DOC040.52.10005.Oct12 Nutrients - Web
DOC040.52.10005.Oct12 Nutrients - Web
DOC040.52.10005.Oct12 Nutrients - Web
Author:
Dipl.-Ing. Michael Winkler
- Project Leader, Product Development and Customer Service
- BIOSERVE GmbH, Mainz
Carbon
Carbon is the principal component of the
organic substances found in wastewater.
It is biodegraded by the microorganisms
in activated sludge under anaerobic conditions (bio-P), in an anoxic environment
(denitrification zone) and in the aerated
part of the biological stage (nitrification
zone). The microorganisms use the carbon compounds to build their cell structures and to generate energy.
Carbon compounds are determined
as COD, BOD5 or TOC
Nitrogen
In the inflow of wastewater treatment
plants, nitrogen is present in organically
bonded form (organic N) and as ammonium nitrogen (NH4-N). During biological
www.hach-lange.com
Nitrification
Denitrification
Organic N compounds
(urea, proteins, etc.)
Hydrolysis and ammonification
Ammonium-nitrogen NH4-N
Nitrate-nitrogen NO3-N
Nitrate reductase
- Oxygen
Nitrite-nitrogen NO2-N
Nitrosomonas
+ Oxygen
Nitrite-nitrogen NO2-N
Nitrite reductase
- Oxygen
Nitrate-nitrogen NO3-N
Oxygen
Carbon dioxide CO2
NO, N2O
Nitrobacter
+ Oxygen
Organic C compounds
Sulphur
Septic domestic wastewater and some
industrial wastewater contain reduced
sulphur compounds (hydrogen sulphide,
sulphides and thiosulphates). Sulphur is
an indispensable component of proteins.
In wastewater treatment plants, reduced
sulphur compounds are not only oxidised
chemically to sulphate but are also oxidised by some bacteria to form sulphur
and, since this process generates energy,
are stored inside cells as food reserves.
High concentrations of reduced
sulphur compounds in wastewater can,
however, cause a number of problems
(Table 2).
C:N:P ratio (BOD5:TN:Ptot)
The content of the individual nutrients in
wastewater should correspond to the
needs of the bacteria in the activated
sludge, and there should be a balanced
relationship between C, N and P. This is
crucial to the effectiveness of the biodegradation processes. During aerobic wastewater treatment, the C:N:P ratio should
be in the range between 100:10:1 and
100:5:1.
NUTRIENTS_CALCULATION
If the wastewater in the inflow to the biological stage is deficient in one of the
main nutrients, a wide range of problems
may occur (Table 3).
For efficient denitrification, a certain
proportion of readily biodegradable C
compounds must be present. After
municipal wastewater has passed
through the primary settling tank, it has a
BOD5:N ratio of 100:25 (=5). If the ratio
falls below 100:40 (=2.5), the efficiency
of the denitrification process is impaired,
resulting in higher nitrate values in the
outflow. If bypassing the primary treatment and increasing the denitrification
volume fail to bring about any improve-
Causes/Origin of wastewater
High concentrations of sulphur compounds from chemical and protein processing
industries (meat and poultry
processing)
Anaerobic processes in the
sewerage system, which
cause sulphur compounds
to be reduced to hydrogen
sulphide
Possible consequences
Corrective action
Avoid blockages in the
Corrosion in sewers and
sewerage network
tank walls in wastewater
Add iron salts to the sewer
treatment plants
(e.g. at the pumping stations)
Neighbours suffer odour
nuisance
Increased growth of
sulphur oxidising filamentous
bacteria (Type 021 N)
Table 3: Causes and effects of nutrient deficiencies in the biological stage of wastewater treatment
Shortage of
Carbon
Nitrogen
Phosphorus
Possible consequences
Profuse development of filamentous
bacteria (sludge bulking and foam)
Insufficient denitrification
Corrective action
Bypass the primary treatment
Increase the denitrification volume while
retaining sufficient volume for the nitrification
(minimum sludge age of 9 days)
www.hach-lange.com
Example
A municipal wastewater treatment
plant with a high proportion of industrial
wastewater has the following nutrient
parameters in the inflow to the biological
treatment stage (Table 5).
The BOD5:N ratio of 2.45 is too low for
adequate denitrification to occur. External carbon compounds should therefore
be added. However, a number of calculations have to be carried out before this
is done:
Possible consequences
Inadequate denitrification
(high nitrate values in the
outflow)
High COD in the outflow of
the wastewater treatment
plant
Deterioration of bio-P
Corrective action
Addition of C sources to
improve denitrification
Use chemicophysical methods
(ozone treatment, activated
carbon filter, membrane technology) for poorly biodegradable and non-biodegradable
substances
NUTRIENTS_CONTROL
10,000
110
45
3,5
2.45
5.5mg/L
2mg/L
0mg/L
8mg/L
15.5mg/L
www.hach-lange.com
Ethanol
2.09
0.52
1.35
780
To denitrify the remaining 13 mg/L nitrogen, the microorganisms in the activated sludge must be provided with
an additional source of carbon. A daily
wastewater volume of 10,000 m3 has a
nitrogen load of 130 kg. According to
DWA Work Sheet A131, the external
carbon requirement is 5 kg COD/1 kg
NO3-N. This means that, for complete
denitrification to occur, 650 kg COD are
needed per day. If the additional carbon
is provided in the form of acetic acid,
the data provided in Table 8indicate that
607 kg would have to be added each
day. The targeted dosage is based on
the NO3-N values.
Conclusions
Unfavourable nutrient ratios and high
concentrations of individual substances
reduce the degradation efficiency of
biological wastewater treatment processes. Early recognition and continuous
monitoring of critical parameters is therefore essential in order to enable plant
operators to take rapid corrective action
when necessary. Only in this way can
compliance with legal outflow values be
ensured and unnecessarily high wastewater levies be avoided. LANGE cuvette
tests and continuously operating process
measurement devices have demonstrated that they are indispensable aids
to achieving greater transparency and
reliability.
Filter
Final sedimentation
Thickener
Aeration
Primary settling
Screen/grit chamber
Digester
Channel
Storm-water tank
Sludge dewatering
Fig. 2: Schematic representation of a wastewater treatment plant with measurement locations for nutrient monitoring
NUTRIENTS_MEASUREMENT SOLUTIONS
LT 200
Alternative
HT 200S
Cuvette tests
PHOSPHAX sc
AISE sc
AN-ISE sc
NISE sc
NITRATAX sc
SC1000 Controller
Alternative
SC200 Controller
Literature
1. ATV-Handbuch: Biologische und weitergehende Abwasserreinigung, Ernst & SohnVerlag 1997
2. K. Hnel: Biologische Abwasserreinigung mit
Belebtschlamm, VEB Gustav Fischer Verlag,
1986
3. K. Mudrack, S. Kunst: Biologie der Abwasserreinigung, Gustav Fischer Verlag, 1994
4. Arbeitsblatt DWA A 131
5. S. Kunst, C. Helmer, S. Knoop: Betriebsprobleme auf Klranlagen durch Blhschlamm,
Schwimmschlamm, Schaum, Springer-Verlag
2000
6. D. Jenkins, M. G. Richard, G. T. Daigger:
Manual on the causes and control of activated sludge bulking, foaming, and other solids
separation problems, Lewis Publishers 2004
7. Poster Betriebssicherheit und Kosteneinsparung mit HACH LANGE, DOC140.72.00449
DOC040.52.10005.Oct12
AMTAX sc