3 Phase Short Circuit
3 Phase Short Circuit
ANSI/IEC/IEEE
and
Protective Device Evaluation
Users Guide
Copyright 2012
All Rights Reserved
Version 7.00.00
November 2012
Table of Contents
1
INTRODUCTION .................................................................................................................................................. 3
2.1
2.2
2.3
10
11
12
INTRODUCTION ............................................................................................................................................... 54
HOW TO PERFORM EQUIVALENT/REDUCTION CALCULATIONS ..................................................................... 54
SIMPLIFYING THE ORIGINAL SYSTEM BY USING THE COMPUTED EQUIVALENT ............................................ 58
VALIDATION AND VERIFICATION OF THE EQUIVALENT ................................................................................... 62
ANSI/IEEE STANDARD.................................................................................................................................. 72
List of Figures
ii
Table 1: Recommended ANSI Source Impedance Multipliers for 1st Cycle and Interrupting Times ................. 7
Table 2: 30 cycles calculation impedance .......................................................................................................... 8
Table 3: IEC c factor ......................................................................................................................................... 29
Table 4: Resistivity and equivalent earth penetration ....................................................................................... 85
Table 5: IEC voltage factor................................................................................................................................ 86
Table 6: CB rated interrupting time in cycles .................................................................................................... 92
Table 7: K factor ................................................................................................................................................ 95
Table 8: Default Device X/R Values Using DesignBases Library .................................................................... 96
Table 9: n factor based on PF and short circuit level ...................................................................................... 104
Table 10: Icu and k factor................................................................................................................................ 108
Table 11: CB Name plate data ........................................................................................................................ 109
Note:
You can view this manual on your CD as an Adobe Acrobat PDF file. The file name is:
3_Phase_Short_Circuit.pdf
You will find the Test/Job files used in this tutorial in the following location:
C:\DesignBase\Samples\3PhaseSC
Test Files:
ANSI-YY, IEC3632, T123, SC_MCC_SCHEDULE, REDUCTION_ORIGNAL,
REDUCTION_EQUIVALENT
IMPORTANT NOTE: Power Analytics Corporations software products are tools intended to be used
by trained professionals only. They are not substitutes for your professional judgment or for
independent verification and testing of results as they pertain to your specific application. Use of all
Power Analytics Corporation software products is governed by the terms and conditions of the EndUser License Agreement (EULA) you accepted when purchasing and installing the software. You
must comply with these terms and conditions in applying the instructional material in this manual. If
you do not have or are unfamiliar with the contents of your EULA for this software, you should
request, read, and understand a copy of your EULA before proceeding.
Please accept and respect the fact that Power Analytics Corporation has enabled you to make an authorized
disk as a backup to prevent losing the contents that might occur to your original disk drive. DO NOT sell, lend,
lease, give, rent or otherwise distribute Power Analytics Corporation programs / User's Guides to anyone
without prior written permission from Power Analytics Corporation.
All Rights Reserved.
No part of this publication may be reproduced without prior written consent from
Power Analytics Corporation.
iii
The salient features of the Paladin DesignBase advanced short circuit program:
1.1
New Bus Short Circuit Evaluation feature (PDE). Seamlessly provides instant comparison
of short circuit results and bus ratings.
New Impedance Tolerance feature for generators, transformers and feeders. Enables easy
setup of multiple maximum and minimum fault calculations.
Improved photovoltaic short circuit model. Introduces advanced inverter options for
accurate calculations.
New Case Study feature that enables to save customized short circuit options.
New VFD Regenerative Mode. Augments IEC-61363 motor short circuit model with a new
user defined percent rating of let-through current.
INTRODUCTION
A short circuit is an accidental electrical contact between two or more conductors. Protective devices such as
circuit breakers and fuses are applied to isolate faults and to minimize damage and disruption to plants
operation.
2.1
Type of Faults
8%
12 %
10 %
70 %
Severity of fault:
Normally three-phase symmetrical short circuit (3P) can be regarded as the most severe condition. There are
cases that can lead to single phase fault currents exceeding the three-phase fault currents; however, the total
energy is less than a three-phase fault. Such cases include faults that are close to the following types of
equipment:
2.2
Terminology
Arcing Time - the interval of time between the instant of the first initiation of the arc in the protective device
and the instant of final arc extinction in all phases.
Available Short Circuit Current - the maximum short circuit current that the power system could deliver at a
given circuit point assuming negligible short circuit fault impedance.
Breaking Current - the current in a pole of a switching device at the instant of arc initiation (pole separation).
It is also known as Interrupting Current in ANSI Standards.
Close and Latch Duty - the maximum rms value of calculated short circuit current for medium and highvoltage circuit breakers, during the first cycle, with any applicable multipliers with regard to fault current X/R
ratio. Often, the close and latching duty calculation is simplified by applying a 1.6 factor to the first cycle
symmetrical AC rms short circuit current. Close and latch duty is also called first cycle duty, and was
formerly called momentary duty.
Close and Latch Capability - the maximum asymmetrical current capability of a medium or high-voltage
circuit breaker to close, and immediately thereafter latch closed, for normal frequency making current.
The close and latch asymmetrical rms current capability is 1.6 times the circuit breaker rated maximum
symmetrical AC rms interrupting current. Often called first cycle capability. The rms asymmetrical rating
was formerly called momentary rating.
Contact Parting Time - the interval between the beginning of a specified over current and the instant when
the primary arcing contacts have just begun to part in all poles. It is the sum of the relay or release delay and
opening time.
Crest Current / Peak Current the highest instantaneous current during a period.
Fault an abnormal connection, including the arc, of relative low impedance, whether made accidentally or
intentionally, between two points of different voltage potentials.
3 *I a * UN
3 *I K "*UN
Power utilities, all rotating electric machinery, and regenerative drives are sources in fault calculations.
Duty
Table 1: Recommended ANSI Source Impedance Multipliers for 1st Cycle and Interrupting Times
Source Type
1/2-Cycle
Calculations
Interrupting
Time
calculations
Reference
"
s
Local Generator
Synchronous Motor
"
Z dv
Zs
"
dv
Z"
ANSI C37.010
"
dv
ANSI C37.010
"
1.5* Z dv
ANSI C37.010
"
ANSI C37.010
1.5* Z
1.2* Z
1.67* Z
"
3* Z
"
"
ANSI C37.010
ANSI C37.13
Harmonic Filters
Z%
100
Tuned _ harmonic
Xd =
1 LRC
For Induction
Motors
Duty
Interrupting capability
Interrupting capability
N/A
N/A
N/A
Z s"
Generators
'
Z dv
Induction Motors
Synchronous Motors
Infinite impedance
Xd
3.1
To start DesignBase Short Circuit program, Open the T123 sample file under the C:\DesignBase\Samples
folder and click on the short circuit icon as shown below:
The short circuit toolbar will appear showing the analysis method pick list and their corresponding tools
Paladin DesignBase provides several short circuit calculation methods based on ANSI/IEEE Standards and
IEC Standards for both AC three-phase and single-phase networks. The following short circuit calculation
methods are available:
While the T123 sample file is open in DesignBase, Click on the Options icon and the window below will
appear.
Calculation Tab: This tab has the same fields for AC ANSI/IEEE, AC Classical, AC IEC 60909, AC
IEC 61363 and AC Single Phase calculation.
AC Single Phase, faults can be performed only at all buses in this release,
Control Tab: this tab depends on the short circuit method that user selects.
Tolerance Tab: this tab enables to specify equipment impedance tolerances
Case Study: enables users to save combination of customized short circuit options
Base voltage:
o Adjusted by tap/turn ratio if power transformer is run on off nominal taps
o System voltage
Prefault voltage represents the bus voltage at the instant the fault is applied at that bus. It can be:
system voltage, load flow calculated bus voltage or actual/name plate voltage
Default output: Annotation or report
10
Contribution level: Branch contribution levels away from the fault location to be shown in results. The
calculated results are displayed either on the one-line diagram (if Default Output: Annotation is
selected by the user) or printed in the output report (if Default Output: Report is selected by the user)
Fault impedance. This option is applied if the fault is calculated at one bus only
Fault location: selected buses, all buses, sliding fault or series fault; (Sliding and series fault does not
apply to IEC61363 or AC Single phase calculation)
Miscellaneous options: use only X to calculate the faults
Duty type for PDE based on: maximum branch fault flow or total bus fault current
Fault Location
Selection of One Bus: A Bus can be selected:
Graphically on the one line diagram, by a simple click on the desired bus symbol, or
By highlighting the bus name in the Short Circuit Option window and then clicking on the Add
button; the selected bus will be transferred to the Selected Buses list. To remove a bus from the
Selected Buses list highlight the bus name and click on the Remove button.
