Modbus Parameters
Modbus Parameters
2012 BB
Scaling
Read
Write
Holding Register
Note
Reread event
1=1
401991...401995
Events
1=1
401996...402000
Mirror of registers
402490...402494
Mirror of registers
402101...402105
1=1
402001
1=1
402007
1=1
402008
1A=1
402009
1A=1
402010
1A=1
402011
1.00 A = 100
402012
1.000 A = 100
402013
1000 V = 1000
Voltage scaling
402014
1000 V = 1000
Voltage scaling
402015
1000 V = 1000
Voltage scaling
402016
1000 V = 1000
Voltage scaling
402017
1000 V = 1000
Voltage scaling
402018
1000 V = 1000
Voltage scaling
402019
1.0 % = 10
402020
50.000 Hz = 5000
Frequency scaling
402021
1000 Kw = 1000
Power scaling
402022
Reactive power
Power scaling
402023
Apparent power
Power scaling
402024
Power factor
1.00 = 100
402025
Energy Eexp
1=1
402026
Eexp/10^4
10^4 = 1
402027
Eexp/10^8
10^8 = 1
402028
1=1
402029
10^4 = 1
402030
Energy EqExp
EqExp/10^4
Name
Scaling
Read
Write
Holding Register
EqExp/10^8
10^8 = 1
402031
Energy Eimp
1=1
402032
Eimp/10^4
10^4 = 1
402033
Eimp/10^8
10^8 = 1
402034
1=1
402035
EqImp/10^4
10^4 = 1
402036
EqImp/10^8
10^8 = 1
402037
1.000 = 1000
402038
1A=1
402039
1000 V = 1000
Voltage scaling
402040
1000 V = 1000
Voltage scaling
402041
Open = 0, Close =
1, Undef = 2
Open = 0, Close =
1, Undef = 2
Open = 0, Close =
1, Undef = 2
Open = 0, Close =
1, Undef = 2
Open = 0, Close =
1, Undef = 2
Open = 0, Close =
1, Undef = 2
Remote = 0, Local
=1
1=1
402042
402043
402044
402045
402046
402047
402048
402049
Open = 0, Close =
1, Undef = 2
Open = 0, Close =
1, Undef = 2
1=1
402050
402051
402052
1=1
402057
1=1
402058
1s =1
402059
1=1
402060
1A=1
402061
Energy EqImp
Tan phi
Phase current IL
Obj1 state
Obj2 state
Obj3 state
Obj4 state
Obj5 state
Obj6 state
Remote/Local State
Output relays
Obj7 state
Obj8 state
Digital inputs 21...32
Note
2/15
Name
Scaling
Read
Write
Holding Register
1A=1
402062
1A=1
402063
IL1 difference
1.00 x In = 100
402064
IL2 difference
1.00 x In = 100
402065
IL3 difference
1.00 x In = 100
402066
1=1
402101...402105
Events
Event code
402101
402102
402103
402104
402105
1.00 x In = 100
402110
Fault current
1.00 x In = 100
402111
Fault current
1.00 x In = 100
402112
Fault current
Fault reactance
Algorithm condition
Alarm L1...L3:
bit 0 = L1,
bit 1 = L2,
bit 2 = L3
1.00 x In = 100
402113
402115
OK = 0, NegX = 1,
BigX = 2, LongFlt =
3, NoDI = 4,
NoPreFlt = 5,
NoPostFlt = 6,
ShrtFlt = 7
1=1
402116
402121
Note
See Modbus
Application Note
3/15
Name
Scaling
Read
Write
Holding Register
1=1
402122
1.00 pu = 100
402130
Fault current
1.00 pu = 100
402131
Fault current
1.00 pu = 100
402132
Fault current
1.00 pu = 100
402133
Fault current
1.00 pu = 100
402134
Diagnostic register 1
1=1
402191
Diagnostic register 2
1=1
402192
Diagnostic register 3
1=1
402193
Diagnostic register 4
1=1
402194
HARMONICS of IL1:
402201 = DC component,
402202 = 1. harmonic,
...
