils sont appropris, mais en
fonction de leur dfinition.
La Figure 2B.1 reprsente deux courants de court-circuit primaire types. Le premier apparat
un angle dapparition de dfaut = 90 , ce qui conduit au courant de crte le plus lev et
au flux de crte embrass par lenroulement secondaire le plus lev pour un t al long (voir
Figure 2B.2), tandis que le second apparat = 140 , ce qui conduit une asymtrie
moindre. Cependant, pour un t al court, ce dernier cas conduit un courant et un flux plus
lev que dans le cas du courant de crte le plus grand.
ik(t)
ik( = 140)

ik,dc( = 90)
ik( = 90)

IEC 1556/12

Figure 2B.1 Courants de court-circuit prsentant la crte la plus leve ( = 90) et


prsentant une asymtrie infrieure ( = 140)

== 90
90
==100
100
==110
110
==120
120

max

m ax

==130
130
==140
140
==150
150
==160
160
==170
170

0
-2

0.005

0.01

0.015

0.02

0.025

0.03

0.035

180
0.04 ==180
0.045

tt

IEC 1557/12

Figure 2B.2 La courbe max (t), compose des valeurs de flux les plus leves,
considrant tous les angles d'enclenchement apprciables
Il est possible dutiliser une plage dangle dapparition de dfaut ventuellement rduite pour
dfinir une asymtrie rduite, ce qui peut aboutir un facteur K td rduit dans certains cas
particuliers.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

ik,dc( = 140)

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

120

61869-2 CEI:2012

NOTE La possibilit de limiter l'angle dapparition du courant n'est pas traite dans cette norme, mais sera
discute dans le Rapport Technique IEC 61869-100

Facteur de dimensionnement pour le rgime transitoire K td

2B.1.2

Le facteur de dimensionnement pour le rgime transitoire K td est le paramtre final du


dimensionnement du circuit magntique. Il est mentionn sur la plaque signaltique. Il peut
tre calcul daprs diffrentes fonctions du facteur transitoire K tf , comme indiqu dans les
quations ci-dessous et reprsent la Figure 2B.3.
Dans certains cas, le systme de protection associ peut avoir besoin dune valeur t al qui
nest pas constante et dpend de diffrents paramtres du courant de court-circuit. Aussi le
constructeur du systme de protection peut indiquer le facteur de dimensionnement pour le
rgime transitoire K td , en raison dessais de stabilit au systme de protection.
Le facteur transitoire K tf donn dans cette partie est dtermin laide de lquation
diffrentielle du circuit quivalent, avec une inductance constante du circuit magntique du
transformateur de courant, avec une charge ohmique et sans tenir compte de la rmanence.
Les solutions de lquation diffrentielle sont donnes soit sous forme de diagrammes de
courbes, soit comme formules simplifies.
Lquation diffrentielle et la solution exacte sont donnes dans le Rapport Technique CEI 61869-100 TR.

K tf et le flux embrass par lenroulement secondaire dpendent tous deux du temps et, au
final, du temps limite de prcision t al requis par le systme de protection. Si lon effectue un
calcul avec linductance linaire, la solution nest valide que jusqu la premire saturation du
transformateur de courant.

K
Ktfp,max
tfp,max

K
Ktftf
K
Ktfp
tfp
K
Ktf,max
tf,max

KKtf,max
tf,max

(1)
(1)
tttf,max
tf,max

(2)
(2)

(3)
(3)
t tfp,max
tfp,max

tt
IEC 1558/12

Figure 2B.3 Plages de temps appropries pour le calcul du facteur transitoire


Dans la Figure 2B.3, la courbe K tf,max est construite comme suit:
Pour chaque point de temps de la courbe max (Figure 2B.2), la valeur K tf est calcule selon
3.4.233. K tfp est la courbe denveloppe correspondante. La courbe du facteur transitoire est
constitue de trois plages dfinies par trois fonctions de K tf :
Plage 1:

0 t al < t tf,max :

Dans la premire plage, la courbe K tf suit la courbe K tf, max . La plage commence au temps
zro et se termine lorsque la courbe K t f, max touche sa courbe enveloppe de crte K tfp au
temps

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

NOTE

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012

121

t tf,max =

(2B.5)

Lquation (2B,5) est la simplification dune quation plus gnrale avec = 90, mais elle est
convenable pour lapplication pratique.
Dans cette plage de temps, K tf, max considre langle de commutation dans le cas le plus
dfavorable

(t ' al ) ,

ce qui conduit au flux le plus lev au temps limite de prcision

t ' al .

Les Figures numrotes Figure 2B.4 Figure 2B.6 reprsentent les courbes pour diffrents
temps tal en fonction de la constante de temps du primaire Tp . Une constante de temps
secondaire Ts a t choisie assez grande pour le calcul. Des valeurs infrieures de Ts
donnent des valeurs K tf lgrement infrieures.
NOTE

Une plus grande diversit de courbes est donne dans le Rapport Technique CEI 61869-100 TR.