If one Bus is selected, the short circuit program can determine the bus post-fault voltage and branch
contributions up to 50 levels away of that fault.
Selecting More Than One Bus:
Graphically on the drawing space: click onto the desired first bus, then hold down the shift key;
while the shift key is being held down, select each bus individually
Menu Driven: highlight the desired bus ID in the Short Circuit Option and then click on Add; the
selected buses will be transferred to the Selected Buses list. To remove a bus or several buses
from the Selected Buses List, highlight the bus ID and click on the Remove button. The highlighted
bus/buses will be transferred to the All Buses List.
Notes: Faults at more than one bus, are faulted individually in turn, not simultaneously. Depending
on the specified fault type, the program will place a three-phase, line-to-ground, line-to-line, and lineto-line-to-ground fault at each selected bus which is faulted for short circuit studies.
Selecting All Buses: Fault at all buses can be simulated by selecting the All Buses option under
the Short Circuit Analysis Basic Option.
Faults at All Buses, are faulted individually, not simultaneously. Depending on the specified fault
type, the program will place a three-phase, line-to-ground, line-to-line, and line-to-line-to-ground fault
at all buses which are faulted for short circuit studies.
On the drawing are displayed short circuit components and units as per user selection in the Short
Circuit Back Annotation window.
All faulted buses are colored in Red.
For this tutorial select in the Options window the following options:
11
Fault location: 18
Then click on the analyze icon. The following results will be displayed on the drawing.
12
Sliding Fault:
Paladin DesignBase Short Circuit Program can simulate a fault along a feeder/cable/transmission line. Using
this option eliminates the need to create a dummy bus at a location along the feeder. The figure below shows
examples of evenly spaced sliding faults (F1, F2, F3, and F4) and single point sliding fault at a specific
location (F).
To Bus
From Bus
F1
F2
F3
F4
13
3-Phase Fault
14
Units:
Note:
Line-to-line fault
Line-to-ground fault
Double-Line-to-Ground fault
For this tutorial, select branch contribution, then the Any Position option. Enter 150 feet in the Away From
Bus field and click OK. The following report will be generated after clicking on the Analyze icon on the
Short Circuit toolbar.
Paladin DesignBase
3-Phase Short Circuit v7.00.00
Project No. :
Page
: 1
Project Name:
Date
: 10/23/2012
Title
:
Time
: 02:53:14 pm
Drawing No. :
Company :
Revision No.:
Engineer:
Jobfile Name: T123
Check by:
Scenario
: 1 : mode1
Case
: 1 : Base
-------------------------------------------------------------------------------Electrical One-Line 3-Phase Network for ANSI PDE
-------------------Calculation Options
-------------------Calculating Single Bus Fault
with Fault Z =
0.00000
+ j
0.00000 Ohms
Fault Phases:
Phase A for Line-Ground Fault
Phase B,C for Line-Line or Line-Line-Ground Fault
ANSI/IEEE Calculation:
Using ANSI Std. C37.010-1979 or above.
Separate R and X for X/R, Complex Z for Fault Current
The Multiplying Factors to calculate Asym and Peak are Based on Actual X/R
Peak Time Applies ATPC Equation
Transformer Phase Shift is considered.
Generator and Motor X/R is constant.
Base
Voltages : Use System Voltages
Prefault Voltages : Use System Voltages
15
Page
: 2
:
:
:
:
3C
3C
12
150
->12
Fault R(Ohms) :
Fault X(Ohms) :
Length(Feet) :
0
0
300
Page
: 3
:
:
:
:
System Volt:
0.48
Fault Type
Spot RMS( kA
Spot X/R
3C
3C
12
150
:
):
:
->12
Fault R(Ohms) :
Fault X(Ohms) :
Length(Feet) :
0
0
300
Prefault Volt:
0.48
kV
3-phase
31.17
10.68
Base
Volt:
L-L
27.00
0.48
L-G
28.73
kV
kV
L-L-G
31.31
16
Series Fault:
Series fault types (one phase open, two phases open, and unequal series impedances) with or without
neutral unbalance are supported in the Paladin DesignBase short circuit program. The series fault types are
shown in the figure below. It should be noted that series faults are meaningful only if pre-fault loads have
been taken into account (i.e. load flow solution is considered). For series faults, the equivalent voltage at the
opening point is computed from the pre-fault system current at the unbalance point. The default fault
impedances Za, Zb, and Zn are:
17
Click Ok and the Report Manager for Series Fault Calculation will appear. Only one feeder can be
selected at a time to performed series faults.
18
At the fault (open location) the user can select the fault impedance in ohms.
For this tutorial, the One Phase Open option is used. The following report will be generated after clicking on
the Analyze button on the Short Circuit toolbar.
19
Paladin DesignBase
3-Phase Short Circuit v7.00.00
Project No. :
Page
: 1
Project Name:
Date
: 10/23/2012
Title
:
Time
: 03:56:14 pm
Drawing No. :
Company :
Revision No.:
Engineer:
Jobfile Name: T123
Check by:
Scenario
: 1 : mode1
Case
: 1 : Base
-------------------------------------------------------------------------------Electrical One-Line 3-Phase Network for ANSI PDE
-------------------Calculation Options
-------------------Calculating Series Fault
Fault Phases:
Phase A for One Phase Open Fault
Phase B,C for Two Phases Open Fault
Classical Calculation:
Complex Z for X/R
3C
->12
Prefault Voltage
System
Base
-------------------------Bus
Bus Name
kV
kV
kV
%
Degree
----- ------------------------ -------- -------- -------- -------- -------From 3C
0.48
0.48
0.48
100.10
0.05
To
12
0.48
0.48
0.48
99.94
-0.0
Fault Impedance(Ohms) :
Za =
Zb = Zc =
Zn =
Fault Current Direction :
0 +j
0 +j
0 +j
0
0
0
20
AC ANSI/IEEE Standard
The AC ANSI/IEEE short circuit analysis method is based on a separate R and X matrix method:
Fault current multiplying factors allow setting up marginal coefficients while fault calculations are performed.
The tab provides also information on ANSI Standard impedances first cycle and interrupting cycles: 2-8
cycles as per ANSI/IEEE Std.
For calculating the MF, users can select:
Based on X/R using the equations in section 2.0
Or regardless of the X/R value, the MF is fixed
21
X"
X /R
The above resistance is maintained constant for all time bands and sequences (negative, zero, positive).
3.6
The AC Classical short circuit analysis method is based on the Complex E/Z calculation method and the X/R
ratio is extracted from the complex impedance matrix (X/R). The Calculation Tab is the same as in AC
ANSI/IEEE Standard and provides the same options.
Fault Current Multiplying Factors allow setting up marginal coefficients while fault calculations are performed.
The user can also select the Machine Current Decay, in cycles.
22
X"
X /R
The above resistance is maintained constant for all time bands and sequences (negative, zero, positive). In
this case the X/R ratio will be variable for different time bands and sequences.
3.7
This analysis method is based on the IEC60909 Standard. The Calculation Tab is similar to the AC and
ANSI/IEEE Standard and provides the same options. Users can select calculations based on different
versions of the standard:
1988 Version
2001 Version
23
X"
X /R
The above resistance is maintained constant for all time bands and sequences (negative, zero, positive). In
this case the X/R ratio will be variable for different time bands and sequences.
In the IEC 60909 short circuit program, the control tab allows users to select:
Fault Current Multiplying Factors
The method employed in calculating the Peak Current (method A, B, C or Classical Thevenin)
Also, as per IEC 60909 standard, users can select:
System Voltage
IEC maximum Voltage
IEC minimum Voltage
3.7.1
Method A: uniform ratio R/X. The smallest X/R ratio determines the k factor
Method B: applies to the calculation of peak current in mesh networks X=1.15 multiplied by the X b. Xb
from Fig.8 page 47 IEC 60909 Std.
Method C: applies to the calculation of peak current in mesh networks; The value of X is calculated
from Fig. 8, IEC 60909 and depends on X/R ratio of the network
DesignBase Thevenin: X is calculated from the Thevenin equivalent
24
KG
Un
cmax
(18, IEC 60909 Std.)
U rG 1 X d" sin G
Where:
25
Users should check the above field if the short circuit occurs from a network transformer.
