0% found this document useful (0 votes)
60 views1 page

Retightening and Replacement of Transformer Accessories: Ranel Bagonoc

Eight modules of a transmitter were damaged on April 12, 2015 when the power supplier provided single phase voltage instead of the required three phase voltage. An inspection the next day found that the 20 year old transformer was defective, with corroded connectors and dried insulating oil, causing unstable voltage. A list of replacement parts and accessories for the transformer was provided, along with labor costs to fix the issues causing the power problems.

Uploaded by

Arkie Baja
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
60 views1 page

Retightening and Replacement of Transformer Accessories: Ranel Bagonoc

Eight modules of a transmitter were damaged on April 12, 2015 when the power supplier provided single phase voltage instead of the required three phase voltage. An inspection the next day found that the 20 year old transformer was defective, with corroded connectors and dried insulating oil, causing unstable voltage. A list of replacement parts and accessories for the transformer was provided, along with labor costs to fix the issues causing the power problems.

Uploaded by

Arkie Baja
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 1

April 22, 2015

MR. JEONY BIGAY:

We hereby inform you about the incident that happened last April 12, 2015.
During my sign on, eight modules of the transmitter has been damaged. As I tried
to troubleshoot the problem, I managed to discover that the CENECO (Central
Negros Electric Cooperative) was supplying high single phase voltage instead of the
required three-phase voltage.
The day after the incident, CENECO conducted an online site testing and
found out that the transformer was defective due to the fact that it has been almost
20 years. It was also discovered that the connectors are corroded and the insulating
oil of the transformer has dried up. These cause the inefficient performance of the
transformer thus, supplying unstable voltage to the transmitter.
This list consist of the following items to be bought given by the CENECO:
Retightening and replacement of transformer accessories
-

20m
20m
3pcs
6pcs
3 set
3 set
3pcs

4/0 Copper Wire


#6 Stranded Copper Wire
Hot Wire Clamp
350HYD Connector
Disconnecting Cut Out
Lightning Arrester
300HYD Connector

Labor: P10, 000.00

RANEL
BAGONOC
TEHCNICAL
DIRECTOR