Electrical Safe Work Practice
Electrical Safe Work Practice
Electrical Safe Work Practice
CONTENTS
ELECTRICAL SAFE WORK PRACTICES HES-206
Section
Title
Page
1.0
Purpose
206 - 1
2.0
Scope
206 - 1
3.0
206 - 2
4.0
206 - 3
5.0
206 - 40
5.1
206 - 40
5.2
Substations
206 - 41
5.3
206 - 42
5.4
206 - 43
5.5
Lines
206 43
5.6
206 47
5.7
206 47
5.8
Signage
206 47
5.9
206 48
6.0
206 - 49
7.0
206 - 52
8.0
Employee Training
206 - 54
9.0
Facility Work
206 - 59
10.0
206 - 61
11.0
References
206 - 62
Appendices
Appendix A Clearance and Approach Boundaries Figures and Tables
Appendix B Limits of Approach
Appendix C Flame-Resistant Clothing Recommendations
Appendix D Sample Calculation of Flash Protection Boundary Dc, Arc in Open Air Ema,
and Arc in Cubic Box Emb
Appendix E Recommended Personal Protective Equipment
Appendix F Work Area Protection
Appendix G Job Briefing and Planning Checklist
Appendix H Energized Electrical Work Permit
Appendix I Substation Project Installation Safety Assessment Checklist
Appendix J Substation Inspection Checklist
Appendix K Electrical Control Room Inspection Checklist
Appendix L Test Procedure for Daily Inspection of Rubber Gloves
Appendix M Safety Tags
Appendix N Grounding Cable and Jumper Ratings
Appendix O Equipotential Grounding Techniques
Appendix P Principles of Electrical Safety
Appendix Q OSHA Regulations (Standards 29 CFR)
Appendix R Sample Procedures for Overhead Electrical Lines and Equipment
Appendix S Example of Flash Protection Labels for Electrical Equipment
Appendix T - Glossary
1.0
Purpose
Most incidents and injuries related to electrical systems can be avoided by following the safe
work practices described in this document. In addition to the personal pain of suffering an
injury, incidents can result in lost time, medical costs, equipment damage, production loss,
and legal costs.
2.0
Scope
2.1
This document provides the minimum safety knowledge and procedures that allow
individuals and facilities to work with, or in proximity to, energized high- and low-voltage
sources. (In the language of applicable safety standards, this is formally designated to be
working near or working on exposed live parts - See Appendix T - Glossary.) Individuals
and facilities, however, are responsible for customizing this information to include details
and activities specific to their locations.
2.2
Safety Considerations
This practice sets minimum safety rules and safe work recommendations for the design,
operation, and maintenance of high- and low-voltage systems throughout Chevron Pipe Line
Company (hereinafter referred to as company) facilities. It is imperative that, at a
minimum, these guidelines are met (or exceeded) to enhance employee safety. If more
stringent local governmental codes, accepted employee safety practices, or design criteria
exist, follow those codes or standards.
2.3
This document applies to all employees, contractors, and visitors while they are close to
energized conductors, energized exposed parts of electrical equipment, or conductors and
equipment that potentially may become energized.
2.4
This practice applies to new or modified high- and low-voltage installations. Existing
installations need not be physically modified to comply with this document unless qualified
personnel consider the modifications necessary to protect affected persons from recognized
hazards.
2.5
References
For the purpose of this practice, low voltage means 1,000 volts nominal or less phase-tophase or conductor-to-conductor, and high voltage means voltages above 1,000 volts ac,
phase-to-phase.
2.6
Knowledge of this practice by itself does not make a person a qualified electrical worker.
Each site should establish guidelines for informal and formal training, as well as the levels of
experience needed for workers in the electrical field or other workers whose job function
exposes them to a potential electrical hazard. (NFPA 70E, 110.3; NFPA 70E, 110.6)
3.0
3.1
Location Management
3.2
adopting precautions that are within the individuals authority to prevent accidents,
and taking positive action to obtain necessary precautions for those concerns not
within the individuals authority to assure employee safety.
ensuring that the site safety rules, training requirements, and operating procedures, as
contained in this or other practices, are observed by the employees under his or her
direction.
ensuring that the tools or devices used are suited for the work at hand and that
applicable tools have been inspected and tested as required.
3.3
Employee
The employee is the person most responsible for his or her own safety.
Qualified and authorized employees should remain knowledgeable about applicable
electrical safety concerns as contained in this practice or other practices.
Affected employees should be aware of electrical hazards, where electrical work is not
their primary task, but where the opportunity for contact exists (i.e., during lockout/tagout,
when working near open crane rails or motor control centers and switchgear, around cable
ladders, and resetting devices and equipment).
3.4
Escort
The escort is a qualified employee whose responsibility is to safeguard the people in his or
her care and to assure that safety regulations are observed.
3.5
Contractors and visitors are to follow, at a minimum, all safety regulations of this facility as
contained in this practice.
4.0
4.1
Page 206-3
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
4.1.1
General Policies
The companys general policy is that NO maintenance or construction/installation
work is performed on any conductors and/or exposed equipment parts at 50 volts
and above while energized. (NFPA 70E, 130.1; OSHA regulation 1910.333(a)(1))
If exposed live parts are not placed in an electrically safe work condition (i.e., for
the reasons of increased or additional hazards or infeasibility), work to be
performed is considered energized electrical work and should only be performed
as permitted by written permit. The energized electrical work permit could include
the following items:
a) A description of the circuit and equipment to be worked on and their
location
b) Justification for why the work must be performed in an energized
condition
c) A description of the safe work practices to be employed
d) Results of the shock hazard analysis
e) Determination of shock protection boundaries
f) Results of the flash hazard analysis
g) The flash protection boundary
h) The necessary PPE to safely perform the assigned task
i) Means employed to restrict the access of unqualified persons from the
work area
j) Evidence of completion of a job briefing, including a discussion of any
job-specific hazards
k) Energized Work Approval (authorizing or responsible management, safety
officer, or owner, etc.) signature(s)
NOTE:
Work performed by qualified persons on or near live parts related to tasks, such as
testing, troubleshooting, voltage measuring, etc., can be performed without an
energized electrical work permit provided appropriate safe work practices and
personal protective equipment are provided and used.
Page 206-4
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
protection boundary, and the necessary PPE used by people while working within
the boundary, is determined during this analysis.
4.1.2
When these activities, listed as exceptions, place the worker in close proximity to
exposed live parts, appropriate PPE should be used. Such PPE, in addition to the
minimum basic PPE requirements for electrical personnel, may include:
Page 206-7
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
4.2
4.2.1
Hazards
When working on or near energized equipment, there are two primary hazards to
consider:
Shock hazard.
Flash Hazard Analysis and Arc Flash Protective Equipment (NFPA 70E, 130.3)
Flash hazard analysis should be done before a person approaches any exposed
electrical conductor or circuit part not placed in an electrically safe work
condition.
Establish a flash protection boundary and require all personnel crossing the
boundary to wear appropriate arc flash protective equipment. This requirement
provides protection from vaporized metal, arc radiation, or hot gases should an arc
flash occur on the equipment. (OSHA regulation 1910.269(l)(6)(i-iii))
The size of the flash protection boundary is determined by:
The size of the source transformer or the available short-circuit megavolt
amperes (MVA)
Page 206-8
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
4.2.3
Approach Distances
(NFPA 70E, 130.2; OSHA regulation 1910.269(l)(2);(Table A-6); OSHA
regulation 1910.333(c)(3)(i-ii);(Table 5-5))
The approach distance to exposed live parts varies depending on a persons status:
Affected persons (persons who are not authorized or qualified) should
adhere to the limited approach boundary (Ten (10)-Foot Rule) and not
encroach on this distance from an exposed live part.
Authorized persons, who are specifically trained for a task, may work
inside the limited approach boundary, but should never be allowed to work
as close as the restricted approach boundary allowed for a qualified
employee, as shown in Appendix A, Table A-6.
Page 206-9
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Crossing the prohibited approach boundary and entering the prohibited space is
considered the same as making contact with exposed live parts.
4.2.5
4.2.6
4.2.7
Employees on the ground should stay clear of overhead work to reduce the
potential of being struck by falling objects.
Page 206-10
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
4.2.8
Work that uses mechanical equipment (other than insulated aerial lifts)
near parts energized at more than 600 volts
Work using live-line tools, as long as the employee cannot make contact
with exposed live parts through inadvertent reach
The energized part is insulated from the employee and any other
conductive object at a different potential.
Page 206-12
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
The work on the exposed live parts does not expose the
worker to accidental contact with other exposed live
parts in the vicinity of the task.
4.3
Equipment/Line Status
4.3.1
Basic Rule
Electrical equipment and lines should be considered energized until put in an
electrically safe work condition, i.e., disconnected from energized parts, tested,
locked out and/or tagged out, and grounded in accordance with section 4.9
Lockout/Tagout and section 4.10 Grounding. (NFPA 70E, 130.1; OSHA
regulation 1910.269(l)(1); OSHA regulation 1910.333(a)(1))
4.3.2
Identify all potential voltage sources and make plans to positively control all
conductors and isolating devices. Additionally:
a) Determine all possible voltage sources; check all drawings, diagrams,
identification tags, etc.
b) Interview individuals familiar with the facility.
c) Interrupt all load current and then open isolation devices.
d) Where possible, visually verify open disconnects.
e) Apply lockout/tagout devices according to procedure.
f) Use voltage detection devices adequately rated for the situation and
determine that the voltage detector is operating properly before and after
each test.
g) Apply ground connection devices rated for the available short-circuit duty
where:
Conductors could become energized.
b) Purchase panel boards (1,000 volts and less) pre-equipped with locking
devices and use these devices for lock out.
c) Remove fuses from low-voltage switches that have covered blades, if
applicable, after verifying there is no voltage.
d) Withdraw draw-out circuit breakers to the farthest position in the cubicle
(with the line and load stabs disconnected) and completely remove the
circuit breaker if a ground-and-test device will be applied. (NFPA 70E,
120.1)
e) Remove high-voltage motor starter (sometimes referred to as NEMA E2
starter) contactor assemblies completely from their cubicles, to avoid
accidental rolling of the contactor truck back onto the contact stabs.
f) Open isolation disconnects on circuit breakers within open-air
switchyards. Remove any fuses for additional isolation.
g) Do not rely on control circuit isolation for lockout purposes. Provide
primary circuit isolation on circuit breakers and motor starters (i.e.,
withdraw, or rack out, circuit breakers or open disconnect switches).
(OSHA regulation 1910.269(x)"Energy isolating device")
Any voltage testing procedure should include the following considerations:
What voltage detector will be used and what will be done to verify proper
operation of the voltage detector before and after use.
Page 206-15
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
4.4
4.4.1
4.4.2
Remove all personal safety locks and tags from points of disconnect.
Page 206-16
4.5
4.5.1
Preparation
Written Switching Order (NFPA 70E, 130.1)
A written switching order is recommended before any switching is performed on
the high-voltage distribution power system (this recommendation does not include
switching of individual motors). The switching order should be:
Written by a qualified employee.
4.5.3
During Switching
Page 206-17
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
During switching, follow the written switching order in the order the steps are
written, check off each switching step when completed, and record the time of
completion.
The following switching procedures are recommended:
a) The person receiving a switching command repeats the switching
command and confirms it with the person issuing the order before
executing the command.
b) If switching commands are given by radio, use a unique switching
channel. Cross-talk on the radio during switching could cause a switching
error.
c) When the switching is complete, document the status of the power system.
Use of a status board or pin board is one method of accomplishing this.
d) Document information on power system abnormalities to inform off-shift
personnel who may be involved in responding to power system problems.
Post this information near a power system status board or pin board.
e) Post any issues involving open electrical clearances (or parts of the power
system under lockout/tagout), the location of any safety grounds, and other
power system safety issues near the power system status board or pin
board.
f) A second person stands clear and acts as a safety observer for the person
doing the switching. The safety observer assures that each step the switch
operator is about to perform is correct.
4.5.4
f) Work zones
During the job briefing, each person involved should ask himself or herself the
following questions prior to starting the task:
Do I thoroughly understand the job?
As work progresses during the day after the initial job briefing, a person working
alone should plan and review his or her work as if a briefing were held before
each task.
Refer to the Job Briefing and Planning Checklist in Appendix G.
4.6
Clothing/Apparel
The employer should assure that employees who are exposed to exposed live parts
are trained in the hazards of arcs and flames of arcs. (OSHA regulation
1910.269(l)(6)(iii); NFPA 70E 130.3 (B), 130.7 Clothing/Apparel)
Page 206-19
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
For calculated incident energy exposures 2 cal/cm2, and below, employees may
wear non-melting clothing as described in Hazard/Risk Category O. (NFPA 70E,
130.7 (C)(5)Exc.)
The employer must assure that conductive articles are not worn in close proximity
or within reaching distance of exposed live parts. This requirement includes rings,
bracelets, metal watchbands, unrestrained metal-framed eyewear, metal dangling
jewelry, and key chains. (OSHA regulation 1910.269(l)(6))
4.6.2
4.6.3
Wear approved safety glasses with non-conductive sideshields at all times when
working with or in close proximity to potentially energized conductors or exposed
non-insulated parts. (See ANSI Z87.1).
Goggles and/or arc-rated face shields may also be needed for the task.
4.6.4
Hand Protection
Wear leather gloves for arc-flash protection when insulating rubber gloves are not
applicable. (NFPA 70E 130.7 (C)(13)(c))
Always use insulating rubber gloves with leather protectors (when required for
shock protection) in the following situations:
When working on energized, or potentially energized, conductors or
equipment
The work on the exposed live parts does not expose the
worker to accidental contact with other exposed live
parts in the vicinity of the task.
