Lightening Arrester Simulation
Lightening Arrester Simulation
I. NOMENCLATURE
PCC- Point of common coupling
LA-lightning arrester
BIL-basic insulation level
MOV-metal oxide varistor
ATP-Alternative Transient program
EMTP-Electromagnetic Transients Program
LLS-Lightning locating systems
II. INTRODUCTION
discharges which may have missed the rods, [2]. The wires
must be well grounded otherwise the lightning current may
jump from the wires into the protected structure in search of a
better ground. Grounding is accomplished by connecting the
wires to long rods which are driven into ground or by
connecting the wires to large buried metallic conductors. The
buried conductors have to be connected to all nearby gas
pipes, water pipes, or other buried metallic pipes or cables.
To protect high voltage transmission lines from lightning,
the metallic rods and wire conductors are replaced by a system
of wires suspended between tall towers arranged around the
structure. These grounded wires are strung above the high
voltage lines to intercept strokes that would otherwise hit the
power lines, [2].
If a lightning stroke hits a power line, the only way to
protect it is using a lightning arrester (LA). The lightning
arrester is a non-linear device that acts as an open circuit to
low potentials, but conducts electrical current at very high
potentials. When lightning strikes a line protected with a
lightning arrester, the non-linear resistance draws the current
to ground.
One of the most common lightning arresters is the MOV
(metal oxide varistor) lightning arrester, [4]. The MOV has a
piece of metal oxide that is joined to the power and grounding
line by a pair of semiconductors. The semiconductors have a
variable resistance dependent on voltage. When the voltage
level in the power line is at the rated voltage for the arrester,
the electrons in the semiconductors flow in a way that creates
a very high resistance. If the voltage level in the power line
exceeds the arrester rated voltage, the electrons behave
differently and create a low resistance path that conducts the
injected lightning current to the ground system.
D. Description of a Lightning Discharge
A lightning discharge is called a flash, [2]. The duration of
a flash is only a few tenths of a second. Cloud to ground
flashes are composed of a single stroke or a multiple number
of component strokes. Multiple stroke flashes have 3 to 4
strokes. The strokes are typically 40 to 50 milliseconds apart.
The typical lightning peak currents measured at ground
range from 10 kA to 20 kA, but occasionally they range up to
hundreds of thousands of amperes, [2]. The peak current is
reached in a few millionths of a second, and then it decreases
terminating in a thousandth of a second or so unless
continuing current flows. It is very common that first stokes
have larger currents that subsequent strokes, but this is not
always true.
Lightning flashes which contain continuing currents are
called hot lightning, [2]. The continuing current lasts for one
or two tenths of a second and have a typical peak value of 100
A. Hot lightning ignites fires. The lightning that does not
contain a continuing current is called cold lightning, [2]. Cold
lightning does not set fires, but it is very destructive.
E. Starting a Lightning
The usual flash between the cloud and the ground is
initiated in the base of the cloud, [2]. The initiating discharge,
3
TABLE 1. LIGHTNING CURRENT MAGNITUDE DISTRIBUTION
J. Bipolar Lightning
Lightning current waveforms exhibiting polarity reversals
are denominated bipolar lightning, [8].
Many bipolar
lightning current waveforms have been observed in winter
lightning studies in Japan.
There are basically three types of bipolar lightning
discharges, although some events may belong to more than
one category, [8]:
The first type of bipolar discharges is associated with
a polarity reversal during a slowly-varying
(millisecond-scale) current component, for example
the initial continuous current in object-initiated
lightning or in rocket-triggered lightning. The polarity
reversal may occur one or more times and may
involve an appreciable no-current interval between
opposite polarity portions of the waveform.
The second type of bipolar discharges is characterized
by different polarities of the initial stage current and of
the following return stroke or strokes. The initial
stage current in this waveform is negative and the
return stroke current, followed by a continuing current
is positive.
The third type of bipolar discharges involves return
strokes of opposite polarity. All documented bipolar
discharges in this category (return strokes of opposite
polarity) are of the upward type.
Bipolar lightning discharges are usually initiated by
upward leaders from tall objects, [8]. It appears that positive
and negative charge sources in the cloud are tapped by
different upward branches of the lightning channel.
