Cruz
Cruz
BSEE/4TH YEAR
ENGR. GERARD FRANCESCO DG. APOLINARIO
EE406/EEF2FA2
ASSESMENT TASK-M[SO(A)]
FEBRUARY 13, 2016
A STANDARD PRACTICE FOR UTILITY COMPANIES IS TO DIVIDE ITS CUSTOMERS INTO SINGLE-PHASE USERS AND THREE-PHASE USERS.
THE UTILITY MUST PROVIDE THREE-PHASE USERS, TYPICALLY INDUSTRIES, WITH ALL THREE PHASES. HOWEVER, SINGLE-PHASE USERS,
RESIDENTIAL AND LIGHT COMMERCIAL, ARE CONNECTED TO ONLY ONE PHASE. TO REDUCE CABLE COSTS, ALL SINGLE-PHASE USERS IN
A NEIGHBORHOOD ARE CONNECTED TOGETHER. THIS MEANS THAT EVEN IF THE THREE PHASE USERS PRESENT PERFECTLY BALANCED
LOADS TO THE POWER GRID, THE SINGLE-PHASE LOADS WILL NEVER BE IN BALANCE, RESULTING IN CURRENT FLOW IN THE NEUTRAL
CONNECTION.
A DISTRIBUTION TRANSFORMER BANK OF THREE SINGLE-PHASE TRANSFORMER IS CONNECTED Y-Y (SHOWN IN FIGURE a.)). THE
SECONDARIES OF THE BANK SUPPLY POWER TO A 4003 V, 3-, FOUR-WIRE SYSTEM. THE LOAD IN THE SYSTEM CONSIST OF:
STREET LIGHTS A 48 kW, 1-, PHASE AN
STREET LIGHTS B 30 kW, 1-, PHASE BN
STREET LIGHTS C 60 kW, 1-, PHASE CN
15 RESIDENTIAL HOUSES 10 kW, 0.95 LAGGING, 1- EACH, PHASE AN
35 RESIDENTIAL HOUSES 10 kW, 0.95 LAGGING, 1- EACH, PHASE BN
25 RESIDENTIAL HOUSES 10 kW, 0.95 LAGGING, 1- EACH, PHASE CN
2 COMMERTIAL ESTABLISHMENT 15 kVA, 0.94 LAGGING, 1- EACH, PHASE AN
3 COMMERTIAL ESTABLISHMENT 15 kVA, 0.94 LAGGING, 1- EACH, PHASE BN
4 COMMERTIAL ESTABLISHMENT 15 kVA, 0.94 LAGGING, 1- EACH, PHASE CN
BLDG 1 20 kVA, 0.6 pf LAGGING, 3-
BLDG 2 12 kW, 0.75 pf LAGGING, 3-
BLDG 3 18 kW, 0.8 pf LAGGING, 3-
BLDG 4 10 kVA, 0.6 pf LEADING, 3-
1 MALL 400 kVA, 0.8 pf LAGGING, 3-
FIND:
a.) THE TRANSFORMER TURNS RATIO
b.) THE APPROPRIATE NEUTRAL IMPEDANCE IF THE NEUTRAL VOLTAGE IS TO REMAIN BETWEEN 10 V TO 20 V
c.) THE CAPACITOR TO BE CONNECTED IN EACH PHASE TO MAINTAIN THE POWER FACTOR TO 0.95 LAGGING
SOLUTION:
a.) =
13.8103
400
69
2
= 69: 2
15(10 )
cos1 0.95
0.95
2 =
4000
2 = 394.7368 18.1949
35(10 )
cos 1 0.95
2 = 0.95
400 120
2 = 921.0526 138.1949
25(10 )
cos1 0.95
0.95
2 =
400 240
2 = 657.8947101.8051
BLDG 1 (3-):
20 cos1 0.6
4 =
3(4000)
4 = 16.6667 53.1301
4 = 16.6667 173.1301
4 = 16.6667 293.1301
BLDG 2 (3-):
12 cos1 0.75
5 =
3(0.75)(4000)
5 = 13.3333 41.4096
5 = 13.3333 161.4096
5 = 13.3333 281.4096
BLDG 3 (3-):
18 cos1 0.8
6 =
3(0.8)(4000)
6 = 18.75 36.8699
6 = 18.75 156.8699
6 = 18.75 276.8699
BLDG 4 (3-):
10 cos1 0.6
7 =
3(4000)
7 = 8.333353.1301
7 = 8.3333 66.8699
7 = 8.3333 186.8699
1 MALL (3-):
8 =
3(4000)
8 = 333.3333 36.8699
8 = 333.3333 156.8699
8 = 333.3333 276.8699
FOR THE NEUTRAL IMPEDANCE, THE NEUTRAL VOLTAGE MUST BE BETWEEN 10 V TO 20 V (i.e., 10<V<20).