NOTE:
Page 206-21
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
(130.8(C)(12)(f))
Only use gloves that have been dielectrically tested within the previous six (6)
months. (ref. ASTM F496) (OSHA regulation 1910.137(b)(2)(viii))
Inspect and air test gloves before each use and immediately following any incident
that can reasonably be suspected as having caused damage. Air testing is
performed by trapping air in the glove and examining for pin hole or other
apparent leakage (see Appendix L - Test Procedure for Daily Inspection of Rubber
Gloves) (ASTM F496).
Store gloves in an approved glove bag or an equivalent protective location. If
possible, store gloves with the cuffs down.
Do not exceed the rating on the glove as shown in Table 1.
TABLE 1: Insulating Rubber Glove Ratings
Insulating Rubber Gloves
4.6.5
Class
00
500 volts
2,500 volts
1,000 volts
5,000 volts
7,500 volts
10,000 volts
17,000 volts
20,000 volts
26,500 volts
30,000 volts
36,000 volts
40,000 volts
4.7
Tools
Page 206-22
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Store live-line tools in a clean and dry location. Live-line tools should not be
placed on the ground.
Wipe clean each live-line tool and visually inspect it for defects before use each
day. If, after wiping, the tool has contaminants that could affect its insulating
qualities or if its mechanical integrity is questionable, remove the tool from
service and have it repaired.
Following repair, retest the tool using the testing program procedures described
below.
Testing Procedure (OSHA regulation 1910.269(j)(2)(iii))
Remove each live-line tool from service at least every two years and administer
the following examination and tests:
a) Thoroughly examine the tool for defects.
b) If defects or contaminants that could affect the insulating qualities or
mechanical integrity of the tool are found, the tool may be repaired and
refinished or permanently removed from service.
c) If no defects are detected and no contaminants found, clean and wax the
tool using only a wax approved for live-line tools.
d) Use a test method that tests the entire working length of the tool.
e) Tools made of fiberglass-reinforced plastic (FRP) should be tested with
wet conditions applied over the entire working length of the tool.
f) If the tool is made of FRP, the test consists of applying 100,000 volts per
foot (30 cm) of length for five (5) minutes. (ref. IEEE 978) (OSHA
regulation 1910.269(j)(1)(I); IEEE Std. 978)
g) Other high voltage tests are acceptable if the employer can demonstrate
that these are equivalent (such as IEEE Std. 978-1984).
4.7.2
Portable and vehicle-mounted generators being used to supply cord- and plugconnected equipment should meet the following requirements:
The generator frame should have a connection to ground (earth) (OSHA
regulation 1910.269(i)(3)).
The generator can supply only the equipment located on the generator or
vehicle and cord- and plug-connected equipment through receptacles
mounted on generator or vehicle.
NOTE:
4.7.3
Do not exceed the working load for which the ladder or platform was designed.
4.8
Work Zone
Work zones may be needed to safeguard personnel from potential hazards. Use barricades, in
conjunction with safety signs, to limit or prevent access to work areas where hazards may
exist. (NFPA 70E, 130.7 (E); OSHA regulations 1910.269(l)(2). (u)(4), (o)(3))
In some instances, it is appropriate to barricade or otherwise identify a work area as
containing electrical hazards not normally encountered during routine operation of the
equipment and/or conductors. This process would normally be the case during maintenance
or renovations to existing installations and additions to installations where electrical
equipment and/or conductors are located. Appropriate identification alerts employees of the
hazards in their work areas. (OSHA regulations 1910.335(a)(2)(ii) and 1910.335(b))
4.8.1
4.8.2
The red tape should be imprinted with wording such as Danger - Do not
Enter.
Area Protection
Page 206-25
If the work exposes energized or moving parts that are normally protected:
Display danger signs.
Erect suitable barricades to restrict other personnel from entering the area.
When working in a restricted section that borders other sections (i.e., a portion of
a substation, one section of switchgear, a row of transformers or breakers, or one
panel of a switchboard), a qualified employee should:
Mark the work area conspicuously.
NOTE:
Enclosed Spaces
These recommendations apply only to enclosed spaces, such as manholes,
unvented vaults, tunnels, etc., that can be entered by employees. All other
confined spaces as defined by OSHA are covered by 29 CFR 1910.146 (OSHA
regulations). (NFPA 70E, 130.6 (F); NESC 423)
Assure that employees use safe work practices for entry into and work within
enclosed spaces and for rescue of employees from such places. If hazards remain
after the precautions taken for enclosed space or if the escape procedures cannot
be met, follow the permit-space or confined space requirements of 29 CFR
1910.146. (OSHA regulation 1910.269(e); OSHA regulation 1910.146)
Employees who enter enclosed spaces or serve as attendants should be trained in
the following:
Page 206-26
first aid, hazards of enclosed space entry, enclosed space entry procedures,
and enclosed space rescue procedures.
f) Make sure that all employees are in constant communication. This
communication can consist of visual, voice, or signal line communication.
g) Permit an employee to enter if the nature of the visit does not involve the
energized cables or equipment, but it is for housekeeping, inspection,
meter reading, or similar activities. This entrance is permitted only if all
confined space entry requirements are met and the task can be done safely.
h) Provide rescue equipment at the work site to assure the prompt and safe
rescue of employees from the enclosed space. Rescue equipment includes
a mechanical device to retrieve personnel, a full body harness (wristlets
may be used in lieu of the harness), and a retrieval line.
i) If using pulling tapes, install them in the direction that presents the least
amount of hazard to employees. Station an employee at the far end of the
duct line to assure that required minimum approach distances are
maintained to protect employees. (OSHA regulation 1910.269(t)(4))
j) Move an energized, armored, insulated, high-voltage cable only after the
location manager or his or her designee has approved a documented plan.
k) Be sure to move an energized, insulated, low-voltage cable only under the
direct supervision of a qualified employee and while using insulating
gloves.
l) Before proceeding, inspect any cable to be moved for defects, using
appropriate PPE. See Appendix C for PPE requirements.
NOTE:
4.9
4.10
Grounding
Page 206-30
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
CAUTION:
Grounds left on equipment when re-energized present a shortcircuit hazard. Use a positive method of control to assure
removal before re-energizing (tags, leaving doors or covers
open, leaving the ground cables clearly visible, use of magnetic
ground signs, etc.).
4.10.2
Special Precautions
Remember that motor space heaters are usually supplied from foreign
voltage sources.
Ground all motors equipped with power factor correction capacitors. Additionally,
ground all motor circuits above 600 volts before working on the motor. Use a
switchgear ground and test device, or connect grounds at the load-side cable
connections of the circuit breaker or starter.
4.10.3
Page 206-31
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
4.10.4
Cable Cutting
Ground both ends where practical. Use a cable penetrator tool (such as A. B.
Chance companys catalog number C600-1625) to penetrate the insulation at the
point of the cut if the cable cannot be visibly traced from the point of the cut to
one of the two ends.
4.10.5
Traditional Methods
This section describes the procedure for grounding transmission and distribution
lines and equipment:
a) Before work on lines or equipment designated as de-energized, issue a
clearance that all isolating points have been locked and tagged and
appropriate safety grounds have been installed, as detailed in this section.
(For exceptions, see section 4.10.6.) (NFPA 70E, 120.1, 120.2(F)(2)(g);
OSHA regulation 1910.269(d)(2))
b) Before any ground is installed, first test the lines or equipment for absence
of voltage unless a previously installed ground is present. (OSHA
regulation 1910.269(n)(5))
c) Before installing grounds, visually inspect the grounding equipment to
confirm the equipments integrity.
d) Install temporary protective grounding equipment at the work location.
(OSHA regulation 1910.269(n)(3); NFPA 70E, 120.3)
e) If installation of grounds at the work location is not feasible, install
grounds on each side of the work location as close to the work location as
possible.
f) Single-point grounding (equipotential grounding, see section 4.10.9) is an
acceptable means of grounding.
g) Ground static capacitors (surge protection capacitors and power factor
correction capacitors) before working on them even if there is no
possibility of their becoming energized. Wait five minutes between
isolating the capacitor and applying the grounds.
CAUTION:
4.10.6
Grounds left on equipment when re-energized present a shortcircuit hazard. Use a positive method of control to assure
removal before re-energizing (tags, leaving doors or covers
open, leaving the ground cables clearly visible, use of magnetic
ground signs, etc.).
If the parts are free from voltage, the grounding may be completed.
4.10.7
Determine the source of the voltage to assure that the presence of this
voltage does not prohibit completion of the grounding.
Removing Grounds
Grounds may be removed temporarily for testing. During the test procedure,
consider the previously grounded lines and equipment as energized.
When removing grounds:
First remove the grounding devices from the de-energized parts using liveline tools.
4.10.8
4.10.9
Equipotential Grounding
Equipotential grounding is a technique used in transmission and distribution lines.
Different methods include single-point, double-point, remote double-point, and
personal grounding. These grounding techniques require much skill. Before using
these methods, complete hands-on training and receive qualification.
Single-point grounding occurs when a worker connects all three phases together
with jumpers and then attaches the phases through a single jumper to a cluster bar.
The cluster bar is attached to the pole below the workers . The cluster bar is
connected by a jumper to the neutral conductor, if available. If a ground fault
should occur, the worker will be at the same voltage as the lines and current
should not flow through his or her body.
Double-point grounding is necessary if work at the pole involves breaking the
circuit. It is necessary to ground sources that may come from either direction. The
phases are connected to each other, on both sides of the worker, to the cluster bar
below the workers feet and to the neutral.
Remote double-point grounding allows the worker more movement between the
jumper sets, but offers less protection than other methods. The grounds are
connected to structures, such as towers, on each side of the work location. In this
case, fault current would flow through the towers into the earth. With this method,
it is still possible to have potentially fatal current flow through the workers body.
It is not recommended unless additional safeguards are taken (see Personal
Grounding, below).
Personal grounding is where a jumper connects the conductor being worked on to
the cluster bar and to the neutral. These can be installed quickly and may be used
in addition to remote grounding when full three-phase grounding at the work site
is inappropriate.
NOTE:
4.10.10
Page 206-34
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
4.11
4.11.1
In General
Inspect the critical safety components of mechanical elevating and rotating
equipment before use on each shift. Check the lower and upper controls to assure
they are functioning correctly. Follow the manufacturers recommended checklist
for the inspection. (OSHA regulation 1910.269(p)(1)(i))
No vehicular equipment with an obstructed view to the rear can be used for offhighway job sites, unless one of the following provisions is met:
The vehicle has a reverse signal alarm louder than the surrounding noise
level.
Page 206-35
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
the mobile equipment is moved to the job site. This notification is the
responsibility of location personnel.
4.11.2
Outrigger-equipped Vehicles
Operate outrigger-equipped vehicles with outriggers extended and firmly set to
provide stability. (OSHA regulation 1910.269(p)(2))
Outriggers may not be retracted or extended beyond the clear view of the operator,
unless all employees are outside the range of possible equipment motion.
If the work area or terrain prohibits full use of outriggers, operate the equipment
according to the manufacturers specifications for operation without outriggers.
4.11.3
Operator Training
Mobile equipment operators not qualified in electrical work need the following
training if their equipment has the potential of coming as close as 10 (see the
Ten (10)-Foot Rule definition in Appendix T - Glossary) to energized lines or
equipment:
Training in the potential electrical shock hazards associated with
equipment operation under these conditions
4.11.4
any other cause, ground the vehicle or barricade around it. (OSHA
regulations 1910.269(p)(4)(iii) and (c)(4))
d) If it is difficult for the operator to accurately determine the distance
between the equipment and the energized parts, assign another person to
observe the clearance and give timely warnings when the minimum
clearance distance is approached. (OSHA regulation 1910.269(p)(4)(ii))
e) It is generally recommended that no equipment or material be hoisted over
energized, non-insulated high-voltage conductors or equipment. Any
exception to this policy should require approval by the location manager or
his or her designee. Submit a documented plan for this type of work.
f) When operating in close proximity to energized conductors or circuit
parts, inspect all mobile equipment in accordance with the section of this
practice on inspection and testing of mechanized equipment (section 7.4).
Properly ground or barricade this equipment in accordance with the
section on grounding mobile equipment (section 4.11.5). (OSHA
regulation 1910.269(p)(4)(i); NFPA 70E, 130.5 (E); OSHA regulation
1910.333(c)(3)(iii)(c))
g) Post minimum approach distances on a plate of durable non-conductive
material so it is visible to the operator.
Mobile Equipment in Transit
The following clearances must be observed for equipment in transit with no load
and the boom is lowered:
For voltages less than 50 kV, observe a minimum clearance of 4 (122
cm).
For voltages higher than 50 kV, increase the clearance 4 (10 cm) for
every 10 kV over that voltage.
When visual conditions make it difficult for the operator to maintain the
desired clearance, designate a person to observe clearance for the operator.
EXCEPTION: An exception to this procedure is where lines have been deenergized and visibly grounded or where insulating barriers
have been erected to prevent physical contact. (NFPA 70E,
130.5 (E)(1)); OSHA regulation 1910.333(c)(3)(iii)).
4.11.5
Page 206-37
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Ground leads should be not less than 2/0 flexible-stranded copper rubber-covered
cable to provide physical strength. The cable jacket is for mechanical protection of
the conductor only.
Ground leads should be visually inspected for any type of damage or wear before
installing.
Methods
Only personnel trained in the proper grounding techniques should attach/detach
grounding sets.
Ground mobile equipment before raising a crane or derrick boom or similar
equipment.
On a vehicle, trailer, or other mobile equipment (i.e., cranes, line trucks, and aerial
lifts), make a connection from a suitable ground plate or stud on the vehicle to the
best ground available in the immediate work area.
On distribution circuits, the best ground available is normally the common
neutral or ground grid system. The second choice is a tower or other grounded
structure. Only use a driven ground rod as a final alternative. Instruct workers to
stay clear of the driven ground location. Use other protective means, such as
barricades, as necessary to avoid step potential and touch potential hazards
that may occur around the driven rod during a ground fault.
