Cable Sizing Calculation - Appendix E Cables Selection Chart
Cable Sizing Calculation - Appendix E Cables Selection Chart
ON - APPENDIX E
selection chart
APPENDIX E
TABLE 1 - CABLE SELECTION CHART FOR 400V MOTOR FEEDER (installed in air on cable tray) - RUNNING CONDITIONS
TABLE 2 - CABLE SELECTION CHART FOR 400V MOTOR FEEDER (installed in air on cable tray) - STARTING CONDITIONS
TABLE 3 - CABLE SELECTION CHART FOR 400V MOTOR FEEDER (installed in air on cable tray) - RUNNING & STARTING CONDITIONS
TABLE 4 - CABLE SELECTION CHART FOR 400V MOTOR FEEDER (installed underground in sand filled trenches) - RUNNING CONDITIONS
TABLE 5 - CABLE SELECTION CHART FOR 400V MOTOR FEEDER (installed underground in sand filled trenches) - STARTING CONDITIONS
TABLE 6 - CABLE SELECTION CHART FOR 400V MOTOR FEEDER (installed underground in sand filled trenches) - RUNNING & STARTING CONDIT
TABLE 7 - CABLE SELECTION CHART FOR 400V MOTOR FEEDER (installed underground in ducts) - RUNNING CONDITIONS
TABLE 8 - CABLE SELECTION CHART FOR 400V MOTOR FEEDER (installed underground in ducts) - STARTING CONDITIONS
TABLE 9 - CABLE SELECTION CHART FOR 400V MOTOR FEEDER (installed underground in ducts) - RUNNING & STARTING CONDITIONS
TABLE 10 - CABLE SELECTION CHART FOR 11 kV MOTOR FEEDER (installed in air on cable tray) - RUNNING & STARTING CONDITIONS
TABLE 11 - CABLE SELECTION CHART FOR 11 kV MOTOR FEEDER (installed underground in sand filled trenches) - RUNNING & STARTING CONDI
TABLE 12 - CABLE SELECTION CHART FOR 6 kV MOTOR FEEDER (installed in air on cable tray) - RUNNING & STARTING CONDITIONS
TABLE 13 - CABLE SELECTION CHART FOR 6 kV MOTOR FEEDER (installed underground in sand filled trenches) - RUNNING & STARTING CONDIT
TABLE 14 - CABLE SELECTION CHART FOR 400V OUTGOING FEEDERS (installed in air on cable tray)
TABLE 15 - CABLE SELECTION CHART FOR 400V OUTGOING FEEDERS (installed underground in sand filled trenches)
TABLE 16 - CABLE SELECTION CHART FOR 400V OUTGOING FEEDERS (installed underground in ducts)
TABLE 17 - CABLE SELECTION CHART FOR 11 kV MOTOR FEEDER (installed underground in ducts) - RUNNING & STARTING CONDITIONS
TABLE 18 - CABLE SELECTION CHART FOR 6 kV MOTOR FEEDER (installed underground in ducts) - RUNNING & STARTING CONDITIONS
Page 5 of 80
APPENDIX E
Page 6 of 80
APPENDIX E
Page 7 of 80
APPENDIX E
Page 8 of 80
APPENDIX E
TABLE 1 - CABLE SELECTION CHART FOR 400V MOTOR FEEDER (installed in air on cable tray) - RUNNING CONDITIONS
Cable data
2 x 3 cores
cable
22
9.448
0.09
4x4
42
0.676
28
5.878
0.09
797
594
413
307
233
172
128
106
88
4x6
54
0.676
37
3.927
0.08
1188
885
615
458
348
256
190
158
131
97
4x10
75
0.676
51
2.333
0.08
1476
1026
764
580
428
318
264
219
162
132
4x16
100
0.676
68
1.466
0.08
1612
1201
912
673
500
416
344
255
208
176
0.676
86
0.927
0.08
1413
1043
777
645
534
395
322
273
202
165
0.07
1421
1060
878
728
538
439
372
276
225
186
1162
962
712
581
492
365
298
246
1338
990
808
686
509
417
344
1317
1075
913
679
557
460
1108
825
677
559
976
802
663
1159
954
788
1163
960
kW (rated)
4x25
127
3x35/25
158
0.676
107
0.668
3x50/25
192
0.676
130
0.493
0.07
3x70/35
246
0.676
166
0.342
0.07
0.676
201
0.246
0.07
0.07
cos
1.1
1.5
2.2
5.5
7.5
11
15
18.5
22
30
37
45
0.81
0.79
0.81
0.82
0.82
0.83
0.85
0.83
0.83
0.83
0.83
0.84
0.85
0.86
0.86
81.40%
82.80%
84.30%
85.50%
86.60%
87.70%
88.70%
88.70%
89.80%
90.60%
91.20%
91.60%
92.30%
92.70%
93.10%
FLC
[Amps]
2.4
3.3
4.7
6.2
8.1
10.9
14.4
17.6
21.3
28.8
35.3
41.3
55.2
67.0
81.1
FLC x 1.25
[Amps]
3.0
4.1
5.8
7.7
10.2
13.6
17.9
22.1
26.6
36.0
44.1
51.6
69.0
83.7
101.4
498
371
258
192
146
107
80
* CABLE REACTANCE
@ 50Hz [/km] = X
* CABLE RESISTANCE
@ 90OC [/km] = Rx
0.676
DERATING FACTOR
32
CABLE RATING
[Amps]
N/A
Load data
4x2.5
Cable type
(No. conductors x CSA)
[mm2]
Cables in parallel
CIRCUIT TYPE
3x95/50
298
3x120/70
346
0.676
234
0.195
3x150/95
399
0.676
270
0.158
0.07
3x185/95
456
0.676
308
0.126
0.07
3x240/120
538
0.676
364
0.096
0.07
3x300/150
621
0.676
420
0.077
0.07
3x95/50
298
0.676
403
0.246
0.07
3x120/70
346
0.676
468
0.195
0.07
1118
3x150/95
399
0.676
539
0.158
0.07
1325
3x185/95
456
0.676
617
0.126
0.07
3x240/120
538
727
0.096
0.07
0.676
Cable ampacities are from IEC 60364-5-52 Table B.52-12, column 3 (see Appendix C)
* Cable Resistance and Reactance are according IEC 60228
1122
919
Cable length =
Page 9 of 80
APPENDIX E
TABLE 1 - CABLE SELECTION CHART FOR 400V MOTOR FEEDER (installed in air on cable tray) - RUNNING CONDITIONS
Cable data
* CABLE REACTANCE
@ 50Hz [/km] = X
* CABLE RESISTANCE
@ 90OC [/km] = Rx
Load data
CABLE (CIRCUIT) INSTALLED
RATING [Amps]
DERATING FACTOR
CABLE RATING
[Amps]
Cable type
(No. conductors x CSA)
[mm2]
Cables in parallel
CIRCUIT TYPE
kW (rated)
cos
1.1
1.5
2.2
5.5
7.5
11
15
18.5
22
30
37
45
0.81
0.79
0.81
0.82
0.82
0.83
0.85
0.83
0.83
0.83
0.83
0.84
0.85
0.86
0.86
Page 10 of 80
APPENDIX E
Load data
55
75
90
110
132
0.86
0.86
0.86
0.86
0.87
93.50%
94.00%
94.20%
94.50%
94.70%
98.7
133.9
160.4
195.4
231.3
123.4
167.4
200.4
244.2
289.1
378
279
233
459
339
283
544
401
335
275
647
477
399
327
276
789
582
486
399
338
922
680
568
466
395
756
557
465
382
321
919
677
566
464
391
1089
803
670
550
464
954
797
654
552
1164
972
798
675
203
283
1295
Page 11 of 80
APPENDIX E
Load data
55
75
90
110
132
0.86
0.86
0.86
0.86
0.87
Page 12 of 80
APPENDIX E
TABLE 2 - CABLE SELECTION CHART FOR 400V MOTOR FEEDER (installed in air on cable tray) - STARTING CONDITIONS
Cable data
Load data
2 x 3 cores
cable
32
4x4
42
4x6
* CABLE REACTANCE
@ 50Hz [/km] = X
* CABLE RESISTANCE
@ 90OC [/km] = Rx
DERATING FACTOR
CABLE RATING
[Amps]
4x2.5
kW (rated)
cos
cos starting
1.1
1.5
2.2
5.5
7.5
11
15
18.5
22
30
37
45
0.81
0.79
0.81
0.82
0.82
0.83
0.85
0.83
0.83
0.83
0.83
0.84
0.85
0.86
0.86
0.7
0.7
0.63
0.62
0.62
0.55
0.55
0.5
0.5
0.5
0.45
0.45
0.4
0.4
0.4
81.40%
82.80%
84.30%
85.50%
86.60%
87.70%
88.70%
88.70%
89.80%
90.60%
91.20%
91.60%
92.30%
92.70%
93.10%
FLC
[Amps]
2.4
3.3
4.7
6.2
8.1
10.9
14.4
17.6
21.3
28.8
35.3
41.3
55.2
67.0
81.1
n = LRC/FLC
4.7
5.0
5.2
6.0
6.3
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
11.3
16.5
24.2
37.1
51.2
70.9
93.3
114.7
138.5
187.1
229.3
268.3
358.8
435.4
527.3
15
458
313
238
158
114
93
70
501
380
252
182
148
112
100
83
745
564
374
270
219
166
148
123
91
1239
936
620
448
362
275
245
203
150
135
1458
965
698
562
427
378
313
232
208
177
1065
852
647
570
472
349
311
266
219
180
1137
864
758
628
464
412
352
288
237
196
972
805
596
525
448
364
300
248
792
691
591
475
392
323
1005
869
743
592
488
403
857
678