A network transformer (see the figure below) is when a transformer is connecting two or more networks at
different voltages (IEC Std.). For two-winding transformers with and without on-load tap-changer, an
impedance correction factor KT is to be introduced in addition to the impedance evaluated according to IEC
(equation (7) to (9)).
K T 0.95
cmax
1 0.6 X T
26
27
If this option is selected, DesignBase adjusts Z T by using actual transformer tap. In this case, the program
considers the transformer impedance as a function of the transformer tap position.
If the 1988 IEC 60909 version is selected, the c factor values are provided by the program, as in table 3:
28
cmax
cmin
Standard:
Above 1000 V:
Low Voltage networks: 230/400V, 3P3W
Other voltage levels, 3P3W
1.1
1.05
1.05
1
1
1
1
1.05
0.95
1
User Defined:
Above 1000 V:
Low voltage networks: 230/400V, 3P3W/4W
Other voltage levels 3P3W/4W
If the user select the 2001 IEC 60909 version then the c factor values are provided by the
program, as follows:
cmax
cmin
Standard:
Above 1000 V:
A
Other
1.1
1.05
1
0.95
User Defined:
Above 1000 V:
Other
29
IEC 61363 Standard calculates the short circuit instantaneous current as a function of time and displays its
instantaneous values. The method provides an accurate evaluation of the short circuit current for sizing
protective devices and coordinating relays for isolated systems (off-shore platforms and ships electrical
design). The machines sub-transient reactance and time constants are used by this method. The Calculation
Tab is similar to the AC ANSI/IEEE Standard and provides the same options.
DesignBase AC IEC 363 Short Circuit program tools are shown below:
Options
Report Manager
Back Annotation
Analyze
Generators are modeled by their positive sequence sub-transient reactance, and motors are modeled by their
locked-rotor impedance. The sub-transient and transient time constants and dc time constants are also
considered in the calculations.
This application allows users to display results in a standard report format, annotate results on the one line
diagram, and plot short circuit results varying with time.
For this tutorial, open the IEC3632 sample file under the IEC363SC sample folder and then follow the steps
below:
1. Launch the short Circuit program, by clicking on the short circuit program icon.
2. Select the AC IEC 61363 analysis method, and then click on the Options icon to open the Short
Circuit Analysis Basic Option window. The Options features are similar to the ANSI Method.
30
31
As can be seen from the window above, Reports can be set to the following options:
Fast
User Defined
Curve with Time
The AC IEC 61363 Short Circuit program Abbreviations are displayed below:
32
If User Defined Report is selected the additional User Defined Output Options will appear:
33
In order to display Short Circuit Results varying with time, Select Bus B1. Then, click on the Report
Manager icon. Select Curve with Time and then click OK.
34
35
The AC Single Phase Method is based on the Complex E/Z calculation method and the X/R ratio is extracted
from the complex impedance matrix (X/R). The Calculation Tab is the same as in AC ANSI/IEEE Standard
and provides the same options.
Open the ANSI-YY sample file located in the short circuit sample folder. All the following steps and
explanations are applicable to AC Classical, ANSI/IEEE, and IEC-60909 short circuit analysis methods.
Launch the short circuit toolbar, and click on the report manager Icon
The Report Manager provides:
Output Reports: Fast, User Defined, PDE, Misc.
Output Destination: output to CSV or output to Text File
Fast Report:
Users can select Fault Type, Time Bands, Input Data, Abbreviation, Report Style, Unit & Log. If the fault is
at one bus, the Branch Contribution option can be used.
Select the Fault Types as shown below: 3-P, L-G, L-L, LL-G. Time Bands cycle.
36
icon.
The rms short circuit currents values at 1/2 Cycle are calculated at selected buses or at all buses depending
on the bus selection (in the short circuit Options dialog or directly on the drawing).
The positive, negative, and zero sequence sub-transient reactance X are used in modeling both the
generators and motors. Motors are normally not grounded and therefore the grounding option should be
none.
User Defined Reports:
It is similar to the Fast Report, but additionally users can select the Phase Bus/Branch Components: X/R,
AC, DC, Asym, Angle.
37
An excel report will be generated under the DesignBase output folder as shown below.
38
39
Generator, motor, and transformer grounding types and winding connections are taken into
consideration while building up the system positive, negative, and zero sequence networks
The positive, negative, and zero sequence sub-transient reactance is used for modeling both the
Generators and motors
For steady short circuit, generators are modeled by their positive, negative, and zero sequence
reactance
Short circuit current contributions from motors are ignored in steady short circuit calculations
The rms short circuit currents values after 30 cycles are calculated (as per ANSI/IEEE Standards or
IEC 60909 Standard) at selected buses or at all buses based on user bus selection (in the short
circuit Options dialog or directly on the drawing). The short circuit current contributions from motors
are ignored, and the generators are modeled by their positive sequence transient reactance X.
40
Paladin DesignBase PDE is a fast and accurate tool which evaluates buses and protective devices such as:
LV, MV and HV CBs, fuses, and switches based on ANSI/IEEE and IEC Standards.
Some features of the PDE program are:
PDE output results are either graphically displayed onto the one line diagram (in green if the equipment
passes or in red if they fail), or as a Text Report, based on user selection.
The fault study is per the Standard selected by the user: IEEE/ANSI C37 Standard or IEC 60909. The
program calculates momentary symmetrical and asymmetrical rms, momentary asymmetrical crest,
interrupting symmetrical rms, and interrupting adjusted symmetrical rms short circuit currents at faulted
buses.
The circuit duties are checked against equipment interrupting capabilities, and if:
41
If Annotation is selected as the Default Output, the PDE results will be displayed on the one line Diagram.
If Max Branch Fault Flow is selected under the Duty Type for PDE, protective device evaluation will be
done based on branch short circuit current versus total bus fault current.
Note:
The Total Bus Fault Current method is the most conservative method. This option is present in both
ANSI/IEEE and IEC-60909.
42
Click OK and then run the short circuit program. The Protective Device Evaluation List shown below will be
displayed:
43
Double click on breaker A10 in the equipment list. The Peak closing and latching current is 0 when it should
be bigger than the 40 kA Asymmetrical current to be consistent. Change the Peak current to 50 kA and the
data error message will disappear.
44
45
Short circuit results can be displayed on the one the one-line diagram by selecting Annotation in the short
circuit Options.
To customize the annotation, click on the Short Circuit Back Annotation icon
The Annotation window below will appear:
Select this option to display the
bus Pre-Fault Voltage
Select the color and font size
Select this option to display the
Fault Branch Current
Select the back annotation ON or OFF, Auto-refresh, Font, Font Style, size and font color for additional
customizations.
46
Schedule is a Paladin DesignBase feature that allows users to combine several motors and loads in a single
symbol.
Open the SC_MCC_SCHEDULE sample file under C:\DesignBase\Samples\3PhaseSC. The following
networks are represented:
a) Model with each motor individually represented
b) Model with the three motors in a) combined inside a MCC schedule
Double click on the motor MCC symbol to see the motors representation inside the schedule.
47
48
49
Step 3: In the Report Manager select the Fast report, Fault Type, and Time Band shown below:
50
51
Step 6: Click Analyze icon. The fault results will be displayed as a Text output Report:
-------------------Calculation Options
-------------------Calculating Single Bus Fault
with Fault Z =
0.00000
+ j
0.00000 Ohms
Fault Phases:
Phase A for Line-Ground Fault
Phase B,C for Line-Line or Line-Line-Ground Fault
Classical Calculation:
Complex Z for X/R
Item
---1
2
3
Cd
-MI
MI
MI
MCC
Prefault Voltage:
480.0
52
Cable Data
-----------------Length
R
X
(Feet) Ohms/K Ohms/K
------ ------ -----100 0.0433 0.0338
100 0.0433 0.0338
50 0.0433 0.0338
53
NETWORK REDUCTION/EQUIVALENT
10.1
Introduction
In an interconnected power system, engineers are often required to exchange their system models with their
neighboring utilities in order to study the entire system. However, it is not necessary to model the entire
neighboring system if an exact equivalent representation can be obtained.
DesignBase short circuit program allows the computation of network equivalent systems that can be used for
any type of fault analysis.
This section illustrates step-by-step instructions on how to compute power system equivalents at given
buses. A verification and validation is also performed to verify the results.
10.2
To perform the equivalent calculation of a power system, the part of the system that need to be reduced
should be first identified. In this tutorial the sample file REDUCTION_ORIGINAL.axd will be used. To open
it, go to File>Open Drawing File>C:\DesignBase\Samples\Network Reduction.
