This document analyzes the loads on a wall located in the basement of a building. It summarizes the permanent and useful loads. The permanent loads include the roof load (30.6 kN/m), floor loads (58.28 kN/m), load from parapets (4.686 kN/m), and self-weight of the wall (26.1 kN/m) for a total of 119.666 kN/m. The useful loads include snow load on the flat roof (6.615 kN/m) and load from floors above (17.64 kN/m) for a total of 24.255 kN/m. In total, the loads on the
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
294 views3 pages

Analiza Opterećenja Zidane Zgrade

This document analyzes the loads on a wall located in the basement of a building. It summarizes the permanent and useful loads. The permanent loads include the roof load (30.6 kN/m), floor loads (58.28 kN/m), load from parapets (4.686 kN/m), and self-weight of the wall (26.1 kN/m) for a total of 119.666 kN/m. The useful loads include snow load on the flat roof (6.615 kN/m) and load from floors above (17.64 kN/m) for a total of 24.255 kN/m. In total, the loads on the
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 3

Univerzitet u Sarajevu

Graevinski fakultet .g. 2010/11


Zidane konstrukcije

ANALIZA OPTEREENJA
1

+1.70

+1.02

-1.02

-1.70

STALNO OPTEREENJE OD STROPOVA (2 i 3)


1. KROV
Teraco

2 cm

(0,0224=0,48 kN/m)

Hidroizola cija

Termoizola cija
Parobrana

(HI 2+3 ; TI 8 cm ; PB 0,05 cm) Ukupno:HI+TI+PB=0,50 kN/m

Sloj za nagib
AB ploa
Malter na plafonu

5 cm
15 cm
2 cm

UKUPNO G KROVA

(0,0524=1,20 kN/m)
(0,1525=3,75 kN/m)
(0,0219=0,38 kN/m)

6,94 kN/m

2. STROP
Parket
Cem.Estrih
PVC folija
Termoizolacija 3
AB ploa
Malter na plafonu

2 cm
5 cm

(0,026,4=0,128 kN/m)
(0,0522=1,10 kN/m )

Ukupno:PVCf+HI=0,25 kN/m
15 cm
(0,1525=3,75 kN/m)
2 cm
(0,0219=0,38 kN/m)

Univerzitet u Sarajevu
Graevinski fakultet .g. 2010/11
Zidane konstrukcije

UKUPNO G STROPA

5,608 kN/m

Za stropove pod pozicijom 2 za stalno optereenje uzima se jo i optereenje od pregradnih


zidova na 10% povrine prostorija i visine zida 2,60 m.
0,1(0.152,618)=0,70 kN/ m
Iz sigurnosnih razloga uzet emo da je utjecaj od pregradnih zidova na stropove 1,0 kN/ m
stropa.
pa slijedi da je ukupna teina stropa pod pozicijom 2.
G(str.2)=1,0+5,608=6,608 kN/m
Ukupni teret od krova i stropa na vrh zida koji se nalazi u suterenu.
poz.1 6,94(2,13+2,25)=30,60 kN/m
poz.2 6,61(2,13+2,25)=29,142(stropa)=58,28 kN/m

UKUPNO:88,88 kN/m
STALNO OPTEREENJE OD SERKLAA
25(0,250,25)=1,56 kN/m
Ukupni teret od serklaa na vrh zida koji se nalazi u suterenu.
25(0,250,25) 4(serklaa)=4,686 kN/m
VLASTITA TEINA ZIDA
(0,041,019)(251,02,213)=13,05 kN/m
Utjecaj od vlastite teine zida na vrh zida koji se nalazi u suterenu iznosi:
(0,041,019)(251,02,213) 2(zida)=26,1 kN/m
REKAPITULACIJA STALNOG OPTEREENJA NA VRH ZIDA U SUTERENU
-KROV
(Poz.1)
-STROPOVI (Poz.2)
-SERKLAI
-VLASTITA TEINA ZIDA

30,60 kN/m
58,28 kN/m
4,686 kN/m
26,10 kN/m

UKUPNO G : 119,666 kN/m


2

Univerzitet u Sarajevu
Graevinski fakultet .g. 2010/11
Zidane konstrukcije

KORISNO OPTEREENJE
Za ravni krov optereenje snijegom
q(snijega)=1,50 kN/m
Optereenje snijegom po metru dunom zida iznosi:
Qs=1,5(2,13+2,28)=6,615 kN/m
Korisno optereenje za stropove stambenih prostorija (poz.2) predvieno standardom EC1
[2.E2] iznosi q=2 kN/m.
Q=2(2,13+2,28)=8,822(etae)=17,64 kN/m
REKAPITULACIJA VELIINE KORISNOG OPTEREENJA NA VRH ZIDA U
SUTERENU
-SNIJEG NA RAVNOM KROVU
-KORISNO OPTEREENJE NA ETAAMA

6,615 kN/m
17,64 kN/m

UKUPNO Q : 24,255 kN/m