IV. DEVELOPMENT OF SIMULATION
A. Test System
To assess the impact of lightning strikes on electric power
systems, a test system was assembled using ATPDraw. The
test system is based on the IEEE 34 bus test feeder system [9],
which features three phase balanced and unbalanced loads and
distributed single phase loads. The systems infinite bus is a
69kV connection from the utility. This bus becomes the point
of common coupling (PCC) for a 24.9kV feeder. The original
34 bus IEEE test system featured a 2.5 MVA substation
transformer; this transformer was adjusted to a higher value of
22 MVA, to compensate for additional loads that were going
to be included in the simulation. Per unit impedance values
were kept the same and internal transformer impedance values
were adjusted to the new capacity. The 69kV to 24.9kV
substation transformer and the 24.9kV to 4.16kV transformer
at bus 832 were simulated as a saturable three phase delta-wye
devices based on the standard ATP GENTRAFO model.
Regulating transformers were not included in these
simulations; their impact would be negligible in this kind of
analysis and the added simulation complexity did not justify
the extra precision. For the general system configuration see
figure 1.
B. Lightning flash
The lightning flash simulated in ATPDraw was based on
the cold lightning flash characteristic described in [2]. The
flash is composed of three sequential spikes of varying
magnitudes. The first strike has a magnitude of 20kA, while
subsequent strokes have magnitudes of 12kA and 9kA
respectively. It was implemented in ATPDraw using three
shunt connected ideal current sources. The first stroke has a
duration of 0.6 ms and is presented figure 3.
center strike case and two line end cases (node 806 and 808).
Line end cases were added to see the effects of a lightning
strike directly to the loads, while the center cases were
designed to assess the propagation of the induced lightning
surge across the line. Case numbers and descriptions are
specified in table 4.
TABLE 4: CASE LIST AND CASE DESCRIPTIONS
V. DISCUSSION
C. Cases
Two different scenarios were analyzed for this study. Each
scenario had several cases with varying contact locations. The
first scenario included cases with no lightning arresters
installed on the loads or on the substations, while the second
scenario provided lightning arresters on the loads and
substations, as typically found in distribution feeders. Three
cases were defined for each scenario. Each scenario had a
Fig. 9: Bus 840/848 waveforms with lightning arresters. Note: Only Phase B
is displayed.
Fig. 7: Substation bus voltage after strike.
The plot shown above proves that even though voltages are
being kept at acceptable levels at buses 808 and 806 (bus 806
LA plot not shown, but contain same values of bus 808),
energy dissipation is exceeding maximum total capacity of the
arresters. The plot does seem to indicate, that the arresters
would remain operational until nearing completion the first
stroke. Subsequent strokes most likely will cause arrester
failure. Thus, even though simulations indicate maximum
voltages of 52kV for buses 806/808, this value can be
realistically much higher. This indicates that if such event
could happen in the feeder, higher energy class rated arresters
are required. Otherwise, the LAs must be replaced after an
event of the simulated magnitude. Nevertheless, the arresters
should have dissipated the first and most severe stroke before
failure, most preventing propagation of the highest surges. It
is not unlikely then, that adjacent arresters would dissipate the
additional energy from lesser subsequent discharges without
failure. Maximum voltages across the feeder metered buses
and LA energy dissipation is presented at the end of the
discussion in tables 5 and 6, respectively.
VI. CONCLUSIONS
In this paper, the effects of a lightning strike is presented
and analyzed. A multiple stoke lightning flash was
successfully simulated in ATP. The lightning was used to
investigate the impact of such transient phenomena in a
distribution feeder based upon the IEEE 34 bus test-feeder
configuration. Impact was mitigated using distribution level
surge arresters.
Voltages on buses 806, 808, 832, 840, 848 and the
substation bus were monitored to quantify the effect of a
direct lightning stroke on line 806-808. Several contact points
along line 806-808 were selected to discover the worst case
event.
We can conclude that operating a feeder with no lightning
protection, is very detrimental for system performance. Also,
exposes loads and system devices to unnecessary overvoltages
which may cause insulation flashovers and device failures.
The installation of lightning arresters helps decrease the
adversarial effects resulting of the lightning strike in the
feeder. Our study shows that for certain operating
characteristics of the lightning arrester it can help mitigate one
direct hit multiple-stroke lightning. Nevertheless, the lightning
[4]
[5]
[6]
[7]
[8]
[9]
[10]
[11]
[12]
[13]
VIII. BIOGRAPHIES
Doeg Rodriguez-Sanabria is from Dorado, Puerto
Rico. He is a graduate student at the university of
Puerto Rico-Mayagez, where he will attain a MSEE
on May 2004.