10 < < 20
20
10
<
<
480.9335 480.9335
20.7929103 < < 41.5858103
THE APPROPRIATE NEUTRAL IMPEDANCE MUST BE BETWEEN 20.7929 m TO 41.5858 m
4002
= 5.33330
1 =
30 0
STREET LIGHTS C (1-):
4002
) = 2.66670
1 = (
60 0
4002
2 =
10
15
cos1 0.95
0.95
= 0.9627 + 0.3164
2
4002
2 =
10
35
cos 1 0.95
0.95
= 0.4126 + 0.136
2
2 =
10
35
cos1 0.95
0.95
= 0.5776 + 0.1898
2
+
+
1
1
1
1
+
+
+
4002
3 =
4002
3 =
1
3(10 ) cos 0.94
3 = 3.3422 + 1.2131
4002
3 =
4(10 ) cos1 0.94
3 = 2.5067 + 0.9098
BLDG 1 (3-):
3(400)2
4 = 4 = 4 = (
)
20 cos 1 0.6
= = = 14.4 + 19.2
4
BLDG 2 (3-):
3(400)2
5 = 5 = 5 = (
)
12
cos1 0.75
0.75
5 = 5 = 5 = 22.5 + 19.8431
BLDG 3 (3-):
3(400)2
)
6 = 6 = 6 = (
18
1
cos 0.8
0.8
6 = 6 = 6 = 17.0667 + 12.8
3(400)2
)
8 = 8 = 8 = (
400 cos1 0.8
= = = 0.96 + 0.72
BLDG 4 (3-):
3(400)2
7 = 7 = 7 = (
)
10 cos 1 0.6
= = = 28.8 38.4
7
1 MALL (3-):
BY PER PHASE ANALYSIS, WE CAN SOLVE FOR THE EQUIVALENT IMPEDANCE IN EACH PHASE AS:
1
= 1 2 3 4 5 6 7 8 =
= 0.3869 + 0.1666
1
1
1
1
1
1
1
1
+
+
+
+
+
+
+
1 2 3 4 5 6 7 8
1
= 0.2521 + 0.1024
= 1 2 3 4 5 6 7 8 =
1
1
1
1
1
1
1
1
+ + + + + + +
1 2 3 4 5 6 7 8
1
= 0.2829 + 0.1118
= 1 2 3 4 5 6 7 8 =
1
1
1
1
1
1
1
1
+
+
+
+
+
+
+
+
+
1
1
1
1
+
+
+
+ +
=
=
1
1
1
1
1
+ + +
2 +
1
1
1
+
+
= 481.3698177.3446 / 2 =
+
+
= 9.3358 22.2179 /
( 1 =
10< <20
10< 1 1 <20
2 +
1
2 +
1
>
1
10
1
1
> 2 +
10
1
1
2 >
10
<
1
2
10
1
20
1
>
20
1
>
2
20
1
<
1
2
20
1
1
<
<
481.3698177.3446
481.3698177.3446
9.3358 22.2179
9.3358 22.2179
10
20
FOR THE CAPACITOR CONNECTED IN EACH PHASE, WE MUST SOLVE FIRST FOR THE POWER IN EACH PHASE TO MAINTAIN THE
POWER FACTOR TO 0.95 LAGGING (WE CANNOT USE = 3 2 HERE SINCE THE SYSTEM IS UNBALANCED) THEN WE CAN SOLVE
FOR THE CAPACITANCE THROUGH THE EQUATION = (tan tan )
= 48 0 +
cos1 0.95 + 2(15 ) cos1 0.94 +
0.95
= 348.8667 + 150.2321 = 379.83923.2981
= 348.8667
= (tan tan )
20 cos1 0.6
3
12
+ 0.75
cos1 0.75
3
18
+ 0.8
cos1 0.8
3
10 cos1 0.6
4002
= 348.8667 (tan (cos1 0.95) tan 23.2981)
1
2(60)
= 589.6207
12
18
1
cos 1 0.8
35(10 )
20 cos1 0.6 0.75 cos 0.75
cos 1 0.95 + 3(15 ) cos1 0.94 +
+
+ 0.8
3
0.95
3
3
10 cos 1 0.6 400 cos 1 0.8
+
+
3
3
= 30 0 +
= (tan tan )
4002
= 544.9667 (tan (cos 1 0.95) tan 22.0818)
1
2(60)
= 695.7145
12
18
1
cos1 0.8
25(10 )
20 cos1 0.6 0.75 cos 0.75
cos1 0.95 + 4(15 ) cos1 0.94 +
+
+ 0.8
3
0.95
3
3
10 cos 1 0.6 400 cos 1 0.8
+
+
3
3
= 489.0667 + 193.3358 = 525.894421.5697
= 489.0667
= 60 0 +
= (tan tan )
4002
= 489.0667 (tan (cos 1 0.95) tan 21.5697)
1
2(60)
= 540.2587
METHOD 2: (POWER FACTOR CORRECTION USING = 2 , THROUGH THE EQUIVALENT RESISTANCE IN EACH PHASES)
FOR THE TOTAL POWER IN PHASE A:
= 2 ( ) = 949.59742 (0.3869)=348881.3574 W
= (tan tan )
4002
= 348881.3574 (tan (cos1 0.95) tan 23.2968)
1
2(60)
= 589.4899
= (tan tan )
4002
= 544958.2069 (tan (cos 1 0.95) tan 22.1064)
1
2(60)
= 700.2219
= (tan tan )
4002
= 489001.3491 (tan (cos 1 0.95) tan 21.5636)
1
2(60)
= 539.1559