Follow the correct grounding sequence:
First, attach the ground lead to the best available ground.
4.11.6
Sample Procedures for Working Near Overhead Electrical Lines and Equipment
For procedures used by one business unit for working near overhead lines and
equipment, see Appendix R.
4.12
Infrared Testing
(ASTM E1934-99a)
4.12.1
Safety Interlocks
Page 206-38
Safety interlock systems offer a high degree of personnel safety and should be
used in all designs. Generally, do not bypass the interlock system or otherwise
render it inoperative while the equipment is energized. (NFPA 70E Part II 2-3, 11;
OSHA regulation 1910.269(v)(1)(ii))
Where defeating safety interlocks is required, a temporary bypass is allowed only
with approval of the switching authority.
After testing is completed, restore the interlocking system to full operable
condition. Follow procedures for working inside the restrictive approach boundary
when it is necessary to defeat an electrical safety interlock.
4.12.2
Approved clothing.
Safety shoes.
Safety shoes.
Leather gloves.
Page 206-39
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
5.0
5.1
Many equipment design elements are covered in the companys Safety in Designs manual.
Design, operation, and maintenance considerations for personnel safety relevant to electrical
safety issues might include any combination of the following:
a) Separate low-energy circuits from circuits having a large arc flash hazard.
b) Apply current-limiting fuses, where appropriate, to reduce the arc flash hazard.
c) Purchase motor control centers with guards covering internal exposed live parts
above 120 volts.
d) Use ground-fault circuit interrupters to reduce shock hazards for portable
equipment.
e) Include fast protection that will clear faults as quickly as possible and reduce the
arc exposure time in the protective system design. Differential protection, with a
total fault clearing time of approximately 0.1 second, will greatly reduce arc
exposure and the probability of escalation to a more severe fault involving two or
more phases. Differential protection is recommended for all switchgear operating
at over 1000 volts.
f) Limit transformer sizes to 1,500 kVA and below to avoid excessive flash energy
for 480- and 600-volt systems.
g) Keep the arc flash hazard on 208Y/120 volt systems to a minimum risk level by
limiting the size of supply transformers at this voltage to less than 125 kVA.
(IEEE Std. 1584-2002 9.3.2)
h) Specify remote closing and tripping capability, using either a plug-in cord and
control or a supervisory control panel switch (for remote-operation), for all circuit
breakers operating at over 1,000 volts. This process allows the operator to be
outside of the flash protection boundary while closing or tripping a circuit breaker.
i) Specify two tie circuit breakers between switchgear buses to improve the
electrical isolation for busbar or switchgear maintenance. Workers could then
work on or within a switchgear cubicle without the possibility of one set of circuit
breaker stabs being energized.
j) Specify closed-door and remotely operated racking (insertion and removal)
capability for switchgear.
k) Specify insulated bus, which prevents or minimizes arc propagation within the
gear after the fault initiates and can reduce the arc flash hazard, for all electrical
switchgear and control gear of all voltages.
Page 206-40
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
NOTE:
5.2
Substations
Design and construct all new substations in accordance with national and local codes and in
such a manner as to afford maximum protection of the public, qualified employees and nonqualified employees.
When modifying existing substations, make every effort to upgrade the station to current
practices.
When designing, modifying, or constructing substations, follow these recommendations:
a) Always provide and maintain sufficient access and working space.
b) Consider designs that have no accessible conductors and use insulated cable and
dead-front switchgear for all new or revised 600 volt to 38 kV distribution
systems. (Generally, this consideration excludes incoming power feeds.)
c) Connect all equipment and structures to a common ground grid.
d) Make sure that draw-out-type breakers are in the open position when removed or
inserted. The control circuit should also be blocked or rendered inoperative, if the
design permits.
e) Locate all exposed live parts, including the energized racks of static capacitors, to
provide personnel clearance in accordance with Appendix A, Table A-1.
f) Enclose substations that are not totally enclosed and that have exposed, energized
parts by fences at least seven (7) (2.1 meters) in height, with gates secured by
suitable locks.
Page 206-41
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
5.3
Cabinet or enclosure.
Balcony or platform.
For systems exceeding 1,000 volts, the above applies with the following additions: (OSHA
regulations 1910.269(v)(4) and (v)(5))
The following recommendations should be followed for the guarding of all exposed live
parts:
a) Enclose energized parts installed in rooms and similar spaces with fences, screens, or
walls.
b) Lock all entrances not guarded by an attendant.
Page 206-42
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
c) Display signs warning unqualified personnel to keep out at the entrance to enclosures
or spaces with exposed live parts.
d) Do not allow unqualified employees to enter these rooms and spaces while supply
lines and equipment are energized.
e) Place guards around all exposed live parts that have voltages above 150 volts to
ground and that have no insulation covering, unless the location of these parts gives
enough horizontal and vertical clearance to prevent inadvertent contact.
f) For protection of personnel and equipment, all exposed live parts should remain
guarded during all functions except fuse replacement or other needed access permitted
to qualified personnel only.
g) Put barriers in place when guards are removed to prevent harmful contact.
h) Design covers or guards that must at any time be removed while the parts they guard
are energized, so that they cannot readily be brought into contact with the energized
parts.
(Also see OSHA regulations 1910.269(u)(4)(i-v))
5.4
5.5
Lines
(NESC Part 2)
Design and construct all new lines in accordance with national and local codes and in such a
manner to afford maximum protection for the safety of the public, qualified employees, and
non-qualified employees.
When modifications are made to existing lines, efforts should be made to upgrade these lines
to current practices.
5.5.1
5.5.2
5.5.3
The employer must confirm the structural capacity of elevated structures, such as
poles and towers, before they are subjected to the stresses of climbing or the
installation or removal of equipment. If inadequate, brace or support the structure
to prevent failure.
When poles are set, moved, or removed near overhead conductors, avoid direct
contact between the pole and energized conductors. Wear protective equipment or
use insulated devices to handle poles. Do not contact the pole with any noninsulated parts of the body. (OSHA regulation 1910.269(q)(1)(ii))
Guard or place attendants at pole holes where employees are working. (OSHA
regulation 1910.269(q)(1)(iv))
Employ precautions during the installation or removal of lines near energized
conductors or energized equipment, such as barriers or the tension stringing
method. (OSHA regulation 1910.269(q)(2)(i))
Consider conductors, cables, pulling, and tensioning equipment energized if the
conductor being installed is close enough to energized conductors that any of the
following failures could energize the installation tools or equipment:
Failure of the tensioning equipment
Page 206-45
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Use tag lines and other similar devices to position tower sections being
assembled, unless these devices present a greater hazard.
Keep load lines fully attached until loads are safely secured.
Page 206-46
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
5.6
Where high-voltage power lines cross over fences, ground the fence at the point of
crossing and at a distance not to exceed 150 (45 m) on either side.
When fences run under or are parallel to high-voltage power lines, ground them at
intervals not to exceed 150 (45 m).
In the conditions described in the two points above, bond any gate or other opening by
a buried bonding strap.
When using armored high-voltage cables, the grounding practices described in this section
need not apply.
5.7
Where these items are parallel to, or pass under, high-voltage power lines, follow proper
grounding design.
5.8
Signage
Signs are essential for conveying information regarding a potential electrical shock hazard.
They are also used to convey operation and/or maintenance information.
This section of the practice makes no attempt to describe all types of signs, all locations
where signs may be required, or all possible lettering to be used. Use the references listed
within this practice to obtain the necessary information for sign requirements at your location.
5.8.1
Design
Consider the following for signage requirements:
Material Make signs out of a durable material that is appropriate for the
anticipated environmental conditions and expected length of exposure.
5.8.2
Colors and shapes Make the color and shape of the sign consistent with
regulatory and consensus practices requirements.
Lettering Use large and highly visible lettering and anticipate dark or
low-light situations.
Location
Page 206-47
5.9
5.9.1
connection boxes, and motor starters with DANGER HIGH VOLTAGE KEEP
OUT.
Mark building services over 600 volts with DANGER HIGH VOLTAGE
KEEP OUT.
Mark the feeder or circuit number on the front and rear of permanent structure of
the switchgear or equipment, but not on removable enclosure covers to the
equipment.
5.9.2
5.9.3
Other
Indicate the voltage of exposed parts at outdoor switchgear or transformer
locations.
Identify disconnects that have no load interrupting or fault closing rating with
clear signs to prevent improper operation.
If a back-feed is possible, identify with a warning sign.
If there is an external or foreign voltage source, identify the source with a
warning sign.
Identify clearly all disconnect devices and the equipment with which they are
associated. (OSHA regulation 1910.303(f))
Identify clearly the rear doors of switchgear compartments.
6.0
6.1
When entering an attended substation, employees other than those assigned to station work
should report to the employee in charge. Upon reporting, these employees should receive
special safety instructions and a job briefing. (OSHA regulation 1910.269(u)(6))
6.1.1
6.1.2
Keep substation lots free of debris. Do not store materials and equipment not
necessary for distribution and transmission system repair and maintenance (R &
M) in substation lots.
Establish specific storage locations for distribution and transmission, repair, and
maintenance materials. Specifically identify and periodically inspect the storage
location. The location manager or his or her designee should approve storage
areas.
6.1.3
6.1.4
6.2
(NFPA 70E, 130.2; OSHA regulations 1910.269(u)(4) and (u)(5); (v)(4) and (v)(5); NESC
124)
Provide guards around all exposed live parts where the clearance requirements of Appendix
A, Table A-1 cannot be met. (Refer to NESC section 124.)
When necessary to assure reasonable safety, guard certain exposed live parts or give
clearances in excess of those specified. These parts include those over or near passageways
through which material may be carried and those on or near spaces such as corridors,
storerooms, and boiler rooms used for non-electrical work. Use substantial guards and
completely shield or enclose the energized parts without openings. Guards for spaces
accessible to unqualified personnel should be removable only by means of tools or keys.
Guard each portion of parts whose potential is unknown in the same manner as described
above. Guarding should be based on the maximum voltage that may be present on the surface
of that portion. Examples of such parts include telephone wires exposed to induction from
high-voltage lines, ungrounded neutral connections, ungrounded frames, ungrounded parts of
insulators or surge arresters, or ungrounded instrument cases connected directly to a highvoltage circuit.
Page 206-50
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Guards less than 4 (10 cm) outside the guard zone should completely enclose the parts from
contact up to the heights listed in Appendix A, Table A-1 column 2. They should not be
closer to the exposed live parts than the distance specified in Table A-1 column 4, except
when suitable insulating material is used with circuits less than 2,500 V to ground.
6.3
Rights-of-Way
Maintain rights-of-way in a clear and orderly condition, and keep trees and brush well clear
of overhead lines.
Prohibit any vehicle that could inadvertently come within 10 (305 cm) of an energized line
(see the definition of Ten (10)-Foot Rule in Appendix T - Glossary) from parking in this area.
Examples would be aerial lifts, mobile cranes, dump trucks, dumpsters, and high lift fork
trucks.
Recommend that areas with a horizontal distance of 10of an overhead line be coned off
with appropriate barricades prior to starting any work near an overhead line.
6.3.1
For lines and equipment energized at more than 50 kV, the distance is 10
(305 cm) plus 4 (10 cm) for every 10 kV over 50 kV.
In areas restricted to qualified employees, do not store material within the working
space around energized lines or equipment.
Page 206-51
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
7.0
7.1
Documentation
Maintain test records on all equipment, rubber goods and live-line tools.
7.2
7.2.1
7.2.2
When the gloves might have been damaged, test before the next use.
Electrically test insulating rubber sleeves in accordance with the procedures for
in-service care of insulating gloves and sleeves described in ASTM F496.
Store insulating rubber sleeves in canvas bags designed for that purpose.
7.2.3
Test line hoses and covers upon indication that the insulating value is suspect.
Visually inspect this equipment for defects before use and installation on
energized conductors, devices, or equipment, and at other times if damage is
suspected.
Do not use damaged or possibly damaged equipment until it has passed an
electrical retest.
7.3
Tools
7.3.1
Live-line Tools
Visually inspect live-line tools for defects and contamination on a regularly
established basis. (OSHA regulation 1910.269(j)(2)(iii))
Before using the tool each day, visually inspect it for defective hardware
attachments, cracks, deformities, contamination, proper operation, and
cleanliness. (OSHA regulation 1910.269(j)(2))
Wax and then dielectrically test the tool every two years (24 months).
Dielectrically test fiberglass tools while wet. IEEE 978-1984, The Guide for InService Maintenance and Electrical Testing of Live-Line Tools, may be used for
reference.
7.3.2
Insulated Tools
Assure that insulated tools meet the requirements of ASTM F1505 Specification
for Insulated Hand Tools. (NFPA 70E, 130.7 (D); OSHA regulation
1910.335(a)(2))
7.4
Mechanized Equipment
7.4.1
Insulated Equipment
For insulated, extendible-boom aerial personnel devices, articulating-boom aerial
personnel devices, and any combination thereof (such as line trucks), perform the
following:
Inspect annually (every 12 months).
7.4.2
Non-Insulated Equipment
For non-insulated, digger-derrick, extensible-boom equipment, follow the
inspection and test procedures stated in ANSI A10.31.
7.4.3
8.0
Employee Training
8.1
Types of Training
8.2
8.2.1
8.2.2
Recordkeeping
The location management should assure that all required training is completed and
documented. (OSHA regulation 1910.269(a)(2)(vii); OSHA regulation
1910.269(d)(2)(ix))
Establish and maintain records for each person considered a qualified employee
as defined in Appendix T of this practice. The records should include:
Name and identification.
