Over Current Protection
Over Current Protection
Introduction
As the fault impedance is less than load impedance, the fault current is
more than load current. If a short circuit occurs the circuit impedance is
reduced to a low value and therefore a fault is accompanied by large current.
The characteristic with definite minimum time and of inverse type is also called
Inverse Definite Minimum Time (IDMT) characteristics (Fig.1).
These current flows through relay coils and the relay picks-up, the relay
contacts close, thereby the trip circuit is closed and the circuit breaker-
operates The over-current protection scheme with three over-current relays
(Fig. 2) responds to phase faults and earth faults including single-phase to earth
fault.
Therefore such schemes are used with solidly earthed systems where phase to
phase and phase to earth faults are likely to occur.
For proper functioning of over-current and earth fault protection, the choice of
CT's and polarity connections should be correct.
2 Two OC relays
with two CT's
for phase to
phase fault
protection.
4 Three OC EF setting
relays with less than
three CT's for phase fault
phase to setting
phase fault
protection and
phase to earth
fault.
5 Two OC and
one EF relays
for phase to
phase and
phase to earth
fault
protection
Earth-Fault Protection
When the fault current flows through earth return path, the fault is called Earth
Fault. Other faults which do not involve earth are called phase faults. Since
earth faults are relatively frequent, earth fault protection is necessary in most
cases. When separate earth fault protection is not economical, the phase
relays sense the earth fault currents. However such protection lacks
sensitivity. Hence separate earth fault protection is generally provided. Earth
fault protection senses earth fault current. Following are the method of earth
fault protection.
IR+I Y +I B =0
The earth-fault relay is connected such that the residual current flows through
it (Figs.3 and Fig. 4), in the absence of earth-fault,
Therefore, the residually connected earth-fault relay does not operate.
However, in presence of earth fault the conditions is disturbed and
(IR+I Y +I B ) is no more zero. Hence flows through the earth-fault relay. If
the residual current is above the pick-up value, the earth-fault relay
operates.
In the scheme discussed here the earth-fault at any location near or away
from the location of CT's can cause the residual current flow. Hence the
protected
zone is not definite. Such protection is called unrestricted earth-fault protection
The zone of protection cannot be accurately defined. The protected area is not
restricted to the transformer/generator winding alone. The relay senses the
earth faults
beyond the transformer/generator winding hence such protection is called
unrestricted earth-fault protection. The earth-fault protection by relay in neutral
to earth circuit depends upon the type of neutral Earthing. In case of large
generators, voltage transformer is connected between neutral and earth
. Let Ia, Ib and I c , be the three line currents and Φa, Φb and Φc be corresponding
components of magnetic flux in the core. Assuming linearity, we get resultant
flux Φ as,
Φ=k (Ia + Ib + I c )
(Ia + Ib + I c )= 3 I c= I n
Where, Io is zero sequence current and In, is current in neutral to ground circuit.
During normal condition, when earth fault is absent,
(Ia + Ib + Ic) = 0
If = 3Iao = In
Hence the zero-sequence component of I o produces the resultant flux Φr in
the core. Hence core balance current transformer is also called as zero
sequence current transformers (ZSCT).
Application for Core Balance CT's with Cable Termination Joints
The termination of a three core cable into three separate lines or bus-bars is
through cable terminal box. Ref. (Fig. 7), the Core Balance Protection is used
along with the cable box and should be installed before making the cable joint.
The induced current flowing through cable sheath of normal healthy cable
needs particular attention with respect to the core balance protection.
The sheath currents (Ish) flow through the sheath to the cover of cable-box and
then to earth through the earthing connection between cable-box. For
eliminating the error due to sheath current (Ish) the earthing lead between the
cable-box and the earth should be taken through the core of the core balance
protection.
Thereby the error due to sheath currents is eliminated. The cable box should be
insulated from earth.
