0% found this document useful (0 votes)
307 views3 pages

7sd522 Diff

1. This document provides the final settings for a longitudinal differential protection relay for a 380kV feeder. 2. Measurements were taken at various injected currents and the differential protection pickup and dropout settings were determined to be 0.2A and 0A respectively within 30 seconds of operation. 3. Under switch-on conditions, the pickup setting is increased to 0.25A for 30 seconds to prevent unwanted operation during energization. 4. The high set differential protection setting was set to a pickup of 1.7A within 15-17 seconds to coordinate with the other settings. 5. A second harmonic test was performed and the measured currents were within 15% of the injected current,

Uploaded by

Insan Aziz
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
307 views3 pages

7sd522 Diff

1. This document provides the final settings for a longitudinal differential protection relay for a 380kV feeder. 2. Measurements were taken at various injected currents and the differential protection pickup and dropout settings were determined to be 0.2A and 0A respectively within 30 seconds of operation. 3. Under switch-on conditions, the pickup setting is increased to 0.25A for 30 seconds to prevent unwanted operation during energization. 4. The high set differential protection setting was set to a pickup of 1.7A within 15-17 seconds to coordinate with the other settings. 5. A second harmonic test was performed and the measured currents were within 15% of the injected current,

Uploaded by

Insan Aziz
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 3

ARABIA ELECTRIC LTD.

Equipment

Longitudinal Differential Protection Relay Type 7SD522 (-F87L)


FINAL SETTINGS
Contract No.

: 20531092/00

Bay/Feeder

: = C03+R11, DIA-3
HVE OHL (AC-10)

Substation
IN = 1 A

: 380 KV IWPP S/S


fN = 60 HZ
UH = 110 DC

Relay Type

: 7SD5221-4AB29-2CL5/FF

Serial No.

:BF0702087442

1. Measurements:
C.T Ratio: 2500/1
Phases

Injected current
Secondary

L1E
L2E
L3E
3I0

0.25
0.5
0.75
-

Measurement
Values
Primary
Id %

Is %

See attached Relay Print Out (2-Sheets)

1- Differential Protection
2. I DIFF > (add: 1210):

Pick up current (A)


Drop off current (A)
Time (m. sec)

Setting
0.2
0

L1-E
0.212
0.102
29.6

L2-E
0.213
0.108
27.8

L3-E
0.216
0.106
29

Note: For determining pick up and drop off current the injection is done gradually.

DATE:
19.04.2009
NAME

SIEMENS
EHAB USSAMA

SEC
M. SURRATI

SIGNATURE
PTD SE 07/2005

Page 1 of 3

SIEMENS Ltd. Saudi Arabia


Arabia Electric Ltd (E)

ARABIA ELECTRIC LTD. Equipment

Longitudinal Differential Protection Relay Type 7SD522 (-F87L)


FINAL SETTINGS
Contract No.

: 20531092/00

Bay/Feeder

: = C03+R11, DIA-3
HVE OHL (AC-10)

Substation
IN = 1 A

: 380 KV IWPP S/S


fN = 60 HZ
UH = 110 DC

Relay Type

: 7SD5221-4AB29-2CL5/FF

Serial No.

:BF0702087442

3. I - DIFF > value under switch on condition (add:1213 ):


Setting = 0.25 A
Under switch on condition, the relay will operate on the setting of {IDIFF > value under switch
on condition add (1213)} not I DIFF > value add ( 1210 ), that is during the seal in time after
manual close add ( 1150A ) and after this time the relay will operate with its normal setting I
DIFF > value add ( 1210 ).
So, you inject current more than 0.1 A add (1210 ) and less than 0.3A add ( 1213 ) in the
same time of manual close or during the 30 sec after manual close, you will find that the relay
will not trip with I DIFF > value add ( 1210 ),until the 30 sec elapsed.
But if the current was more than 0.17 A the relay will trip instantaneously by I DIFF > value
under switch on condition add ( 1213 ).

Pick up current (A)


Drop off current (A)
Time (msec)

Setting
0.25
0

L1-E
0.267
0.137
28.1

L2-E
0.266
0.136
26.3

L3-E
0.267
0.138
30.6

4. I DIFF >> (add :1233):

DATE:
19.04.2009
NAME

SIEMENS
EHAB USSAMA

SEC
M. SURRATI

SIGNATURE
PTD SE 07/2005

Page 2 of 3

SIEMENS Ltd. Saudi Arabia


Arabia Electric Ltd (E)

ARABIA ELECTRIC LTD. Equipment

Longitudinal Differential Protection Relay Type 7SD522 (-F87L)


FINAL SETTINGS
Contract No.

: 20531092/00

Bay/Feeder

: = C03+R11, DIA-3
HVE OHL (AC-10)

Substation
IN = 1 A

: 380 KV IWPP S/S


fN = 60 HZ
UH = 110 DC

Relay Type

: 7SD5221-4AB29-2CL5/FF

Serial No.

:BF0702087442

Raise the setting of I DIFF > add ( 1210 ) and I DIFF > value under switch on condition
add ( 1213 ) above setting of I DIFF >> add ( 1233 ).
Pick up current (A)
Time (m. sec)

Settings
1.7
0

L1-E
1.66
15

L2-E
1.67
13

L3-E
1.67
17

5. 2nd HARMONIC TEST:

Id> Set
200mA

Injected
(A)
1

DATE:
19.04.2009
NAME

SETTING
HARMONICS
15% = 0.15A

SIEMENS
EHAB USSAMA

L1

L2

L3

0.18

0.18

0.18

SEC
M. SURRATI

SIGNATURE
PTD SE 07/2005

Page 3 of 3

SIEMENS Ltd. Saudi Arabia


Arabia Electric Ltd (E)

You might also like