Unit Charged-60%

The document provides electricity meter readings and calculations for different feeders. It lists the KWH readings on two dates for each feeder, calculates the difference in units, and multiplies by the meter factor to get the total outgoing units. It then notes that the CT polarity was reversed, so the recorded units need to be increased by 33.33%. It calculates the units the meter should have recorded, finds the meter is 60% slow, and adjusts the total outgoing units accordingly. It finally calculates the percentage loss, noting it is within the permissible limit.

Uploaded by

Shahzad Bhatti
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
27 views1 page

Unit Charged-60%

The document provides electricity meter readings and calculations for different feeders. It lists the KWH readings on two dates for each feeder, calculates the difference in units, and multiplies by the meter factor to get the total outgoing units. It then notes that the CT polarity was reversed, so the recorded units need to be increased by 33.33%. It calculates the units the meter should have recorded, finds the meter is 60% slow, and adjusts the total outgoing units accordingly. It finally calculates the percentage loss, noting it is within the permissible limit.

Uploaded by

Shahzad Bhatti
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 1

KWH Reading

on 12.07.12 at 3:00

KWH Reading
on 04.07.12 at 4:00

Differnce

M.F

Total Unit

I/Coming Feeder

1231622

886307

345315

690630

Dewan Dastigeer

316134

244030

72104

144208

Hoota City

824168

639037

185131

370262

Mohsin Shah

30143

30134

60268

Feeder Name

Total
Out Going
unit

574738

As the C.T polarity of KWH Meter was reverse so KWH Meter recorded the 33.33% Units
So KWH Meter Should Recorded the Unit

180804

Meter is 60% Slow then

108482.4

Now Total Out going unit wii be

683220.4

% Loss

Ali Ahmed
Test Inspector (P&I)
Sub-Division Sahiwal

1.0728754905

The Loss is within Permissible limit

Shahzad
Assistant Engineer (P&I)
Sub-Division Sahiwal