System Validation
System Validation
Fig. 12.1 Power World Simulation of Distribution System Design for Telecommunication
Tower at 100%
Section 12.2
The data in figure 12.2 shows the line data simulated in Power World software at
100% of the Load Capacity.
Section 12.2
Fig. 12.3 Power World Simulation of Distribution System Design for Telecommunication
Tower at 75%
On figure 12.3, it can be appreciated the Power World Simulation of the
Distribution System of Wireless Solutions at 75%. The voltage is shown in real and per unit
value, and the current and angle are shown as well. (See Figure 12.4)
Section 12.2
Fig. 12.5 Power World Simulation of Distribution System Design for Telecommunication
Tower at 50%
On figure 12.5, it can be appreciated the Power World Simulation of the
Distribution System of Wireless Solutions at 50%. The voltage is shown in real and per unit
value, and the current and angle are shown as well. (See Figure 12.6)
%Results
Section 12.2
Z_Line =
0.3906
A=
31.7500
I_Secondary_Nominal =
266.6667
I_Secondary_Full_Load =
312.5000
I_Primary_Nominal =
8.3990
I_Primary_Full_Load =
9.8425
V_Bus_C =
240
V_Bus_B =
7620
V_Bus_A =
7.6232e+03
%Voltage Drop
Section 12.2
Length_Conductor_Primary_Side = 1800;
Length_Conductor_Secondary_Side = 40;
I2 = 390.6;
I1 = 9.8;
K1 = 21.2;
K2 = 12.9;
Circular_Mil_Conductor_Secondary = 500000;
Circular_Mil_Conductor_Primary = 106000;
%Voltage Drop Calculation
Voltage_Drop_Secondary_Side = ((2)*(K2)*(Length_Conductor_Secondary_Side)*(I2)) /
(Circular_Mil_Conductor_Secondary)
Voltage_Drop_Primary_Side = ((2)*(K1)*(Length_Conductor_Primary_Side)*(I1)) /
(Circular_Mil_Conductor_Primary)
%Results
Voltage_Drop_Secondary_Side =
0.8062
Voltage_Drop_Primary_Side =
7.056
Section 12.2