8.3
8.3.1
Responsibilities
The company should verify, through regular supervision and inspections
conducted at least annually, that each employee is complying with the required
safety-related work practices. (OSHA regulation 1910.269(a)(2)(iii); NFPA 70E,
120.2 (B)(7); OSHA regulation 1910.269(d)(2))
NOTE:
Supervisors should make sure procedures are in place and that employees are
trained in those procedures. (NFPA 70E, 110.3)
Employees must follow safe work practice procedures, including using PPE and
understand how an employees qualification status relates to the current task.
8.3.2
First aid
8.4
Page 206-57
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
8.5
Be able to identify and understand the relationship between electrical hazards and
possible injury.
Have familiarity with safety-related work practices, safety procedures, and other
personnel safety requirements that relate to job assignments.
Have familiarity with any other safety practices, including applicable emergency
procedures related to work and safety.
Skills and techniques necessary to distinguish potential exposed live parts from the
other parts of electric equipment, machines, and processes.
Skills and techniques necessary to determine the nominal voltage of exposed live
parts.
8.6
Refresher Training
Frequent training and reinforcement of electrical safety is essential, especially for items such
as power system components that are maintained infrequently. (OSHA regulation
1910.269(a)(2)(iv))
Establish schedules for refresher training, or retraining of personnel as the situation dictates,
including:
If a supervisor, periodic audits, or the annual inspection reveals that employees are
not complying with required safety-related work practice.
Conduct refresher training on this Electrical Safe Work Practice at least every three years and
preferably more often. Computer-based refresher training courses are available on the
company intranet.
8.7
Lockout/Tagout Training
(OSHA regulation 1910.269(d)(2)(vi), and (vii); OSHA 1910.333(b); NFPA 70E, 120.2)
Refer to company procedure HES-203 Lockout Tagout.
8.8
Retraining
Equipment changes.
9.0
Facility Work
9.1
Location Management
Location management should assure that the following meet or exceed all safety regulated
recommendations of this practice, along with required and consensus design and safety
practices:
Design criteria for all existing electrical facilities, modifications to the existing
facilities, and new construction
Page 206-59
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
9.2
Contractors
Contractors are responsible for ensuring that equipment they supply and use meets
facility safety and health practices.
Key contractor personnel should be trained in this document (Electrical Safe Work
Practice).
As contractor employees are replaced or added, or contractor work is further sublet, the
primary contractor is responsible for advising or informing new contractor employees of all
electrical safety considerations that may apply to them under this, or other applicable rules or
specifications.
9.3
(OSHA regulation 1910.335(b)(3); NFPA 70E, 130.2 (D)(2); NFPA 70E, 130.7 (E)(3))
Any person without qualified or authorized training requires an escort within areas where
physical safe work distance clearances (see Appendix A, Table A-1 and Table A-2) cannot be
met. In general, this requirement includes all secured electrical installations and
conductor/bus minimal clearance from buildings, rooftops, or other structures.
Examples of non-qualified and non-authorized personnel may include non-trained visitors,
non-electrical maintenance employees (e.g., grass cutters, painters, roof repair personnel),
potential contractor personnel, and equipment vendors.
9.4
It is essential that general switching and controlling procedures between power generators
and user locations be well understood and documented.
Page 206-60
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
9.5
Accident/Incident Investigation
A local electrical safety team should investigate all electrical contacts, near misses, and
switching errors. Recommendations should be made to improve the electrical safety program.
These recommendations should be sent to the corporate safety division and corporate
business unit managers for further evaluation and distribution.
It is important that these accidents/incidents and near misses be evaluated from a fact-finding,
versus a fault finding approach.
9.6
More often if changes occur that are likely to increase the potential for electrical
shock hazard (i.e., an increased frequency of electrical accidents, changes in the work
force, renovation of the current system, or new construction)
10.0
Locations with exposed parts that are energized or potentially energized should be locked,
including:
Substations.
10.1
Safety Lock
A safety lock is a controlled lock with unique lock/one key or unique lock group/one key.
Its function is to protect personnel, and should be installed on each tagout/lockout location.
Use of a safety lock on high- and low-voltage distribution systems is recommended to
prevent a switch or breaker from unintentionally operating. This process is important for
protecting workers.
Page 206-61
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
10.2
The function of an operating system lock is to prevent unintentional operation of a highvoltage line switch. Unique one-lock/one-key locks are not required but are strongly
recommended for operating system locks.
10.3
In the interest of overall employee safety, a one-lock/one-key system offers the highest degree
of safety in any locking situation.
10.4
Equipment access interlock systems offer a high degree of personal safety and should be used
in all design considerations with the exception of phasing of conductors following new or
revised installations. (NFPA 70E, 110.8 (B)(4); OSHA regulation 1910.333(c)(10))
Except for phasing of conductors following new or revised installations, do not bypass, or
otherwise render inoperative, interlock systems while the equipment is energized. When
performing the phasing task, additional personal protective equipment may be required.
10.5
Where generating and switching locations are influenced by distance, do not compromise
personnel safety by lack of a positive locking or other procedure.
It is recommended that a formal written agreement be made between the parties outlining the
agreed-upon clearance or lockout/tagout procedure.
Provide all clearances in writing.
The clearance or lockout/tagout system associated with the remote location may be used but
do not compromise the safety of the Facility clearance or lockout/tagout policy.
11.0
References
11.1
Safety-Toe Footwear
11.2
11.3
Subpart J
Subpart J
Subpart R
1910.268 Telecommunications
Subpart R
Subpart S
Subpart K
Subpart E
Subpart P
1926 Excavations
11.4
IEEE 978
IEEE 1584
ANSI/IEEE
11.5
NFPA 70
NFPA 70B
NFPA 70E
11.6
All company facilities should meet or exceed the above referenced guidelines, codes and
regulations.
Page 206-64
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Live Part
Vertical Clearance
Table A-1, Column 2
Vertical Clearance of
Unguarded Parts
Horizontal Clearance of
Unguarded Parts
kV
Feet
In.
Feet
In.
Feet
In.
m/cm
.151 to 2.4
2.67
1.02
7.6 cm
7.2
10
2.69
1.02
13.8
2.74
1.07
10.1
cm
23.0
2.82
1.14
34.5
2.90
1.22
15.2
cm
22.8
cm
Page 206-A1
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Vertical Clearance of
Unguarded Parts
Horizontal Clearance of
Unguarded Parts
kV
Feet
In.
Feet
In.
Feet
In.
m/cm
46.0
10
3.00
1.32
69.0
10
3.18
11
1.50
11
30.4
cm
115.0
11
3.53
1.85
138.0
12
3.71
2.03
161.0
12
10
3.91
2.24
230.0
14
10
4.52
2.84
93.9
cm
362.0
20
6.1
14
4.5
11
1.12 m
550.0
28
8.6
22
10
7.0
19
10
1.32 m
40.6
cm
58.4
cm
1.93 m
3.6 m
6.0 m
(Table derived from Table 124-1 NESC C2-2002. From IEEE Std. C2-2002. Copyright 2001 IEEE. All rights reserved.)
Page 206-A2
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
(Open Conductors)
Neutrals and
Grounded Guys
0 to 750V
(Phase-to-Gnd)
751V to 22kV
(Phase-to-Gnd)
Feet
Meters
Feet
Meters
Feet
Meters
1. Railroad tracks
23.5
7.2
24.5
7.5
26.5
8.1
15.5
4.7
16.5
5.0
18.5
5.6
3. Residential driveways
15.5
4.7
16.5
5.0
18.5
5.6
15.5
4.7
16.5
5.0
18.5
5.6
9.5
2.9
12.5
3.8
14.5
4.4
14.0
4.0
15.0
4.6
17.0
5.2
17.5
5.3
18.5
5.6
20.5
6.2
20 to 200 acres
25.5
7.8
26.5
8.1
28.5
8.7
31.5
9.6
32.5
9.9
34.5
10.5
37.5
11.4
38.5
11.7
40.5
12.3
Where wires, conductors, or cables run along and within the limits of highway or other road rightof-way, but do not overhang the roadway
9. Roads in urban districts
15.5
4.7
16.5
5.0
18.5
5.6
13.5
4.1
14.5
4.4
16.5
5.0
For unguarded rigid exposed live parts (fuse cutouts, pole transformer bushing, etc.) clearance, refer to Table 232-2
NESC C2-2002.
(Table is based on Table 232-1 NESC C2-2002. From IEEE Std. C2-2002. Copyright 2001 IEEE. All rights reserved.)
Page 206-A3
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Minimum Clearance
1
751 V - 22 kV
Phase-to-Ground
Feet
Meters
7.5
2.30
12.5
3.8
13.5
4.1
13.5
4.1
18.5
5.6
1. Horizontal
2.3
2.3
13.5
4.1
8.0
2.30
A. Buildings
1. Horizontal
2. Vertical
(Table is based on Table 234-1 NESC C2-2002 From IEEE Std. C2-2002. Copyright 2001 IEEE. All rights reserved.)
Page 206-A4
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
0 to 8.7 kV
8.7 to 50 kV
Same Utility
Different Utilities
in.
cm
in.
cm
in.
Communication
Conductors and
Cables
40
100
40
100
40
Plus
A
100
16
41
16
Plus
A
41
40
Plus
A
100
16
41
16
Plus
A
41
40
Plus
A
100
16
Plus
A
41
Plus
A
41
16
Plus
A
41
2, 3
16
16
cm
Plus
A
2, 3
41
Increase to 40" (100 cm) if live line maintenance is performed and adjacent circuits are neither de-energized nor covered.
Example:
Different utilities, other utility does live line maintenance 26.6 kV circuit above a 13.9 kV circuit. Phases may be displaced
by 180 degrees, therefore voltage difference is considered to be
26.6 + 13.9 = 40.5 kV
A = 0.4 (40.5 - 8.7) = 12.72" (32 cm)
Clearance = 40 + 13 = 53" (133 cm)
(Table is based on Table 235-5 NESC C2-2002 From IEEE Std. C2-2002. Copyright 2001 IEEE. All rights reserved.)
Page 206-A5
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Feet
Meters
Feet
Meters
Communication Conductors,
Cables and Messengers
0.60
1.50
0.60
0.60
0.60
0.60
1.20
1.80
0.60
0.60
Rules 230C1, C2, and C3 cover cables supported on effectively grounded bare messengers or neutral conductors, cables having
effectively grounded sheaths or shields, or 5 kV non-shielded cables supported and cabled together on effectively grounded bare
messengers.
This clearance may be reduced to 4' (1.20 m) where supply conductors of 750 V to 8.7 kV cross a communication line more than
6' (1.80 m) horizontally from a communications structure.
Trolley and electrified railroad contact conductors of more than 750V should have at least 6' (1.80 m) of clearance.
(Table is based on Table 233-1 NESC C2-2002. See the NESC table and notes for complete details. From IEEE Std. C22002. Copyright 2001 IEEE. All rights reserved.)
Page 206-A6
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
(Reprinted with permission from NFPA 70E-2003, Standard for Electrical Safety in the Workplace, copyright 2004,
National Fire Protection Association, Quincy, MA 02269. This guideline is not the complete and official position of the
NFPA on the referenced subject, which is represented only by the standard in its entirety.)
Page 206-A7
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Restricted
Approach
Boundary
Prohibited
Approach
Boundary
Exposed
Moveable
Conductor
Exposed Fixed
Circuit Part
Includes
Inadvertent
Movement Adder
Less than 50
Not specified
Not specified
Not specified
Not specified
51 to 300
10' 0
3' 6
Avoid contact
Avoid contact
301 to 750
10' 0
3' 6
1' 0
0' 1
751 V to 15 kV
10' 0
5' 0
2' 2
0' 7
15.1 to 36 kV
10' 0
6' 0
2' 7
0' 10
36.1 to 46 kV
10' 0
8' 0
2' 9
1' 5
46.1 to 72.5 kV
10' 0
8' 0
3' 3
2' 1
72.6 to 121 kV
10' 8
8' 0
3' 2
2' 8
138 to 145 kV
11' 0
10' 0
3' 7
3' 1
161 to 169 kV
11' 8
11' 8
4' 0
3' 6
230 to 242 kV
13' 0
13' 0
5' 3
4' 9
345 to 362 kV
15' 4
15' 4
8' 6
8' 0
500 to 550 kV
19' 0
19' 0
11' 3
10' 9
765 to 800 kV
23' 9
23' 9
14' 11
14' 5
Notes:
1. Affected persons, persons who are not authorized or qualified must not cross the limited approach boundary. (See Appendix B,
Item B.1; section 4.2.3)
2. Authorized persons, persons who are specifically task trained, may work inside the limited approach boundary. However, in no
case should an authorized person be allowed to work as close to exposed live parts as the restricted approach boundary allowed
for a qualified person. (See section 4.2.3)
3. Qualified persons may work up to the restricted approach boundary. For a qualified person to cross the restricted approach
boundary he/she should follow the rules outlined in Appendix B, Item B.2; section 4.2.3)
4. Qualified persons who cross the prohibited approach boundary should follow work procedures required to make contact with
exposed live parts. To cross the prohibited approach boundary is considered the same as making contact with exposed live parts.
(See Appendix B, Item B.2)
This table is based on NFPA 70E-2004, Table 130.2 (C). Reprinted with permission from NFPA 70E-2004, Standard for
Electrical Safety in the Workplace, copyright 2004, National Fire Protection Association, Quincy, MA 02269. This table
is not the complete and official position of the NFPA on the referenced subject, which is represented only by the Standard
in its entirety.
Page 206-A8
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Observing a safe approach distance from exposed live parts is an effective means of
maintaining electrical safety. As the distance between a person and the exposed live
parts is decreased, the potential for electrical accident increases.
B.
S a fe Ap p ro a c h Dis ta n c e
1. Unqualified Persons
Unqualified persons are safe when they maintain a distance from the exposed live
parts, including the longest conductive object being handled, so that they cannot
contact or enter a specified air insulation distance to the exposed live parts. This
safe approach distance is the limited approach boundary.