558
461
756
623
514
840
692
571
773
638
LRC
[Amps]
22
9.448
0.676
28
5.878
0.09
15
733
54
0.676
37
3.927
0.08
15
1090
4x10
75
0.676
51
2.333
0.08
15
4x16
100
0.676
68
1.466
0.08
15
4x25
127
0.676
86
0.927
0.08
15
3x35/25
158
0.676
107
0.668
0.07
15
3x50/25
192
0.676
130
0.493
0.07
15
3x70/35
246
0.676
166
0.342
0.07
15
3x95/50
298
0.676
201
0.246
0.07
15
3x120/70
346
0.676
234
0.195
0.07
15
3x150/95
399
0.676
270
0.158
0.07
15
0.676
308
0.126
0.07
15
0.07
15
0.676
0.09
N/A
Cable type
(No. conductors x CSA) [mm2]
Cables in parallel
CIRCUIT TYPE
1071
3x185/95
456
3x240/120
538
0.676
364
0.096
3x300/150
621
0.676
420
0.077
0.07
15
3x95/50
298
0.676
403
0.246
0.07
15
3x120/70
346
0.676
468
0.195
0.07
15
922
3x150/95
399
0.676
539
0.158
0.07
15
1029
3x185/95
456
0.676
617
0.126
0.07
15
3x240/120
538
0.676
727
0.096
0.07
15
Cable ampacities are from IEC 60364-5-52 Table B.52-12, column 3 (see Appendix C)
* Cable Resistance and Reactance are according IEC 60228
695
805
Cable length =
Page 13 of 80
APPENDIX E
TABLE 2 - CABLE SELECTION CHART FOR 400V MOTOR FEEDER (installed in air on cable tray) - STARTING CONDITIONS
Cable data
Load data
* CABLE REACTANCE
@ 50Hz [/km] = X
kW (rated)
* CABLE RESISTANCE
@ 90OC [/km] = Rx
DERATING FACTOR
CABLE RATING
[Amps]
Cable type
(No. conductors x CSA) [mm2]
Cables in parallel
CIRCUIT TYPE
cos
cos starting
1.1
1.5
2.2
5.5
7.5
11
15
18.5
22
30
37
45
0.81
0.79
0.81
0.82
0.82
0.83
0.85
0.83
0.83
0.83
0.83
0.84
0.85
0.86
0.86
0.7
0.7
0.63
0.62
0.62
0.55
0.55
0.5
0.5
0.5
0.45
0.45
0.4
0.4
0.4
Page 14 of 80
APPENDIX E
Load data
55
75
90
110
132
0.86
0.86
0.86
0.86
0.87
0.4
0.38
0.38
0.37
0.36
93.50%
94.00%
94.20%
94.50%
94.70%
98.7
133.9
160.4
195.4
231.3
6.5
6.5
6.5
6.5
6.5
641.7
870.4
1042.3
1269.9
1503.1
331
251
209
379
286
239
423
318
266
220
469
352
294
243
207
525
392
327
270
230
571
425
355
293
249
662
501
418
348
298
758
572
478
397
339
845
636
531
441
376
939
704
588
487
415
783
654
541
460
204
266
Page 15 of 80
APPENDIX E
Load data
55
75
90
110
132
0.86
0.86
0.86
0.86
0.87
0.4
0.38
0.38
0.37
0.36
Page 16 of 80
APPENDIX E
TABLE 3 - CABLE SELECTION CHART FOR 400V MOTOR FEEDER (installed in air on cable tray) - RUNNING & STARTING CONDITIONS
Cable data
Load data
2 x 3 cores
cable
32
4x4
42
4x6
* CABLE REACTANCE
@ 50Hz [/km] = X
* CABLE RESISTANCE
@ 90OC [/km] = Rx
DERATING FACTOR
CABLE RATING
[Amps]
4x2.5
kW (rated)
cos
cos starting
1.1
1.5
2.2
5.5
7.5
11
15
18.5
22
30
37
45
0.81
0.79
0.81
0.82
0.82
0.83
0.85
0.83
0.83
0.83
0.83
0.84
0.85
0.86
0.86
0.7
0.7
0.63
0.62
0.62
0.55
0.55
0.5
0.5
0.5
0.45
0.45
0.4
0.4
0.4
81.40%
82.80%
84.30%
85.50%
86.60%
87.70%
88.70%
88.70%
89.80%
90.60%
91.20%
91.60%
92.30%
92.70%
93.10%
FLC
[Amps]
2.4
3.3
4.7
6.2
8.1
10.9
14.4
17.6
21.3
28.8
35.3
41.3
55.2
67.0
81.1
n = LRC/FLC
4.7
5.0
5.2
6.0
6.3
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
11.3
16.5
24.2
37.1
51.2
70.9
93.3
114.7
138.5
187.1
229.3
268.3
358.8
435.4
527.3
15
458
313
238
158
114
93
70
501
380
252
182
148
112
100
83
745
564
374
270
219
166
148
123
91
1239
936
620
448
362
275
245
203
150
132
1458
965
698
562
427
378
313
232
208
176
1065
852
647
570
472
349
311
266
202
165
1137
864
758
628
464
412
352
276
225
186
972
805
596
525
448
364
298
246
792
691
591
475
392
323
1005
869
743
592
488
403
857
678
558
461
756
623
514
840
692
571
773
638
LRC
[Amps]
23
9.448
0.72
30
5.878
0.09
15
733
54
0.72
39
3.927
0.08
15
1090
4x10
75
0.72
54
2.333
0.08
15
4x16
100
0.72
72
1.466
0.08
15
4x25
127
0.72
91
0.927
0.08
15
3x35/25
158
0.72
114
0.668
0.07
15
3x50/25
192
0.72
138
0.493
0.07
15
3x70/35
246
0.72
177
0.342
0.07
15
3x95/50
298
0.72
215
0.246
0.07
15
3x120/70
346
0.72
249
0.195
0.07
15
3x150/95
399
0.72
287
0.158
0.07
15
0.72
328
0.126
0.07
15
0.07
15
0.72
0.09
N/A
Cable type
(No. conductors x CSA) [mm2]
Cables in parallel
CIRCUIT TYPE
1071
3x185/95
456
3x240/120
538
0.72
387
0.096
3x300/150
621
0.72
447
0.077
0.07
15
3x95/50
298
0.72
429
0.246
0.07
15
3x120/70
346
0.72
498
0.195
0.07
15
922
3x150/95
399
0.72
575
0.158
0.07
15
1029
3x185/95
456
0.72
657
0.126
0.07
15
3x240/120
538
0.72
775
0.096
0.07
15
Cable ampacities are from IEC 60364-5-52 Table B.52-12, column 3 (see Appendix C)
* Cable Resistance and Reactance are according IEC 60228
695
805
Cable length =
Page 17 of 80
APPENDIX E
TABLE 3 - CABLE SELECTION CHART FOR 400V MOTOR FEEDER (installed in air on cable tray) - RUNNING & STARTING CONDITIONS
Cable data
Load data
* CABLE REACTANCE
@ 50Hz [/km] = X
kW (rated)
* CABLE RESISTANCE
@ 90OC [/km] = Rx
DERATING FACTOR
CABLE RATING
[Amps]
Cable type
(No. conductors x CSA) [mm2]
Cables in parallel
CIRCUIT TYPE
cos
cos starting
1.1
1.5
2.2
5.5
7.5
11
15
18.5
22
30
37
45
0.81
0.79
0.81
0.82
0.82
0.83
0.85
0.83
0.83
0.83
0.83
0.84
0.85
0.86
0.86
0.7
0.7
0.63
0.62
0.62
0.55
0.55
0.5
0.5
0.5
0.45
0.45
0.4
0.4
0.4
Page 18 of 80
APPENDIX E
Load data
55
75
90
110
132
0.86
0.86
0.86
0.86
0.87
0.4
0.38
0.38
0.37
0.36
93.50%
94.00%
94.20%
94.50%
94.70%
98.7
133.9
160.4
195.4
231.3
6.5
6.5
6.5
6.5
6.5
641.7
870.4
1042.3
1269.9
1503.1
331
251
209
379
286
239
423
318
266
220
469
352
294
243
207
525
392
327
270
230
571
425
355
293
249
662
501
418
348
298
758
572
478
397
339
845
636
531
441
376
939
704
588
487
415
783
654
541
460
203
266
Page 19 of 80
APPENDIX E
Load data
55
75
90
110
132
0.86
0.86
0.86
0.86
0.87
0.4
0.38
0.38
0.37
0.36
Page 20 of 80
APPENDIX E
TABLE 4 - CABLE SELECTION CHART FOR 400V MOTOR FEEDER (installed underground in sand filled trenches) - RUNNING CONDITION
Cable data
2 x 3 cores
cable
15
9.448
0.09
4x4
39
0.5115
20
5.878
0.09
797
594
413
307
233
172
128
4x6
49
0.5115
25
3.927
0.08
1188
885
615
458
348
256
190
158
4x10
65
0.5115
33
2.333
0.08
1476
1026
764
580
428
318
264
219
4x16
84
0.5115
43
1.466
0.08
1612
1201
912
673
500
416
344
255
0.5115
55
0.927
0.08
1413
1043
777
645
534
395
322
273
0.07
1421
1060
878
728
538
439
372
1162
962
712
581
492
365
1338
990
808
686
509
417
1317
1075
913
679
557
460
1108
825
677
559
976
802
663
1159
954
788
1163
960
kW (rated)
4x25
107
3x35/25
129
0.5115
66
0.668
3x50/25
153
0.5115
78
0.493
0.07
3x70/35
188
0.5115
96
0.342
0.07
0.5115
116
0.246
0.07
0.07
cos
1.1
1.5
2.2
5.5
7.5
11
15
18.5
22
30
37
45
0.81
0.79
0.81
0.82
0.82
0.83
0.85
0.83
0.83
0.83
0.83
0.84
0.85
0.86
0.86
81.40%
82.80%
84.30%
85.50%
86.60%
87.70%
88.70%
88.70%
89.80%
90.60%
91.20%
91.60%
92.30%
92.70%
93.10%
FLC
[Amps]
2.4
3.3
4.7
6.2
8.1
10.9
14.4
17.6
21.3
28.8
35.3
41.3
55.2
67.0
81.1
FLC x 1.25
[Amps]
3.0
4.1
5.8
7.7
10.2
13.6
17.9
