Cable Sizing With Clarifications1111111
Cable Sizing With Clarifications1111111
Proj.No. :
1361
rev 0
BUILDING (40)
route/type
AIR
XLPE
destination
From
To
Length
:
:
:
MDB.1
SMSB.40.G.1
150
m
Design Current ,
Ib =
Nearest Nominal AT ,
load
0.380 kV
238 kW
0.8 p.f.
Max. Dem. KW
3 x kV x p.f.
In=
500
452
A
TO IEC STANDARD.
630 AF
frame
.
BREAKER SIZING
Correction Factor,C.F.=
Ca x Cg x Cf x Ci
= 1 x Cg x 1 x 1
= 0.91
target Ampacity, It =
Ib
C.F.
ccc >=
ccc =
=
It
404
use
Sewedy p. 15
Sewedy p.17, 18
for S =
497
404
735
2
808
mm2 -- Sewedy p. 63
2
// cables x 185 mm
A ( catalog ccc )
AIR
multicore
3.48
+ Cable
10.44
Receiving End
13.92
CCC x C.F
=
185
------>>
15.77
(=kV*1000/sqrt(3)*R.E.Imped.milli Ohms)
>=
735 >=
In
500
, or ,
SUCCEED
(Should be <=
2.5
%)
DESIGN
SUCCEED
VERIFICATION