Unqualified persons must not cross the flash protection boundary unless they are
wearing appropriate personal protective clothing and are under the close
supervision of a qualified person.
Where there is a need for an unqualified person(s) to cross the limited approach
boundary, a qualified person must advise him or her of the possible hazards and
continuously escort the unqualified person(s) while inside the limited approach
boundary. Under no circumstance is the escorted unqualified person(s) permitted
to cross the restricted approach boundary.
Note that the flash protection boundary may be greater than the limited approach
boundary for higher capacity systems.
2. Qualified Persons
Determine the flash protection boundary and, if the boundary is to be crossed, use
appropriate arc-flash protective equipment.
For a person to cross the limited approach boundary and enter the limited space,
he or she must be qualified to perform the job/task. An exception to this
requirement is that an authorized person is permitted to cross the limited approach
boundary if he or she is specifically trained for the task to be done.
Page 206-B1
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
To cross the restricted approach boundary and enter the restricted space, the
qualified person must:
To cross the prohibited approach boundary and enter the prohibited space, which
is considered the same as making contact with exposed live parts, the qualified
person must:
Have a documented plan justifying the need to work that close and have it
approved by authorized management.
Page 206-B2
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
B.
De te rm in e th e Fla s h P ro te c tio n Bo u n d a ry
The flash protection boundary is determined during the flash hazard analysis and is
used to initiate the need for PPE.
Refer to section 130 of NFPA 70E-2004 for formulas and other information needed to
establish the flash protection boundary. This section in NFPA 70E also contains
information and recommendations that address the PPE required for personnel to
cross inside the flash protection boundary.
See the following table for default distances for the flash protection boundary for
normal systems. This information is not from NFPA 70E, but usually represents a
conservative approach if information is not available. Do not use the table for highcapacity systems (e.g., low voltage systems supplied by transformers 1500 kVA and
larger, or high-voltage systems with greater than 1000 MVA short circuit capacity).
The flash protection boundary may alternatively be calculated using information and
formulas outlined in NFPA 70E-2004. The flash protection boundary is the distance
at which the incident energy level equals 1.2 cal/cm2.
TABLE C-1 Default Distances for Flash Protection Boundary for Normal Systems
Arc Location Relative to
Equipment
Flash Protection
Boundary ()
Arc in Air
200 to 1000
Arc in Enclosure
200 to 1000
10
Arc in Enclosure
20
C.
Existing knowledge about arc flash exposure at voltage levels above 600 volts is
limited. Methods of calculating the exposure, other than the equations given in NFPA
70E-2000, exist and may be used. Commercial and shareware programs are available
for calculating these values. It is important to investigate the limitations of any
programs to be used.
Page 206-C1
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Experience suggests that the calculation of arc flash exposure above 600 volts is
conservative and becomes more conservative as the voltage increases. It should be
noted that all present methods of calculating incident energy and arc flash exposure at
higher voltage levels have limitations.
Equations for calculating the incident energy produced by a three-phase arc on
systems rated 600 volts and below for an Arc in Open Air (Ema) and an Arc in a
Cubic Box (Emb - arc flashes emanating from within switchgear, motor control
centers, or other electrical equipment enclosures) may be calculated by using the
formulas derived in the IEEE paper by R.L. Doughty, T.E. Neal, and H. L. Floyd,
Predicting Incident Energy to Better Manage the Electric Arc Hazard on 600 Volt
Power Distribution Systems, IEEE, IAS 45th Annual PCIC Conference Sept.28-30,
1998.
NOTE:
D.
De te rm in e P P E Re q u ire m e n ts
Flame-resistant (FR) clothing and PPE are used by the employee based upon the
incident energy exposure associated with the specific task. As an alternative, the PPE
requirements outlined in Table C-2 (extracted from NFPA 70E 130.7 (C)(9)(a)) may
be used. For additional information refer to Tables C-3 and C-4 (NFPA Tables 130.7
(C)(10) and 130.7 (C)(11)), and Table C-4 (NFPA Table H-1).
NOTE:
Page 206-C2
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Hazard/Risk
Category
V-rated
Gloves
V-rated
Tools
Panelboards or Switchboards rated >240 V and up to 600 V (with molded case or insulated case
circuit breakers) See Notes 1, 3, and 7
CB or fused switch operation with covers on
2*
600 V Class Motor Control Centers (MCCs) See Notes 2 (except as indicated) and 3
CB or fused switch or starter operation with enclosure doors
closed
2*
2*
2*
Page 206-C3
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Hazard/Risk
Category
V-rated
Gloves
V-rated
Tools
2*
2*
Other 600 V Class (277 V to 600 V, nominal) equipment, including lighting or small power
transformers See Notes 2 except as indicated, and 3 and 7.
Removal of bolted covers (to expose bare, energized parts)
2*
2*
2*
2*
Page 206-C4
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Hazard/Risk
Category
V-rated
Gloves
V-rated
Tools
2*
Hazard/Risk
Category
V-rated
Gloves
V-rated
Tools
Legend:
V-rated Gloves are gloves rated and tested for the maximum line-to-line voltage upon which work will be done.
V-rated Tools are tools rated and tested for the maximum line-to-line voltage upon which work will be done.
2* means that a double-layer switching hood and hearing protection are required for this task in addition to the other
Hazard/Risk Category 2 requirements of Table 130.7(C)(10)
Y = yes (required)
N = no (not required)
Notes:
1.
Maximum of 25 kA short circuit current available, 0.03 second (two (2)-cycle) fault clearing time
2.
Maximum of 65 kA short circuit current available, 0.03 second (two (2)-cycle) fault clearing time
3.
For < 10 kA short circuit current available, the Hazard/Risk Category required may be reduced by one Number
4.
Maximum of 42 kA short circuit current available, 0.33 second (20-cycle) fault clearing time
5.
Maximum of 42 kA short circuit current available, 0.5 second (30-cycle) fault clearing time
6.
For < 25 kA short circuit current available, the Hazard/Risk Category required may be reduced by one Number.
7.
For systems rated 600 volts and below, the listed fault currents and upstream protective device clearing times are based
on an 18 working distance.
8.
For systems rated greater than 1kV, the Hazard/Risk Categories listed are based on a 36 working distance.
9.
If approved arc-resistant designs or remote-operating (outside the Flash Protection Boundary) techniques are applied
that permit closed-door completion of the task, the HRC is 0.
Page 206-C6
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
TABLE C-3 Protective Clothing and Personal Protective Equipment (PPE) Matrix
(Extracted from NFPA 70E-2004, Table 130.7 (C)(10))
Protective Clothing and Equipment
-1
Hazard/Risk Category Number
0
(Note 3)
Non-melting (according to ASTM F 1506-00) or Untreated Natural Fiber
T-shirt (short-sleeved)
X
(Note 4)
X
(Note 6)
X
(Note 4)
X
(Note 6)
(Note 5)
AN
(Note 7)
AN
X
(Note 9)
X
(Note 9)
X
(Note 9)
AN
Shirt (long-sleeved)
Pants (long)
FR Clothing (Note 1)
Long-sleeved Shirt
Pants
Coverall
Jacket, Parka, or Rainwear
(Note 5)
AN
FR Protective Equipment
Flash Suit Jacket (multi-layer)
Head Protection
Hard Hat
Eye Protection
Safety Glasses
AL
AL
AL
AL
AL
AL
X
(Note 8)
Safety Goggles
Face and head area protection
Face protection arc-rated face shield or flash
suit hood
Flash suit hood
AN
AN
AN = As Needed
AR = As Required
X = Minimum Required
Notes:
1. See 1. See Table 130.7(C)(11). (Arc rating for a garment is expressed in cal/cm2.)
2. If voltage-rated gloves are required, the leather protectors worn external to the rubber gloves satisfy this requirement.
3. Hazard/Risk Category Number 1 is only defined if determined by Notes 3 or 6 of Table 130.7(C)(9)(a).
4. Regular weight (minimum 12 oz./yd2 fabric weight), untreated, denim cotton blue jeans are acceptable in lieu of FR pants.
The FR pants used for Hazard/Risk Category 1 shall have a minimum arc rating of four (4.)
5. Alternate is to use FR coveralls (minimum arc rating of four (4) instead of FR shirt and FR pants.
6. If the FR pants have a minimum arc rating of 8, long pants of non-melting or untreated natural fiber are not required beneath the
FR pants.
7. Alternate is to use FR coveralls (minimum arc rating of four (4) over non-melting or untreated natural fiber pants and T-shirt.
8. A face shield with a minimum arc rating of 8, with wrap-around guarding to protect not only the face, but also the forehead, ears,
and neck (or, alternatively, a flash suit hood), are required.
9. Alternate is to use two sets of FR coveralls (the inner with a minimum arc rating of four (4) and outer coverall with a minimum arc
rating of five (5) over non-melting or untreated natural fiber clothing, instead of FR coveralls over FR shirt and FR pants over nonmelting or untreated natural fiber clothing.
Page 206-C7
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Clothing Description
(Typical number of clothing layers is given in parentheses)
Required Minimum
Arc Rating of PPE
cal/cm
25
40
N/A
Note: Arc rating is defined in Article 100 and can be either ATPV or EBT. ATPV is defined in the ASTM F 1959-99 as the incident
energy on a fabric or material that results in sufficient heat transfer through the fabric or material to cause the onset of a second
degree burn based on the Stoll curve. EBT is defined in ASTM F 1959-99 as the average of the five highest incident energy
exposure values below the Stoll curve where the specimens do not exhibit breakopen. EBT is reported when ATPV cannot be
measured due to FR fabric breakopen.
Page 206-C8
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
APPLICABLE TASKS
All Hazard/Risk Category 1 and 2 tasks listed in
Table 130.7 (C)(9)(a).
On systems operating at less than 1,000 volts, these
tasks include work on all equipment except:
Insertion or removal of low-voltage motor
starter buckets.
Insertion or removal of power circuit breakers
with the switchgear doors open.
Removal of bolted covers from switchgear.
On systems operating at 1,000 volts or greater,
tasks also include the operation, insertion, or
removal of switching devices with equipment
enclosure doors closed.
* Note other PPE required for the specific tasks listed in Tables 130.7 (C)(9)(a) and130.7 (C)(10), which include arc-rated face
shields or flash suit hoods, FR hardhat liners, safety glasses or safety goggles, hard hat, hearing protection, leather gloves,
voltage-rated gloves, and voltage-rated tools.
Page 206-C9
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
TABLEC-6 Guideline for the use of Hazard/Risk Category (HRC) 2 and HRC 4 Personal
Protective Equipment
The following guideline can be used to determine the suitability of Hazard/Risk Category
(HRC) 2 and HRC 4 personal protective equipment on systems rated up to 15 kV, line-toline. See Tables C-6.1 and C-6.2 for recommended limitations of system three-phase shortcircuit currents for the listed fault-clearing times. The limitations listed below are based on
IEEE Std 1584-2002 calculation methods.
Table C-6.1 Low-Voltage Systems Maximum Three-Phase Bolted-Fault Current Limits (in
kiloamperes), at Various System Voltages and Fault-Clearing Times of Circuit Breakers, for
the Recommended Use of Hazard/Risk Category (HRC) 2 and HRC 4 Personal Protective
Equipment in an Arc-in-a-Box Situation (see Notes below)
System Voltage (volts,
phase-to-phase)
Upstream Protection
Fault-Clearing Time
(seconds)
690
600
480
400
208
Inst
0.10
0.20
0.33
0.50
Inst
0.10
0.20
0.33
0.50
Inst
0.10
0.20
0.33
0.50
Inst
0.10
0.20
0.33
0.50
Inst
0.10
Maximum Three-Phase
Bolted-Fault Current for
use of HRC 2 PPE
(8 cal/cm 2 )
(40 cal/cm2 )
38 kA
20 kA
10 kA
NR
NR
48 kA
24 kA
12 kA
NR
NR
68 kA
32 kA
15 kA
NR
NR
87 kA
39 kA
18 kA
NR
NR
200 kA*
104 kA
180 kA
93 kA
48 kA
29 kA
20 kA
200 kA*
122 kA
60 kA
36 kA
24 kA
200 kA*
183 kA
86 kA
50 kA
32 kA
200 kA*
200 kA*
113 kA
64 kA
39 kA
Not applicable
200 kA*
Notes:
1. Three-phase Bolted Fault value is at the terminals of the equipment on which work is to be done.
2. Upstream Protection Fault-Clearing Time is normally the short-time delay setting on the trip unit of the low-voltage power
circuit breaker upstream of the equipment on which work is to be done.
3. For application of this table, the recommended maximum setting (pick-up) of either the instantaneous or short-delay
protection of the circuit breakers trip unit is 30% of the actual available three-phase bolted fault current at the specific work
location.
4. Working distance for the above arc-flash exposures is assumed to be 0.46 m (1.5').
5. Flash Protection Boundary (threshold distance for a second-degree skin burn) is 1.7 m (6') for HRC 2 and 4.9 m (16') for
HRC 4. PPE is required for all personnel working within the Flash Protection Boundary.
6. Instantaneous (Inst) protection implies the circuit breaker trip unit has no intentional time delay and the circuit breaker is
assumed to clear the fault within 0.050 sec of initiation.
7. NR Not Recommended
8. (*) maximum equipment short-circuit current rating available
9. Systems are assumed to be resistance grounded, except for 208 V (solidly grounded).
Page 206-C10
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
15 kV Class and
12 kV Class
5 kV Class
Upstream
Protection FaultClearing Time
(seconds)
Maximum Three-Phase
Bolted-Fault Current for
use of HRC 2 PPE
2
(8 cal/cm )
0.10
45 kA
0.35
13 kA
63 kA
0.70
7 kA
32 kA
1.0
5 KA
23 kA
0.10
50 kA
0.35
15 kA
0.70
8 kA
37 kA
1.0
5 kA
26 kA
2
2
Notes:
1. (*) maximum equipment short-circuit current rating available
2. Upstream Protection Fault-Clearing Time is the protective relaying operating time at 90% of the actual available threephase bolted fault current at the specific work location (the time for the output contact operating the trip coil of the circuit
breaker to be closed), plus the circuit breaker operating time (upstream of the equipment on which work is to be done).