1. Cable terminal box
2. Sheath of 3 core cable connection to (1)
3. Insulator support for 1
4. Earthing connection passing through 5
5. Core balance CT
The metal-clad switchgear can be provided with frame leakage protection. The
switchgear is lightly y insulated from the earth. The metal-frame-work or enclosure
of the switchgear is earthed with a primary of a CT in between (Fig. 8).
The concrete foundation of the switchgear and the cable-boxes and other
conduits are slightly insulated from earth, the resistance to earth being about 12
ohms. In the event of an earth fault within the switchgear, the earth-fault current
finds the' path through the neutral connection. While doing so, it is sensed by
the earth fault relay.
Earthing bus
Earth fault current
EF Relay
Earth
B C
A
R R R R
Directional of flow
For tripping
CB
The current coils in the directional over-current relay are normally connected to
a secondary of line CT. The voltage coil of directional element is connected to
a line VT, having phase to phase output (of 110 V). There are four common
methods of connecting the relay depending upon phase angle between current
in the current coil and voltage applied to the voltage coil.
When fault current can flow in both directions through the relay location, it
is necessary to make the response of the relay directional by the
introduction of directional control elements. These are basically power
measuring devices in which the system voltage is used as a reference for
establishing the relative direction or phase of the fault current.
1. The power system, apart from loads, is reactive so that the fault
power factor is usually low. A relay
V a , Vb and Vc. Normal system
voltages
V b 1 and V c 1 Voltages at fault
location on faulted phases
V b 2 and V c 2 Voltages remote
from fault location
Fig.12 Phase voltages for a
B-C fault
Responding purely to the active component would not develop a high
torque and might be much slower and less decisive than it could be.
1. The system voltage must collapse at the point of short circuit.
When the fault is single-phase, it is the particular voltage across the
short-circuited points which are reduced. So a B—C phase fault will
cause the B and C phase voltage vectors to move together, the locus
of their ends being the original line be for a homogeneous system, as
shown in (Fig.12)
At the point of fault the vectors will coincide, leaving zero voltage across the
fault, but the fault voltage to earth will be half the initial phase to neutral
voltage. At other points in the system the vector displacement will be less,
but relays located at such points will receive voltages which are
unbalanced in their value and phase position.
The effect of the large unbalance in currents and voltages is to make the
torques developed by the different phase elements vary widely and even
differ in sign if the quantities applied to the relay are not chosen carefully.
To this end, each phase of the relay is polarized with a voltage which will
not be reduced excessively except by close three-phase faults, and which
will remain in a satisfactory relationship to the current under all conditions.
Previous Next
Relay connections
This is the arrangement whereby suitable current and voltage quantities are
applied to the relay. The various connections are dependent on the phase
angle, at unity system power factor, by which the current and voltage
applied to the relay are displaced.
Relay maximum torque
The maximum torque angle (MTA) is defined as the angle by which the
current applied to the relay must be displaced from the voltage applied to
the relay to produce maximum torque.
Although the relay element may be inherently wattmetric, its characteristic
can be varied by the addition of phase shifting components to give
maximum torque at the required phase angle.
A number of different connections have been used and these are discussed
below. Examination of the suitability of each arrangement involves
determining the limiting conditions of the voltage and current applied to
each phase element of the relay, for all fault conditions, taking into account
the possible range of source and line impedances.
30° relay connection (0° MTA)
The A phase relay is supplied with current la and voltage V ac. In this case,
the flux due to the voltage coil lags the applied V ac voltage by 90°, so the
maximum torque occurs when the current lags the system phase to neutral
voltage by 30°. For unity power factor and 0 .5 lagging power factor the
maximum torque available is 0 .866 of maximum. Also, the potential coil
voltage lags the current in the current coil by 30° and gives a tripping zone
from 60° leading to 120° lagging currents, as shown in (Fig. 13a).