22.1
26.6
36.0
44.1
51.6
69.0
83.7
101.4
498
371
258
192
146
107
* CABLE REACTANCE
@ 50Hz [/km] = X
* CABLE RESISTANCE
@ 90OC [/km] = Rx
0.5115
DERATING FACTOR
30
CABLE RATING
[Amps]
N/A
Load data
4x2.5
Cable type
(No. conductors x CSA)
[mm2]
Cables in parallel
CIRCUIT TYPE
3x95/50
226
3x120/70
257
0.5115
131
0.195
3x150/95
287
0.5115
147
0.158
0.07
3x185/95
324
0.5115
166
0.126
0.07
3x240/120
375
0.5115
192
0.096
0.07
3x300/150
419
0.5115
214
0.077
0.07
3x95/50
226
0.5115
231
0.246
0.07
3x120/70
257
0.5115
263
0.195
0.07
1118
3x150/95
287
0.5115
294
0.158
0.07
1325
3x185/95
324
0.5115
331
0.126
0.07
3x240/120
375
384
0.096
0.07
0.5115
Cable ampacities are from IEC 60364-5-52 Table B.52-5, column 8 (see Appendix C)
* Cable Resistance and Reactance are according IEC 60228
1122
919
Cable length =
Page 21 of 80
APPENDIX E
TABLE 4 - CABLE SELECTION CHART FOR 400V MOTOR FEEDER (installed underground in sand filled trenches) - RUNNING CONDITION
Cable data
* CABLE REACTANCE
@ 50Hz [/km] = X
* CABLE RESISTANCE
@ 90OC [/km] = Rx
Load data
CABLE (CIRCUIT) INSTALLED
RATING [Amps]
DERATING FACTOR
CABLE RATING
[Amps]
Cable type
(No. conductors x CSA)
[mm2]
Cables in parallel
CIRCUIT TYPE
kW (rated)
cos
1.1
1.5
2.2
5.5
7.5
11
15
18.5
22
30
37
45
0.81
0.79
0.81
0.82
0.82
0.83
0.85
0.83
0.83
0.83
0.83
0.84
0.85
0.86
0.86
Page 22 of 80
APPENDIX E
Load data
55
75
90
110
132
0.86
0.86
0.86
0.86
0.87
93.50%
94.00%
94.20%
94.50%
94.70%
98.7
133.9
160.4
195.4
231.3
123.4
167.4
200.4
244.2
289.1
459
544
647
789
582
922
680
568
756
557
465
382
919
677
566
464
1089
803
670
550
464
954
797
654
552
1164
972
798
675
1295
Page 23 of 80
APPENDIX E
Load data
55
75
90
110
132
0.86
0.86
0.86
0.86
0.87
Page 24 of 80
APPENDIX E
TABLE 5 - CABLE SELECTION CHART FOR 400V MOTOR FEEDER (installed underground in sand filled trenches) - STARTING CONDITION
Cable data
Load data
2 x 3 cores
cable
30
4x4
39
4x6
4x10
* CABLE REACTANCE
@ 50Hz [/km] = X
* CABLE RESISTANCE
@ 90OC [/km] = Rx
DERATING FACTOR
CABLE RATING
[Amps]
4x2.5
kW (rated)
cos
cos starting
1.1
1.5
2.2
5.5
7.5
11
15
18.5
22
30
37
45
0.81
0.79
0.81
0.82
0.82
0.83
0.85
0.83
0.83
0.83
0.83
0.84
0.85
0.86
0.86
0.7
0.7
0.63
0.62
0.62
0.55
0.55
0.5
0.5
0.5
0.45
0.45
0.4
0.4
0.4
81.40%
82.80%
84.30%
85.50%
86.60%
87.70%
88.70%
88.70%
89.80%
90.60%
91.20%
91.60%
92.30%
92.70%
93.10%
FLC
[Amps]
2.4
3.3
4.7
6.2
8.1
10.9
14.4
17.6
21.3
28.8
35.3
41.3
55.2
67.0
81.1
n = LRC/FLC
4.7
5.0
5.2
6.0
6.3
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
11.3
16.5
24.2
37.1
51.2
70.9
93.3
114.7
138.5
187.1
229.3
268.3
358.8
435.4
527.3
15
458
313
238
158
114
93
501
380
252
182
148
112
745
564
374
270
219
166
148
1239
936
620
448
362
275
245
203
1458
965
698
562
427
378
313
232
1065
852
647
570
472
349
311
266
1137
864
758
628
464
412
352
972
805
596
525
448
364
300
792
691
591
475
392
323
1005
869
743
592
488
403
857
678
558
461
756
623
514
840
692
571
773
638
LRC
[Amps]
15
9.448
0.5115
20
5.878
0.09
15
733
49
0.5115
25
3.927
0.08
15
1090
65
0.5115
33
2.333
0.08
15
4x16
84
0.5115
43
1.466
0.08
15
4x25
107
0.5115
55
0.927
0.08
15
3x35/25
129
0.5115
66
0.668
0.07
15
3x50/25
153
0.5115
78
0.493
0.07
15
3x70/35
188
0.5115
96
0.342
0.07
15
3x95/50
226
0.5115
116
0.246
0.07
15
3x120/70
257
0.5115
131
0.195
0.07
15
3x150/95
287
0.5115
147
0.158
0.07
15
0.5115
166
0.126
0.07
15
0.07
15
0.5115
0.09
N/A
Cable type
(No. conductors x CSA) [mm2]
Cables in parallel
CIRCUIT TYPE
1071
3x185/95
324
3x240/120
375
0.5115
192
0.096
3x300/150
419
0.5115
214
0.077
0.07
15
3x95/50
226
0.5115
231
0.246
0.07
15
3x120/70
257
0.5115
263
0.195
0.07
15
922
3x150/95
287
0.5115
294
0.158
0.07
15
1029
3x185/95
324
0.5115
331
0.126
0.07
15
3x240/120
375
0.5115
384
0.096
0.07
15
Cable ampacities are from IEC 60364-5-52 Table B.52-5, column 8 (see Appendix C)
* Cable Resistance and Reactance are according IEC 60228
695
805
Cable length =
Page 25 of 80
APPENDIX E
TABLE 5 - CABLE SELECTION CHART FOR 400V MOTOR FEEDER (installed underground in sand filled trenches) - STARTING CONDITION
Cable data
Load data
* CABLE REACTANCE
@ 50Hz [/km] = X
kW (rated)
* CABLE RESISTANCE
@ 90OC [/km] = Rx
DERATING FACTOR
CABLE RATING
[Amps]
Cable type
(No. conductors x CSA) [mm2]
Cables in parallel
CIRCUIT TYPE
cos
cos starting
1.1
1.5
2.2
5.5
7.5
11
15
18.5
22
30
37
45
0.81
0.79
0.81
0.82
0.82
0.83
0.85
0.83
0.83
0.83
0.83
0.84
0.85
0.86
0.86
0.7
0.7
0.63
0.62
0.62
0.55
0.55
0.5
0.5
0.5
0.45
0.45
0.4
0.4
0.4
Page 26 of 80
APPENDIX E
Load data
55
75
90
110
132
0.86
0.86
0.86
0.86
0.87
0.4
0.38
0.38
0.37
0.36
93.50%
94.00%
94.20%
94.50%
94.70%
98.7
133.9
160.4
195.4
231.3
6.5
6.5
6.5
6.5
6.5
641.7
870.4
1042.3
1269.9
1503.1
331
379
423
469
352
525
392
571
425
355
662
501
418
348
758
572
478
397
339
845
636
531
441
376
939
704
588
487
415
783
654
541
460
Page 27 of 80
APPENDIX E
Load data
55
75
90
110
132
0.86
0.86
0.86
0.86
0.87
0.4
0.38
0.38
0.37
0.36
Page 28 of 80
APPENDIX E
TABLE 6 - CABLE SELECTION CHART FOR 400V MOTOR FEEDER (installed underground in sand filled trenches) - RUNNING & STARTING COND
Cable data
Load data
2 x 3 cores
cable
32
4x4
42
4x6
* CABLE REACTANCE
@ 50Hz [/km] = X
* CABLE RESISTANCE
@ 90OC [/km] = Rx
DERATING FACTOR
CABLE RATING
[Amps]
4x2.5
kW (rated)
cos
cos starting
1.1
1.5
2.2
5.5
7.5
11
15
18.5
22
30
37
45
0.81
0.79
0.81
0.82
0.82
0.83
0.85
0.83
0.83
0.83
0.83
0.84
0.85
0.86
0.86
0.7
0.7
0.63
0.62
0.62
0.55
0.55
0.5
0.5
0.5
0.45
0.45
0.4
0.4
0.4
81.40%
82.80%
84.30%
85.50%
86.60%
87.70%
88.70%
88.70%
89.80%
90.60%
91.20%
91.60%
92.30%
92.70%
93.10%
FLC
[Amps]
2.4
3.3
4.7
6.2
8.1
10.9
14.4
17.6
21.3
28.8
35.3
41.3
55.2
67.0
81.1
n = LRC/FLC
4.7
5.0
5.2
6.0
6.3
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
11.3
16.5
24.2
37.1
51.2
70.9
93.3
114.7
138.5
187.1
229.3
268.3
358.8
435.4
527.3
15
458
313
238
158
114
93
501
380
252
182
148
112
745
564
374
270
219
166
148
1239
936
620
448
362
275
245
203
1458
965
698
562
427
378
313
232
1065
852
647
570
472
349
311
266
1137
864
758
628
464
412
352
972
805
596
525
448
364
300
792
691
591
475
392
323
1005
869
743
592
488
403
857
678
558
461
756
623
514
840
692
571
773
638
LRC
[Amps]
18
9.448
0.57
24
5.878
0.09
15
733
54
0.57
31
3.927
0.08
15
1090
4x10
75
0.57
43
2.333
0.08
15
4x16
100
0.57
57
1.466
0.08
15
4x25
127
0.57
72
0.927
0.08
15
3x35/25
158
0.57
90
0.668
0.07
15
3x50/25
192
0.57
109
0.493
0.07
15
3x70/35
246
0.57
140
0.342
0.07
15
3x95/50
298
0.57
170
0.246
0.07
15
3x120/70
346
0.57
197
0.195
0.07
15
3x150/95
399
0.57
227
0.158
0.07
15
