Concordia University Department of Eletrical and Computer Engineering ELEC 433 - ELEC 6411 Power Electronics
This document describes a power supply system that converts a 48V battery bank to a 120V/60Hz AC output. It includes:
1) A PWM boost converter that regulates the DC bus voltage at 100V as the battery discharges from 48V to 80% of its rated value.
2) A DC capacitor filter on the DC bus that limits voltage ripple to 10% of the 100V DC bus voltage.
3) An ideal step-up transformer with a turns ratio calculated to match the DC bus and AC output voltages.
4) An output LC filter tuned to resonate the dominant harmonic at 10% of the fundamental frequency to filter the output.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
49 views3 pages
Concordia University Department of Eletrical and Computer Engineering ELEC 433 - ELEC 6411 Power Electronics
This document describes a power supply system that converts a 48V battery bank to a 120V/60Hz AC output. It includes:
1) A PWM boost converter that regulates the DC bus voltage at 100V as the battery discharges from 48V to 80% of its rated value.
2) A DC capacitor filter on the DC bus that limits voltage ripple to 10% of the 100V DC bus voltage.
3) An ideal step-up transformer with a turns ratio calculated to match the DC bus and AC output voltages.
4) An output LC filter tuned to resonate the dominant harmonic at 10% of the fundamental frequency to filter the output.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3
CONCORDIA UNIVERSITY
DEPARTMENT OF ELETRICAL AND COMPUTER ENGINEERING
ELEC 433 ELEC 6411 Power Electronics Example on Dc-dc converters and Dc-Ac converters 1) Consider an emergency 2.5kVA/120V/60Hz power supply fed by a 48V battery bank. It is composed of a battery bank, a PWM dc-dc boost converter, a dc bus with a capacitor filter, a PWM dc-ac single-phase converter, a step-up transformer and an output LC filter. The dc-ac converter (inverter) is controlled with SPWM (10 KHz) and fixed modulating factor (ma = 1). The duty-cycle of the dc-dc converter varies to compensate for the voltage decrease in the battery, as it discharges with time. The dc bus is to be regulated at 100 V. A) Calculate the expected range of D, for the dc-dc converter, assuming that the system will shut down when the battery voltage drops to 80% of its rated value to prevent deep discharge. B) Considering the input current of the dc-ac converter to be pure dc, calculate the dc bus capacitor filter so that the ripple is limited to 10% of the dc voltage. C) Calculate the required turns ratio of the transformer (ideal). D) Calculate the resonant frequency of the output LC filter so that the magnitude of the dominant harmonic across the load is limited to 10% of the fundamental component. Consider that the system operates with rated power.
Page 2 of 3
Proposed problem (Final 2004)
1) Consider a 1.5kVA/220V/60Hz single-phase emergency power supply fed by a 48V battery bank. It is composed of a battery bank, a PWM step-up (boost) dc-dc converter switching at 20 kHz, a PWM dc-ac converter, a transformer and an output LC filter. A) Choose the rated value for the regulated dc bus (between the dc-dc and the dc-ac converters) assuming that Dmax is limited to 0.7 and that the system shuts down when the battery voltage falls below 80% of its rated value. B) The dc-ac converter is controlled with voltage cancellation and a constant overlap angle (). Choose a suitable value for the overlap angle and justify your choice. C) Calculate the required turns ratio of the transformer (ideal). D) Calculate the resonant frequency of the LC filter so that the magnitude of the dominant harmonic is limited to 10% of the fundamental component.