Let assume the right part of the system, circled in red blow, need to be replaced by an equivalent at buses
BBB138, GGG138, and ZZZ69:
54
Step2: Specify where the equivalent should be computed. The Options of the short circuit program should
be set as shown below. It can be seen that buses GGG139, BBB138, and ZZZ69 are selected.
55
Step4: To select the equivalent system report, choose the Misc option, and then select Equivalent Sys. as
shown below. Click OK.
56
Important Note: Since the equivalent elements (feeders/transformers, generators) represent a part of a
complex system, the following can occur:
1) The impedances may have negative resistances and/or reactances.
2) The positive and negative sequence values of the links (feeders/transformers) can be assumed to be
the same even though their computed values may not be equal.
3) If the impedance value of a link between two buses is extremely high (i.e. no coupling between
buses), it is safe to ignore the link.
57
As described in the previous section, the equivalent system contains equivalent elements (generators,
feeders and transformers). In order to reconstruct the original system with the equivalent, we need to join the
part of the system which was not reduced (in our example, the left side of the network) to the new equivalent
part.
Based on the report obtained in the previous section, the data for each equivalent element was used to build
the network Reduction_Equivalent.axd under C:\DesignBase\Samples\Network Reduction.
58
59
60
61
To verify and validate the network equivalent feature, the steps below are performed:
1) In the original system (without reduction) compute a three-phase and single line to ground fault at
buses BBB138, GGG138, and ZZZ69
2) In the reconstructed system (remaining system joined with the equivalent system compute a threephase and single line to ground fault at buses BBB138-EQUI, GGG138-EQUI, and ZZZ69-EQUI.
3) The results obtained in step 1 should agree with the results obtained in step 2 above.
62
Comparison of these results shows that the equivalent system was accurately modeled and can be used
reliably in short circuit studies. The errors are less than 0.3%.
Bus
Name
Pre_Flt
Voltage,
in V
BBB138
GGG138
ZZZ69
138000
138000
69000
3 P Flt, in A
L- G Flt, in A
Original
Net.
Equivalent
Net
Error,
in %
Original
Net
Equivalent
Net
Error,
in %
1272
1464
2644
1273
1465
2645
0.08
0.07
0.04
1726
1957
3240
1728
1959
3242
0.12
0.10
0.06
63
11.1
Users have the option to input the Power Utility Maximum and Minimum Contribution and the associated X/R
ratio.
64
65
Whenever there is a schedule, you will see the composition rating on this screen. The HP is the average
value of the motor in schedules. Motors fed from VFD are not considered during short circuit calculations.
User will need to activate this field for all motors fed from VFD.
66
67
68
11.7
69
11.9
70
UPS
These two scenarios can be modeled simultaneously by simply putting the UPS source in Bypass mode
and specifying the corresponding Bypass Protective Device as shown below:
In Bypass mode, the fault contribution to a Short Circuit downstream of the UPS unit will only come from the
Utility source via the Bypass branch.
71
12.1
ANSI/IEEE Standard
MFm 1 2e
For:
2
X
R
,1
Note: In the short circuit option tab Control for ANSI/IEEE the user has the option to calculate MFm based
on X/R or use MFm=1.6
Peak Multiplying Factor
Is defined as:
MFPeak 2 (1 e
2
X /R )
,2
where is the instant of time when fault occurs, X/R for ANSI breaker duties are calculated from separate R
and X network.
72
For:
MFPeak 2.7 .
Note: In the short circuit option tab Control for ANSI/IEEE the user has the option to calculate MFpeak
based on X/R or use MFpeak = 2.7.
The per unit reactance external to the generator is less than 1.5 times the generator per-unit sub
transient reactance on a common system base MVA
Its contribution to the total symmetrical rms Amperes will be greater than 0.4 *
where the
EG
,
X d"
EG
is the generator short circuit current for a three-phase fault at its terminal bus
X d"
The per unit reactance external to the generator is equal to or exceeds 1.5 times the
generator per unit sub transient reactance on a common system base MVA
The generator short circuit contribution may be written as:
IG
EG
( XExternal X d" )
Its contribution to the total symmetrical rms Amperes is less than or equal to 0.4 *
where the
EG
,
X d"
EG
is the generator short circuit current for a three-phase fault at its terminal bus
X d"
73
and:
NACD
I Re mote
I Total
When all contributions are remote, or when there is no generator, then NACD 1
When all contributions are local, then NACD 0
12.2
IEC 60909
While using the IEC standard the following system components formulae are used:
The network components like power transformers, reactors, feeders, overhead lines, cables and other similar
equipment, positive-sequence and negative-sequence short-circuit impedances are equal:
Z (1) Z ( 2 ) ,
is determined by assuming an AC voltage between the three paralleled conductors and the joint return (for
example earth, earthing arrangement, neutral conductor, earth wire, cable sheath and cable armoring). In
this case, the three-fold zero-sequence current flows through the joint return.
The impedances of generators (G), network transformers (T) and power station units (S) will be multiplied
with the impedance correction factors KG, KT and KS or KSO when calculating short-circuit currents with the
equivalent voltage source at the short-circuit location according to the standard [1].
12.2.1 System Parameters
Power transformer parameters
The impedance module ZT can be calculated from the rated transformer data as follows:
74
ZT
u kr U rT2
, ,
100 S rT
Where:
UrT is the rated voltage of the transformer, on the high-voltage or low-voltage side.
SrT is the rated apparent power of the transformer.
ukr is the short-circuit voltage at rated current in percent.
The positive-sequence short-circuit resistance RT of a two-winding transformer is given by the relationship:
RT
PkrT
,,
3 I rT2
Where:
PkrT is the total loss of the transformer in the windings at rated current.
IrT - the rated current of the transformer on the high-voltage or low-voltage side.
Note:
The resistance RT is to be considered if the peak short-circuit current ip or the DC component iDC is to be
calculated.
For large transformers, the resistance is so small that the impedance is represented by the reactance only,
when calculating short-circuit currents.
The positive-sequence short-circuit reactance XT of a two-winding transformer results as follows:
X T ZT2 RT2 , . ,
10
xT
S rT
XT ,
U rT2
11
Note:
The ratio RT/XT generally decreases with transformer size.
The impedance
impedance
Z (1)
ZT
Z T Z (1) Z ( 2 ) , .
75
12
Z(2)
The actual data for two-winding transformers (used as network transformers or in power stations) are given in
IEC 60909-2.
The zero-sequence short-circuit impedance
manufacturer:
Z ( 0 )T
Z ( 0 )T R( 0 )T jX ( 0 )T ,
13
Zero-sequence impedance arrangements for the calculation of unbalanced short-circuit currents are given in
IEC 60909-4.
For two-winding power transformers with and without on-load tap-changer, an impedance correction factor
KT is to be introduced in addition to the impedance evaluated according to equations (1.2) (1.4):
KT
0.95 cmax
,
1 0.6 xT
14
where cmax (from table 2.2) is related to the nominal voltage of the network connected to the LV side of the
network transformer and the transformer relative reactance is calculated with the relationship (11).
The correction factor will not be introduced for unit transformers of power station units.
The correction factor KT is multiplying all the components of the transformer positive-sequence impedance,
according to the following relationship:
Z TK KT Z T KT RT j KT X T , 15
The impedance correction factor will be applied also to the negative-sequence and the zero-sequence
impedance of the transformer when calculating unbalanced short circuit currents.
If the long-term operating conditions of network transformers before the short circuit are known for sure, then
the following equation may be used instead of equation (1.10) in order to calculate the correction factor KT:
KT
Un
cmax
,
b
b
U 1 xT I T / I rT sin Tb
16
Where:
cmax is the voltage factor from table 1.2, related to the nominal voltage of the network connected to the
LV side of the network transformer.
Ub - the highest operating voltage before short circuit.
I Tb - the highest operating current before short circuit (this depends on network configuration and
relevant reliability philosophy).
76
tr
U rTHV
,
U rTLV
17
where UrTHV and UrTLV are transformer rated voltages of the HV and LV windings, respectively.
Reactors
Assuming geometric symmetry, the positive-sequence, the negative-sequence and the zero-sequence shortcircuit impedances of reactors are equal:
Z (1) Z ( 2 ) Z ( 0 ) ,
18
ZR X R
ukR U n
,
100 3 I rR
19
Where:
ukR and IrR are given on the reactor rating plate.
UN the system nominal voltage.