The most satisfactory maximum torque angle for this connection, that
ensures correct operation when used for the protection of plain feeders, is
0°, and it can be shown that a directional element having this connection
and 0° MTA will provide correct discrimination for all types of faults, when
applied to plain feeders
If applied to transformer feeders , however, there is a danger that at least
one of the three phase relays will operate for faults in the reverse direction;
for this reason a directional element having this connection should never
be used to protect transformer feeders.
This connection has been used widely in the past, and it is satisfactory
under all conditions for plain feeders provided that three phase elements
are employed. When only two phase elements and an earth fault element
are used there is a probability of failure to operate for one condition. An
inter-phase short circuit causes two elements to be energized but for low
power factors one will receive inputs which, although correct, will produce
only a poor torque. In particular a B—C fault will strongly energize the B
element with lb current and Vba voltage, but the C element will receive I c and
the collapsed V cb voltage, which quantities have a large relative phase
displacement, as shown in (Fig. 13b). This is satisfactory provided that
three phase elements are used, but in the case of a two phase and one
earth fault element relay, with the B phase element omitted, operation will
depend upon the C element, which may fail to operate if the fault is close to
the relaying point.
The A phase relay is supplied with lab current and Vac voltage. In this case,
the flux due to the voltage coil lags the applied voltage to the relay by 90°,
so maximum torque is produced when the current lags the system phase to
neutral voltage by 60°. This connection, which uses Vac voltage with delta
current produced by adding phase A and phase B currents at unity power
factor, gives a current leading the voltage Vac by 60°, and provides a correct
directional tripping zone over a current range of 30° leading to 150°
lagging. The torque at unity power factor is 0 .5 of maximum torque and at
zero power factor lagging 0 .866; see (Fig.14).
It has been proved that the most suitable maximum torque angle for this
relay connection, that is, one which ensures correct directional
discrimination with the minimum risk of mal-operation when applied to
either plain or transformer feeders, is 0°.
When used for the protection of plain feeders there is a slight possibility of
the element associated with the A phase mal-operating for a reversed B—C
fault.
60° No. 2 connection (0° MTA)
The A phase relay is supplied with current la and voltage In this case, the
flux of the voltage coil lags the applied voltage by 90° so the maximum
torque is produced when the current lags the system phase to neutral
voltage by 60°. This connection gives
A phase element connected
Ia —Vc
B phase element connected
Ib — Va
C phase element connected
Ic —Vb
90° relay quadrature connection
This is the standard connection for the type CDD relay; depending on the
angle by which the applied voltage is shifted to produce the relay maximum
torque angle, two types are available.
90°- 30° characteristic (30° MTA)
The A phase relay is supplied with la current and Vbc voltage displaced by
30° in an anti-clockwise direction. In this case, the flux due to the voltage
coil lags the applied voltage Vbc by 60°, and the relay maximum torque is
produced when the current lags the system phase to neutral voltage by 60°.
This connection gives a correct directional tripping zone over the current
range of 30° leading to 150° lagging; see (Fig.16). The relay torque at unity
power factor is 0.5 of the relay maximum torque and at zero power factor
lagging 0.866. A relay designed .for quadrature connection and having a
maximum torque angle of 30° is recommended when the relay is used for
the protection of plain feeders with the zero sequence source behind the
relaying point.
90°- 45° characteristic (45° MTA)
The A phase relay is supplied with current la and voltage Vbc displaced by
45° in an anti-clockwise direction. In this case, the flux due to the voltage
coil lags the applied voltage V bc by 45°, and the relay maximum torque is
produced when the current lags the system phase to neutral voltage by 45°.
This connection gives a correct directional tripping zone over the current
range of 45° leading to 135° lagging.
The relay torque at unity power factor is 0 .707 of the maximum torque and
the same at zero power factor lagging; see (Fig.17).
Parallel feeders
If non-directional relays are applied to parallel feeders, any faults that
might occur on any one line will, regardless of the relay settings used,
isolate both lines and completely disconnect the power supply. With this
type of system configuration it is necessary to apply directional relays at
the receiving end and to grade them with the non-directional relays at the
sending end, to ensure correct discriminative operation of the relays during
line. faults. This is done by setting the directional relays R'1 and R'2 as
shown in (Fig.18) with their directional elements looking into the protected
line, and giving them lower time and current settings than relays R1 and R2.