3. Working distance for the above arc-flash exposures is assumed to be 0.92 m (3')
4. Systems are assumed to be resistance grounded
The cal/cm2 in parentheses in the last column are calculated at the maximum equipment short-circuit current ratings available.
Page 206-C11
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
For systems 600 volts and below, the flash protection boundary is 4.0', based on the product
of clearing times of 0.1 seconds and the available fault currents of 50 kA or any combination
not to exceed 300 kA cycles (5,000 ampere seconds).
At voltage levels above 600 volts, the flash protection boundary is the distance at which the
incident energy level equals 1.2 cal/cm2.
The flash protection boundary can alternatively be calculated as shown below.
A.
2.
3.
4.
Page 206-D1
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Incident Energy produced by a three-phase arc on systems rated 600 volts and below:
Calculate Maximum open arc incident energy Ema
Ema = (5271)(DA)-1.9593 (tA)[0.0016(Isc)2 - 0.0076(Isc) +0.8938] = Ema in cal/cm2
Ema = maximum open arc incident energy, cal/cm2
DA = distance from arc electrodes, inches (for distances 18 and greater)
tA = arc duration, seconds
Isc = bolted fault short circuit current, kA (for the range of 16 to 50 kA)
C1.
Incident energy produced by a three-phase arc on systems rated 600 volts and below:
Calculate Maximum arc in cubic box incident energy Emb
Emb = (1038.7)( DB )-1.4738 (tA)[0.0093(Isc)2 - 0.3453(Isc) + 5.9675] = Emb in cal/cm2
Emb = maximum 20 cubic box incident energy, cal/cm2
DB = distance from arc electrodes, inches (for distances 18 and greater)
tA = arc duration, seconds
Isc = bolted fault short circuit current, kA (for the range of 16 to 50 kA)
Page 206-D2
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
C2.
Sample Calculation - Arc in Cubic Box Emb -- 480 volt motor starter bucket
with upstream protection time of 0.18 second
Incident energy produced by a three-phase arc on systems rated 600 volts and below:
Calculate Maximum arc in cubic box incident energy Emb
Emb = (1038.7)( DB )-1.4738 (tA)[0.0093(Isc)2 - 0.3453(Isc) + 5.9675] = Emb in cal/cm2
C3.
Sample Calculation - Arc in Cubic Box Emb -- 480 volt motor starter
bucket with upstream protection time of 0.10 second
Incident energy produced by a three-phase arc on systems rated 600 volts and below:
Calculate Maximum arc in cubic box incident energy Emb
Emb = (1038.7)( DB)-1.4738 (tA)[0.0093(Isc)2 - 0.3453(Isc) + 5.9675] = Emb in cal/cm2
Manufacturer
and Model No.
(Note 6)
Available Sizes
Color
Clothing (Note 1)
Mens Coveralls
WORKRITE ,
110NMX-45
Royal
Blue
Womens Coveralls
4.5 oz. NOMEX IIIA
WORKRITE,
1114SB
Royal
Blue
Insulated Coveralls
6.0 oz. NOMEX IIIA over 9 oz. NOMEX
insulation (Note 3)
WORKRITE,
590NMX-60
Royal
Blue,
Navy,
Khaki
WORKRITE,
577NMX-60
Royal
Blue,
Navy,
Khaki
WORKRITE,
290NMX-45
Light
Blue,
Navy,
Khaki
WORKRITE,
2914xx
xx = SL
(Light
Blue),
SN
(Navy),
SK
(Khaki)
WORKRITE,
290NMX-60
Light
Blue,
Navy,
Khaki
WORKRITE,
228IND-70
Medium
Blue,
Navy,
Royal
Blue
WORKRITE,
298IND-70
Medium
Blue,
Khaki
BULWARK ,
SCG2LD
Regular, S 3XL
Long M 3XL
Light
Blue
Denim
Page 206-E1
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Item
Manufacturer
and Model No.
(Note 6)
Available Sizes
Color
BULWARK,
SCU3LB
Regular, S 3XL
Light
Blue
WORKRITE,
229IND-70
Navy
WORKRITE,
400NMX-75
Waist 28 34,
Inseam to 34; Waist
35 50, Inseam to 36
Royal
Blue,
Navy,
Spruce
WORKRITE,
440NMX-75
Waist 28 34,
Inseam to 34; Waist
35 50, Inseam to 36
Navy
WORKRITE,
410NMX-85
Waist 28 34,
Inseam to 34; Waist
35 50, Inseam to 36
Denim
WORKRITE,
418IND-12
Waist 28 34,
Inseam to 34; Waist
35 50, Inseam to 36
Denim
WORKRITE,
410NMX-75
Waist 28 34,
Inseam to 34; Waist
35 50, Inseam to 36
Royal
Blue,
Navy
BULWARK,
PCJ2DD
Waist 28 50,
Inseam to 37
Blue
Denim
WORKRITE,
4317Sx
x=B
(Royal
Blue),
N (Navy)
WORKRITE,
409IND-95
Navy
BULWARK,
PCW3NV
Navy
WORKRITE,
7900SZ
Black
BULWARK,
SRU2xx
Regular: S-3XL
Long: M-2XL
Xx = GB
(Heather
Blue)
TN (Tan)
BULWARK,
SRU3TN
S-2XL
Tan
KEVLAR Gloves
Page 206-E2
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Manufacturer
and Model No.
(Note 6)
Item
Available Sizes
Color
ANSELL
Pn# 70225L, M,
or S
N/A
Safety Label
Solutions (SLS)
C8002-42DHYD
(Roll of 500)
N/A
Safety Labels
Danger Arc Flash Hazard labels
Word Message: "Arc Flash Hazard. Follow
requirements in NFPA 70E for safe work
practices and appropriate PPE. Failure to
comply can result in death or injury."
Electrical Testers
FLUKE
T5 1000
N/A
N/A
High-voltage testers
HD Electric
Mark series
(phase-to-phase)
or "EM" models
(phase-toground)
MARK: to 75 kV
N/A
WORKRITE,
610GOR (jacket);
630GOR (overall)
Small XX Large
Yellow,
Navy
Nasco, ArcLite
1000 Series
(1103JBO for
jacket, 1101TBO
for overall)
Small 5X Large
(contact Nasco for
sizing)
Burnt
Orange
Nasco, ArcTuff
2000 Series
Small 5X Large
(contact Nasco for
sizing)
Yellow,
Fluoresc
ent
Orange
EM: to 25 kV
Rainwear
OBERON /,
ARC50-CT-501
501 = L (42-44), XL
(46-48), 2XL (50-52),
3XL (54-56), 4XL (5860),
5XL (62-64)
OBERON,
ARC50-PANTS501
501 = L (36-38), XL
(40-42), 2XL (44-46),
3XL (48-50), 4XL (5254),
5XL (56-58)
Page 206-E3
Item
Manufacturer
and Model No.
(Note 6)
Available Sizes
Color
OBERON,
21ARCAF-C+500
Slight
green tint
OBERON,
ARC50-C
OBERON,
ARC50AF-H
N/A
Green
tint
Nasco, ArcHood
N/A
Yellow,
Orange,
with other
colors
available
Flash Hood
SALISBURY ,
11-00BL
8 12
Blue
SALISBURY,
110G (elastic
back) or 100S
(pull strap)
8 12
N/A
SALISBURY, 511Y
8 12
Yellow
SALISBURY,
200S
(pull strap)
8 12
N/A
SALISBURY, 3512
N/A
N/A
SALISBURY, 2014B
8 12
Black
Page 206-E4
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Manufacturer
and Model No.
(Note 6)
Item
Available Sizes
Color
SALISBURY,
133-4
8 12
N/A
SALISBURY, 3514
N/A
N/A
SALISBURY (see
SALISBURY
catalog)
N/A
NOTES:
1.
Other womens work wear is available for maternity wear; contact WORKRITE.
2.
This garment qualifies as two (2) layers of FR clothing. A cost-effective Hazard/Risk Category 4 FR clothing system could
include this garment worn over 4.5 oz. NOMEX coveralls and untreated natural fiber shirt or T-shirt and untreated natural
fiber pants, worn with an appropriately rated switching hood.
3.
This garment qualifies as three (3)-layer FR clothing. A cost-effective Hazard/Risk Category 4 FR clothing system could
include this garment worn over an untreated natural fiber shirt, T-shirt, and denim blue jeans, worn with an appropriately
rated switching hood.
4.
A cost-effective Hazard/Risk Category 4 FR clothing system could include this garment worn over 4.5 oz. NOMEX fabric,
worn with an appropriately rated switching hood. The burnt-orange ArcLite/NOMEX layered system has been tested and
met an ATPV of 40.
5.
Where more than one high-voltage level exists at a facility (e.g., 4.16 kV and 13.8 kV), recommend keeping only the
highest Class of high voltage glove available for use.
6.
Personal protective equipment is evolving. Contact the following companies to obtain current information. Company
addresses, phone numbers, and website links:
BULWARK
545 Marriott Drive
Nashville, TN 37214
(800-667-0700 --United States
and Canada call toll free)
http://www.bulwark.com/
Nasco Industries, Inc
3 NE Twenty-First Street
Washington, IN 47501
(812-254-7393, 800-767-4288 -United States and Canada call
toll free)
Fluke Corporation
P.O. Box 9090
6920 Seaway Blvd.
Everett, WA 98206-9090
HD Electric Company
1475 Lakeside Drive
Waukegan, IL 60085 USA
http://www.us.fluke.com
http://www.hdelec.com
Oberon Company
435 Coggeshall Street
P.O. Box 61008
New Bedford, MA 02746-0008
(800-322-3348 -- United States and
Canada call toll free)
(847) 473-4980
http://www.safetylabelsolutions.com
http://www.oberoncompany.com/in
dex.en.html
Vallen Safety Supply
(800) 482-5536
http://www.vallen.com
http://www.whsalisbury.com/
WORKRITE
500 East Third Street
P.O. Box 1192
Oxnard, CA 93032-1192
(805-483-0175, 800-521-1888 -- United States
and Canada call toll free)
http://www.workrite.com/
Page 206-E5
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
In tro d u c tio n
B.
De vic e s to Be Us e d
Only those signs, standards, barricades, flags and cones that conform to federal, state
or local codes should be used.
All state and local traffic codes should be followed when providing work area
protection.
Store warning devices and equipment in a proper manner when not in use or removed
from the work area.
Page 206-F1
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
C.
Fla g p e rs o n s
Use flag persons or other appropriate traffic controls whenever there is any doubt that
effective protection can be provided by signs, signals, and barricades and where state or local
standards dictate their use.
Flag persons should follow these guidelines:
Wear a blaze orange warning vest or other high-visibility garment. Warning garments
worn at night should be of a reflectorized material.
Assure they can fully observe the operation and guide vehicular traffic in such a
manner as to minimize the possibility of accidents or injury.
When flag persons are used at both ends of a job site, use reliable communications or
prearranged signals to insure proper traffic flow.
Flag persons using hand-signaling equipment should insure that signals provide sufficient
warning to protect themselves and the work site.
Use signal flags only in an emergency. The flags should be red and at least 24 square.
Sign paddles (stop and slow) should be on a six-foot (6') staff.
In periods of darkness or reduced visibility red lights should be used. Flashlights may be used
in emergencies.
Page 206-F2
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Ask
Safety procedures
Vendor information
Status board
Know
Who is in charge?
Think
About the extra event What if?
What else ?
Telephone location?
Extinguisher?
Page 206-G1
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
3)
Justification of why the circuit/equipment cannot be deenergized or the work deferred until the next scheduled outage
Requestor/Title
Date
Check when
PART II: TO BE COMPLETED BY THE ELECTRICALLY QUALIFIED PERSON DOING THE WORK
complete
1) Detailed job description procedure to be used in
performing the above described work
2)
3)
4)
5)
6)
7)
8)
9)
10) Do you agree the above described work can be done safely?
Yes
Maintenance/Engineering Manager
Safety Manager
No
Date
General Manager
Date
Note: Once the work is complete, forward this form to the site Safety Department for review and retention.
Page 206-H1
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Item
Yes
No
N/A
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
Comments
Page 206-I1
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Item
Yes
No
N/A
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
Comments
Page 206-I2
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Item
Yes
No
N/A
30.
31.
32.
33.
34.
35.
36.
37.
38.
39.
40.
41.
42.
43.
Comments
Page 206-I3
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Item
Yes
No
N/A
1.
2.
Gates locked
3.
Fence secure
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
Comments
Page 206-J1
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
NAME OF EQUIPMENT
TRANSFORMER
Name on transformer
Top oil temperature
Oil level
Tank pressure, psi
Fan operation
Pump operation
Oil leaks?
Abnormal noises?
Condition of :
Paint
Bushings
Terminals, bushing studs, other electrical
connections evidence of corrosion or
heating?
Radiators
CIRCUIT BREAKER
Name on circuit breaker
Oil leaks?
Condition of :
Paint
Bushings
Terminals, bushing studs, other electrical
connections evidence of corrosion or
heating?
SWITCHES
Name on switch
Switch operating handle and operating pipe
bonded to ground?
Switching ground mat available and bonded to
ground?
Switch fully closed or open?
Evidence of corrosion or heating?
STATION BATTERIES
Condition of batteries and terminals
Volts
Battery station ventilation
BATTERY CHARGER
Volts
Condition of eyewash station
Page 206-J2
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
ENCLOSED SWITCHGEAR
Names on switches
Feed to, Fed From information on switch
Condition of cabinet:
Paint
Doors closed
Sign of corrosion or heating?
