03 Directional Overcurrent
03 Directional Overcurrent
If fault current can flow in both directions through the relay location it is necessary to
add directional properties to the overcurrent relays in order to obtain correct
discrimination. Directional protection is commonly applied in two areas, namely,
parallel feeders(transformers) and ring mains.
RING MAINS
The more usual application of directional relays is to ring mains. In the case of a ring
system, fed at one point only the relays at the generation end and at the mid-point
substation, where the setting of both overcurrent relays are identical, the relays can
be made non-directional, provided that in the latter case the relays are located on the
same feeder, one at each substation. In this respect it is interesting to note that
when the numbers of feeders in the rings is an even number, the two relays with the
same operating time are at the same substation and will have to be directional
whereas when the number of feeders is odd, the two relays with the same operating
time are at different substations and therefore, do not need to be directional. Also at
intermediate substations it will be noted that whenever the times of the two relays at
a substation are different, the difference in operating time is never less than the
grading interval of 04 seconds and consequently it is permissible for the relay with
the larger operating time to be non-directional.
Grading Ring Mains
The usual practice for grading relays in an interconnected system is to open the ring
at the supply point and to grade the relays first clockwise and then anti-clockwise.
Thus, the relays looking in a clockwise direction around the ring are arranged to trip
in the sequence 1 - 2 - 3 - 4 - 5 - 6 and the relays looking in the anti-clockwise
direction are arranged to trip in the sequence 1' - 2' - 3' - 4' - 5' - 6'. The arrows
indicate the direction in which the power must flow in order that the directional units
will close their contacts and prepare the overcurrent elements for operation. The
double headed arrows on each of the two feeders at the generating station indicate
non-directional relays, directional features being unnecessary at these points,
because power can flow in one direction only, that is out of the generating station. At
all other points single headed arrows are shown. These indicate directional relays
connected so as to operate with power flow in the direction of the arrow which is in
every case from the substation bus bars and into the protected line. See Figure 1.
This rule is invariable and applies to all forms of directional relays. Selection of the
faulty section is by time and fault power direction. Fault power has two phases x and
y. It divides between the two paths in the inverse ratio of the impedances and
passes through all the substations in the ring. Thus, at every substation one set of
relays will be inoperative because the power flow is against the arrow and other set
operative because the flow is with the arrow. In every case it will be found that the
time settings of the relays that are inoperative are shorter than those of the operative
relays, except in the case of substation C where the settings happened to coincide.
In this way, all relays with short time on sections between the fault one and the
generating station are prevented from operation. The others, which are operative are
graded downwards towards the fault and the last to be traversed by the fault current,
namely that on the faulty feeder section, has the shortest time and operates first.
This applies to both paths to the fault. Consequently, the faulty section is the only
one to be isolated and supply is maintained to all substations.
Page 1
b)
Open the ring at one the supply points by means of a suitable high set
instantaneous overcurrent relays and then proceed to grade the ring as in the
case of a single infeed.
Treat the inter-connector between the two sources of supply as a continuous
bus, separate from the ring and protect it by means of a unit system of
protection such as pilot wire relays. Then proceed to grade the ring as in the
case of a single infeed.
PARALLEL FEEDERS
If non-directional overcurrent relays are applied to parallel feeders any faults
occurring on any one line will inevitably, irrespective of the relay setting chosen,
isolate both lines and completely disrupt the supply. To ensure discriminative
operation of the relays during line faults, it is usual with this type of system to design
and connect relays R1' and R2' such that they will only operate for faults occurring on
the protected line in the direction indicated by the arrows. See Figure 2. With
parallel feeders to ensure correct discrimination during line faults, it is important that
the correct directional relay R1' or R2' operates before the non-directional relays R1
and R2. For this reason relays R1' and R2' are given lower time settings than relays
R1 and R2 and also lower current settings. The usual practice is to set relays R1'
and R2' to 50% of the normal full load of the circuit (ensure that the relays are
capable of carrying without damage, twice their setting current continuously),
operating with an IDMT characteristic with a TMS =1.0
Care should be taken when using definite time relays. For such applications the
directional relays should be set above full load current to prevent them operating due
to load current reversal as a result of a phase to phase fault on the other side of the
transformer.