Ktf,
tf,max
max

ttalal

14 ms
13 ms
12 ms

Figure 2B.4
Dtermination de K tf
pour la plage 1
50 Hz
et T s = 1,8 s

11 ms

10 ms
9 ms

8 ms
7 ms

6 ms
5 ms

4 ms
3 ms
2 ms

0
0

10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200

(ms)
Tpp [ms]

Ktf,max
tf,max

IEC 1559/12

tal
tal

11 ms

10 ms
9 ms

Figure 2B.5
Dtermination de K tf
pour la plage 1
60 Hz
et T s = 1,5 s

8 ms
3

7 ms
6 ms

5 ms
4 ms

3 ms
2 ms

0
0

10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200
Tp (ms)
IEC 1560/12

Tp [ms]

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

122

61869-2 CEI:2012

K
Ktf,max
tf, max

ttalal

42 ms
39 ms
36 ms

Figure 2B.6
Dtermination de K tf
pour la plage 1
16,7 Hz
et T s = 5,5 s

33 ms

27 ms

30 ms
24 ms
2

21 ms

15 ms

18 ms
12 ms
9 ms
6 ms

0
0

10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200

TTpp[ms]
(ms)

t tf,max t al < t tfp,max

La deuxime plage de temps se poursuit avec la courbe enveloppe K tfp pour = 90 qui
conduit au flux de crte le plus lev, soit = 90 .

tfp

TsTp
Tp Ts

t / T
tal / Tp tal / TS
+ sin( )e al S + 1
e

cos( ) e

(2B.6)

jusquau maximum de la courbe au temps:

Tp
t

Plage 3:

tfp,max

TpTs
Tp Ts

ln

Ts

Ts Tp
sin( )
2
Ts
cos( )

cos( ) +

(2B.7)

t tfp,max t al

La troisime plage de temps se poursuit avec le maximum constant K tfp,max , donn


lquation (2B.8) pour les temps limites de prcision plus grands. K tfp,max est dfini comme
maximum de la courbe K tfp .

Tp
T
s Tp

Ts Tp
Tp
sin( )
cos( ) +
2
Tp + Ts

Ts
Ts

T cos( ) +
sin( )
K
tfp,max = p

cos(
)
T

+1

(2B.8)

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Plage 2:

IEC 1561/12

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012
2B.1.3

123

Cycles de fonctionnement C-O-C-O

Le dimensionnement pour le rgime transitoire destin aux cycles de fonctionnement


rarmement automatique doit tre effectu sparment pour chaque cycle, selon les
quations donnes ci-dessus.
Pour les noyaux ayant une constante de temps assigne de la boucle secondaire leve
(typiquement classe TPX), il ny a presque pas de diminution du flux aprs t:

K td,(COCO) = K td (t ' ) + K td (t al" )

(2B.9)

Pour les circuits ayant une petite constante de temps assigne de la boucle secondaire
(typiquement classes TPY et TPZ), le flux diminue de manire exponentielle avec la
constante de temps du secondaire Ts pendant le temps de rptition de dfaut t fr . Dans ce
cas, il nexiste pas de formule analytique pour le temps t pendant le premier dfaut, et il faut
considrer de diffrentes situations:

sat

2(t)

tsat

0
tal

tal

t
tfr

IEC 1562/12

Figure 2B.7 Limitation du flux magntique considrant la saturation du noyau


Figure 2B.7 reprsente une situation typique o la saturation est atteinte aprs t al . Le flux
( 2 (t)) est limit au niveau de saturation ( sat ) avant que t ne soit atteint. Pendant t fr , le flux
dcroit une valeur qui est assez faible pour rester en-dessous de la saturation jusqu tal .
Si la saturation est ignore, (voir courbe 1 (t)), le flux recommence augmenter partir dun
niveau suprieur au dbut du second dfaut. Cet exemple montre linterdpendance de
dimensionnement des noyaux entre le premier et le second dfaut, et la dtermination de K td .
NOTE 1 La formule pour les cycles de fonctionnement C-O-C-O qui tait donne dans lancienne norme
IEC 60044-6 ignore le phnomne de saturation pendant le temps du premier dfaut. En consquence, une valeur
K td , trop leve est obtenue dans beaucoup de situations.

Pour cette raison, il convient de tracer un graphe par analogie avec Figure 2B.7, afin de se
rendre compte de la situation relle. Lquation suivante donne une limite suprieure pour
K td :

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

1(t)

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

124

61869-2 CEI:2012

K td,(COCO)max = max K td (t 'al ) , K td (t ' )e (tfr +t ''al ) / Ts + K td (t al" )

(2B.10)

NOTE 2 Dans le Rapport Technique CEI 61869-100 TR, des mthodes de calcul sont donnes pour la
dtermination de K td ,

2B.2 Dtermination de la caractristique de magntisation du circuit


magntique
2B.2.1

Gnralits

La mesure de la caractristique de magntisation du circuit magntique implique

La mesure de linductance de magntisation L m ;


La mesure du Facteur de rmanence K R ;

La dtermination de lerreur aux conditions limites, utilisant une mthode indirecte.

(t ) = (u (t ) Rct im (t ))dt

(2B.11)

o i m est la valeur instantane du courant de magntisation.


