RDS-14th Floor - New

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

14th Floor Room Data Sheet

S.No.

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23

Room/Space

Corridor
Electrical Room
Lift lobby
Corridor
Corridor
Telephone Room
Royal Consult 1
Waiting
Majlis
Lobby
Royal Suite 1
Carer Room
Corridor
Clean Room
Staff Room
Service Lift Lobby
Corridor
Royal Suite 2
Carer Room
Lobby
Corridor
Majlis
Store

Height(
Space Code Served by Area (m )
m)
2

RM 8001

RM 8015
RM 8014
RM 8006
RM 8003
RM 8004
RM 8035
RM 8029
RM 8020
RM 8021
RM 7901
RM 8028
RM 8009
RM 8036
RM 8008
RM 8011
RM 8026

FCU-1
FCU-1
FCU-2
FCU-2
FCU-3
FCU-3
FCU-4
FCU-5
FCU-6
FCU-7
FCU-7
FCU-8
FCU-9
FCU-10
FCU-10
FCU-10
FCU-11
FCU-12
FCU-13
FCU-14
FCU-14
FCU-15
FCU-16

16.00
5.36
15.85
28.03
13.34
8.37
27.66
24.75
71.78
8.76
51.10
18.67
51.54
9.83
10.70
29.66
58.97
47.79
18.35
8.06
17.48
66.27
18.90

2.7
3.4
2.7
2.7
2.7
3.4
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7

Supply
Airflow
(CFM)
505
155
300
260
794
200
1353
1323
740
520
1280
580
551
314
308
814
1214
1168
834
358
1005
1000
921

Air
Design Airflow
Changes
as per
ASHRAE Std.
per Hour
Consultant
ACH
(ACH)
(CFM)
19.9
14.5
11.9
5.8
37.5
11.9
30.8
33.6
6.5
37.4
15.8
19.5
6.7
20.1
18.1
17.3
13.0
15.4
28.6
27.9
36.2
9.5
30.7

759
200
480
480
759
200
1417
1391
1183
282
1774
578
578
314
314
555
1391
1391
959
319
640
1183
959

HTM Std.
ACH

2
2
2
2
6
4
4
2
6
6
2
4
4
2
2
6
6
2
2
4

8
8

8
8

You might also like