Synchronous Generators and Motors
The synchronous generator rated impedance is given by:
Z rG
x"d
2
U rG
,,
S rG
20
77
X d"
,
x
Z rG
"
d
21
The following values for the fictitious resistances RGf may be used for the calculation of the peak short-circuit
current with sufficient accuracy:
X d" for generators with UrG > 1 kV and SrG 100 MVA;
X d" for generators with UrG > 1 kV and SrG < 100 MVA;
RGf = 0.07
X d" for generators with UrG 1 kV.
RGf = 0.15
RGf = 0.05
In addition to the decay of the DC component, the factors 0.05, 0.07, and 0.15 also take into account the
decay of the AC component of the short-circuit current during the first half-cycle after the short circuit took
place.
The influence of various winding-temperatures on RGf is not considered.
The values RGf cannot be used when calculating the aperiodic component iDC of the short-circuit current.
When the effective resistance of the stator of synchronous machines lies much below the given values for
RGf, the manufacturers values for RG should be used.
The subtransient impedance
the formula:
ZG
Z G RG jX d" ,
22
When calculating initial symmetrical short-circuit currents in systems fed directly from generators without
transformers unit, the corrected impedance
Z GK
Z GK K G Z G K G RG j K G X d" , 23
with the correction factor KG for SG, given by the relationship:
KG
cmax U n
,
1 x sin rG U rG
"
d
where:
cmax is the voltage factor according to table 2.2.
UN - the nominal voltage of the system.
78
24
x"d - the relative subtransient reactance of the generator related to the rated impedance, according to the
(21) relationship.
I rG .
The correction factor KG (equation 24) for the calculation of the corrected subtransient impedance
cU
/ 3
Z GK
has
n
been introduced because the equivalent voltage source
is used instead of the subtransient
voltage E behind the subtransient reactance of the synchronous generator.
If the terminal voltage of the generator is different from UrG, it may be necessary to introduce:
U G U rG 1 pG ,
X"
25
X"
q
d and
If the values of
reactances are different, for the negative-sequence reactance
SM, their arithmetical mean can be used:
X ( 2)G
X d" X q"
2
Z ( 0 )G
of the
26
Z ( 2 )GK
Z ( 2)GK K G RG j K G X ( 2)G ,
X ( 2 )G
27
Z ( 0 )GK K G R( 0 )G jX ( 0 )G ,
28
When an impedance is present between the star-point of the generator and earth, the correction factor KG
will not be applied to this impedance.
I"
When calculating the initial symmetrical short-circuit current k , the peak short-circuit current ip, the
symmetrical short-circuit breaking current Ib, and the steady-state short-circuit current Ik, synchronous
compensators are treated in the same way as SG.
If synchronous motors have a voltage regulation, they are treated like synchronous generators. If not, they
are subject to additional considerations.
79
S rM
rM
PrM
,
cos rM
29
where PrM, cosrM and rM are respectively the active rated power, rated power factor and rated efficiency
of the motor, in accordance with its nameplate data.
The rated current of the AM is given by the relationship:
I rM
3 U rM
PrM
,
rM cos rM
30
I"
MV and LV motors contribute to the initial symmetrical short-circuit current k , to the peak short-circuit
current ip, to the symmetrical short-circuit breaking current Ib and, for unbalanced short circuits, also to the
steady-state short-circuit current Ik.
MV motors have to be considered in the calculation of maximum short-circuit current.
LV motors are to be taken into account in auxiliaries of power stations and in industrial and similar
installations, for example in networks of chemical and steel industries and pump stations.
The contribution of AM in LV power supply systems to the short-circuit current
I k"
I"
contribution is not higher than 5 % of the initial short-circuit current k 0 M , calculated without motors:
"
I rM 0.05 I k 0 M ,
31
Where:
I rM
is the sum of the rated currents of motors connected directly (without transformers) to the
network where the short-circuit occurs;
80
Z rM
S rM
2
U rM
,
I LR / I rM
32
Where:
UrM is the rated voltage of the motor;
SrM - the rated apparent power of the motor (see relationship (1.25));
(ILR/IrM) - the ratio of the locked-rotor current to the rated current of the motor.
The following relations may be used with sufficient accuracy in order to calculate AM parameters:
RM/XM=0.10, with XM=0.995ZM for MV motors with rated powers per pair of poles (PrM/p)1 MW;
RM/XM=0.15, with XM=0.989ZM for MV motors with rated powers per pair of poles (PrM/p)<1 MW;
RM/XM=0.42, with XM = 0.922ZM for LV motor groups, with connection cables,
where p is the pair of poles number.
If the ratio (RM/XM) is known, then the motor reactance XM will be calculated as follows:
XM
ZM
1 RM / X M
33
RM X M RM / X M ,
34
For the determination of the initial short-circuit current according to the short-circuit currents calculation
method, AM are substituted by their impedances
systems:
ZM ,
Z M RM jX M" ,
35
The zero-sequence system impedance Z(0)M of the motor will be given by the manufacturer, if needed.
MV and LV motors, which are connected by two-winding transformers to the network in which the short circuit
occurs, may be neglected in the calculation of short-circuit currents for a short-circuit at the feeder connection
point Q, if there is the following condition:
81
0.8
PrM
S rT 100 c S rT
"
3 U nQ I kQ
36
0.3
Where:
PrM
is the sum of the rated active powers of the medium-voltage and the low-voltage motors which will be
considered.
S rT - the sum of the rated apparent powers of all transformers, through which the motors are directly fed.
"
I kQ
- the initial symmetrical short-circuit current at the feeder connection point Q without supplement of the
motors.
UnQ - the nominal voltage of the system at the feeder connection point Q.
Lines Constants
The positive-sequence short-circuit impedance,
Z L RL jX L ,
37
1
mm2 / m for Copper;
54
1
1
Al mm2 / m for Aluminum and Ala mm2 / m for Aluminum alloy.
34
31
Cu
'
The effective resistance per unit length RLr of overhead lines at the conductor temperature 20C may be
calculated from the nominal cross-section qn and the resistivity :
'
RLr
qn
, / m,
38
The line resistance RLr at the reference temperature r=20C can be determined if its length lL is known:
82
39
Line Resistances RL (overhead lines and cables, line conductors and neutral conductors) will be introduced
at a higher temperature
40
Where:
=0,004 K-1 is the temperature factor of resistivity, valid with sufficient accuracy for most practical
purposes for copper, aluminum and aluminum alloy.
e - the conductor temperature in degrees Celsius at the end of the short-circuit duration (for e, see
also IEC 60865-1, IEC 60949 and IEC 60986).
r=20C - the reference conductor temperature in degrees Celsius.
RLr - the resistance value at a reference temperature of 20C.
The geometric mean distance between conductors, or the center of bundles, in the case of overhead lines, is
determined by the relationship:
d 3 d L1L 2 d L 2 L3 d L3L1 ,
41
Where:
rB n n r R n1 ,
42
Where:
n is the number of bundled conductors;
r - the radius of a single conductor;
R is the bundle radius (see IEC 60909-2).
Where:
83
43
0 = 410-7 H/m;
f the nominal frequency of the power system;
n - the number of bundled conductors, or n=1 for a single conductor;
d - the geometric mean distance between conductors, according to (2.37) relationship;
r - the radius of a single conductor or, in the case of conductor bundles, r is to be substituted by rB, from
the (43) relationship.
The overhead line reactance XL follows to be determined, like in the resistance case, if its length l L is done:
X L X L' l L , ,
44
Z ( 1 ) R( 1 ) jX ( 1 ) ,
45
Z ( 0 ) R( 0 ) jX ( 0 ) ,
46
The impedances ( 1 ) L and ( 0 ) L of LV and HV cables depend on national techniques and standards and
may be taken from IEC 60909-2, from textbooks or manufacturers data.
However, the impedance of a network feeder at the connection point Q is given by:
ZQ
where
2
c U nQ
"
kQ
c U nQ
"
3 I kQ
47
"
I kQ
is the initial symmetrical short-circuit current.
1.85
E
0
, m,
Where:
84
48
E is the earth type resistivity, having values in accordance with table 2.1 content.
= 2f - angular frequency.
0 = 4107 H/m vide absolute magnetic permeability.