NOTE Comme le terme courant dexcitation est rserv pour la valeur efficace dun courant alternatif (voir
3.3.207), i m et le terme courant de magntisation sont utiliss pour les valeurs instantanes des mthodes en
courant continu et de dcharge dun condensateur.

Les mthodes dcrites dans les articles suivants sont bases sur cette relation.
Linfluence de la chute de tension dans la rsistance de lenroulement secondaire doit tre
estime. Si elle dpasse 2 %, cette chute doit tre dduite de la tension mesure.

im

Rct

u(t)

IEC 1563/12

Figure 2B.8 Circuit de base


Pour les transformateurs de courant de classe TPX, il est ncessaire de dmagntiser le
circuit magntique avant chaque essai en raison de la valeur leve du facteur de
rmanence. Pour les transformateurs de courant de classe TPY, le flux rmanent est souvent
si faible quil peut tre nglig. La dmagntisation exige des moyens supplmentaires grce
auxquels on peut imposer au circuit magntique, partir de ltat de saturation, des cycles

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Toutes ces dterminations sont fondes sur lquation suivante. Si une tension arbitraire u(t)
est applique aux bornes secondaires (voir Figure 2B.8), le flux du circuit magntique (t)
embrass par lenroulement secondaire au temps t est fonction de cette tension, selon
lquation:

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012

125

dhystrsis dont lamplitude dcrot lentement. Une source de courant continu est
normalement prvue lorsque la mthode dessai en courant continu doit tre utilise.
On peut appliquer la mthode en courant alternatif, la mthode en courant continu ou la
mthode par dcharge dun condensateur.
2B.2.2
2B.2.2.1

Mthode en courant alternatif


Dtermination de linductance de magntisation L m

Une tension alternative pratiquement sinusodale u(t) est applique aux bornes secondaires,
et la valeur correspondante du courant dexcitation est mesure. Lessai peut tre effectu
une frquence rduite f pour viter une contrainte de tension inacceptable sur lenroulement
et sur les bornes secondaires. Aux frquences basses, les effets des pertes parasites par
courants de Foucault dans le circuit magntique et des courants capacitifs entre les couches
de lenroulement sont moins susceptibles de perturber les mesures. Le rsultat doit tre
visualis comme courbe de saturation.

On obtient la valeur crte du flux embrass par lenroulement secondaire selon

2U
2f '

o U est la valeur efficace mesure de la tension applique la frquence f.


En consquence, la tension de saturation U sat correspond avec le flux de saturation sat
selon

sat =

2 U sat
2f '

NOTE 201 U sat doit tre estime gale la tension o la courbe est pratiquement horizontale. Linfluence de
lincertitude dans la dtermination de U sat est pratiquement ngligeable pour la dtermination de L m .

Considrant cette quation, la courbe donne la relation entre la valeur crte du courant
dexcitation et la valeur crte du flux embrass par lenroulement secondaire. Linductance
de magntisation L m est dfinie par la pente moyenne de la courbe entre 20 % et 70 % du
flux de saturation sat . Elle est calcule suivant:

Lm =

0,5 U sat 2
(i70 i20 ) 2f '

o 20 est la valeur crte du courant dexcitation 20 % U sat ;


70 est la valeur crte du courant dexcitation 70 % U sat .
NOTE 202 Cette formule diffre lgrement de la formule donne dans lancienne norme IEC 60044-6 cause
de la dfinition amliore de la saturation.

2B.2.2.2

Dtermination de lerreur aux conditions limites

Larrangement dessai selon 2B.2.2.1 doit tre utilis.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

La tension dexcitation doit tre mesure avec un appareil qui donne une rponse
proportionnelle la valeur moyenne du signal redress, mais est gradu en valeur efficace.
Le courant dexcitation doit tre mesur laide dun appareil de mesure de valeur crte.

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

126

61869-2 CEI:2012

La tension doit tre augmente jusqu une tension gale E al selon

Eal = K ssc K td ( Rct + Rb ) I sr


La valeur de crte du courant secondaire dexcitation ( al ) ne doit pas dpasser la valeur
donne ci-dessous:
Pour les classes TPX et TPY:

Ial 2 I sr K ssc

Pour la classe TPZ:

K td 1

+ ac
Ial 2 I sr K ssc
2f R TS

NOTE Pour les transformateurs de courant de classe TPZ, la prcision nest spcifie que pour la composante
alternative; toutefois, lors de la dtermination de la valeur admissible de I al pendant les essais indirects, il est
galement ncessaire de tenir compte de la composante continue du courant dexcitation. Dans lquation cidessus, la composante continue est reprsente par (K td 1).