402216 = 15. harmonic
1%=1
402201...402216
HARMONICS of IL2
1%=1
402221...402236
HARMONICS of IL3
1%=1
402241...402256
HARMONICS of Ua
1%=1
402301...402316
HARMONICS of Ub
1%=1
402321...402336
HARMONICS of Uc
1%=1
402341...402356
HARMONICS of I'L1
1%=1
402401...402416
HARMONICS of I'L2
1%=1
402421...402436
HARMONICS of I'L3
1%=1
402441...402456
1=1
402490...402494
Release = 1
402501
1=1
402502
1%=1
402503
Fault L1L3:
bit 0 = L1,
bit 1 = L2,
bit 2 = L3
Reread event
Release latches
Synchronize minutes
Grp. 2 remote scaling
Note
4/15
Name
Scaling
Read
Write
Holding Register
Set RTC:
402504 = seconds,
402505 upper byte =
minutes,
402505 lower byte = hours,
402506 upper byte = day,
402506 lower byte = month,
402507 = year
1=1
402504...402507
1=1
402508
1=1
402509
1=1
402510
1.00 s = 100
402511
1=1
402512
1=1
402513
1=1
402514
1.00 s = 100
402515
1=1
402516
1=1
402517
1=1
402518
1=1
402519
1.00 s = 100
402520
1=1
402521
1=1
402522
1=1
402523
1.00 s = 100
402524
Ambient temperature
1 C = 100
402525
1 = 0, 2 = 1
402526
1=1
402527
1=1
402528
1=1
402529
1.00 s = 100
402530
1=1
402531
1=1
402532
1=1
402533
Note
5/15
Name
Scaling
Read
Write
Holding Register
1.00 s = 100
402534
Reset diagnostics
Reset = 1
402535
Clear = 1
402536
Pos. sequence I1
1A=1
403001
Neg. sequence I2
1A=1
403002
Current -seq./+seq.
1.0 % = 10
403003
?? = 0, OK = 1,
Reverse = 2
1.0 % = 10
403004
403005
IL1 THD
1.0 % = 10
403006
IL2 THD
1.0 % = 10
403007
IL3 THD
1.0 % = 10
403008
Phase current IL
1A=1
403009
1A=1
403010
1A=1
403011
1 Arms = 1
403012
1 Arms = 1
403015
1 Arms = 1
403016
1 Arms = 1
403017
Temperature rise
1.0 % = 10
403018
Ambient temperature
1 C = 100
403019
IL1da demand
1A=1
403020
IL2da demand
1A=1
403021
IL3da demand
1A=1
403022
1.00 pu = 100
403023
Io1 demand
1.000 pu = 1000
403024
Io2 demand
1.000 pu = 1000
403025
Pos. sequence U1
1000 V = 1000
Voltage scaling
403031
Neg. sequence U2
1000 V = 1000
Voltage scaling
403032
Voltage -seq./+seq.
1.0 % = 10
403033
?? = 0, OK = 1,
Reverse = 2
1.0 % = 10
403034
403035
IoCalc demand
Voltage THD
Note
6/15
Name
Scaling
Read
Write
Holding Register
Ua THD
1.0 % = 10
403036
Ub THD
1.0 % = 10
403037
Uc THD
1.0 % = 10
403038
1000 V = 1000
Voltage scaling
403039
1000 V = 1000
Voltage scaling
403040
1000 V = 1000
Voltage scaling
403041
1000 V = 1000
Voltage scaling
403042
1000 V = 1000
Voltage scaling
403043
1000 V = 1000
Voltage scaling
403044
Voltage mean
Voltage scaling
403045
Input voltage Ua
Voltage scaling
403048
Input voltage Ub
Voltage scaling
403049
Input voltage Uc
Voltage scaling
403050
U12 demand
1000 V = 1000
Voltage scaling
403051
U23 demand
1000 V = 1000
Voltage scaling
403052
U31 demand
1000 V = 1000
Voltage scaling
403053
UL1 demand
1000 V = 1000
Voltage scaling
403054
UL2 demand
1000 V = 1000
Voltage scaling
403055
UL3 demand
1000 V = 1000
Voltage scaling
403056
1.00 = 100
403058
1.000 = 1000
403059
1 = 1
403060
1000 kW = 1000
Power scaling
403061
Power scaling
403062
Power scaling
403063
1000 kW = 1000
Power scaling
403066
Power scaling
403067
Power scaling
403068
1.00 = 100
403069
1000 kW = 1000
Power scaling
403071
Power scaling
403072
Power scaling
403073
Cosine phi
Tan phii
Power angle
Note
7/15
Name
Scaling
Read
Write
Holding Register
1000 kW = 1000
Power scaling
403081
1000 kW = 1000
Power scaling
403082
1000 kW = 1000