Resistivity E and equivalent earth penetration depth for different soil types
Table 4: Resistivity and equivalent earth penetration
Resistivity E,
m
Earth types
Granite
Rocks
Stony soil
>10
3
(310)10
3
(13)10
(0.21.2)10
70200
50100
Clay, loam
Marshy soil
1050
<20
(1.323.22)10
3
(0.781.32)10
660930
(1.22.94)10
3
(0.711.2)10
600850
295660
<415
270600
<380
'
Z W RW'
'
j 0 f r ln
8
rWW
4
, 49
Where:
8
0.06 / km , for f 60 Hz;
r - relative permeability of earth wire. For Aluminum core steel reinforced (ACSR) wires with one
layer of aluminum, r 5 ... 10; for other ACSR wires, r 1; for Steel wires, r 75;
- the earth wires number;
rWW - equivalent earth wire radius, equal to the earth wire radius rW if there is just one earth wire
rWW rW ,
50
and calculated with following formula, if there are two earth wires:
85
rWW rW dW ,
51
Z WL
'
j 0 f ln
dWL
52
Where:
dWL is the geometric mean distance between the earth wire and the line conductors L1, L2 and L3, given by
the formula
53
when there is only one earth wire and by the next formula
54
Sources
As per IEC 60909 the equivalent voltage source (rms) is given by the relationship
U es
c U n
3
, V,
55
Nominal voltage
U n, V
Low voltage,
U n 100,1000kV
Tolerance,
%
6
10
Medium voltage,
U n 1,35kV
1.00
1.10
86
High voltage ,
U n 35 kV
1)
cmaxUn should not exceed the highest voltage Um for equipment of power systems:
cmax U n U m ;
2)
General rules
All network feeders, synchronous and asynchronous machines are replaced by their internal
impedances
The equivalent voltage source is the only active voltage of the system
When calculating short-circuit currents in systems with different voltage levels, it is necessary to
transfer impedances values from one voltage level to another, usually to that voltage level at which
the short-circuit current is to be calculated
For p.u. system no transformation is necessary if these systems are coherent, i.e.
56
87
X TLVK 2 X Qt ,
57
X TLVK KT X TLV ,
58
In the case of a near-to-generator short circuit, the short-circuit current can be considered as the
sum of the following two components:
- the AC component with decaying amplitude during the short circuit
- the aperiodic DC component beginning with an initial value A and decaying to zero
In the calculation of the short-circuit currents in systems supplied by generators, power-station units
and motors (near-to-generator and/or near-to-motor short circuits), it is of interest not only to know
the initial symmetrical short-circuit current I k" and the peak short-circuit current ip, but also the
symmetrical short-circuit breaking current Ib and the steady-state short-circuit current Ik. In this case,
the symmetrical short-circuit breaking current Ib is smaller than the initial symmetrical short-circuit
current I k" . Normally, the steady-state short-circuit current Ik is smaller than the symmetrical shortcircuit breaking current Ib.
The type of short circuit which leads to the highest short-circuit current depends on the values of
the positive-sequence, negative-sequence, and zero-sequence short-circuit impedances of the
system.
"
For the calculation of the initial symmetrical short-circuit current I k the symmetrical short-circuit
breaking current Ib, and the steady-state short-circuit current Ik at the short-circuit location, the
system may be converted by network reduction into an equivalent short-circuit impedance Zk at
the short-circuit location.
This procedure is not allowed when calculating the peak short-circuit current ip. In this case, it is
necessary to distinguish between networks with and without parallel branches.
While using fuses or current-limiting circuit-breakers to protect substations, the initial symmetrical
short-circuit current is first calculated as if these devices were not available. From the calculated
initial symmetrical short-circuit current and characteristic curves of the fuses or current-limiting
circuit-breakers, the cut-off current is determined, which is the peak short-circuit current of the
downstream substation.
Short-circuits may have one or more sources. Calculations are simplest for balanced short circuits on
radial systems, as the individual contributions to a balanced short circuit can be evaluated separately
for each source.
When sources are distributed in meshed network and for all cases of unbalanced short-circuits,
network reduction is necessary to calculate short-circuit impedances Z ( 1 ) Z ( 2 ) and Z ( 0 ) at the
short-circuit location.
88
Z( 0 ) Z( 1 ) Z( 2 ) ,
59
For short-circuits near transformers with low zero-sequence impedance, Z(0) may be smaller than Z(1). In that
"
case, the highest initial short-circuit current I kE
2 E will occur for a line-to-line short circuit with earth
connection. This situation is described by the following relationships:
Z( 2 ) / Z( 0 ) 1;
Z ( 2 ) Z (1) ,
60
I k"
c U n
3 Rk2 X k2
61
89
Rk RQt RTK RL ,
62
X k X Qt X TK X L ,
63
The impedance of the network feeder Z Qt RQt jX Qt is referred to the voltage of the transformer side
connected to the short-circuit location. Resistances Rk
Rk 0.3 X k ,
64
may be neglected.
When there is more than one source contributing to the short-circuit current, and the sources are
unmeshed, the initial symmetrical short-circuit current I k" at the short-circuit location F is the sum of the
individual branch short-circuit currents. Each branch short-circuit current can be calculated as an
independent single-source three-phase short-circuit current in accordance with equation:
I k"
c U n
3 Rk2 X k2
65
Z k Z (1) ,
66
by network reduction (series connection, parallel connection, delta-star transformation) using the positivesequence short-circuit impedances of electrical equipment.
The impedances in systems connected through transformers to the system, in which the short-circuit occurs,
have to be transferred by the square of the rated transformation ratio. If there are several transformers with
slightly differing rated transformation ratios (trT1, trT2,..., trTn), in between two systems, the arithmetic mean
value can be used.
i p 2 I k" ,
67
90
1.02 0.98 e 3( R / X ) ,
68
The peak short-circuit current ip at a short-circuit location F, fed from sources which are not meshed with one
another, is the sum of the partial short-circuit currents:
i p i pi ,
69
id .c . 2 I k" e 2f t ( R / X ) ,
70
Where:
I k" is the initial symmetrical short-circuit current
f - the nominal frequency
t - the time
R/X - the resistance/reactance ratio
Note: The correct resistance RG of the generator armature should be used and not RGf.
Symmetrical short-circuit breaking current
The breaking current at the short-circuit location consists in general of a symmetrical current Ib and a DC
current iDC at the time tmin
For some near-to-generator short circuits the value of iDC at tmin may exceed the peak value of Ib and this can
lead to missing current zeros.
For far-from-generator short circuits, the short-circuit breaking currents are equal to the initial short-circuit
currents:
I b I k" ,
72
"
where the factor depends on the minimum time delay tmin and the ratio I kG / I rG and IrG is the rated
generator current, according to IEC 60909-0/2001-07 1.
91
I b I bi ,
73
I b I k" ,
74
which is usually greater than the real symmetrical short-circuit breaking currents.
12.3
CPT, in Cycles
1.5
2
3
4
1.4
1.2
1.1
1.0
S is the breakers asymmetrical capability factor and is determined based on the rating structure to which the
breaker was manufactured. Most breakers manufactured after 1964 are breakers rated on a symmetrical
current basis. Those manufactured before 1965 were rated on a total current basis. Both the symmetrical
and total current rated breakers have some DC interrupting capability included in their ratings and it is a
matter of how it is accounted for in the total interrupting current.
Note: For circuit breakers rated on Total Current S=1.0
Medium voltage breakers duty is based on:
1. Momentary rating (C&L)
2. Peak (Crest)
3. Interrupting
The Momentary and Peak formulae apply to both breakers symmetrical and total current rated breakers. The
interrupting rating is calculated differently based on the formulae shown in the next sections.
Momentary Duty Calculation (C & L):
92
The CB Closing and Latching Capability defines the CB ability to withstand (close and immediately latch) the
maximum value of the first-cycle short circuit current. The closing and latching capability of a symmetrical
current-rated CB is expressed in terms of Asymmetrical, Total rms current, or peak current.
DesignBase uses the following steps to calculate the circuit breaker momentary duty:
1.
2.
where:
-2
MFm 1 2e X / R
75
Note: In the short circuit option tab Control for ANSI/IEEE the user has the option to calculate MFm
based on X/R or use MFm=1.6
3.
Compare Imom,rms,asym against the medium voltage circuit breaker (C&L,rms ) value:
If Device C&L,rms rating Imom,rms,asym, then the device Pass or otherwise it fails
4.
MFp (1 e
-2
X /R
) 2
,76
and
0.49 - 0.1* e
-X/R
3
77
93
( X / R) mod
(X/R) * 60
System Frequency (Hz)
78
The following steps are used to calculate the circuit breaker interrupting. There are three options:
All Remote i.e. NACD = 1.0. This is the most conservative solution
All Local; i.e. NACD = 0
Adjusted, this is based on actual calculations
1.
2.
Calculate total remote contribution, total local contribution, then the NACD (the current is obtained by
using the (1.5-4) cycle network impedance
3.