Dtermination du facteur de rmanence K R

A la diffrence de ce qui est dcrit dans 2B.2.2.1 et 2B.2.2.2, les formes donde doivent tre
enregistres.
Lorsque lon dtermine le facteur de rmanence K R par la mthode dessai en courant
alternatif, il est ncessaire dintgrer la tension dexcitation selon lquation (1) donne en
2B.2.1. La tension intgre associe au courant correspondant i m affiche une courbe
dhystrsis, reprsentant le flux de saturation sat . On considre que la valeur du flux au
passage par zro du courant reprsente le flux rmanent r . Voir la Figure 2B.9. Le facteur
de rmanence K R est alors calcul comme suit:

KR =

r
sat

(2B.12)

Aux frquences basses, les effets des pertes parasites par courants de Foucault dans le
circuit magntique et des courants capacitifs entre les couches de lenroulement sont moins
susceptibles de perturber les mesures.
NOTE sat doit tre estim comme flux embrass par lenroulement secondaire au niveau o la courbe est
pratiquement horizontale.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

2B.2.2.3

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012

127

sat

ie

IEC 1564/12

2B.2.3
2B.2.3.1

Mthode en courant continu


Gnralits

La mthode de la saturation en courant continu consiste appliquer une tension continue u(t)
pendant une dure telle que la valeur de flux de saturation soit atteinte. La mesure du flux est
dtermine selon lquation (2B.11) donne en 2B.2.1, o u(t) est la tension entre les bornes.
Voir la Figure 2B.10.
im

Rct

u(t)

um(t)

Rd

(t)

im(t)
IEC 1565/12

Figure 2B.10 Circuit pour la mthode en courant continu


La source de tension applique doit tre approprie pour amener le transformateur de courant
la saturation.
La rsistance de dcharge R d doit tre connecte, sinon linductance du circuit magntique
peut provoquer des surtensions trs leves louverture de linterrupteur S, lorsque le
courant inductif est interrompu.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Figure 2B.9 Dtermination du facteur de rmanence par cycle dhystrsis

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

128
2B.2.3.2

61869-2 CEI:2012

Dtermination du facteur de rmanence K R

Le circuit dessai selon 2B.2.3.1 doit tre utilis.


Quelque temps aprs la fermeture de linterrupteur S, le courant dexcitation est considr
comme ayant atteint sa valeur maximale m pour laquelle le flux dans le circuit magntique
demeure constant. Avant datteindre la valeur constante, la courbe i m doit montrer une
augmentation significative de sa pente, indiquant la saturation. La source de tension
applique doit tre approprie pour amener le transformateur de courant la saturation sans
influencer les rsultats dessai cause de ses limites. Cette condition est accomplie si le flux
embrass par lenroulement secondaire atteint une valeur stabilise avant le courant de
magntisation.
Les valeurs croissantes du courant de magntisation et du flux doivent tre enregistres
jusquau moment o ces valeurs deviennent constantes, puis linterrupteur S est ouvert.
Des enregistrements dessai typiques du flux (t) et du courant de magntisation i e (t) sont
reprsents la Figure 2B.11.

im

im
IEC 1566/12

Figure 2B.11 Diagrammes temps-amplitude et flux-courrant


A louverture de linterrupteur S, un courant de dcroissant traverse lenroulement secondaire
et la rsistance de dcharge R d . La valeur du flux correspondant dcrot, mais peut ne pas
devenir nulle lorsque le courant sannule. Si lon a convenablement choisi un courant de
magntisation i m pour parvenir au flux de saturation sat , une fois que le courant sest
annul, la valeur de flux subsistant doit tre considre comme tant gale au flux
rmanent r .
Pour les transformateurs de courant dont le circuit magntique na pas t dmagntis au
pralable, le facteur de rmanence (K R ) peut tre dtermin par le biais dun essai
complmentaire pour lequel les bornes secondaires ont t permutes. La courbe du flux
embrass par lenroulement secondaire contient un dplacement de la moiti du flux de
rmanence mesur apparemment. Pour cette raison, la ligne de zro doit tre dplace
conformment, et les valeurs du flux de saturation et du flux de rmanence doivent tre
adaptes. Voir Figure 2B.12.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

im

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012

129

IImm

IImm

0
0

t
IEC 1567/12

Figure 2B.12 Diagramme avec la ligne de zro dplace

KR =
2B.2.3.3

r
sat

(2B.13)

Dtermination de linductance de magntisation

Le circuit dessai selon 2B.2.3.2 doit tre utilis.


Linductance de magntisation (L m ) peut tre dduite selon lquation suivante:

Lm =

0,5 sat
i70 i20

(2B.14)

o
i 20
i 70

est la valeur de crte du courant de magntisation 20% sat ;


est la valeur de crte du courant de magntisation 70% sat .

NOTE Cette formule diffre lgrement de la formule donne dans lancienne norme IEC 60044-6 cause de la
dfinition amliore de la saturation.

2B.2.3.4

Dtermination de lerreur aux conditions limites

Le circuit dessai selon 2B.2.3.1 doit tre utilis.