0.57
260
0.126
0.07
15
0.07
15
0.57
0.09
N/A
Cable type
(No. conductors x CSA) [mm2]
Cables in parallel
CIRCUIT TYPE
1071
3x185/95
456
3x240/120
538
0.57
307
0.096
3x300/150
621
0.57
354
0.077
0.07
15
3x95/50
298
0.57
340
0.246
0.07
15
3x120/70
346
0.57
394
0.195
0.07
15
922
3x150/95
399
0.57
455
0.158
0.07
15
1029
3x185/95
456
0.57
520
0.126
0.07
15
3x240/120
538
0.57
613
0.096
0.07
15
Cable ampacities are from IEC 60364-5-52 Table B.52-5, column 8 (see Appendix C)
* Cable Resistance and Reactance are according IEC 60228
695
805
Cable length =
Page 29 of 80
APPENDIX E
TABLE 6 - CABLE SELECTION CHART FOR 400V MOTOR FEEDER (installed underground in sand filled trenches) - RUNNING & STARTING COND
Cable data
Load data
* CABLE REACTANCE
@ 50Hz [/km] = X
kW (rated)
* CABLE RESISTANCE
@ 90OC [/km] = Rx
DERATING FACTOR
CABLE RATING
[Amps]
Cable type
(No. conductors x CSA) [mm2]
Cables in parallel
CIRCUIT TYPE
cos
cos starting
1.1
1.5
2.2
5.5
7.5
11
15
18.5
22
30
37
45
0.81
0.79
0.81
0.82
0.82
0.83
0.85
0.83
0.83
0.83
0.83
0.84
0.85
0.86
0.86
0.7
0.7
0.63
0.62
0.62
0.55
0.55
0.5
0.5
0.5
0.45
0.45
0.4
0.4
0.4
Page 30 of 80
APPENDIX E
Load data
55
75
90
110
132
0.86
0.86
0.86
0.86
0.87
0.4
0.38
0.38
0.37
0.36
93.50%
94.00%
94.20%
94.50%
94.70%
98.7
133.9
160.4
195.4
231.3
6.5
6.5
6.5
6.5
6.5
641.7
870.4
1042.3
1269.9
1503.1
331
379
423
469
352
525
392
571
425
355
662
501
418
348
758
572
478
397
339
845
636
531
441
376
939
704
588
487
415
783
654
541
460
Page 31 of 80
APPENDIX E
Load data
55
75
90
110
132
0.86
0.86
0.86
0.86
0.87
0.4
0.38
0.38
0.37
0.36
Page 32 of 80
APPENDIX E
TABLE 7 - CABLE SELECTION CHART FOR 400V MOTOR FEEDER (installed underground in ducts) - RUNNING CONDITIONS
Cable data
2 x 3 cores
cable
17
9.448
0.09
4x4
36
0.605
22
5.878
0.09
797
594
413
307
233
172
128
4x6
44
0.605
27
3.927
0.08
1188
885
615
458
348
256
190
158
4x10
58
0.605
35
2.333
0.08
1476
1026
764
580
428
318
264
219
4x16
75
0.605
45
1.466
0.08
1612
1201
912
673
500
416
344
255
0.605
58
0.927
0.08
1413
1043
777
645
534
395
322
273
0.07
1421
1060
878
728
538
439
372
1162
962
712
581
492
365
1338
990
808
686
509
417
1317
1075
913
679
557
460
1108
825
677
559
976
802
663
1159
954
788
1163
960
kW (rated)
4x25
96
3x35/25
115
0.605
70
0.668
3x50/25
135
0.605
82
0.493
0.07
3x70/35
167
0.605
101
0.342
0.07
0.605
119
0.246
0.07
0.07
cos
1.1
1.5
2.2
5.5
7.5
11
15
18.5
22
30
37
45
0.81
0.79
0.81
0.82
0.82
0.83
0.85
0.83
0.83
0.83
0.83
0.84
0.85
0.86
0.86
81.40%
82.80%
84.30%
85.50%
86.60%
87.70%
88.70%
88.70%
89.80%
90.60%
91.20%
91.60%
92.30%
92.70%
93.10%
FLC
[Amps]
2.4
3.3
4.7
6.2
8.1
10.9
14.4
17.6
21.3
28.8
35.3
41.3
55.2
67.0
81.1
FLC x 1.25
[Amps]
3.0
4.1
5.8
7.7
10.2
13.6
17.9
22.1
26.6
36.0
44.1
51.6
69.0
83.7
101.4
498
371
258
192
146
107
* CABLE REACTANCE
@ 50Hz [/km] = X
* CABLE RESISTANCE
@ 90OC [/km] = Rx
0.605
DERATING FACTOR
28
CABLE RATING
[Amps]
N/A
Load data
4x2.5
Cable type
(No. conductors x CSA)
[mm2]
Cables in parallel
CIRCUIT TYPE
3x95/50
197
3x120/70
223
0.605
135
0.195
3x150/95
251
0.605
152
0.158
0.07
3x185/95
281
0.605
170
0.126
0.07
3x240/120
324
0.605
196
0.096
0.07
3x300/150
365
0.605
221
0.077
0.07
3x95/50
197
0.605
238
0.246
0.07
3x120/70
223
0.605
270
0.195
0.07
1118
3x150/95
251
0.605
304
0.158
0.07
1325
3x185/95
281
0.605
340
0.126
0.07
3x240/120
324
392
0.096
0.07
0.605
Cable ampacities are from IEC 60364-5-52 Table B.52-5, column 8 (see Appendix C)
* Cable Resistance and Reactance are according IEC 60228
1122
919
Cable length =
Page 33 of 80
APPENDIX E
TABLE 7 - CABLE SELECTION CHART FOR 400V MOTOR FEEDER (installed underground in ducts) - RUNNING CONDITIONS
Cable data
* CABLE REACTANCE
@ 50Hz [/km] = X
* CABLE RESISTANCE
@ 90OC [/km] = Rx
Load data
CABLE (CIRCUIT) INSTALLED
RATING [Amps]
DERATING FACTOR
CABLE RATING
[Amps]
Cable type
(No. conductors x CSA)
[mm2]
Cables in parallel
CIRCUIT TYPE
kW (rated)
cos
1.1
1.5
2.2
5.5
7.5
11
15
18.5
22
30
37
45
0.81
0.79
0.81
0.82
0.82
0.83
0.85
0.83
0.83
0.83
0.83
0.84
0.85
0.86
0.86
Page 34 of 80
APPENDIX E
Load data
55
75
90
110
132
0.86
0.86
0.86
0.86
0.87
93.50%
94.00%
94.20%
94.50%
94.70%
98.7
133.9
160.4
195.4
231.3
123.4
167.4
200.4
244.2
289.1
459
544
647
789
582
922
680
568
756
557
465
919
677
566
464
1089
803
670
550
954
797
654
552
1164
972
798
675
1295
Page 35 of 80
APPENDIX E
Load data
55
75
90
110
132
0.86
0.86
0.86
0.86
0.87
Page 36 of 80
APPENDIX E
TABLE 8 - CABLE SELECTION CHART FOR 400V MOTOR FEEDER (installed underground in ducts) - STARTING CONDITIONS
Cable data
Load data
2 x 3 cores
cable
28
4x4
36
4x6
* CABLE REACTANCE
@ 50Hz [/km] = X
* CABLE RESISTANCE
@ 90OC [/km] = Rx
DERATING FACTOR
CABLE RATING
[Amps]
4x2.5
kW (rated)
cos
cos starting
1.1
1.5
2.2
5.5
7.5
11
15
18.5
22
30
37
45
0.81
0.79
0.81
0.82
0.82
0.83
0.85
0.83
0.83
0.83
0.83
0.84
0.85
0.86
0.86
0.7
0.7
0.63
0.62
0.62
0.55
0.55
0.5
0.5
0.5
0.45
0.45
0.4
0.4
0.4
81.40%
82.80%
84.30%
85.50%
86.60%
87.70%
88.70%
88.70%
89.80%
90.60%
91.20%
91.60%
92.30%
92.70%
93.10%
FLC
[Amps]
2.4
3.3
4.7
6.2
8.1
10.9
14.4
17.6
21.3
28.8
35.3
41.3
55.2
67.0
81.1
n = LRC/FLC
4.7
5.0
5.2
6.0
6.3
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
11.3
16.5
24.2
37.1
51.2
70.9
93.3
114.7
138.5
187.1
229.3
268.3
358.8
435.4
527.3
15
458
313
238
158
114
93
501
380
252
182
148
112
745
564
374
270
219
166
148
123
1239
936
620
448
362
275
245
203
1458
965
698
562
427
378
313
232
1065
852
647
570
472
349
311
266
1137
864
758
628
464
412
352
972
805
596
525
448
364
792
691
591
475
392
1005
869
743
592
488
403
857
678
558
461
756
623
514
840
692
571
773
638
LRC
[Amps]
17
9.448
0.605
22
5.878
0.09
15
733
44
0.605
27
3.927
0.08
15
1090
4x10
58
0.605
35
2.333
0.08
15
4x16
75
0.605
45
1.466
0.08
15
4x25
96
0.605
58
0.927
0.08
15
3x35/25
115
0.605
70
0.668
0.07
15
3x50/25
135
0.605
82
0.493
0.07
15
3x70/35
167
0.605
101
0.342
0.07
15
3x95/50
197
0.605
119
0.246
0.07
15
3x120/70
223
0.605
135
0.195
0.07
15
3x150/95
251
0.605
152
0.158
0.07
15
0.605
170
0.126
0.07
15
0.07
15
0.605
0.09
N/A
Cable type
(No. conductors x CSA) [mm2]
Cables in parallel
CIRCUIT TYPE
1071
3x185/95
281
3x240/120
324
0.605
196
0.096
3x300/150
365
0.605
221
0.077
0.07
15
3x95/50
197
0.605
238
0.246
0.07
15
3x120/70
223
0.605
270
0.195
0.07
15
922
3x150/95
251
0.605
304
0.158
0.07
15
1029
3x185/95
281
0.605
340
0.126
0.07
15
3x240/120
324
0.605
392
0.096
0.07
15
Cable ampacities are from IEC 60364-5-52 Table B.52-5, column 8 (see Appendix C)
* Cable Resistance and Reactance are according IEC 60228
695
805