Power scaling
403083
Power scaling
403084
Power scaling
403085
Power scaling
403086
Power scaling
403087
Power scaling
403088
Power scaling
403089
Cosine of phase L1
1.00 = 100
403090
Cosine of phase L2
1.00 = 100
403091
Cosine of phase L3
1.00 = 100
403092
50.000 Hz = 5000
Frequency scaling
403101
Synchrocheck
1000 V = 1000
Voltage scaling
403102
Synchrocheck
1 = 1
403103
Synchrocheck
50.000 Hz = 5000
Frequency scaling
403111
Synchrocheck
1000 V = 1000
Voltage scaling
403112
Synchrocheck
1 = 1
403113
Synchrocheck
1A=1
403151
Frequency fy
Line-to-line voltage U12y
Synchrocheck 1 Phase angle
difference
Frequency fz
Line-to-line voltage U12z
Synchrocheck 2 Phase angle
difference
Positive sequence I'1
Negative sequence I'1
1A=1
403152
1.0 % = 10
403153
?? = 0, OK = 1,
Reverse = 2
1.0% = 10
403154
403155
I'L1 THD
1.0% = 10
403156
I'L2 THD
1.0% = 10
403157
I'L3 THD
1.0% = 10
403158
1A=1
403159
1A=1
403160
1A=1
403161
1 Arms = 1
403162
Note
8/15
Name
Scaling
Read
Write
Holding Register
1 Arms = 1
403165
1 Arms = 1
403166
1 Arms = 1
403167
DI1 counter
1=1
403301
DI2 counter
1=1
403302
DI3 counter
1=1
403303
DI4 counter
1=1
403304
DI5 counter
1=1
403305
DI6 counter
1=1
403306
DI7 counter
1=1
403307
DI8 counter
1=1
403308
DI9 counter
1=1
403309
DI10 counter
1=1
403310
DI11 counter
1=1
403311
DI12 counter
1=1
403312
DI13 counter
1=1
403313
DI14 counter
1=1
403314
DI15 counter
1=1
403315
DI16 counter
1=1
403316
DI17 counter
1=1
403317
DI18 counter
1=1
403318
DI19 counter
1=1
403319
DI20 counter
1=1
403320
DI21 counter
1=1
403350
DI22 counter
1=1
403351
DI23 counter
1=1
403352
DI24 counter
1=1
403353
DI25 counter
1=1
403354
DI26 counter
1=1
403355
DI27 counter
1=1
403356
DI28 counter
1=1
403357
Note
Optional DI19/DI20
card
Optional DI19/DI20
card
9/15
Name
Scaling
Read
Write
Holding Register
DI29 counter
1=1
403358
DI30 counter
1=1
403359
DI31 counter
1=1
403360
DI32 counter
1=1
403361
1=1
403331
1=1
403332
1=1
403333
1=1
403334
1=1
403335
AR start counter
1=1
403336
AR fail counter
1=1
403337
AR shot number
403402
Critical AR req.
1, 2, 3, 4, 5, END =
6
1=1
403403
Reclose locked
1=1
403404
Reclose running
1=1
403405
Final trip
1=1
403406
Autoreclose on
1=1
403407
LOW = 0, OK = 1
403413
403414
Timer 1 status
OK = 0, LOW = 1,
HIGH = 3,
(OK) = 4, (LOW) =
5, (HIGH) = 6,
(LOW)/(HIGH) = 7
0 = 1, 1 = 2
403415
Timer 2 status
0 = 1, 1 = 2
403416
Timer 3 status
0 = 1, 1 = 2
403417
Timer 4 status
0 = 1, 1 = 2
403418
1=1
403419
CBWAlarm 1
1=1
403420
CBWAlarm 2
1=1
403421
1=1
403422
Voltage interrupt
Voltage status
Note
10/15
Name
Scaling
Read
Write
Holding Register
1=1
403423
Virtual outputs
0, 1
403426
Virtual input 1
0, 1
403427
Virtual input 2
0, 1
403428
Virtual input 3
0, 1
403429
Virtual input 4
0, 1
403430
Synchrocheck 1 request
1=1
403431
Synchrocheck 1 OK
1=1
403432
Synchrocheck 1 bypass
1=1
403433
Synchrocheck 1 fail
1=1
403434
Synchrocheck 2 request
1=1
403441
Synchrocheck 2 OK
1=1
403442
Synchrocheck 2 bypass
1=1
403443
Synchrocheck 2 fail
1=1
403444
Logic Cntr1
1=1
403451
Logic Cntr2
1=1
403452
Logic Cntr3
1=1
403453
Logic Cntr4
1=1
403454
Logic Cntr5
1=1
403455
Logic Cntr6
1=1
403456
External AI1
1.00 C = 100
403500
External AI2
1.00 C = 100
403501
External AI3
1.00 C = 100
403502
External AI4
1.00 C = 100
403503
External AI5
1.00 C = 100
403504
External AI6
1.00 C = 100
