ARABIA ELECTRIC LTD.

Equipment

Longitudinal Differential Protection Relay Type 7SD522 (-F87L)


FINAL SETTINGS
Contract No.

: 20531092/00

Bay/Feeder

: = C03+R11, DIA-3
HVE OHL (AC-10)

Substation
IN = 1 A

: 380 KV IWPP S/S


fN = 60 HZ
UH = 110 DC

Relay Type

: 7SD5221-4AB29-2CL5/FF

Serial No.

:BF0702087442

1. Measurements:
C.T Ratio: 2500/1
Phases

Injected current
Secondary

L1E
L2E
L3E
3I0

0.25
0.5
0.75
-

Measurement
Values
Primary
Id %

Is %

See attached Relay Print Out (2-Sheets)

1- Differential Protection
2. I DIFF > (add: 1210):

Pick up current (A)


Drop off current (A)
Time (m. sec)

Setting
0.2
0

L1-E
0.212
0.102
29.6

L2-E
0.213
0.108
27.8

L3-E
0.216
0.106
29

Note: For determining pick up and drop off current the injection is done gradually.

DATE:
19.04.2009
NAME

SIEMENS
EHAB USSAMA

SEC
M. SURRATI

SIGNATURE
PTD SE 07/2005

Page 1 of 3

SIEMENS Ltd. Saudi Arabia


Arabia Electric Ltd (E)

ARABIA ELECTRIC LTD. Equipment

Longitudinal Differential Protection Relay Type 7SD522 (-F87L)


FINAL SETTINGS
Contract No.

: 20531092/00

Bay/Feeder

: = C03+R11, DIA-3
HVE OHL (AC-10)

Substation
IN = 1 A

: 380 KV IWPP S/S


fN = 60 HZ
UH = 110 DC

Relay Type

: 7SD5221-4AB29-2CL5/FF

Serial No.

:BF0702087442

3. I - DIFF > value under switch on condition (add:1213 ):


Setting = 0.25 A
Under switch on condition, the relay will operate on the setting of {IDIFF > value under switch
on condition add (1213)} not I DIFF > value add ( 1210 ), that is during the seal in time after
manual close add ( 1150A ) and after this time the relay will operate with its normal setting I
DIFF > value add ( 1210 ).
So, you inject current more than 0.1 A add (1210 ) and less than 0.3A add ( 1213 ) in the
same time of manual close or during the 30 sec after manual close, you will find that the relay
will not trip with I DIFF > value add ( 1210 ),until the 30 sec elapsed.
But if the current was more than 0.17 A the relay will trip instantaneously by I DIFF > value
under switch on condition add ( 1213 ).

Pick up current (A)


Drop off current (A)
Time (msec)

Setting
0.25
0

L1-E
0.267
0.137
28.1

L2-E
0.266
0.136
26.3

L3-E
0.267
0.138
30.6

4. I DIFF >> (add :1233):

DATE:
19.04.2009
NAME

SIEMENS
EHAB USSAMA

SEC
M. SURRATI

SIGNATURE
PTD SE 07/2005

Page 2 of 3

SIEMENS Ltd. Saudi Arabia


Arabia Electric Ltd (E)

ARABIA ELECTRIC LTD. Equipment

Longitudinal Differential Protection Relay Type 7SD522 (-F87L)


FINAL SETTINGS
Contract No.

: 20531092/00

Bay/Feeder

: = C03+R11, DIA-3
HVE OHL (AC-10)

Substation
IN = 1 A

: 380 KV IWPP S/S


fN = 60 HZ
UH = 110 DC

Relay Type

: 7SD5221-4AB29-2CL5/FF

Serial No.

:BF0702087442

Raise the setting of I DIFF > add ( 1210 ) and I DIFF > value under switch on condition
add ( 1213 ) above setting of I DIFF >> add ( 1233 ).
Pick up current (A)
Time (m. sec)

Settings
1.7
0

L1-E
1.66
15

L2-E
1.67
13

L3-E
1.67
17

5. 2nd HARMONIC TEST:

Id> Set
200mA

Injected
(A)
1

DATE:
19.04.2009
NAME

SETTING
HARMONICS
15% = 0.15A

SIEMENS
EHAB USSAMA

L1

L2

L3

0.18

0.18

0.18

SEC
M. SURRATI

SIGNATURE
PTD SE 07/2005

Page 3 of 3

SIEMENS Ltd. Saudi Arabia


Arabia Electric Ltd (E)