Pour la dtermination de l'erreur aux conditions limites, le courant magntisant
correspondant au flux
l'accroissement du flux.

al

embrass par

le secondaire doit tre mesur pendant

al est le flux embrass au secondaire correspondant E al et est donn comme

al =

2 Eal
=
2f R

im

2 K td K ssc I sr ( Rb + Rct )
2f R

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Le facteur de rmanence K R est calcul selon

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

130

61869-2 CEI:2012

Le courant de magntisation im ne doit pas dpasser les limites suivantes:


Pour classes TPX and TPY:

im 2 I sr K ssc

Pour classe TPZ:

K td 1

+ ac
im 2 I sr K ssc
2f R TS

NOTE Pour les transformateurs de courant de classe TPZ, la prcision nest spcifie que pour la composante
alternative; toutefois, lors de la dtermination de la valeur admissible de I al pendant les essais indirects, il est
galement ncessaire de tenir compte de la composante continue du courant dexcitation. Dans lquation cidessus, la composante continue est reprsente par (K td 1).

2B.2.4

Mthode par dcharge dun condensateur

La mthode par dcharge dun condensateur utilise la charge dun condensateur pour exciter
le circuit magntique du transformateur de courant depuis le secondaire. La mesure du flux
est obtenue partir de lquation 1 donne en 2B.2.1 o u(t) est la tension sur les bornes.
Voir Figure 2B.13.

al =

u(t)

2 Eal
2f R

udt

CT

i(t)
IEC 1568/12

Figure 2B.13 Circuit utilis dans la mthode par dcharge dun condensateur
Au moment o al est atteint, la valeur de crte du courant de magntisation secondaire i m
doit tre mesure, et ne doit pas dpasser la valeur de crte du courant dexcitation
secondaire al .
La constante de temps assigne de la boucle secondaire T s doit tre dtermine en
appliquant aux bornes secondaires du transformateur de courant, une tension afin que
l'intgrale tension-temps atteigne une valeur gale celle qui correspond 90% de al . Le
courant de magntisation i m est mesur et la constante de temps est calcule comme suit:

Ts =

2 0,9 Eal
2f R ( Rct + Rb ) i 'm

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Le condensateur est charg avec une tension suffisamment leve pour produire un flux de
saturation embrass par lenroulement secondaire al correspondant E al . Voir les
Figures 2B.13 et 2B.14.

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012

131

NOTE Cette dfinition nest pas conforme aux dfinitions prcdentes des mthodes en courant continu et en
courant alternatif.

En dterminant le facteur de rmanence K R , la tension intgre dtermine un cycle


dhystrsis avec le courant correspondant. Si le courant de magntisation est tel que
saturation est atteinte, la valeur de flux correspondant au passage par zro du courant est
considre comme r .
Le facteur de rmanence est dtermin:

KR =
im

r
sat

im

sat

td

im
IEC 1569/12

Figure 2B.14 Enregistrements types de la mthode par dcharge dun condensateur

2B.3 Dtermination de lerreur aux conditions limites des transformateurs de


courant pour protection pour rponse en rgime transitoire
2B.3.1

Gnralits

Le courant derreur instantan peut tre mesur de diffrentes manires. Dans tous les cas,
les erreurs du systme de mesure ne doivent pas dpasser 10 % de la limite derreur
correspondant la classe du transformateur de courant soumis lessai pendant la totalit du
cycle de fonctionnement.
2B.3.2

Essai direct

Il est ncessaire de dmagntiser les transformateurs de courant de classe TPX avant lessai
direct en raison de la valeur leve du facteur de rmanence. Il peut tre ncessaire de
dmagntiser les transformateurs de courant de classe TPY si le facteur de rmanence K R
nest pas ngligeable.
Deux essais directs doivent tre effectus la frquence assigne, avec la charge
secondaire assigne:
a) Le courant primaire de court-circuit assign, la frquence assigne, est appliqu sans
dcalage. On mesure la composante alternative de lerreur instantane. Elle doit tre
conforme la valeur thorique de 1/T s .
b) Pour vrifier les exigences derreur du cycle de fonctionnement, lessai suivant sera
ralis:
Le courant primaire de court-circuit assign, la frquence assigne, est appliqu avec le
dcalage requis. Pour les valeurs spcifies de la constante de temps du primaire allant
jusqu 80 ms, lessai est effectu la condition limite de prcision spcifie (cycle de

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

132

61869-2 CEI:2012

fonctionnement spcifi). La constante de temps du primaire ne doit pas diffrer de plus


de 10 % de la valeur spcifie.
Pour les valeurs spcifies de la constante de temps du primaire suprieures 80 ms, les
essais peuvent tre effectus des conditions limites de prcision quivalentes (en
modifiant le cycle de fonctionnement et/ou la charge), sous rserve daccord entre le
constructeur et lacheteur.
Pendant la priode dexcitation, la premire crte du courant primaire ne doit pas tre
infrieure la valeur correspondant aux conditions spcifies.
En pratique, au laboratoire il peut tre difficile de reproduire le cycle de fonctionnement
exact. Dans ce cas, la valeur calcule de K td du cycle de fonctionnement appliqu ne doit
pas tre infrieure la valeur K td du cycle de fonctionnement spcifi. Pour rpondre
cette exigence il est permis dajuster la dure du cycle et/ou la charge secondaire.
NOTE Puisque le calcul de K td se rapporte aux formules aux conditions les plus dfavorables (la formule 6
dans 2B.1.2 peut dlivrer des valeurs K td qui son 30 % plus leves que ncessaire), le transformateur de
courant peut rpondre aux exigences du cycle de fonctionnement sans atteindre le flux correspondant la
valeur calcule de K td .

