Cable Sizing With Clarifications1111111

This document provides sizing calculations for cable C-SMSB.40.G.1 which runs from the main distribution board MDB.1 to switchboard SMSB.40.G.1. It calculates the design current, selects a 630A rated cable based on ampacity tables, and verifies that the cable meets protection and voltage drop criteria.

Uploaded by

hanyalramady
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
84 views1 page

Cable Sizing With Clarifications1111111

This document provides sizing calculations for cable C-SMSB.40.G.1 which runs from the main distribution board MDB.1 to switchboard SMSB.40.G.1. It calculates the design current, selects a 630A rated cable based on ampacity tables, and verifies that the cable meets protection and voltage drop criteria.

Uploaded by

hanyalramady
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

CABLE / BREAKER SIZING SHEET

Proj.No. :
1361

According to IEE, IEC & Egyptian Code

rev 0

BUILDING (40)

CABLE NO.: F-SMSB.40.G.1

Multi-core Copper conductor,Low Voltage,Power cable

route/type
AIR
XLPE

destination

From
To
Length

:
:
:

MDB.1
SMSB.40.G.1
150
m

Design Current ,

Ib =

Nearest Nominal AT ,

load

0.380 kV
238 kW
0.8 p.f.

Max. Dem. KW
3 x kV x p.f.
In=
500

452

CABLE / LOAD DATA

A
TO IEC STANDARD.

630 AF

frame

.
BREAKER SIZING

Correction Factor,C.F.=

Ca x Cg x Cf x Ci
= 1 x Cg x 1 x 1
= 0.91

target Ampacity, It =

Ib
C.F.
ccc >=
ccc =

Select Cable Size:

=
It
404

use

(Ca= 1 for ambient temperature)

Sewedy p. 15

(Cg= 0.91 for grouped cables)


(Cf=1, for cables protected by C.B.)
(Ci=1, for uninsulated installation)
452
= 497
A
0.91

Sewedy p.17, 18

for S =

497

404

Derated Ampacity , Iz=

735

2
808

mm2 -- Sewedy p. 63
2
// cables x 185 mm
A ( catalog ccc )

AIR
multicore

S.C. - CABLE SIZING

S.C.C. Sending End S.E.Imped.(in milli Ohms) =

3.48

+ Cable

Cab.Imped.(in milli Ohms) =

10.44

Receiving End

R.E.Imped.(in milli Ohms) =

13.92

CCC x C.F
=

185

------>>

R.E.Symm.Fault (in kA) =


CHECK PROTECTION CRITERIA :
1- That Iz

15.77

(=kV*1000/sqrt(3)*R.E.Imped.milli Ohms)

>=

735 >=

In
500

, or ,

SUCCEED

CHECK VOLTAGE DROP CRITERIA :


1- Individual V.D. :
V.D.1 = mV/A/m / # cables x Ib x L
mV -> Sewedy p. 23
= 0.241
x
452.4 x 150
XLPE
2
=
8.177 V
=
2.152 %
2- Accumulated V.D. :
Acc V.D.= V.D.1
+ V.D. on upstream cable
= 2.152
+
0.024 % ----> REFER TO DATA OF UPSTREAM CABLE
= 2.176 %

(Should be <=

2.5

%)
DESIGN

SUCCEED

VERIFICATION