Cable length =
Page 37 of 80
APPENDIX E
TABLE 8 - CABLE SELECTION CHART FOR 400V MOTOR FEEDER (installed underground in ducts) - STARTING CONDITIONS
Cable data
Load data
* CABLE REACTANCE
@ 50Hz [/km] = X
kW (rated)
* CABLE RESISTANCE
@ 90OC [/km] = Rx
DERATING FACTOR
CABLE RATING
[Amps]
Cable type
(No. conductors x CSA) [mm2]
Cables in parallel
CIRCUIT TYPE
cos
cos starting
1.1
1.5
2.2
5.5
7.5
11
15
18.5
22
30
37
45
0.81
0.79
0.81
0.82
0.82
0.83
0.85
0.83
0.83
0.83
0.83
0.84
0.85
0.86
0.86
0.7
0.7
0.63
0.62
0.62
0.55
0.55
0.5
0.5
0.5
0.45
0.45
0.4
0.4
0.4
Page 38 of 80
APPENDIX E
Load data
55
75
90
110
132
0.86
0.86
0.86
0.86
0.87
0.4
0.38
0.38
0.37
0.36
93.50%
94.00%
94.20%
94.50%
94.70%
98.7
133.9
160.4
195.4
231.3
6.5
6.5
6.5
6.5
6.5
641.7
870.4
1042.3
1269.9
1503.1
379
423
469
525
392
571
425
355
662
501
418
758
572
478
397
845
636
531
441
939
704
588
487
415
783
654
541
460
Page 39 of 80
APPENDIX E
Load data
55
75
90
110
132
0.86
0.86
0.86
0.86
0.87
0.4
0.38
0.38
0.37
0.36
Page 40 of 80
APPENDIX E
TABLE 9 - CABLE SELECTION CHART FOR 400V MOTOR FEEDER (installed underground in ducts) - RUNNING & STARTING CONDITIONS
Cable data
Load data
2 x 3 cores
cable
* CABLE REACTANCE
@ 50Hz [/km] = X
* CABLE RESISTANCE
@ 90OC [/km] = Rx
DERATING FACTOR
CABLE RATING
[Amps]
kW (rated)
cos
cos starting
1.1
1.5
2.2
5.5
7.5
11
15
18.5
22
30
37
45
0.81
0.79
0.81
0.82
0.82
0.83
0.85
0.83
0.83
0.83
0.83
0.84
0.85
0.86
0.86
0.7
0.7
0.63
0.62
0.62
0.55
0.55
0.5
0.5
0.5
0.45
0.45
0.4
0.4
0.4
81.40%
82.80%
84.30%
85.50%
86.60%
87.70%
88.70%
88.70%
89.80%
90.60%
91.20%
91.60%
92.30%
92.70%
93.10%
FLC
[Amps]
2.4
3.3
4.7
6.2
8.1
10.9
14.4
17.6
21.3
28.8
35.3
41.3
55.2
67.0
81.1
n = LRC/FLC
4.7
5.0
5.2
6.0
6.3
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
11.3
16.5
24.2
37.1
51.2
70.9
93.3
114.7
138.5
187.1
229.3
268.3
358.8
435.4
527.3
15
458
313
238
158
114
93
501
380
252
182
148
112
745
564
374
270
219
166
148
123
1239
936
620
448
362
275
245
203
1458
965
698
562
427
378
313
232
1065
852
647
570
472
349
311
266
1137
864
758
628
464
412
352
972
805
596
525
448
364
792
691
591
475
392
1005
869
743
592
488
403
857
678
558
461
756
623
514
840
692
571
773
638
LRC
[Amps]
4x2.5
28
0.56
16
9.448
4x4
36
0.56
20
5.878
0.09
15
733
4x6
44
0.56
25
3.927
0.08
15
1090
4x10
58
0.56
32
2.333
0.08
15
4x16
75
0.56
42
1.466
0.08
15
4x25
96
0.56
54
0.927
0.08
15
3x35/25
115
0.56
64
0.668
0.07
15
3x50/25
135
0.56
76
0.493
0.07
15
3x70/35
167
0.56
94
0.342
0.07
15
3x95/50
197
0.56
110
0.246
0.07
15
3x120/70
223
0.56
125
0.195
0.07
15
3x150/95
251
0.56
141
0.158
0.07
15
0.07
15
0.09
N/A
Cable type
(No. conductors x CSA) [mm2]
Cables in parallel
CIRCUIT TYPE
1071
3x185/95
281
0.56
157
0.126
3x240/120
324
0.56
181
0.096
0.07
15
3x300/150
365
0.56
204
0.077
0.07
15
3x95/50
197
0.56
221
0.246
0.07
15
3x120/70
223
0.56
250
0.195
0.07
15
922
3x150/95
251
0.56
281
0.158
0.07
15
1029
3x185/95
281
0.56
315
0.126
0.07
15
3x240/120
324
0.56
363
0.096
0.07
15
Cable ampacities are from IEC 60364-5-52 Table B.52-5, column 8 (see Appendix C)
* Cable Resistance and Reactance are according IEC 60228
695
805
Cable length =
Page 41 of 80
APPENDIX E
TABLE 9 - CABLE SELECTION CHART FOR 400V MOTOR FEEDER (installed underground in ducts) - RUNNING & STARTING CONDITIONS
Cable data
Load data
* CABLE REACTANCE
@ 50Hz [/km] = X
kW (rated)
* CABLE RESISTANCE
@ 90OC [/km] = Rx
DERATING FACTOR
CABLE RATING
[Amps]
Cable type
(No. conductors x CSA) [mm2]
Cables in parallel
CIRCUIT TYPE
cos
cos starting
1.1
1.5
2.2
5.5
7.5
11
15
18.5
22
30
37
45
0.81
0.79
0.81
0.82
0.82
0.83
0.85
0.83
0.83
0.83
0.83
0.84
0.85
0.86
0.86
0.7
0.7
0.63
0.62
0.62
0.55
0.55
0.5
0.5
0.5
0.45
0.45
0.4
0.4
0.4
Page 42 of 80
APPENDIX E
Load data
55
75
90
110
132
0.86
0.86
0.86
0.86
0.87
0.4
0.38
0.38
0.37
0.36
93.50%
94.00%
94.20%
94.50%
94.70%
98.7
133.9
160.4
195.4
231.3
6.5
6.5
6.5
6.5
6.5
641.7
870.4
1042.3
1269.9
1503.1
379
423
469
525
392
571
425
355
662
501
418
758
572
478
397
845
636
531
441
939
704
588
487
415
783
654
541
460
Page 43 of 80
APPENDIX E
Load data
55
75
90
110
132
0.86
0.86
0.86
0.86
0.87
0.4
0.38
0.38
0.37
0.36
Page 44 of 80
APPENDIX E
TABLE 10 - CABLE SELECTION CHART FOR 11 kV MOTOR FEEDER (installed in air on cable tray) - RUNNING & STARTING CONDITIONS
Load data
Cable data
running
2 x 3 cores
cable
* CABLE REACTANCE
@ 50Hz [/km] = X
* CABLE RESISTANCE
@ 90OC [/km] = Rx
DERATING FACTOR
CABLE RATING
[Amps]
Cable type
(No. conductors x CSA) [mm2]
Cables in parallel
CIRCUIT TYPE
starting
kW (rated)
3000
3500
4000
4500
5000
5500
3000
3500
4000
4500
5000
5500
cos
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.16
0.16
0.16
0.16
0.16
0.16
cos starting
FLC
[Amps]
96.00%
96.00%
96.00%
96.00%
96.00%
96.00%
96.00%
96.00%
96.00%
96.00%
96.00%
96.00%
183.3
213.8
244.4
274.9
305.4
336.0
183.3
213.8
244.4
274.9
305.4
336.0
1099.6
1069.0
1221.8
1374.5
1527.2
1679.9
n = LRC/FLC
LRC
[Amps]
FLC x 1.25
[Amps]
229.1
267.3
305.4
343.6
381.8
420.0
3x95/16
353
0.676
239
0.246
0.106
3.25
3368
3x120/16
402
0.676
272
0.195
0.102
3.25
4094
3509
3x150/25
454
0.676
307
0.158
0.099
3.25
4853
4160
3640
3x185/25
515
0.676
348
0.126
0.096
3.25
5779
4953
4334
3853
3x240/25
600
0.676
406
0.096
0.093
3.25
7065
6056
5299
4710
3x300/25
727
0.676
491
0.077
0.090
3.25
3x95/16
353
0.676
477
0.246
0.106
3.25
3674
7876
3x120/16
402
0.676
544
0.195
0.102
3.25
4466
8599
3x150/25
454
0.676
614
0.158
0.099
3.25
5294
9219
3x185/25
515
0.676
696
0.126
0.096
3.25
3x240/25
600
0.676
811
0.096
0.093
3.25
6016
6568
6756
7042
7244
6338
3467
7535
7750
6781
6028
5425
4239
8083
8314
7275
6466
5820
4972
Cable length =
4520
6170
System voltage is 11 kV
Page 45 of 80
5609
APPENDIX E
TABLE 10 - CABLE SELECTION CHART FOR 11 kV MOTOR FEEDER (installed in air on cable tray) - RUNNING & STARTING CONDITIONS
Load data
Cable data
running
* CABLE REACTANCE
@ 50Hz [/km] = X
* CABLE RESISTANCE
@ 90OC [/km] = Rx
DERATING FACTOR
CABLE RATING
[Amps]
Cable type
(No. conductors x CSA) [mm2]
Cables in parallel
CIRCUIT TYPE
starting
kW (rated)
3000
3500
4000
4500
5000
5500
3000
3500
4000
4500
5000
5500
cos
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
Page 46 of 80
APPENDIX E
Page 47 of 80
APPENDIX E
Page 48 of 80
APPENDIX E
TABLE 11 - CABLE SELECTION CHART FOR 11 kV MOTOR FEEDER (installed underground in sand filled trenches) - RUNNING & STARTING CON
Load data
Cable data
running
2 x 3 cores
cable
* CABLE REACTANCE
@ 50Hz [/km] = X
* CABLE RESISTANCE
@ 90OC [/km] = Rx
DERATING FACTOR
CABLE RATING
[Amps]