Pour les transformateurs de courant de classes TPX et TPY, le courant derreur


instantan i est mesur: i = is k r ip . La valeur de lerreur doit tre dtermine

Pour les transformateurs de courant de la classe TPZ, on mesure la composante


alternative du courant derreur en prenant la moiti de la valeur crte crte (voir
Figure 2B.15). La valeur de lerreur ac doit tre dtermine selon le paragraphe 3.4.223.
Sa valeur ne doit pas dpasser la limite indique dans le Tableau 206.
NOTE Il est possible que la dfinition de classe ne contienne pas de cycle de fonctionnement. Dans ce cas,
pour les essais, un cycle de fonctionnement conduisant la valeur K td donne doit faire lobjet dun accord
entre le constructeur et lacheteur.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

selon le paragraphe 3.4.222. Sa valeur ne doit pas dpasser la limite indique dans
le Tableau 206.

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012

133

bb

cc
aa

tt
IEC 1570/12

a= idc
b=

2iac

c= iac

+ idc

pour TPY: i

=c

pour TPZ: i

= iac =

b
2
Figure 2B.15 Mesure des courants derreur

Si la valeur relle de K td doit tre dtermine, la dure de lexcitation et/ou la charge


secondaire doit tre augmente, afin que le courant derreur instantan mesur atteigne la
limite de la classe concerne (Tableau 206). Pour la classe TPZ, linterpolation linaire est
utilise pour dterminer linstant o la composante alternative atteint la limite.
Le flux embrass par lenroulement secondaire dir doit tre dtermin comme suit:

Rct + Rb t
(t ) =
Rb is (t )dt
Rb
0
o
t

est l'instant o la limite derreur ou ac est atteinte.

Le facteur de dimensionnement K td du transformateur de courant est le rapport dir la


valeur crte de la composante alternative de en rgime permanent. La composante
alternative peut tre obtenue partir des mesures du flux embrass par lenroulement
secondaire dans lessai a), qui doit tre mise en relation avec la valeur exacte (thortique)
du courant de court-circuit K ssc x I sr . La mesure doit tre ralise avec la formule ci-dessus.
Lerreur de mesure du flux ne doit pas dpasser 5 %.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

o:

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

134
2B.3.3

61869-2 CEI:2012

Dtermination du facteur de construction

Si la conformit avec les exigences dune conception faible ractance de fuite ne peut pas
tre tablie la satisfaction mutuelle du constructeur et de lacheteur par le biais des dessins,
le facteur de construction F c doit tre dtermin comme suit:
Les valeurs de flux embrass par lenroulement secondaire doivent tre dtermines en
essais direct et indirect, la condition de la limite de prcision dans les deux cas. Si une
classe pour rponse en rgime transitoire est spcifie avec la dfinition alternative, un cycle
de fonctionnement et une charge doivent tre choisis afin d'atteindre la valeur spcifie de
K SSC K td.
Le flux embrass par lenroulement secondaire dir , qui est obtenu dans lessai direct selon
2B.3.2 doit tre dtermin.
Dans lessai indirect, le flux embrass par lenroulement secondaire

ind

doit tre dtermin

avec une des mthodes suivantes:

Larrangement dessai selon 2B.2.2.1 doit tre utilis.


La tension doit tre augmente jusqu ce que la limite correspondante du courant
dexcitation al (selon 2B.2.2.2) soit atteinte. La tension obtenue soit note. Le flux
embrass par lenroulement secondaire ind est donn par:

ind =

2 U
2f

o f est la frquence applique.


mthode en courant continu ou par dcharge dun condensateur
Le circuit dessai selon 2B.2.3.1 (mthode en courant continu) ou 2B.2.4 (mthode par
dcharge dun condensateur) doit tre utilis.
Le flux

ind

est le flux embrass par lenroulement secondaire qui correspond la

limite du courant de magntisation selon 2B.2.3.4


F c peut alors tre calcul par

Fc =

ind
dir

Lerreur de mesure du flux ne doit pas dpasser 5 %.


Si F c est suprieur 1,1, le facteur doit tre considr lors du dimensionnement du noyau.
NOTE La valeur du courant primaire ncessaire pour effectuer des essais directs derreur compose sur certains
types de transformateurs peut dpasser la capacit des installations normalement fournies par les constructeurs.
Des essais des niveaux de courant primaire infrieurs peuvent faire lobjet dun accord entre le constructeur et
lacheteur.

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

mthode en courant alternatif:

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012

135

Annexe 2C
(normative)
Preuve de type faible ractance de fuite
On doit montrer que:

le transformateur de courant possde un circuit magntique prsentant pratiquement


la forme dun tore, avec, le cas chant, des entrefers uniformment rpartis:

le transformateur de courant possde un enroulement secondaire uniformment


rparti;

le transformateur de courant possde un conducteur primaire symtrique par rapport


la rotation;

Linfluence des conducteurs de la phase adjacente, lextrieur de lenveloppe du


transformateur de courant, et des phases voisines est ngligeable.