NACD
4.
79
Calculate the Multiplying factor based on the fault location (MFr, or MFl)
Remote If Generator current contribution to fault is less than 40% of a generator terminal fault then
this generator is Remote, or equivalent impedance to generation terminals is > 1.5 times the
Generator Zdv. For remote fault the multiplying factor is MFr:
-4
MFr
1 2e X / R
S
80
94
MFl
K 2 2e X / R
S
81
where:
Table 7: K factor
1.1..1
CPT
1.5
2
3
4
K=
2
3
1.0278 - 0.004288(X/R) + 0.00002945(X/R) - 0.000000068368(X/R)
2
3
1.0604 - 0.007473(X/R) + 0.00006253(X/R) - 0.0000002427(X/R)
2
3
1.0494 - 0.00833(X/R) + 0.00006919(X/R) - 0.000000075638(X/R)
2
3
1.0370 - 0.008148(X/R) + 0.0000611(X/R) - 0.0000002248(X/R)
82
Calculate Iint,
All Remote:
All Local:
Iint = MFr*Iint,rms,sym
Iint = MFl*Iint,rms,sym
6.
Calculate 3 phase Device Duty by adjusting the device interrupting duty based on rated voltage using
the following formula:
Iint = AMFi*Iint,rms,sym
8.
95
Test %PF
15
20
Test X/R
6.59
4.9
50
30
20
1.73
3.18
4.90
The following steps are used to calculate the low voltage circuit breaker interrupting:
1. Calculate the cycle interrupting short circuit (Isym,rms).
2. Calculate Low Voltage Multiplying Factor (LVF)
PCB: Power Circuit Breaker
ICCB: Insulated Case Circuit Breaker
LVFasym
(1 2e
(1 2e
2
Calc X/R
2
Test X/R
( EQ 7)
)
,
83
LVFp
(1 e
(1 e
2
X/Rcalc
2 T
X/Rtest
)
)
,
96
84
0.49 - 0.1e
-X/Rcalc
3
and
T 0.49 - 0.1e
- X/Rtest
3
In Options of the short circuit Tab Control for ANSI/IEEE , the user can select to use
=T = 0.5 instead of using the empirical formula by selecting Applies 0.5 Cycles.
LVFasym
(1 2e
4t
X/Rcalc
(1 2e
4t
X/Rtest
)
)
85
Where t is the breaker minimum short time trip in cycles at interrupting duty. The default value used by
DesignBase is 3 cycles.
The peak interrupting rating is calculated as follows:
LVFp
(1 e
(1 e
2
X/Rcalc
2 T
X/Rtest
)
)
86
Where
0.49 - 0.1e
-X/Rcalc
3
and
T 0.49 - 0.1e
- X/Rtest
3
97
If the fuse is symmetrical rated, then MFasym is calculated using the following formula:
98
MFasym (1 2e
2
X/R
)
87
If the fuse is asymmetrical rated, then MFasym is calculated using the following formula:
MFasym
(1 2e
(1 2e
2
Calc X/R
2
Test X/R
)
)
, 88
Note:
99
For LVCB, MVCB & Fuses Calculate the cycle short-circuit current
(Isym,rms).
For MVCB calculate the Iint,rms,sym.
Run the PDE analysis
Fuses/ Switches
LVCB
MVCB
Fused?
NO
YES
Yes
CB X/R is known?
CB X/R is known?
NO
NO
= 1.73
= 3.18
= 4.9
Calculate LVF
based on EQ-7
Go to
Page 2
IF LVF < 1,
then LVF =1
Yes
NO
MCCB/ICCB/PCBWith Instantaneous :
Iint,adj =LVF*Isym,rms
PCB Without Instantaneous:
Iint,adj =LVFp*Isym,rms( Cyc)
int,adj =LVFasym*Isym,rms(3-8 Cyc)
NO
Pass
Fail
Calculate
%rating=Isym,adj*100/
Device rating
Is Device Symmetrical
rating greater or Equal
to Iint,adj?
Yes
Pass
Fail
Calculate
%rating=Iint,adj*100/
Device rating
100
YES
MVCB From
Page 1
All Local
NACD
NO
Interrupting Duty
YES
YES
NO
Calculate:
Total Remote Contribution
Peak Duty
(Crest)
Peak Duty
(Crest)
Momentary
Duty (C&L)
MFm = 1.6
MFp = 2.7
ALL Remote
Calculate
MFr using EQ-4
Iint=MFr*Iint,rms,sym
All Local
Calculate
Imom,peak=MFp*Isym,rms
Calculate
Imom,asym=MFm*Isym,rms
Calculate
MFl using EQ-5
Iint=MFl*Iint,rms,sym
NACD
Calculate:
NACD using EQ-3
Iint = AMFi*Iint,rms,sym/S
Yes
NO
Calculate
%rating=Imom,peak*100/
device peak (crest) rating
NO
Yes
Pass
Fail
Pass
Fail
NO
Fail
Calculate %rating=Iint*100/
3P device Int rating
101
Momentary
Duty (C&L)
Yes
Pass
Calculate
%rating=Imom,rms,asym*100/
device C&L,rms rating
12.4.1 Circuit-Breakers
Circuit-breaker design techniques have improved over time leading to benefits of technical performances,
reduced size, weight, energy requirements and cost. This progression is also perceived to have led to an
inevitable reduction in inherent design margins such that much of the older equipment, for which extensive
operating experience is available, may have considerable margins in hand-over and above modern
equipment. This trend is not problematic in itself but further emphasizes the need for future testing regimes to
be fully representative of the system conditions in which the equipment needs to function correctly.
In technologies where the interruption capability is fundamentally constant regardless of the switching duty,
interpolation of test evidence is relatively simple and accepted. However, in technologies where the basic
interruption characteristics of the device are duty dependent, such interpolations are far more difficult to
achieve simply and it is quite conceivable that critical fault duties may be identified at fractional short-circuit
levels. In principle, the high energies and relatively low di/dt values associated with an asymmetrical duty
make it less onerous for such a device than an equivalent symmetrical duty. However, the effect of low
energy minor loops and the possibility of extended arcing periods, in what are generally very short overall
travel times, are factors which might prove particularly critical.
Ultimately, equipment testing should consider the equipment under test to be a "black box" model regardless
of the technology being employed, but this presents obvious difficulties if varying design technologies have
specific sensitivities.
It must be stressed at this point that there is no intention to cast doubt on the capabilities of particular
equipment design philosophies merely to emphasize that as refined design techniques lead to minimized
designs so the importance of well constructed and realistic testing regimes increases.
An obvious, but non-preferred, solution to problems of asymmetric switching is to increase circuit-breaker
operating times, although this does not alleviate the duty on other associated equipment and may be
inconvenient from an overall system viewpoint. This contrary to the tendency for reducing protection times in
modern equipment.
High Voltage Breakers. Normally the interrupting current is a constant current at any voltage. However,
some manufacturers do give a different current at various voltages. On the HV breakers it may to check if the
breaker voltage rating is greater than the system voltage. The voltage rating of IEC breakers is the maximum
voltage that the breaker can be applied at.
Low Voltage Breakers. The same standards are used for LVPCB and MCCB.
12.4.2 Rated characteristics to be given for all circuit-breakers
a1) Rated voltage Ur.:
If the manufacturer indicates a few values for the rated voltage, then the greatest represents the maximum
rated voltage;
a2) Rated insulation level;
a3) Rated frequency fr.
The standard values for the rated frequency of high voltage circuit-breakers are 50 Hz and 60 Hz;
102
I cw 12 I e , pt . Tcw 1s ,
89
A complete determination of the rated short-time withstand current is made, on the base of the mentioned
standard, as follows:
90
I cw 30 kA, pt . I e 2,5 kA ,
91
InAC the rated short-time withstand current is compearing with the rms value of the periodical short-circuit
current component. It is necessary that the last mentioned value to be lower than the product between the
short duration acceptable rated current and the factor n, indicated in table 3, in accordance with CEI 60947-1:
I k n I cw ,
92
Values of the power factor, the time constants and the ratio n between the peak value and the rated shorttime withstand current.
103
Power Factor
0,95
0,9
0,8
0,7
0,5
0,3
0,25
0,2
Time constant,
ms
10
15
n factor
1,41
1,42
1,47
1,53
1,70
2,00
2,10
2,20
At the same time, the short duration acceptable rated current represents the upper limit value of the rms
value of the short-circuit current periodical component which is presumed constant during the short timing ,
for which the following normalized values are recommended:
104
The circuit-breaker shall be capable of breaking any short-circuit current up to its rated short-circuit breaking
current containing any AC component up to the rated value and, associated with it, any percentage DC
component up to that specified, under the conditions mentioned above.