Cable type
(No. conductors x CSA) [mm2]
Cables in parallel
CIRCUIT TYPE
starting
kW (rated)
3000
3500
4000
4500
5000
5500
3000
3500
4000
4500
5000
5500
cos
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.16
0.16
0.16
0.16
0.16
0.16
cos starting
FLC
[Amps]
96.00%
96.00%
96.00%
96.00%
96.00%
96.00%
96.00%
96.00%
96.00%
96.00%
96.00%
96.00%
183.3
213.8
244.4
274.9
305.4
336.0
183.3
213.8
244.4
274.9
305.4
336.0
1099.6
1069.0
1221.8
1374.5
1527.2
1679.9
n = LRC/FLC
LRC
[Amps]
FLC x 1.25
[Amps]
229.1
267.3
305.4
343.6
381.8
420.0
3x95/16
309
0.558
172
0.246
0.106
3.25
3x120/16
349
0.558
195
0.195
0.102
3.25
3x150/25
390
0.558
218
0.158
0.099
3.25
3x185/25
436
0.558
243
0.126
0.096
3.25
5779
3x240/25
499
0.558
278
0.096
0.093
3.25
7065
12112
10598
8083
16628
14549
3x300/25
591
0.558
330
0.077
0.090
3.25
8287
14206
12430
8569
17628
15425
3x95/16
309
0.558
345
0.246
0.106
3.25
5774
5052
4491
12376
10829
9626
3x120/16
349
0.558
389
0.195
0.102
3.25
6141
5458
4912
11823
10509
9458
3x150/25
390
0.558
435
0.158
0.099
3.25
6471
5823
5294
11268
10141
9219
3x185/25
436
0.558
487
0.126
0.096
3.25
6935
6304
10850
9864
3x240/25
591
0.558
660
0.096
0.093
3.25
7535
7708
Cable length =
10581
System voltage is 11 kV
Page 49 of 80
APPENDIX E
TABLE 11 - CABLE SELECTION CHART FOR 11 kV MOTOR FEEDER (installed underground in sand filled trenches) - RUNNING & STARTING CON
Load data
Cable data
running
* CABLE REACTANCE
@ 50Hz [/km] = X
* CABLE RESISTANCE
@ 90OC [/km] = Rx
DERATING FACTOR
CABLE RATING
[Amps]
Cable type
(No. conductors x CSA) [mm2]
Cables in parallel
CIRCUIT TYPE
starting
kW (rated)
3000
3500
4000
4500
5000
5500
3000
3500
4000
4500
5000
5500
cos
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
Page 50 of 80
APPENDIX E
Page 51 of 80
APPENDIX E
Page 52 of 80
APPENDIX E
TABLE 12 - CABLE SELECTION CHART FOR 6 kV MOTOR FEEDER (installed in air on cable tray) - RUNNING & STARTING CONDITIONS
Load data
Cable data
running
* CABLE REACTANCE
@ 50Hz [/km] = X
kW (rated)
* CABLE RESISTANCE
@ 90OC [/km] = Rx
DERATING FACTOR
CABLE RATING
[Amps]
Cable type
(No. conductors x CSA) [mm2]
Cables in parallel
CIRCUIT TYPE
cos
starting
250
300
400
500
530
560
600
670
700
250
300
400
500
530
560
0.865
0.865
0.875
0.875
0.875
0.875
0.875
0.885
0.885
0.865
0.865
0.875
0.875
0.875
0.875
0.2
0.2
0.16
0.16
0.16
0.16
cos starting
FLC
[Amps]
93.00%
93.00%
94.00%
94.00%
94.00%
94.00%
94.00%
95.00%
95.00%
93.00%
93.00%
94.00%
94.00%
94.00%
94.00%
29.9
35.9
46.8
58.5
62.0
65.5
70.2
76.7
80.1
29.9
35.9
46.8
58.5
62.0
65.5
179.4
215.3
280.8
351.0
372.0
393.1
n = LRC/FLC
LRC
[Amps]
FLC x 1.25
[Amps]
37.4
44.9
58.5
73.1
77.5
81.9
87.7
95.9
100.1
3x50/16
236
0.676
160
0.195
0.097
3.25
13853
11544
8843
7074
6674
6316
5895
5392
5161
57608
48007
38869
31096
29335
27764
3x70/16
291
0.676
197
0.158
0.094
3.25
16375
13646
10469
8375
7901
7478
6979
6394
6120
62420
52017
41792
33433
31541
29851
3x95/16
353
0.676
239
0.126
0.092
3.25
3x120/25
402
0.676
272
0.096
0.089
3.25
3x150/25
454
307
0.077
0.088
3.25
0.676
7269
Cable length =
System voltage is 6 kV
Page 53 of 80
APPENDIX E
670
700
0.875
0.885
0.885
0.16
0.16
0.16
94.00%
95.00%
95.00%
70.2
76.7
80.1
421.2
460.1
480.7
25913
23721
22704
27861
25504
24411
25962
Page 54 of 80
APPENDIX E
TABLE 13 - CABLE SELECTION CHART FOR 6 kV MOTOR FEEDER (installed underground in sand filled trenches) - RUNNING & STARTING CONDITIONS
Load data
Cable data
running
* CABLE REACTANCE
@ 50Hz [/km] = X
kW (rated)
* CABLE RESISTANCE
@ 90OC [/km] = Rx
DERATING FACTOR
CABLE RATING
[Amps]
Cable type
(No. conductors x CSA) [mm2]
Cables in parallel
CIRCUIT TYPE
300
400
500
530
560
600
670
700
250
300
400
500
530
560
0.865
0.865
0.875
0.875
0.875
0.875
0.875
0.885
0.885
0.865
0.865
0.875
0.875
0.875
0.875
0.2
0.2
0.16
0.16
0.16
0.16
cos starting
FLC
[Amps]
93.00%
93.00%
94.00%
94.00%
94.00%
94.00%
94.00%
95.00%
95.00%
93.00%
93.00%
94.00%
94.00%
94.00%
94.00%
29.9
35.9
46.8
58.5
62.0
65.5
70.2
76.7
80.1
29.9
35.9
46.8
58.5
62.0
65.5
179.4
215.3
280.8
351.0
372.0
393.1
57608
48007
38869
31096
29335
27764
33433
31541
29851
33545
31748
n = LRC/FLC
LRC
[Amps]
FLC x 1.25
[Amps]
3x50/16
213
0.558
119
0.195
0.097
3.25
3x70/16
260
0.558
145
0.158
0.094
3.25
3x95/16
309
0.558
172
0.126
0.092
3.25
3x120/25
349
0.558
195
0.096
0.089
3.25
3x150/25
390
218
0.077
0.558
cos
starting
250
0.088
37.4
44.9
58.5
73.1
77.5
81.9
87.7
95.9
100.1
13853
11544
8843
7074
6674
6316
5895
5392
5161
8375
7901
7478
6979
6394
6120
9365
8864
8273
7594
7269
10807
10087
9283
8886
11701
10796
10334
3.25
Cable length =
System voltage is 6 kV
Page 55 of 80
34145
APPENDIX E
670
700
0.875
0.885
0.885
0.16
0.16
0.16
94.00%
95.00%
95.00%
70.2
76.7
80.1
421.2
460.1
480.7
25913
23721
22704
27861
25504
24411
29631
27124
25962
31869
29173
27922
33190
30382
29080
Page 56 of 80
APPENDIX E
TABLE 14 - CABLE SELECTION CHART FOR 400V OUTGOING FEEDERS (installed in air on cable tray)
Cable data
Load data
CABLE (CIRCUIT)
INSTALLED RATING
[Amps]
* CABLE RESISTANCE
@ 90OC [/km] = Rx
* CABLE REACTANCE
@ 50Hz [/km] = X
4x2.5
32
0.676
22
9.448
0.09
135
81
4x4
42
0.676
28
5.878
0.09
217
130
81
65
52
4x6
54
0.676
37
3.927
0.08
323
194
121
97
78
61
4x10
75
0.676
51
2.333
0.08
541
325
203
162
130
101
81
65
4x16
100
0.676
68
1.466
0.08
854
512
320
256
205
160
81
102
81
798
499
399
319
250
128
160
127
100
1093
683
547
437
342
200
219
174
137
109
909
727
582
455
273
291
231
182
145
116
1277
1021
817
638
364
409
324
255
204
163
128
858
511
549
436
343
275
220
172
137
1050
687
672
533
420
336
269
210
168
840
801
636
501
401
320
250
200
160
960
762
600
480
384
300
240
192
1182
938
739
591
473
370
296
236
872
697
558
436
349
279
687
549
439
343
275
220
2 x 3 cores
cable
N/A
4x25
127
0.676
86
0.927
0.08
3x35/25
158
0.676
107
0.668
0.07
3x50/25
192
0.676
130
0.493
0.07
3x70/35
246
0.676
166
0.342
0.07
3x95/50
298
0.676
201
0.246
0.07
3x120/70
346
0.676
234
0.195
0.07
3x150/95
399
0.676
270
0.158
0.07
0.676
308
0.126
0.07
0.07
In -Rated
current/setting
current of
protective device
[Amps]
CABLE RATING
[Amps]
DERATING FACTOR
CIRCUIT TYPE
10
16
20
51
41
1331
25
1099
32
40
50
80
100
125
160
200
250
3x185/95
456
3x240/120
538
0.676
364
0.096
3x300/150
621
0.676
420
0.077
0.07
3x95/50
298
0.676
403
0.246
0.07
3x120/70
346
0.676
468
0.195
0.07
840
672
538
420
336
269
3x150/95
399
0.676
539
0.158
0.07
1001
801
641
501
401
320
3x185/95
456
0.676
617
0.126
0.07
960
768
600
480
384
3x240/120
538
0.676
727
0.096
0.07
Cable ampacities are from IEC 60364-5-52 Table B.52-12, column 3 (see Appendix C)