Pour les transformateurs de courant des classes TPX, TPY et TPZ le facteur de construction
F c doit tre dtermin selon 2B.3.3. Si F c est infrieure 1,1, le transformateur de courant
est considr comme type faible ractance de fuite.
Pour toutes les autres classes de protection, lerreur compose de lenroulement compte
doit tre dtermin par un essai direct et un essai indirect, et les deux rsultats sont
compars.
Pour lessai direct, lun ou lautre mthode selon 2A.5 ou 2A.6 peuvent tre appliques. Le
courant dessai est donn comme suit:
ALF x I pr
K x x I pr

pour classe P et classe PR;


pour classe PX et classe PXR.

Pour lessai indirect, la mthode selon 7.2.6.203 b) doit tre applique. La tension applique
aux bornes secondaires est donne comme suit:
E ALF

pour classe P et classe PR;

Ek

pour classe PX et classe PXR.

Si lerreur compose de lessai direct est infrieure 1,1 fois lerreur compose de lessai
indirect, le transformateur de courant est considr comme type faible ractance de fuite.
NOTE Selon la dfinition (3.4.235), le terme "type faible ractance de fuite nest pas universelle, mais
apparente sa perfomance (classe de protection).

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Si la conformit avec les exigences dune conception faible ractance de fuite ne peut pas
tre tablie la satisfaction mutuelle du constructeur et de lacheteur par le biais des dessins,
les rsultats dun essai direct et dun essai indirect doivent tre compars comme suit:

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

136

61869-2 CEI:2012

Annexe 2D
(informative)
Technique utilise dans lessai dchauffement des transformateurs
immergs dans lhuile pour dterminer la constante thermique
par estimation exprimentale
Liste des symboles:
Temprature en C

(t)

Temprature de lhuile, variant dans le temps (il peut sagir de la temprature de


lhuile en tte ou de la temprature moyenne de lhuile)

Temprature du milieu de refroidissement extrieur (air ambiant ou eau),


suppose constante

Echauffement de lhuile au-dessus de a


Valeurs finales en rgime tabli

u , u

(t)
To

Ecart restant par rapport la valeur en rgime tabli u


Constante de temps pour la variation exponentielle de lchauffement de lhuile

Intervalle de temps entre les relevs

1 , 2 , 3

Trois relevs de temprature successifs spars dun intervalle de temps h

En principe, il convient de poursuivre lessai jusqu sassurer de lchauffement (de lhuile)


en rgime tabli.
u = a + u

(2D.1)

(t) = a + u (1 e t/To )

(2D.2)

Lcart restant par rapport au rgime tabli est alors:

(t) = u (t) = u x e t/To

(2D.3)

On considre que:

la temprature ambiante est maintenue aussi constante que possible;

la temprature de lhuile (t) sapproche dune valeur finale u selon une fonction
exponentielle avec une constante de temps T o;

lquation (2D.2) est une bonne approximation de la courbe de temprature (voir


Figure 2C.1).

Etant donns trois relevs successifs 1 , 2 et 3 , si la relation exponentielle de


lquation (2D.2) est une bonne approximation de la courbe de temprature, alors les
incrments prsentent la relation suivante:

2 1
= e h/To
3 2
To =

h
1
ln 2
3 2

(2D.4)

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012

137

Les relevs permettent galement une prvision de lchauffement final:

u =

( 2 )2 1 3

(2D.5)

2 2 1 3

Des estimations successives doivent tre effectues. Il convient que celles-ci convergent.
Afin dviter des erreurs numriques alatoires importantes, il convient que lintervalle de
temps h soit approximativement de T o et il convient que 3 / u soit suprieur ou gal 0,95.
Une valeur plus prcise de lchauffement en rgime tabli est obtenue par une mthode
dextrapolation des moindres carrs de tous les points mesurs approximativement au-dessus
de 60 % de u ( u estim par la mthode des trois points).
Une formulation numrique diffrente est:

u = 2 +

ln

(2D.6)

2 1

3 2

3
2

2
1

(t)

h
IEC 1571/12

Figure 2D.1 Extrapolation graphique de lchauffement final

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

( 2 1 ) ( 3 2 )

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

138

61869-2 CEI:2012

Annexe 2E
(informative)
Mthode alternative pour la mesure de lerreur de rapport ()
Pour les transformateurs de courant faible ractance de fuite, lessai indirect suivant conduit
des rsultats trs proches de ceux obtenus dans lessai direct.
Nanmoins, pour les essais individuels de srie visant la dtermination de lerreur de
rapport en rgime tabli, lessai direct doit toujours tre ralis, car cette mthode fournit la
meilleure preuve de la proprit de faible ractance de fuite dun circuit magntique,
incluant lhomognit magntique du circuit magntique. En revanche, la mthode
alternative est approprie aux mesures sur site et la surveillance.
Dans ce cas, on doit noter que cette mthode ne tient jamais compte de linfluence du flux de
courant au voisinage du transformateur de courant.

