Proposed Project: Saving in Power Consumption: by Installing VFD in N Compressor

This document proposes installing a variable frequency drive (VFD) in an N2 compressor to reduce power consumption. It shows the compressor currently uses 72 kW of power when idle without a VFD but would use only 22 kW with a VFD installed. This would save 300 kW of power per day and 9,000 kW per month, saving 198,000 Indian rupees per month.

Uploaded by

techkasamba
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
106 views3 pages

Proposed Project: Saving in Power Consumption: by Installing VFD in N Compressor

This document proposes installing a variable frequency drive (VFD) in an N2 compressor to reduce power consumption. It shows the compressor currently uses 72 kW of power when idle without a VFD but would use only 22 kW with a VFD installed. This would save 300 kW of power per day and 9,000 kW per month, saving 198,000 Indian rupees per month.

Uploaded by

techkasamba
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
You are on page 1/ 3

Proposed Project : Saving in power consumption

by installing VFD in N2 compressor

Saving in power consumption by installing VFD in N2 compressor


80
72
70

60

50

Power consumption in KW/Day

40

30
22
20

10

Without VDF

With VDF

Description
S NO

Description

Value

Unit

Power consumption on no load in KW(Without VFD) in KW

72

KW

Power consumption expected on no load after installation of VFD in KW

22

KW

Running hours of compressor on load

18

Hour

Running hours of compressor on no load

Hour

Power consumption on no load in KW(Without VFD) in KW

72

KW

Power consumption expected after installation of VFD in KW

22

KW

Saving in power in KW/Day

300

KW

Saving in power in KW/Month

9000

KW

Saving in INR/Month

198000

INR