The usual practice is to set relays R'1 and R'2 to 50% of the normal full load
of the protected circuit and 0 .1 TMS, but care must be taken to ensure that
their continuous thermal rating of twice rated current is not exceeded.
Directional relays are more commonly applied to ring mains. In the case of a
ring main fed at one point only, the relays at the supply end and at the mid-
point substation, where the setting of both relays are identical, can be made
non-directional, provided that in the latter case the relays are located on the
same feeder, that is, one at each end of the feeder.
It is interesting to note that when the number of feeders round the ring is an
even number, the two relays with the same operating time are at the same
substation and will have to be directional, whereas when the number of
feeders is an odd number, the two relays with the same operating time are at
different substations and therefore do not need to be directional.
I RS = (Ia + Ib + Ic)
Referring to (Fig. 11) the directional earth-fault relay has two coils. One to
the coils is connected in residual current circuits (Ref. Fig. 5). This coil gets
current during earth-faults. The other coil gets residual voltage,
V RS= V a + V b + V c
('Three phase five limb potential transformer or three separate single phase
potential transformers connected as shown in Fig. 20). The coil connected in
potential-transformer secondary circuit gives a polarizing field.
If a fault occurs at F, the relay at B will operate in 0.25s, and the subsequent
operation of the circuit breaker at B will clear the fault before the relays at C,
D and E have time to operate. The main disadvantage of this method of
discrimination is that the longest fault clearance time occurs for faults in the
section closest to the power source, where the fault level (MVA) is highest.
Discrimination by current relies on the fact that the fault current varies with
the position of the fault, because of the difference in impedance values
between the source and the fault. Hence, typically, the relays controlling the
various circuit breakers are set to operate at suitably tapered values such
that only the relay nearest to the fault trips its breaker. (Fig. 22) illustrates
the method.
(Fig. 22) Radial system with current
discrimination
For a fault at F1, the system short circuit current is given by:
Where
ZS = source impedance
=11 2 / 250 = 0 .485 ohms
ZL1 = cable impedance between C and B 0.24 ohms
ZL2 = cable impedance between B and 4 MVA
transformer 0.04 ohms
ZT = transformer impedance
=0.07(11 2/4) =2.12 ohms
Hence I = 6350/ 2.885 = 2200 A
For this reason, a relay controlling the circuit breaker at B and set to
operate at a current of 2200 A plus a safety margin would not operate for a
fault at F 4 and would thus discriminate with the relay at A. Assuming a
safety margin of 20% to allow for relay errors and a further 10% for
variations in the system impedance values, it is reasonable to choose a
relay setting of 1.3 x 2200, that is, 2860 A for the relay at B. Now, assuming
a fault at F3, that is, at the end of the 11 kV cable feeding the 4 MVA
transformers, the short-circuit current is given by:
I = 6350 /(Zs + ZL1 + ZL2 +ZT)
I = 6350 /(0.485 + 0.24 + 0.04)=8300 Amp.
Alternatively, assuming a source fault level of 130 MVA:
I = 6350 /(0.93 + 0.24 + 0.004)=5250 Amp.
In other words, for either value of source level, the relay at B would
operate correctly for faults anywhere on the 11 kV cable feeding the
transformer.
Previous Next
NOTE: The allowance error in operating time should not be less than 100ms
All this must be obtained without detriment to the general performance of the
relay; in other words, there must be no reduction in the operating torque or
weakening of the damper magnets or contact pressures, and the construction
must remain simple with the minimum number of moving parts. While these
requirements present considerable difficulties in manufacture, owing to
variations in materials and practical tolerances, the progress made in the
GEC Measurements relays has made it possible to discriminate more closely
by reducing the margin between both the current and the time setting of the
relays on adjacent breakers.