403505
External AI7
1.00 C = 100
403506
External AI8
1.00 C = 100
403507
Note
External IO must be
active
External IO must be
active
External IO must be
active
External IO must be
active
External IO must be
active
External IO must be
active
External IO must be
active
External IO must be
11/15
Name
Scaling
Read
Write
Holding Register
Note
active
External AI9
1.00 C = 100
403508
External AI10
1.00 C = 100
403509
External AI11
1.00 C = 100
403510
External AI12
1.00 C = 100
403511
External AI13
1.00 C = 100
403512
External AI14
1.00 C = 100
403513
External AI15
1.00 C = 100
403514
External AI16
1.00 C = 100
403515
External DI1
1=1
403600
External DI2
1=1
403601
External DI3
1=1
403602
External DI4
1=1
403603
External DI5
1=1
403604
External DI6
1=1
403605
External DI7
1=1
403606
External DI8
1=1
403607
External DI9
1=1
403608
External DI10
1=1
403609
External DI11
1=1
403610
External DI12
1=1
403611
External DI13
1=1
403612
External DI14
1=1
403613
External DI15
1=1
403614
External DI16
1=1
403615
External DI17
1=1
403616
External DI18
1=1
403617
External IO must be
active
External IO must be
active
External IO must be
active
External IO must be
active
External IO must be
active
External IO must be
active
External IO must be
active
External IO must be
active
12/15
Name
Scaling
Read
Write
Holding Register
50.000 Hz = 50000
404001
1 kW = 1
404002
1 kvar = 1
404003
1 kVA = 1
404004
1.000 = 1000
404005
Minimum of Io
1.0 % = 10
404006
Minimum of Io2
1.0 % = 10
404007
1 kW = 1
404008
1 kvar = 1
404009
1 kVA = 1
404010
1.000 = 1000
404011
1 kW = 1
404012
1 kvar = 1
404013
1 kVA = 1
404014
Minimum of IL1
1A=1
404015
Minimum of IL2
1A=1
404016
Minimum of IL3
1A=1
404017
1 Arms = 1
404018
1 Arms = 1
404019
1 Arms = 1
404020
Minimum of IL1
1A=1
404021
Minimum of IL2
1A=1
404022
Minimum of IL3
1A=1
404023
1 Arms = 1
404024
1 Arms = 1
404025
Minimum frequency
1 Arms = 1
404026
Minimum of U12
1V=1
404030
Minimum of U23
1V=1
404031
Minimum of U31
1V=1
404032
50.000 Hz = 50000
404101
1 kW = 1
404102
Maximum frequency
Maximum active power
Note
13/15
Name
Scaling
Read
Write
Holding Register
1 kvar = 1
404103
1 kVA = 1
404104
1.000 = 1000
404105
Maximum of Io
1.0 % = 10
404106
Maximum of Io2
1.0 % = 10
404107
1 kW = 1
404108
1 kvar = 1
404109
1 kVA = 1
404110
1.000 = 1000
404111
1 kW = 1
404112
1 kvar = 1
404113
1 kVA = 1
404114
Maximum of IL1
1A=1
404115
Maximum of IL2
1A=1
404116
Maximum of IL3
1A=1
404117
1 Arms = 1
404118
1 Arms = 1
404119
1 Arms = 1
404120
Maximum of IL1
1A=1
404121
Maximum of IL2
1A=1
404122
Maximum of IL3
1A=1
404123
1 Arms = 1
404124
1 Arms = 1
404125
1 Arms = 1
404126
Maximum of U12
1V=1
404130
Maximum of U23
1V=1
404131
Maximum of U31
1V=1
404132
404201
404202
404203
404204
404205
Note
14/15
Name
Scaling
Read
Write
Holding Register
404206
Z12 angle
1 = 1
404207
Z23 angle
1 = 1
404208
Z31 angle
1 = 1
404209
Note
This table was generated from firmware version 10.108. New firmware versions might bring additions to this list.
Please note that all of these registers are not necessarily available on all devices or with some device configurations. For
instance, the holding registers marked with the comment Synchrocheck in the Note column require a device that is
capable of performing synchrocheck as well as having its Voltage measurement mode set appropriately.