PWHT Procedure
PWHT Procedure
PWHT Procedure
د ااه
وت
IBRAHIM BIN S. AL BRAHIM EST
__________________
Binu Joseph
General Manager
This document is issued for used by IBRAHIM BIN S. AL BRAHIM EST. (ISB)
Neither the whole nor any part of this document may be reproduced in
any form without prior written consent of ISB
1
إاه
د ااه
وت
IBRAHIM BIN S. AL BRAHIM EST
TABLE OF CONTENTS
2
إاه
د ااه
وت
IBRAHIM BIN S. AL BRAHIM EST
1.0 Scope
١١ This procedure states explicitly in detail the minimum requirement for the
external load, Post Weld Heat Treatment (PWHT) shall be carried out by the
electrical resistance method for vessels, nozzles, pipes & exchanges.
٢٠ References
The following documents shall be referred to along with this procedure.
a) ASME Boils & Pressure Vessels code section VIII. Dir.1
b) ANSI/ASMI code for pressure piping B31 series.
3
إاه
د ااه
وت
IBRAHIM BIN S. AL BRAHIM EST
٦٠ Method
The procedure for PWHT has to be followed for the various steel grades as mentioned
below.
4
إاه
د ااه
وت
IBRAHIM BIN S. AL BRAHIM EST
All the thermocouple wires should have valid certificate of conformance with a
tolerance of <+/- 0.75% between the temperature ranges 4000 C to 8000 C.
The general ‘K’ type thermocouple wire shall have dimension 1/0.71 mm of Ni-Cr/Ni-A1.
The +ve & -ve charges should be marked properly.
Compensating Cable
The cable recommended shall be twin type wore PVC coated copper/constantan
connection to thermocouple, with proper plug & socket.
Copper constantan compensating cable shall be used for connecting thermocouple
wires & the temperature recorder.
Connect the copper lead (+ve white) to nickel-chromium conductor (non magnetic
yellow) and the constantan lead (-ve) to the nickel –aluminum conductor (magnetic
red)
Compensation Cable Specification
Description:
2 x 13/0.2 mm Cu/Con compensating cable type V, with colour code as per BS 1843
+ve –ve –white
-ve - blue
& sheath red cover
The compensating cable specification should conform to international thermocouple
reference tables BSEN – 60584 – 1 of 1996.
C) Minimum numbers of equally spaced recording thermocouple (T/C), which are required
for any local Post Weld Heat Treatment (PWHT) shall be as follows
I. For pipes having diameter 305mm or less;- 1 T/C.
II. For pipes having diameter > 305mm ≤610 – 2 T/C.
III. For pipes having diameter > 610; - 4 T/C.
• If multiple heating zones are used being not monitored by a primary T/C, then additional
requirements of T/C should be done.
d) For localized PWHT of vessels it should be monitored using a minimum of four sets of
thermocouples, with each set having one T/C on the inside & outside surfaces. The
positioning of each set shall be done on the weld center line at 900 spacing around the
vessel circumference. We may require additional T/C if multiple heating zones are used &
when it is not monitored by a primary set of T/C.
As per client’s requirement or as per code additional thermocouples shall be fixed to
confirm hot zone or gradient limitation.
5
إاه
د ااه
وت
IBRAHIM BIN S. AL BRAHIM EST
f) The thermocouples & positions shall be identified on the particular temperature recording
chart by number of colour / symbol of stamp
g) After the completion of PWHT remove the thermocouples & ground smoothly the area, to
clean & we thus achieve sound metal. As per the specification / instruction of the
inspector the areas are to be examined by MT or PT after grinding.
7.2 Elements
I. The circumferential band width which has to be heated shall be minimum Six (6) times
the thickness of the shell material being welded from each edge of the weld, but not less
than25mm, whichever is greater.
II. The material temperature shall exceed half the heat treatment temperature over a band
at least 2.5 □ Rt where ‘R’ is the bore radius & ‘t’ is the nominal wall thickness on each
side of the weld times.
For welds on pipes diameter ≥250mm, the elements shall be divided in to two or more
control zones, being top & bottom with pads applied symmetrically.
III. If the elements arrangements is not being capable of desired configuration then.
The center time circumferential gap between two bands shall not exceed 30mm or ‘t’
whichever is lesser.
The longitudinal gaps between elements shall not be more than the wall thickness or
50mm, whichever is less. We should be careful to ensure that there are no gaps in 6’O
clock position.
IV. If the welds are of two separate wall thickness then the elements should be so arranged
to give side to side control in addition to top & bottom control.
V. In the case of inclined or vertical welds the pads shall be arranged about the weld to
give independent control above & below weld centerline.
Elements are attached by - Black annealed iron wire
- Mild steel 12mm wide banding strap.
In all cases the minimum requirement shall be two (2) layers for densities (80Kg / m3 &
96Kg / m3)
IV. Insulation shall be fixed using black annealed iron wire taking care, not damaging or
cutting into the insulation.
V. By following proper PWHT cycles, the item or the particular joint shall be completed & the
cooling rate should be controlled under insulation.
7
إاه
د ااه
وت
IBRAHIM BIN S. AL BRAHIM EST
9.0. Precautions
I. Check all cable connections using proper plugs & sockets.
II. Protect the power cables & thermocouple cable from damage.
10.0. Documentations
I. Procure the approval of the PWHT cycle & assignment for the weld joint to be heat
treated. The details to be included in the work sheet are as follows: Material, wall
thickness of shell, heating & cooling rates, soaking temperature & time.
II. Inform the client if you notice any deviation in the heat treatment cycle.
11.0. Report
The heat treatment cycle chart shall be treated as the proof & record for any h.t –
completion. The chart should be providing the following information’s.
I. Client’s Name
II. Contractors
III. Drawing Document Number
IV. Locations of Thermocouples
V. Weld Number on Item
VI. Material Specification
VII. Soaking Time
VIII. Operators / Technicians name & Sign
IX. Date
X. Location map of particular vessels
12.0. Records
Records shall be maintained for a maximum of three months with all charts & documents.
8
إاه
د ااه
وت
IBRAHIM BIN S. AL BRAHIM EST
9
إاه
د ااه
وت
IBRAHIM BIN S. AL BRAHIM EST
ATTACHMENT
THERMOCOUPLE LOCATIONS
NOTE:
1. " " is Thermocouple Location
2. Additional Thermocouple will be used if multiple heat control zones are used, in which a
controlzone is monitored by any of the Primary Thermocouple.
10
إاه
د ااه
وت
IBRAHIM BIN S. AL BRAHIM EST
11