Ip x Np / N s = Is + I e
IsRCT
Re
P1

Ip

RCT

Np : Ns
Ixm
Xm

P2

S1

Us

IRm
Rm

e.m.f

Is

e.m.f
E0

Is

Rb

Ip(Isr/Ipr)

Us
Xb
S2

Im
Ixm

IRm
IEC 1572/12

Figure 2E.1 Circuit quivalent simplifi du transformateur de courant


Une tension pratiquement sinusodale est applique aux bornes secondaires S 1 S 2 du
transformateur de courant. La tension dessai entre les bornes U s test et le courant I s test sont
mesurs. Il convient que la tension injecte gnre une force lectromotrice aux bornes de
linductance principale de mme amplitude que pendant le fonctionnement avec un certain
courant et la charge relle. Il est possible de calculer la force lectromotrice daprs les
rsultats dessai en soustrayant la chute de tension aux bornes de la rsistance de
lenroulement R CT de la tension dessai U s test entre les bornes S 1 S 2 . Cette soustraction
doit tre effectue dans le plan complexe. Le courant mesur I s test est gal au courant
derreur I .
Lerreur de rapport peut tre exprime par:

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Pour la dtermination de lerreur de rapport, le schma de circuit quivalent simplifi


reprsent la Figure 2E.1 est utilis:

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

61869-2 CEI:2012

139

Is Ip

I sr
I pr

I
I p sr
I pr

I s I pr
I p I sr

(2E.1)

Avec:

I p Np

= Ie + I s Ip =

Ns

(I e + I s )N s
Np

(2E.2)

lerreur de rapport peut tre exprime par:

I s N p I pr

(I e + I s ) N s I sr

(2E.3)

Calcul de la tension secondaire aux bornes de S 1 S 2:

U s = I s (Rb + jX b )

Mesure de la rsistance de lenroulement secondaire R (valeur la temprature relle)

Calcul de la force lectromotrice correspondante


E0 = I sR + U s

Injection de

U s Test = E 0 + I s Test R

aux bornes secondaires S 1 S 2


Mesure de la tension U p test aux bornes P 1 P 2
Calcul du rapport des nombres de spires

Np
Ns

U p Test

E0

Calcul du courant I p correspondant

IP =

( I s + I s Test ) N s
Np

Lerreur de rapport peut tre calcule par:

(I

I s N p I pr
s Test

+ I s ) I sr

(avec I s test = I s )

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Pour la dtermination de lerreur de rapport pour un certain courant secondaire I s , la


procdure dessai suivante est propose:

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

140

61869-2 CEI:2012

Annexe 2F
(normative)
Dtermination du rapport des nombres de spires
Le rapport de transformation rel est affect par des erreurs rsultant de trois causes:
a) la diffrence entre linverse du rapport des nombres de spires et le rapport de
transformation assign;
b) le courant dexcitation du circuit magntique (I e );
c) les courants qui traversent les capacits parasites associes aux enroulements.

I ' S ( R + R 'b ) = E S = I ' ' S ( R + R ' 'b )


o R est la rsistance relle de lenroulement secondaire.
Les erreurs de rapport mesures tant dsignes par c et c , lerreur sur le rapport des
nombres de spires est indique par t , et la combinaison du courant dexcitation et des
courants parasites est donne par I x . Les courants derreur respectifs sont donns par:

( 'c t ) k r I ' s = I x = ( ' 'c t ) k r I ' ' s


do:

t =

'c I ' s ' 'c I ' ' s


I 's I ' 's

Si I S = 2I S , lerreur sur le rapport des nombres de spires est donne par 2 c c .


Un essai au courant assign avec une charge minimale connecte au secondaire, suivi par un
essai la moiti du courant assign avec laugmentation convenable de la rsistance de la
boucle secondaire, donne habituellement des rsultats satisfaisants.

___________

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

Dans la plupart des cas, il est raisonnable de supposer que pour une valeur donne (E s ) de la
force lectromotrice induite dans lenroulement secondaire, les courants derreur rsultant
des capacits parasites et de la magntisation du circuit conservent une valeur constante
indpendante de la valeur du courant primaire dexcitation. E s peut thoriquement tre
maintenu une valeur constante pour toute une gamme de courants dexcitation, pourvu que
limpdance de la boucle secondaire puisse tre rgle de faon approprie. Pour les
transformateurs de courant conus pour tre du type faible ractance de fuite, la ractance
de fuite du secondaire peut tre ignore. On ne doit donc considrer que la rsistance de
lenroulement secondaire. Ainsi, pour lun ou lautre des deux courants I s et I" s , lquation de
base dfinissant lexigence de lessai est donne par:

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

2014-04-30; RUBIANO ARIZA, CLARA INES; SIEMENS, RC-CO E BE

ELECTROTECHNICAL
COMMISSION
3, rue de Varemb
PO Box 131
CH-1211 Geneva 20
Switzerland
Tel: + 41 22 919 02 11
Fax: + 41 22 919 03 00
[email protected]
www.iec.ch

COPYRIGHT IEC. ALL RIGHTS RESERVED. USE OF THIS PUBLICATION IS RESTRICTED. LICENCED TO SIEMENS AG, CT SR, D-81730 MUENCHEN

INTERNATIONAL

You might also like