Cabinet grounded
SPARE CIRCUIT BREAKERS, GROUNDING AND
TEST DEVICES
Clean and ready for use?
Identification of voltage, ampere, and breaker
rating
OTHER EQUIPMENT
Page 206-J3
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
General Comments:
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
Page 206-J4
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Item
Yes
No
N/A
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
Comments
General Comments:
Page 206-K1
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
2.
3.
4.
5.
Page 206-L1
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Page 206-M1
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Copper
Grounding
Cable Size,
AWG
Withstand Rating
Symmetrical kA rms
60 Hz
60 Hz
Continuous
Current
Rating,
A rms
15 cycles
30 cycles
6 cycles
15 cycles
30 cycles
60 cycles
(250 ms)
(500 ms)
(100 ms)
(250 ms)
(500 ms)
(1 s)
#2
14.5
10
29
18
13
200
1/0
21
15
47
30
21
14
250
2/0
27
20
59
37
26
18
300
3/0
36
25
74
47
33
23
350
4/0
43
30
94
60
42
29
400
250 MCM
54
39
120
70
49
35
450
350 MCM
74
54
150
98
69
49
550
60 Hz
1.
Withstand and ultimate short circuit properties are based on performance with surges not exceeding 20% asymmetry factor.
2.
Ultimate capacity represents a calculated symmetrical current which the cable or jumper is capable of conducting for the
specified time. These currents are based upon the fusing (melting) current-time values for copper, derived from I. M.
Onderdonks equation with an ambient temperature of 40oC.
Page 206-N1
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Single-Point Grounding
Double-Point Grounding
Remote Grounding
Personal Grounding
Page 206-O1
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
De-energize if Possible
Recognize Potential
Hazard
Anticipate Unexpected
Events
Before beginning work, ask What if..? and decide what you will do if
something goes wrong.
Identify the tools required and do not perform the task until you have
the correct tool.
Page 206-P1
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
1910.146
1910.147
1910.147 App A
1910.269
1910.269 App A
Flow CHARTS
1910.269 App B
1910.269 App C
1910.269 App D
1910.301
Introduction
1910.302
1910.303
General requirements
1910.304
1910.305
1910.306
1910.307
1910.308
Special systems
1910.331
Scope
1910.332
Training
1910.333
1910.334
Use of equipment
1910.335
1910.399
1910 Subpart S
Reference documents
Explanatory data
Page 206-Q1
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Page 206-R1
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
d) Assure that when equipment is working near the proximity of overhead lines a
spotter is designated and observes for safe working clearances around all overhead
lines and directs the operator accordingly.
e) Use warning cones as visible indicators of the 10' safety zone when working near the
proximity of overhead power lines.
NOTE:
P o lic y
All company employees and business partners shall conform to the Overhead Powerline
Proximity Policy. The first line of defense in preventing electrical contact accidents is to
remain outside the minimum safe distance clearances. Because most company and business
partner employees are not qualified to determine voltage, the local area electric shop shall be
called to establish voltages and minimum clearances, and take appropriate action to render
the work safe. Where notification cannot be made one (1) day prior to beginning work,
efforts shall be made to request the local area electric shop to respond immediately.
All company employees and business partners who work near the proximity of overhead lines
shall receive specialized electrical safety training because of their frequent work near
overhead electrical systems. The company Health, Environment & Safety department in
conjunction with the Electrical Safety Inspection and Compliance (ESI&C) team shall
determine training content, duration, and frequency. Training shall be held in conjunction
with local area training, and shall include characteristics, hazards, and precautions for the
prevention of an overhead power line contact.
P ro c e d u re s
A. General
Before starting all operations where potential contact with overhead electrical systems
is possible, the supervisor, head operator, tool pusher, or person lading the work shall
identify overhead lines and equipment and reference their location to prominent
physical features or physically mark the area directly in front of the overhead lines
with safety cones, survey tape, or other means. Electrical line location shall be
Page 206-R2
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
discussed at a pre-work safety meeting of all employees on the job. All company
personnel and business partners shall attend this meeting and require their employees
to conform to OPP electrical safety standards. New/transferred employees will be
informed of electrical hazards and proper procedures during orientations.
On construction projects, the business partner shall identify and reinforce all potential
electrical hazards and document such actions to the company construction/workover
representative. Overhead electrical lines or equipment will be conspicuously marked
and workers will be reminded of their location by the project supervisor. New
employees shall be informed of electrical hazards and proper precautions and
procedures. These procedures shall be adhered to by business partners subject to the
compliance procedures of the contract, including work stoppage in extreme cases.
While there is potential for proximity or contact with overhead electrical systems, the
local area electrical shop shall be called to decide the need to de-energize, safety
ground, remove, or otherwise protect against accidental contact. Where there is a
suspicion of low wires (under 20'), the local area electrical shop shall be notified to
verify and take appropriate action.
All electrical contact incidents, including near-misses, shall be reported to the local
area health, environment and safety specialist.
B. Look Up and Live Flags
To prevent accidental contacts of overhead lines, all aerial lifts, cranes, boom trucks,
service rigs, and similar equipment shall use "LOOK UP AND LIVE" flags. The flags
are visual indicators that the equipment they are working with is being currently used
or has been returned to its "stowed or cradled" position. The flags shall be yellow with
black lettering and shall state in bold lettering LOOK UP AND LIVE.
The procedure for the use of the flag shall be:
When the boom or lift is in its stowed or cradled position the flag shall be
located on the load hook.
Before operating the boom or lift, the operator of the equipment shall access
the work area to determine the location of all overhead lines and communicate
the same to all crews on site. After this is completed, the operator shall
remove the flag from the load hook and transfer the flag to the steering wheel
of the vehicle. After the flag is placed on the steering wheel, the operator may
begin to operate the equipment.
After successfully completing the work activity and returning the equipment to
its stowed or cradled position, the operator shall return the flag to the load
hook.
Page 206-R3
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
The operator of the equipment is responsible for the placement of the LOOK
UP AND LIVE flag.
C. High-Risk Tanks
1. Heavy Equipment or Similar Equipment
Before the start of each workday and where practical, a high visibility
marker, (orange safety cones or other devices) shall be temporarily
installed to mark overhead wires. Supervisors will discuss electrical safety
with appropriate crew members at onsite tailgate safety talks. When
working in proximity to overhead lines, a spotter shall be positioned in a
conspicuous location to direct movement and observe for contact with the
overhead wires. The spotter, equipment operator, and all other employees
working on the job location shall be alert for overhead wires.
2. Aerial Lifts, Cranes, Boom Devices
Where there is potential for proximity or contact with overhead lines or
equipment, work shall not begin until a safety meeting is conducted and
appropriate steps taken to identify, mark, and warn against accidental
contact. The supervisor will review operations daily to assure compliance.
Where the operator's visibility is impaired, a spotter shall guide the
operator. Hand signals shall be used and clearly understood between
operator and spotter. When visual contact is impaired, the spotter and
operator shall be in radio contact. Aerial lifts, cranes, and boom devices
shall have appropriate warning decals, and shall use warning cones or
similar devices to indicate the location of overhead lines and identify the
10' minimum safe working boundary.
3. Tree Work
Wires shall be treated as live and high voltage until verified by the local
area electrical shop. The local area electrical shop or an approved electrical
contractor shall remove branches touching wires before work begins.
Limbs and branches shall not be dropped onto overhead wires. If limbs or
branches fall across electrical wires, all work shall stop immediately and
the local area electrical shop must be called.
When climbing or working in trees, pruners shall try to position
themselves so that the trunk or limbs are between their body and electrical
wires. If possible, pruners shall not work with their back toward electrical
wires. A bucket trunk is the preferential method of pruning when climbing
poses a greater electrical contact threat. Personal protective gear shall have
appropriate di-electric characteristics needed for working near electricity.
Page 206-R4
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Page 206-R5
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Closest Allowable
OPL Location
Radius to
Well
Closest Allowable
OPL Location
Well
FIGURE R-1: Minimum OPL Clearances, Wells near Non-Insulated High- Voltage or
Low-Voltage Systems
Radius to Well
25
50
Rig Tilt
Direction
Un-insulated High-Voltage
All bare wire & >600 volts
Radius to Well
Rig Tilt
Direction
'100
'50
'100
'100
'50
'100
'160
'50
'160
50
tested to be dead. At no time shall the set of grounds be removed until operations or
activities cease and the equipment has been safely removed.
G. Exception for Existing Legacy Facilities
Exceptions for existing, legacy facilities which cannot reasonably be modified.
The rig-to-OPL clearances prescribed above incorporate safety factors plus an
additional buffer distance as a safety precaution. All reasonable efforts should be
made to conform to these standard clearance distances. However, there may be
instances where the potential incremental safety benefit is outweighed by excessive
conversion cost and effort. In such cases, the alternative is to apply legacy clearance
requirements. In such cases, the following conditions must be met:
When the above conditions apply, those clearances described below in Table R-2 can
be used.
Rig Type
Radius to Well
Rig Tilt
Direction
Un-insulated High-Voltage
All bare wire & >600 volts
Radius to Well
Rig Tilt
Direction
Single-Section Rigs
Production & Workover
25
'100
'50
'100
Double-Section Rigs
Drilling & Workover
50
'100
'50
'100
NOTE:
H. Variances
Refer to HES-104 Management of Change and follow instructions for the Variance
Proposal change category.
Page 206-R8
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
If a variance is granted for permanent pieces of equipment, a permanent weatherproof sign, at least 18 by 18, must be posted in a conspicuous location on the
equipment and at the entrance and exit of the location of the equipment. The sign
must detail the hazard(s) present and the appropriate steps required to complete the
work activity.
Em e rg e n c y Re s p o n s e
If an overhead line falls or is contacted:
a) Keep everyone at least 10'away.
b) Use flagging to protect motorists, spectators, and other individuals from fallen or low
wires.
c) Call the local area electrical department or utility immediately.
d) Place guards around the area
e) Do not attempt to move the wire(s).
f) Do not touch anything that is touching the wire(s).
g) Be alert to water or other conductors present.
Crews shall have emergency numbers readily available. These numbers shall include local
area electrical department, utility, police/fire and medical assistance.
If an individual becomes energized, DO NOT TOUCH the individual or anything in contact
with the person. Call for emergency medical assistance and the local area electrical
department or utility immediately. If the individual is no longer in contact with the energized
conductors, CPR, rescue breathing, or first aid should be administered immediately, but only
by a trained person. It is safe to touch the victim once contact is broken or the source deenergized.
Wires that contact vehicles or equipment will cause arcing, smoke, and possibly fire.
Occupants should remain in the cab and wait for the local area electrical department or utility.
If it becomes necessary to exit the vehicle, leap with both feet as far away from the vehicle as
possible, without touching the equipment. Jumping free of the vehicle is the last resort.
If operating the equipment and an overhead wire is contacted, stop the equipment
immediately and, if safe to do so, jump free and clear of the equipment. Maintain your
balance, keep your feet together, and either shuffle or bunny hop away from the vehicle
another 10' or more. Do not return to the vehicle or allow anyone else for any reason to return
to the vehicle until the local area emergency department or utility has removed the powerline
from the vehicle and has confirmed that the vehicle is no longer in contact with the overhead
lines.
Page 206-R9
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
WARNING
WARNING
Circuit Breaker or Fused Switch Operation with covers on and all bolts
intact for any voltage
An 8
rated Face Shield is required for Circuit Breaker or Fused
Switch Operation with covers off < 600 volts
**All bus work shall be worked on de-energized**
working Distance = not less than 18"
Voltage is not greater than 1000 Volts
Incident energy not greater than 8 cal/cm2
* For additional information refer to Tables C-1, C-2, C-3 and C-4 or the
ChevronTexaco ESWP, and NFPA 70E-2004 PPE Requirements
Note: Smaller labels, for application to individual equipment doors, can use the above format, but cut off after the "Minimum Arc Rating of PPE =
" statement.
Page 206-S1
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Appendix MM Glossary
Affected Employee (or Affected Person)
An affected employee is anyone whose job requires him or her to operate a machine or use
equipment that is being serviced or maintained while under lockout or tagout, or whose job
requires him or her to work in an area in which such servicing or maintenance is being
performed.
Additionally, an affected employee is one whose job includes erecting, installing,
constructing, repairing, adjusting, inspecting, operating, or maintaining the equipment or
manufacturing process from a non-electrical perspective.
Examples of affected persons would be employees, contractors, and visitors (facility
inspector; pipeliner; pipeline trainee). (OSHA regulation 1910.269(x), OSHA regulation
1910.147(b) (modified))
ANSI
American National Standards Institute
Approved
Methods, devices, tools, equipment or practices acceptable to the company and/or regulatory
body having jurisdiction.
Arc Flash Protective Equipment
Equipment used to safeguard personnel from momentary electrical arcs. This may include
flame-resistant clothing, flash suits, face protection, hand protection, and/or foot protection.
Arc Rating
The maximum incident energy resistance demonstrated by a material (or a layered system of
materials) prior to breakopen or at the onset of a second-degree skin burn. Arc rating is
normally expressed in cal/cm2. (NFPA 70E, 100)
NOTE:
ASTM
American Society for Testing and Materials
Page 206-T1
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Attendant
An employee assigned to remain immediately outside the entrance to an enclosed or other
designated location to render assistance as needed to employees inside the space. (OSHA
regulation 1910.269(x))
Authorized Employee (or Authorized Person)
An employee who locks out or tags out machines or equipment in order to perform servicing
or maintenance on that machine or equipment. An affected employee becomes an
authorized employee when duties include performing service or maintenance covered
under this practice and include performing the lockout/tagout procedures.
This is also an employee who has been given, by his or her employer, the training, authority,
and responsibility to perform a specific assignment in an electrical area.