The following applies to a standard circuit-breaker:
- at voltages below and equal to the rated voltage, it shall be capable of breaking its rated short-circuit
breaking current
- at voltages above the rated voltage, no short-circuit breaking current is guaranteed. The standard value of
the AC component of the rated short-circuit breaking current shall be selected from the R10 series
specified in IEC 60059. The R10 series comprises the numbers
{1 1,25 1,6 2 2,5 3,15 4 5 6,3 8}
n
Top Tr
id .c. % 100 exp
105
, %
Figure 34: Percentage D.C. current component in relation to the time interval from initiation of short-circuit
current, for different time constant.
These special case time constant values recognize that the standard value may be inadequate in some
systems. They are provided as unified values for such special system needs, taking into account the
characteristics of the different ranges of rated voltage, for example their particular system structures, design
of lines, etc.
In addition, some applications may require even higher values, for example if a circuit-breaker is close to a
generator. In these circumstances, the required DC component and any additional test requirements should
be specified in the inquiry.
106
I cu I k
93
I cm k I cu
94
107
cos
0.50
0.30
0.25
0.20
1.7
2.0
2.1
2.2
The rated short-circuit making capacity implies that the breaker is able to connect the current suitable to this
rated capacity at an applied voltage corresponding to the use rated voltage.
Being an instantaneous value, the rated short-circuit making capacity Icm of an CB is compared with the peak
current ip and the next inequality have to be fulfilled in order that the device withstands the short-circuit
action:
I cm i p
95
The following values apply for the high voltage CB (Ur >1 kV):
for a rated frequency of 50 Hz and the standard value of the time constant of 45 ms it is
equal to 2,5 times the rms value of the AC component of its rated short-circuit breaking
current (Icn), so a following relationship can be written:
I cm k H I cn ,
96
for a rated frequency of 60 Hz and the standard value of the time constant of 45 ms it is
equal to 2,6 times the rms value of the AC component of its rated short-circuit breaking
current
for all special case time constants it is equal to 2,7 times the rms value of the AC
component of its rated short-circuit breaking current, independent of the rated frequency of
the circuit-breaker
108
Information
Abbreviation
Unit
Ur
kV
Up
kV
Us
kV
fr
Hz
Ir
Isc
A
kA
(idc%)
tk
Manufacturer
Type designation and serial number
Rated voltage
Rated lightning impulse withstand
voltage
Rated switching impulse withstand
voltage
Rated frequency
Required marking
condition
Mandatory for CB and
operation device
Mandatory
More than 20 %
Different from 1 s
Coils of operating devices shall have a reference mark permitting the complete data to be obtained
from the manufacturer. Releases shall bear the appropriate data.
The nameplate shall be visible in the position of normal service and installation.
109
12.4.4 FUSES
The fuses can operate as single devices or can be combined with switch disconnectors. The choice depends
on each application requirements and specific network conditions. One of the most critical factors for
optimum protection is proper fuse selection. This can be done based on theoretical calculations but in many
cases practical knowledge obtained from actual test results could make it easier and even more reliable.
The speed at which a fuse blows depends on how much current flows through it and the material of which the
fuse is made. The operating time is not a fixed interval, but decreases as the current increases. Fuses have
different characteristics of operating time compared to current, characterized as "fast-blow", "slow-blow" or
"time-delay", according to time required to respond to an over current condition. A standard fuse may require
twice its rated current to open in one second, a fast-blow fuse may require twice its rated current to blow in
0.1 seconds, and a slow-blow fuse may require twice its rated current for tens of seconds to blow.
A characteristic of modern cartridge fuses is that, owing to the rapidity of fusion in the case of high shortcircuit current levels, a current cut-off begins before the occurrence of the first major peak, so that the fault
current never reaches its prospective peak value [Schneider]. This limitation of current reduces significantly
the thermal and dynamic stresses which would otherwise occur, thereby minimizing danger and damage at
the fault position. The rated short-circuit breaking current of the fuse is therefore based on the rms value of
the AC component of the prospective fault current. No short-circuit current-making rating is assigned to fuses.
Short-circuit currents initially contain DC components, the magnitude and duration of which depend on the
XL/R ratio of the fault current loop. Close to the source (MV/LV transformer) the relationship Ipeak / I rms (of
AC component) immediately following the instant of fault, can be as high as 2.5 (standardized by IEC).
At lower levels of distribution in an installation, as previously noted, XL is small compared with R and so for
final circuits Ipeak / Irms ~ 1.41. The peak-current-limitation effect occurs only when the prospective rms AC
component of fault current attains a certain level. As already mentioned, at lower distribution levels in an
installation, R greatly predominates XL, and fault levels are generally low. This means that the level of fault
current may not attain values high enough to cause peak current limitation. On the other hand, the DC
transients (in this case) have an insignificant effect on the magnitude of the current peak, as previously
mentioned.
12.4.5 Fuse IEC Characteristic Quantities [IEC 60269-1]
Prospective current (of a circuit with respect to a fuse) current that would flow in the circuit if each pole of
the fuse were replaced by a conductor of negligible impedance. For AC, the prospective current is expressed
by the rms value of the AC component.
Note: the prospective current is the quantity to which the breaking capacity and characteristics of the fuse
2
are normally referred, e.g. I t and cut-off current characteristics.
Fuse Breaking capacity value of prospective current that a fuse is capable of breaking at a stated voltage
under prescribed conditions of use and behavior (the rms value of the periodic component, for AC).
Breaking range range of prospective currents within which the breaking capacity of a fuse-link is assured.
Cut-off current maximum instantaneous value reached by the current during the breaking operation of a
fuse-link when it operates in such a manner as to prevent the current from reaching the otherwise attainable
maximum.
110
I t (Joule integral) integral of the square of the current over a given time interval:
I 2t t 1 i 2 dt
0
t
97
Notes:
The pre-arcing I t is the I t integral extended over the pre-arcing time of the fuse
2
2
The operating I t is the I t integral extended over the operating time of the fuse
The energy in Joules released in a 1 resistor in a circuit protected by a fuse is equal to the value of
2
2
the operating I t expressed in A s
I t characteristic curve giving I2t values (pre-arcing I2t and/or operating I2t) as a function of prospective
current under stated conditions of operation.
2
I t zone range contained by the minimum pre-arcing I2t characteristic and the maximum operating I2t
characteristic, under specified conditions.
Rated current of a fuse-link (In) value of current that the fuse-link can carry continuously without
deterioration under specified conditions.
Time-current characteristic curve giving the time, e.g. pre-arcing time or operating time as a function of
the prospective current under stated conditions of operation.
Note: for times longer than 0,1 s, for practical, purposes the difference between pre-arcing and operating time
is negligible.
Time-current zone range contained by the minimum pre-arcing time-current characteristics and the
maximum operating time-current characteristic, under specified conditions.
Conventional non-fusing current (Inf) value of current specified as that which the fuse-link is capable of
carrying for a specified time (conventional time) without melting.
111
112
113
b
Figure 36: IEC PDE Flow Chart Part 2
114
c
Figure 37: IEC PDE Flow Chart Part 3
115
Fuses Evaluation
Compare the voltage rating of the fuse (Ur) against the system voltage (Un) where the fuse is placed:
if the fuse rated voltage
Ur Un then
the device Pass, otherwise Fail (the user have to verify the fuse ratings).
For the Ur Un case, there are two situations:
a. if Ur = Un then the fuse breaking capacity rating (Irb) = the fuse real breaking capacity (Ib);
b. if Ur > Un then the real breaking capacity of the fuse will be used in the next steps; for this
situation calculate the fuse real breaking capacity:
Ib
Ur
I rb .
Un
Compare the fuse real breaking capacity against the initial symmetrical short-circuit current I k" :
"
Calculate
%rating
I"k
Ib
Calculate
% rating
ip
I cm
100 .
Top Tr
Calculate i dc % exp
116
Where:
Top represents the minimum opening time and it is specified by the manufacturer;
Tr according to the specifications from figure 2,b;
circuit time constant, given in paragraph.
2
I asymsc I k
i %
1 dc .
100
Compare the asymmetrical short-circuit presumed current with the CB short-circuit breaking current Icn.
if Iasymsc < Icn then the LVCB Pass, otherwise Fail.
For both situations of the last comparison
calculate % rating
I asymsc
I cn
100 .
117