Earthing and Fault Levels: Voltage Type of Earthing Fault Current Fault Level
Earthing and Fault Levels: Voltage Type of Earthing Fault Current Fault Level
The following earthing systems and design fault currents (3-phase symmetrical) are in use
throughout the distribution network:
Voltage
132kV
33kV
11kV
6.6kV
LV
Type of earthing
Solid Earthing
Impedance Earthed
Impedance Earthed
Impedance Earthed
Solid Earthed (PME)
Fault current
21.9kA
17.5kA
13.1kA
21.9kA
27kA
Fault level
5000MVA
1000MVA
250MVA
250MVA
19.4MVA
Where the network is impedance earthed the typical neutral earth resistor will limit the earth
fault current to 1000A per transformer, i.e. giving a maximum earth fault level of up to 3kA.
Earthing for substations and networks must comply with the following documents:
CP335 - Earthing design for 132kV, 33kV and 33/11/6.6kV primary substations and
equipment
These documents, in turn, reference a number of industry standards including ENATS 41-24,
ENA ER S34, ER S36 and BS7430.
Design earth fault clearance times are:
Voltage
132kV
33kV
11/6.6kV
Clearance time
200ms
500ms
1s