* Cable Resistance and Reactance are according IEC 60228
1001
63
473
Cable length =
Page 57 of 80
CIRCUIT TYPE
MAX VOLT. DROP [%]
* CABLE REACTANCE
@ 50Hz [/km] = X
* CABLE RESISTANCE
@ 90OC [/km] = Rx
CABLE (CIRCUIT)
INSTALLED RATING
[Amps]
DERATING FACTOR
CABLE RATING
[Amps]
APPENDIX E
TABLE 14 - CABLE SELECTION CHART FOR 400V OUTGOING FEEDERS (installed in air on cable tray)
Cable data
Load data
Page 58 of 80
APPENDIX E
Page 59 of 80
APPENDIX E
Page 60 of 80
APPENDIX E
TABLE 15 - CABLE SELECTION CHART FOR 400V OUTGOING FEEDERS (installed underground in sand filled trenches)
Cable data
Load data
CABLE (CIRCUIT)
INSTALLED RATING
[Amps]
* CABLE RESISTANCE
@ 90OC [/km] = Rx
* CABLE REACTANCE
@ 50Hz [/km] = X
4x2.5
30
0.5115
15
9.448
0.09
135
81
4x4
39
0.5115
20
5.878
0.09
217
130
81
65
4x6
49
0.5115
25
3.927
0.08
323
194
121
97
78
4x10
65
0.5115
33
2.333
0.08
541
325
203
162
130
101
4x16
84
0.5115
43
1.466
0.08
854
512
320
256
205
160
81
798
499
399
319
250
128
160
1093
683
547
437
342
200
219
174
909
727
582
455
273
291
231
1277
1021
817
638
364
409
324
255
858
511
549
436
343
275
1050
687
672
533
420
336
269
840
801
636
501
401
320
960
762
600
480
384
300
1182
938
739
591
473
370
872
697
558
436
349
687
549
439
343
275
2 x 3 cores
cable
N/A
4x25
107
0.5115
55
0.927
0.08
3x35/25
129
0.5115
66
0.668
0.07
3x50/25
153
0.5115
78
0.493
0.07
3x70/35
188
0.5115
96
0.342
0.07
3x95/50
226
0.5115
116
0.246
0.07
3x120/70
257
0.5115
131
0.195
0.07
3x150/95
287
0.5115
147
0.158
0.07
0.5115
166
0.126
0.07
0.07
In -Rated
current/setting
current of
protective device
[Amps]
CABLE RATING
[Amps]
DERATING FACTOR
CIRCUIT TYPE
10
1331
16
20
25
1099
32
40
50
80
100
125
160
200
250
3x185/95
324
3x240/120
375
0.5115
192
0.096
3x300/150
419
0.5115
214
0.077
0.07
3x95/50
226
0.5115
231
0.246
0.07
3x120/70
257
0.5115
263
0.195
0.07
840
672
538
420
336
269
3x150/95
287
0.5115
294
0.158
0.07
1001
801
641
501
401
320
3x185/95
324
0.5115
331
0.126
0.07
960
768
600
480
384
3x240/120
375
0.5115
384
0.096
0.07
Cable ampacities are from IEC 60364-5-52 Table B.52-5, column 8 (see Appendix C)
* Cable Resistance and Reactance are according IEC 60228
1001
63
473
Cable length =
Page 61 of 80
APPENDIX E
TABLE 15 - CABLE SELECTION CHART FOR 400V OUTGOING FEEDERS (installed underground in sand filled trenches)
Cable data
MAX VOLT. DROP [%]
* CABLE REACTANCE
@ 50Hz [/km] = X
CABLE (CIRCUIT)
INSTALLED RATING
[Amps]
DERATING FACTOR
CABLE RATING
[Amps]
* CABLE RESISTANCE
@ 90OC [/km] = Rx
Load data
CIRCUIT TYPE
Page 62 of 80
APPENDIX E
Page 63 of 80
APPENDIX E
Page 64 of 80
APPENDIX E
TABLE 16 - CABLE SELECTION CHART FOR 400V OUTGOING FEEDERS (installed underground in ducts)
Cable data
Load data
CABLE (CIRCUIT)
INSTALLED RATING
[Amps]
* CABLE RESISTANCE
@ 90OC [/km] = Rx
* CABLE REACTANCE
@ 50Hz [/km] = X
4x2.5
28
0.605
17
9.448
0.09
135
81
4x4
36
0.605
22
5.878
0.09
217
130
81
65
4x6
44
0.605
27
3.927
0.08
323
194
121
97
78
4x10
58
0.605
35
2.333
0.08
541
325
203
162
130
101
4x16
75
0.605
45
1.466
0.08
854
512
320
256
205
160
81
798
499
399
319
250
128
160
1093
683
547
437
342
200
219
174
909
727
582
455
273
291
231
182
1277
1021
817
638
364
409
324
255
204
858
511
549
436
343
275
1050
687
672
533
420
336
269
840
801
636
501
401
320
960
762
600
480
384
300
1182
938
739
591
473
370
872
697
558
436
349
687
549
439
343
275
2 x 3 cores
cable
N/A
4x25
96
0.605
58
0.927
0.08
3x35/25
115
0.605
70
0.668
0.07
3x50/25
135
0.605
82
0.493
0.07
3x70/35
167
0.605
101
0.342
0.07
3x95/50
197
0.605
119
0.246
0.07
3x120/70
223
0.605
135
0.195
0.07
3x150/95
251
0.605
152
0.158
0.07
0.605
170
0.126
0.07
0.07
In -Rated
current/setting
current of
protective device
[Amps]
CABLE RATING
[Amps]
DERATING FACTOR
CIRCUIT TYPE
10
16
51
1331
20
25
1099
32
40
50
80
100
125
160
200
250
3x185/95
281
3x240/150
324
0.605
196
0.096
3x300/150
365
0.605
221
0.077
0.07
3x95/50
197
0.605
238
0.246
0.07
3x120/70
223
0.605
270
0.195
0.07
840
672
538
420
336
269
3x150/95
251
0.605
304
0.158
0.07
1001
801
641
501
401
320
3x185/95
281
0.605
340
0.126
0.07
960
768
600
480
384
3x240/150
324
0.605
392
0.096
0.07
Cable ampacities are from IEC 60364-5-52 Table B.52-5, column 8 (see Appendix C)
* Cable Resistance and Reactance are according IEC 60228
1001
63
473
Cable length =
Page 65 of 80
CIRCUIT TYPE
MAX VOLT. DROP [%]
* CABLE REACTANCE
@ 50Hz [/km] = X
* CABLE RESISTANCE
@ 90OC [/km] = Rx
CABLE (CIRCUIT)
INSTALLED RATING
[Amps]
DERATING FACTOR
CABLE RATING
[Amps]
APPENDIX E
TABLE 16 - CABLE SELECTION CHART FOR 400V OUTGOING FEEDERS (installed underground in ducts)
Cable data
Load data
Page 66 of 80
APPENDIX E
Page 67 of 80
APPENDIX E
Page 68 of 80
APPENDIX E
TABLE 17 - CABLE SELECTION CHART FOR 11 kV MOTOR FEEDER (installed underground in ducts) - RUNNING & STARTING CONDITION
Load data
Cable data
running
2 x 3 cores
cable
* CABLE REACTANCE
@ 50Hz [/km] = X
* CABLE RESISTANCE
@ 90OC [/km] = Rx
DERATING FACTOR
CABLE RATING
[Amps]
Cable type
(No. conductors x CSA) [mm2]
Cables in parallel
CIRCUIT TYPE
starting
kW (rated)
3000
3500
4000
4500
5000
5500
3000
3500
4000
4500
5000
5500
cos
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.16
0.16
0.16
0.16
0.16
0.16
cos starting
FLC
[Amps]
96.00%
96.00%
96.00%
96.00%
96.00%
96.00%
96.00%
96.00%
96.00%
96.00%
96.00%
96.00%
183.3
213.8
244.4
274.9
305.4
336.0
183.3
213.8
244.4
274.9
305.4
336.0
1099.6
1069.0
1221.8
1374.5
1527.2
1679.9
n = LRC/FLC
LRC
[Amps]
FLC x 1.25
[Amps]
229.1
267.3
305.4
343.6
381.8
420.0
3x95/16
263
0.605
159
0.246
0.101
3.25
3x120/16
306
0.605
185
0.195
0.097
3.25
3x150/25
342
0.605
207
0.158
0.094
3.25
3x185/25
379
0.605
229
0.126
0.092
3.25
3x240/25
438
0.605
265
0.096
0.089
3.25
7165
3x300/25
513
0.605
310
0.077
0.088
3.25
8355
14323
12533
8740
17979
15732
3x95/16
263
0.605
318
0.246
0.101
3.25
3396
5822
5094
6230
12815
11213
3x120/16
306
0.605
370
0.195
0.097
3.25
7090
6203
5514
14037
12283
10918
3x150/25
342
0.605
414
0.158
0.094
3.25
7368
6549
5894
13206
11739
10565
3x185/25
379
0.605
459
0.126
0.092
3.25
7795
7015
6377
12484
11236
10215
3x240/25
438
0.605
530
0.096
0.089
3.25
8599
7817
12085
10986
8392
Cable length =
System voltage is 11 kV
Page 69 of 80
APPENDIX E
TABLE 17 - CABLE SELECTION CHART FOR 11 kV MOTOR FEEDER (installed underground in ducts) - RUNNING & STARTING CONDITION
Load data
Cable data
running
* CABLE REACTANCE
@ 50Hz [/km] = X
* CABLE RESISTANCE
@ 90OC [/km] = Rx
DERATING FACTOR
CABLE RATING
[Amps]
Cable type
(No. conductors x CSA) [mm2]