A person who can demonstrate by experience and training (as stated in section 8.0 of this
practice) the ability to recognize potentially hazardous electrical energy.
Examples include electricians, pipeline mechanics, supervisors, operators, engineers,
custodians, painters, gaugers, meter provers/meter calibrators, I&E specialists, CP specialists,
etc. (OSHA regulation 1910.269(x) (modified; OSHA regulation 1910.147(b) (modified))
Automatic Circuit Recloser
A self-controlled device for interrupting and reclosing an alternating current circuit with a
predetermined sequence of opening and reclosing, followed by a resetting, hold-closed, or
lockout operation. (OSHA regulation 1910.269(x))
Barricade
A physical obstruction such as tapes, ropes, cones, or A-frame type wood or metal structures
intended to provide a warning about and limit access to a hazardous area. (NFPA 70E, 100)
Barrier
A physical obstruction intended to prevent contact with equipment or exposed live parts, or
to prevent unauthorized access to a work area. (NFPA 70E, 100)
Bond
The electrical interconnection of conductive parts designed to maintain a common electrical
potential across the connection. (OSHA regulation 1910.269(x))
Bus
A conductor or group of conductors that serves as a common connection for two or more
circuits. (OSHA regulation 1910.269(x))
Page 206-T2
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Bushing
An insulating structure, including a through conductor (or providing a passageway for such a
conductor), that can be mounted on a barrier, conducting or otherwise, to insulate the
conductor from the barrier and conduct current from one side of the barrier to the other.
(OSHA regulation 1910.269(x) (modified))
Cable
A conductor with insulation, or a stranded conductor with or without insulation and other
coverings (single-conductor cable), or a combination of conductors insulated from one
another (multiple-conductor cable). (NESC; OSHA regulation 1910.269(x))
Cable Sheath
A conductive, protective covering applied to cables (may be multiple layers, one or more of
which may be conductive). (NESC; OSHA regulation 1910.269(x))
Circuit
A conductor or system of conductors through which an electric current is intended to flow.
(NESC; OSHA regulation 1910.269(x))
Clearance (Between Objects)
The clear distance between two objects, measured surface to surface. (NESC; OSHA
regulation 1910.269(x))
Clearance (For Work)
Authorization by the proper authority that a specified line or piece of equipment is safe to
work on or in (i.e., de-energized, drained, purged, depressurized, etc.) and that it is being
turned over to the Person-in-Charge (PIC). (NESC; OSHA regulation 1910.269(x)
(modified))
Clearance (From Hazard)
The separation distance from energized lines or equipment.
Close Proximity
An object close enough to reach, fall into, or otherwise accidentally touch.
Common Lockout System
A lockout system that permits the use of locking devices but is not unique or uniquely
controlled (see Unique Lockout System below).
Communications Lines (Lines, Communications)
Conductors and their supporting or containing structures that are used for public or private
signal or communication service, operate at potentials not exceeding 400 volts to ground or
Page 206-T3
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
750 volts between any two points of the circuit, and the transmitted power of which does not
exceed 150 watts.
When operated at not more than 90 V ac or 150 V dc, no limit is placed on the transmitted
power of the system. Under specified conditions, communication lines may include
communication circuits exceeding the preceding, where such circuits are also used to supply
power solely to communication equipment. (NESC)
Conductor
A material, usually in the form of a wire, cable, or busbar suitable for carrying an electric
current. (NESC)
Conductor, Bare
A conductor having no covering or electrical insulation, whatsoever. (NFPA 70E, 100)
Conductor, Covered
A conductor encased within material of composition and thickness such that it is not
recognized as electrical insulation. (NESC; NFPA 70E, 100; OSHA regulation 1910.269(x))
Conductor, Insulated
A conductor encased within material of composition and thickness such that it is recognized
as electrical insulation. (NFPA 70E, 100)
Confined Space
A space that meets all of following criteria:
Is large enough and so configured that an employee can bodily enter and perform
assigned work; and
Has limited or restricted means of entry or exit, (for example, tanks, vessels, silos,
storage bins, hoppers, vaults, and pits are spaces that may have limited means of
entry); and
(OSHA 1910.146(b))
CPR
Cardiopulmonary Resuscitation
Current-Carrying Part
A conducting part in an electric circuit intended to be connected to a source of voltage. Noncurrent-carrying parts are those not intended to be so connected. (NESC; OSHA regulation
1910.269(x))
Page 206-T4
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
De-energized
Free from any electrical connection to a source of potential difference and from electric
charge; not having a potential different from that of the earth. (NFPA 70E, 100; OSHA
regulation 1910.269(x))
Designated Person
An employee designated by the employer to perform specific duties and who is
knowledgeable in the construction and operation of the equipment and the hazards involved.
(OSHA regulation 1910.269(x) (modified))
Di-electric Testing
A controlled method used to test the electrical safety integrity of personal protective and liveline equipment.
Disconnect
A device designed to connect or disconnect machines, equipment, and/or other installations
from an electrical energy source.
Disconnecting Means
A device, or group of devices, or other means by which the conductors of a circuit can be
disconnected from their source of supply. (NFPA 70E, 100)
EHV (Extra High Voltages)
For the purposes of this practice, EHV is any voltage above 230 kV.
Electric Line Truck
A truck used to transport personnel, tools, and material for electric supply line work. (OSHA
regulation 1910.269(x))
Electric Utility
An organization responsible for the installation, operation, and maintenance of an electric
supply system. (OSHA regulation 1910.269(x))
Electrically Safe Work Condition
A state in which the conductor or circuit part to be worked on or near has been disconnected
from energized parts, locked/tagged in accordance with established standards, tested to assure
the absence of voltage, and grounded in accordance with section 4.10. (NFPA 70E, 100
(modified))
Employee
One employed by another, usually for wages or salary.
Page 206-T5
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Enclosed Space
A working space, such as a manhole, vault, tunnel, or shaft that has a limited means of egress
or entry, is designed for periodic employee entry under normal conditions, and does not
contain a hazardous atmosphere. Under abnormal conditions, however, it may contain a
hazardous atmosphere. (OSHA regulation 1910.269(x))
NOTE:
Spaces that are enclosed but not designed for employee entry
under normal operating conditions are not considered
enclosed spaces for the purposes of this practice. Similarly,
spaces that are enclosed and that are expected to contain a
hazardous atmosphere are not considered to be enclosed
spaces for the purposes of this practice.
Energized
Electrically connected to or having a source of voltage. (NFPA 70E, 100)
Energy Isolating Device
A physical device that prevents the transmission or release of energy, including but not
limited to, a manually operated electric circuit breaker, a disconnect switch, a manually
operated switch, a slide gate, a slip blind, a line valve, blocks, and any similar device with a
visible indication of the position of the device.
Push buttons, selector switches, and other control-circuit-type devices are not energy isolating
devices. (OSHA regulation 1910.269(x), OSHA regulation 1910.147(b))
Energy Source
Any electrical, mechanical, hydraulic, pneumatic, chemical, nuclear, thermal, or other energy
source that could cause injury to personnel. (OSHA regulation 1910.269(x); OSHA
regulation 1910.147(b) (modified))
Equipotential Grounding (Earthing)
A grounding (earthing) scheme which places the worker in an envelope of equal potential.
When everything that the worker can touch is of the same potential, no current can flow
through the worker between two different touch points.
Equipment (Electrical)
A general term including material (fittings, devices, appliances, fixtures, etc.) that is used as
part of, or in connection with, an electrical installation. (OSHA regulation 1910.269(x))
Escort
A Qualified Employee (see definition below) who accompanies non-qualified employees or
visitors in the vicinity (i.e., within the limited approach boundary) of electrical equipment or
lines.
Page 206-T6
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Guarded
Covered, shielded, fenced, enclosed, or otherwise protected by means of suitable covers,
casings, barriers, rails, screens, mats, or platforms to remove the likelihood of approach or
Page 206-T7
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
contact by persons or objects to a point of danger. (NFPA 70E, 100; OSHA regulation
1910.269(x))
Hazard Risk Analysis
The decision-making process used to determine the degree and extent of the hazard
associated with a particular task, the appropriate protective equipment needed, and the job
planning necessary to complete the task safely.
Hazardous Atmosphere (as applied to confined/enclosed spaces, 29 CFR 1910.269)
An atmosphere that may expose employees to the risk of death, injury, acute illness,
incapacitation, or render them unable to escape unaided from an enclosed space from one or
more of the following causes:
Flammable gas, vapor, or mist in excess of 10 percent of its lower flammable limit
(LFL);
Page 206-T8
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Insulation (Cable)
That which is relied upon to insulate the conductor from other conductors or conducting parts
or from ground. (NESC)
ISO
International Standards Organization
Isolated
(As applied to location) Not readily accessible to persons unless special means of
access are used.
Page 206-T9
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Location Manager
General manager of the facility. An example of a location manger is a team leader.
Low Voltage
Any electrical circuit that normally operates at 1,000 volts nominal or less phase-to-phase or
conductor-to-conductor. However, where governmental codes stipulate voltages less than
1,000 volts phase-to-phase as high voltage, that voltage should be used as the upper limit.
Manhole
A subsurface enclosure, which personnel may enter for the purpose of installing, operating,
and maintaining submersible equipment or cable. (NESC; OSHA regulation 1910.269(x))
Mobile Equipment
Mobile equipment includes, but is not limited to, cranes, bucket trucks, aerial lifts, and
similar types of equipment.
Near Proximity
A minimum clearance of 10' (305 cm) to energized lines and equipment operating at 50 kV,
or less. This distance increases 4 (10 cm) for every 10 kV over 50 kV.
Non-hazardous Work
Work that is not considered to be prohibited, restricted, or limited work. An example is
working on control circuits below 50 V ac or dc to ground.
NOTE:
Non-insulated Conductor
A conductor that has no insulating properties other than air. (See also, Conductor, Bare,
above.)
Operating System Lock
A keyed lock placed on an electrical distribution system to prevent unintentional opening of a
disconnect. Operating system locks may be unique or common-lock systems. This type of
lock is not a personal safety lock. (See Safety Lock, below.)
Page 206-T10
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Person-in-Charge (PIC)
A person in charge of work or employees, regardless of his or her title. Examples include a
supervisor, foreman, lineman in charge, lead people, etc. or a qualified employee who has
been authorized and designated to be locally in charge of company work.
Examples of PICs are team leaders, project managers, project engineers, maintenance
coordinators, construction reps, job inspectors, and others designated as responsible for work
being performed.
Potentially Energized
A non-insulated conductor or device that, by nature of design or location, may be energized
by an adjacent energized conductor, switch closure, or back-feed.
Prohibited Approach Boundary
An approach limit at a distance from an exposed live part within which work is considered
the same as making contact with the live part. (NFPA 70E, 100)
Prohibited (Live) Work
Work that requires intentional hand, body, or tool contact with exposed conductors or circuit
parts operating at 50 V ac or dc or above (conductor-to-conductor or conductor-to-ground), or
work that requires approach of exposed, energized conductors or circuit parts to conductive
objects or unguarded body parts closer than the prohibited approach boundary distance
listed in Appendix A, Table A-6.
Qualified Employee (or Qualified Person)
One who has skills and knowledge related to the construction and operation of electrical
equipment and installations and has received safety training on the hazards involved. (NFPA
70E, 100)
Examples of qualified persons include I&E specialists and CP specialists.
Restricted Approach Boundary
An approach limit at a distance from an exposed live part within which there is an increased
risk of shock, due to electrical arc over combined with an inadvertent movement, for
personnel working in close proximity to the live part. (NFPA 70E, 100)
Restricted (Proximity) Work
Work that requires approaching exposed, energized (50 V ac or dc or above) conductors or
circuit parts with conductive objects or unguarded body parts within the restricted approach
boundary distance listed in Appendix A, Table A-6.
Page 206-T11
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Tagout Device
A prominent warning device, such as a tag and a means of attachment, which can be securely
fastened to an energy-isolating device in accordance with an established procedure, to
indicate that the energy-isolating device and the equipment being controlled must not be
operated until the tagout device is removed.
Ten-Foot Rule
An unqualified person must maintain a minimum distance of 10' from exposed live parts.
(See Limited Approach Boundary, Appendix A, Table A-6.)
To prevent physical contact with energized or isolated ungrounded power lines, equipment or
machines should be operated as follows: the minimum clearance between the lines and every
part of the equipment or machine or its load should be 10' (305 cm) for lines rated 50 kV or
below; this distance is increased four inches (4) (10 cm) for each 10 kV above 50 kV.
Touch Potential
A ground potential gradient difference that can cause current flow from hand-to-hand or
hand-to-foot through the body. (NFPA 70E, 100)
Unique Lockout System
A controlled lockout system (unique lock/one key or unique lock group/one key) requiring
special authorization for use. (See Lockout.)
Unqualified Person
A person who is not a qualified employee. (See Qualified Employee.) (NFPA 70E, 100)
Vault
An enclosure, above or below ground, which personnel may enter for the purpose of
installing, operating, or maintaining equipment or cable. (OSHA regulation 1910.269(x))
Voltage
The effective (rms) potential difference between any two conductors or between a conductor
and ground. Voltages are expressed in nominal values unless otherwise indicated. The
nominal voltage of a system or circuit is the value assigned to a system or circuit of a given
voltage class for the purpose of convenient designation. The operating voltage of the system
may vary above or below this value. (NESC; OSHA regulation 1910.269(x))
Working Near (Live Parts)
Any activity inside a Limited Approach Boundary. (NFPA 70E, 100)
Working On (Live Parts)
Coming in contact with live parts with the hands, feet, or other body parts, with tools, probes,
or with test equipment, regardless of the personal protective equipment a person is wearing.
Page 206-T13
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice
Page 206-T14
Revised/Printed September 2010, Uncontrolled when printed
HES 206 Electrical Safe Work Practice