ESTABLISING DIRECTION
The direction of alternating current can only be determined with respect to a common
reference. In relay terms, the reference is commonly referred to as the polarising
quantity. The most convenient reference quantity is polarising voltage taken from the
power system voltages.
The relay compares the power system current against this fixed polarising reference
to determine direction of operation.
Page 2
RELAY CONNECTIONS
This is the angle by which the current applied to the relay is displaced from the
voltage applied to the relay at unity power factor.
The 90 connection (quadrature connection) is now used for all overcurrent relays.
30 and 60 connections were used in the past, but no longer, as the 90 connection
gives better performance. The 90 connection is achieved by using IA and VBC.
Hence, for an A phase fault the polarising voltage does not collapse. Without a
polaring voltage most relays are unable to make a directional decision. Modern
numerical relays are able to use prefault data to make a decision, a technique
referred to as memory polarising.
90 Connection - 45 RCA
The 'a' phase relay is supplied with Ia current and Vbc volts displaced 45 in an anticlockwise direction. In this case the relay maximum sensitivity is produced when the
current lags the system phase to neutral voltage by 45. This connection gives a
correct directional tripping zone over the range of current 45 leading to 135 lagging.
See Figure 3.
Page 3
Page 4
Icb
3Ic
IL
-2Ic
IL
Where :
Ica
Icb
Ic
The vector diagram of the currents in the sound phases shows that the total wattage
component of the currents in the restraining quadrant, hence the relays on the
healthy feeders will not operate. However, the current in the faulty feeder show that
the wattage component of the currents is in the operating quadrant and hence, the
relay in the faulty feeder will operate.
The current transformers are of a special design, class 02, having an exceptionally
low phase angle error and because of this cannot be balanced accurately for currents
greatly in excess of rated current. The relay is provided with 0 MTA.
Insulated System
The diagram in Figure 5 shows a system of radial feeders, with a phase to ground
fault on the 'C' phase of one of the feeders. The residual current flowing in the
current coil of the relay on the faulty feeder, neglecting the effect of magnetising
current, is proportional to the 2 Ic where IC is the vector sum of the currents in the
healthy phases Ica and Icb. Since the system is an insulated one, the fault has the
effect of raising the neutral point of the system by a voltage equivalent to the phase
voltage and the voltages of the healthy feeders by 3 .
Page 5
G.S.
~
2.1
2.1
6'
6
0.1
0.1
1'
1.7
1.7
5
5'
Y
FAULT
2'
0.5
4'
1.3
1.3
3
3'
0.9
0.9
C
FIGURE 1
RING MAIN OVERCURRENT PROTECTION
Page 6
0.5
R1
R1'
LOAD
R2
R2'
FIGURE 2
RING MAIN OVERCURRENT PROTECTION
Page 7
Ia
Vb'c
Va
Vbc
Vc
Vb
0 LINE
UNITY P.F.
Ia
RCA LINE
Vb'c
45
135
90 LINE
ZERO P.F.
LAGGING
Vab
Va
Vc
Vca
Vb
Vbc
ZERO SENSITIVITY
LINE
FIGURE 3
90 CONNECTION 45 RCA
Page 8
a b c
Ica
Icb
Ic
Ica
Icb
Source
Ic
IL
Ica
Icb
IL
3Ic
Ic
2Ic
Location of CT's
IL
b
Restrain
Restrain
Icb
Ica
IL
3Ic
Is
Operate
VPO
Ica
Ic
Icb
Operate
VPO
Healthy Feeders
Faulty Feeder
FIGURE 4
Page 9
a b c
Ica
Icb
Ic
Ica
Icb
Source
Ic
Ica
Icb
2Ic
3Ic
Location CT's
Faulty Feeder
VRE
a
Icb
Ic
-3Ic
Ica c
Healthy Feeders
VRE
VRE
-2Ic
RCA
Operate
Restrain
VPO
Ic = Ica + Icb
RCA
Operate
Restrain
VPO
FIGURE 5
Page 10