Cables in parallel
CIRCUIT TYPE
starting
kW (rated)
3000
3500
4000
4500
5000
5500
3000
3500
4000
4500
5000
5500
cos
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
Page 70 of 80
APPENDIX E
Page 71 of 80
APPENDIX E
Page 72 of 80
APPENDIX E
TABLE 18 - CABLE SELECTION CHART FOR 6 kV MOTOR FEEDER (installed underground in ducts) - RUNNING & STARTING CONDITIONS
Load data
Cable data
running
* CABLE REACTANCE
@ 50Hz [/km] = X
kW (rated)
* CABLE RESISTANCE
@ 90OC [/km] = Rx
DERATING FACTOR
CABLE RATING
[Amps]
Cable type
(No. conductors x CSA) [mm2]
Cables in parallel
CIRCUIT TYPE
cos
starting
250
300
400
500
530
560
600
670
700
250
300
400
500
530
560
0.865
0.865
0.875
0.875
0.875
0.875
0.875
0.885
0.885
0.865
0.865
0.875
0.875
0.875
0.875
0.2
0.2
0.16
0.16
0.16
0.16
cos starting
FLC
[Amps]
93.00%
93.00%
94.00%
94.00%
94.00%
94.00%
94.00%
95.00%
95.00%
93.00%
93.00%
94.00%
94.00%
94.00%
94.00%
29.9
35.9
46.8
58.5
62.0
65.5
70.2
76.7
80.1
29.9
35.9
46.8
58.5
62.0
65.5
179.4
215.3
280.8
351.0
372.0
393.1
n = LRC/FLC
LRC
[Amps]
FLC x 1.25
[Amps]
37.4
44.9
58.5
73.1
77.5
81.9
87.7
95.9
100.1
3x50/16
182
0.605
110
0.195
0.097
3.25
13853
11544
8843
7074
6674
6316
5895
5392
5161
57608
48007
38869
31096
29335
27764
3x70/16
224
0.605
136
0.158
0.094
3.25
16375
13646
10469
8375
7901
7478
6979
6394
6120
62420
52017
41792
33433
31541
29851
3x95/16
263
0.605
159
0.126
0.092
3.25
9927
9365
8864
8273
7594
7269
35557
33545
31748
3x120/25
306
0.605
185
0.096
0.089
3.25
11419
10807
10087
9283
8886
36078
34145
3x150/25
342
207
0.077
12537
11701
10796
10334
0.605
0.088
3.25
Cable length =
System voltage is 6 kV
Page 73 of 80
35560
APPENDIX E
670
700
0.875
0.885
0.885
0.16
0.16
0.16
94.00%
95.00%
95.00%
70.2
76.7
80.1
421.2
460.1
480.7
25913
23721
22704
27861
25504
24411
29631
27124
25962
31869
29173
27922
33190
30382
29080
Page 74 of 80
LV cables
Nominal area
of conductor
(mm2)
Reactance at 50 Hz
R in okm/km
20C
90C
Inductance L in
MH/km
2.5
7.41
9.45
0.297
4.61
5.88
0.279
3.08
3.93
0.266
10
1.83
2.33
0.25
16
1.15
1.47
0.242
25
0.727
0.93
0.244
35
0.524
0.67
0.237
50
0.387
0.49
0.235
70
0.268
0.34
0.231
95
0.193
0.25
0.225
120
0.153
0.20
0.224
150
0.124
0.16
0.224
185
0.0991
0.13
0.224
240
0.0754
0.10
0.224
300
0.0601
0.08
0.222
400
0.047
0.06
0.221
LV cables
Current [A]
Reactance at 50 Hz
Reactance X in
ohm/km
0.093
0.088
0.084
0.079
0.076
0.077
0.074
0.074
0.073
0.071
0.070
0.070
0.070
0.070
0.070
0.069
U/G -D2
30
39
49
65
84
107
129
153
188
226
257
287
324
375
419
Air-E
32
42
54
75
100
127
158
192
246
298
346
399
456
538
621
U/G-D1
28
36
44
58
75
96
115
135
167
197
223
251
281
324
365
MV cables
6kV
11kV
Reactance X
in ohm/km
Reactance X
in ohm/km
0.127
0.12
0.115
0.109
0.101
0.097
0.094
0.092
0.089
0.088
0.134
0.127
0.121
0.115
0.106
0.102
0.099
0.096
0.093
0.09
Rated
output
1.1
1.5
2.2
3
4
5.5
7.5
9
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
Running
4.7
81.40%
0.81
5
82.80%
0.79
5.2
84.30%
0.81
6
85.50%
0.82
6.3
86.60%
0.82
6.5
87.70%
0.83
6.5
88.70%
0.85
6.5
88.70%
0.83
6.5
89.80%
0.83
6.5
90.60%
0.83
6.5
91.20%
0.83
6.5
91.60%
0.84
6.5
92.30%
0.85
6.5
92.70%
0.86
6.5
93.10%
0.86
6.5
93.50%
0.86
6.5
94.00%
0.86
6.5
94.20%
0.86
6.5
94.50%
0.86
6.5
94.70%
0.87
6.5
93.00%
0.87
6.5
93.00%
0.87
cos
Starting
0.7
0.7
0.63
0.62
0.62
0.55
0.55
0.5
0.5
0.5
0.45
0.45
0.4
0.4
0.4
0.4
0.38
0.38
0.37
0.36
0.35
0.3
Rated
output
185
200
220
250
280
300
315
335
375
400
425
450
475
500
530
560
600
630
670
710
750
800
Running
6
0.93
0.865
6
0.93
0.865
6
0.93
0.865
6
0.93
0.865
6
0.93
0.865
6
0.93
0.865
6
0.94
0.865
6
0.94
0.875
6
0.94
0.875
6
0.94
0.875
6
0.94
0.875
6
0.94
0.875
6
0.94
0.875
6
0.94
0.875
6
0.94
0.875
6
0.94
0.875
6
0.94
0.875
6
0.94
0.885
6
0.95
0.885
6
0.95
0.885
6
0.95
0.885
6
0.95
0.885
cos
Starting
0.2
0.2
0.2
0.2
0.2
0.2
0.16
0.16
0.16
0.16
0.16
0.16
0.16
0.16
0.16
0.16
0.16
0.16
0.16
0.16
0.16
0.16
850
0.95
0.885
0.16
900
950
1000
1120
1250
1400
1600
1800
2000
2500
3500
4000
4500
5000
6
6
6
6
6
6
6
6
6
6
5
5
5
5
0.96
0.96
0.96
0.96
0.96
0.96
0.96
0.96
0.96
0.96
0.96
0.96
0.96
0.96
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.16
0.16
0.16
0.16
0.16
0.16
0.16
0.16
0.16
0.16
0.16
0.16
0.16
0.16
Cable data
Load data
CABLE (CIRCUIT)
INSTALLED RATING
[Amps]
* CABLE RESISTANCE
@ 90OC [/km] = Rx
* CABLE REACTANCE
@ 50Hz [/km] = X
32
0.72
23
9.448
0.09
498
371
258
192
146
107
80
66
4x4
42
0.72
30
5.878
0.09
797
594
413
307
233
172
128
106
88
4x6
54
0.72
39
3.927
0.08
1188
885
615
458
348
256
190
158
131
97
4x10
75
0.72
54
2.333
0.08
1476
1026
764
580
428
318
264
219
162
132
112
4x16
100
0.72
72
1.466
0.08
1612
1201
912
673
500
416
344
255
208
176
130
4x25
127
0.72
91
0.927
0.08
1413
1043
777
645
534
395
322
273
202
165
3x35/25
158
0.72
114
0.668
0.07
1421
1060
878
728
538
439
372
276
225
3x50/25
192
0.72
138
0.493
0.07
962
712
581
492
365
298
3x70/35
246
0.72
177
0.342
0.07
1338
990
808
686
509
417
3x95/50
298
0.72
215
0.246
0.07
1317
1075
913
679
557
3x120/70
346
0.72
249
0.195
0.07
1108
825
677
3x150/95
399
0.72
287
0.158
0.07
976
802
3x185/95
456
0.72
328
0.126
0.07
1159
954
3x240/150
538
0.72
387
0.096
0.07
3x300/150
621
0.72
447
0.077
0.07
3x95/50
298
0.72
429
0.246
0.07
3x120/70
346
0.72
498
0.195
0.07
3x150/95
399
0.72
575
0.158
0.07
3x185/95
456
0.72
657
0.126
0.07
3x240/150
538
0.72
775
0.096
0.07
Cable ampacities are from IEC 60364-5-52 Table B.52-12, column 3 (see Appendix C)
* Cable Resistance and Reactance are according IEC 60228
* Rx = 1.275 * Ro (ohm/km) : Where Ro = Resistance @20 degrees C. (see Appendix A)
kW (rated)
1.1
1.5
2.2
5.5
7.5
11
15
18.5
22
30
37
0.81
0.79
0.81
0.82
0.82
0.83
0.85
0.83
0.83
0.83
0.83
0.84
0.85
0.86
81.40%
82.80%
84.30%
85.50%
86.60%
87.70%
88.70%
88.70%
89.80%
90.60%
91.20%
91.60%
92.30%
92.70%
FLC
[Amps]
2.4
3.3
4.7
6.2
8.1
10.9
14.4
17.6
21.3
28.8
35.3
41.3
55.2
67.0
FLC x 1.25
[Amps]
3.0
4.1
5.8
7.7
10.2
13.6
17.9
22.1
26.6
36.0
44.1
51.6
69.0
83.7
cos
CABLE RATING
[Amps]
DERATING FACTOR
2 x 3 core
cable
n/a
4x2.5
Cable type
(No. conductors x CSA)
[mm2]
Cables in parallel
CIRCUIT TYPE
1162
1163
Cable length =
45
55
75
90
110
132
0.86
0.86
0.86
0.86
0.86
0.87
93.10%
93.50%
94.00%
94.20%
94.50%
94.70%
81.1
98.7
133.9
160.4
195.4
231.3
101.4
123.4
167.4
200.4
244.2
289.1
186
246
203
344
283
208
460
378
279
233
559
459
339
283
232
663
544
401
335
275
788
647
477
399
327
276
960
789
582
486
399
338
1122
922
680
568
466
395
919
756
557
465
382
321
1118
919
677
566
464
391
1325
1089
803
670
550
464
1295
954
797
654
552
1164
972
798
675