0% found this document useful (0 votes)
35 views1 page

EEE 361 Lab Pre Work 2

(i) The document provides instructions for lab pre-work that must be done individually and submitted on time with a calculator brought to the lab. (ii) The pre-work asks students to explain the purpose of open and short circuit transformer tests and draw the schematic diagrams for each test. (iii) It also asks students to determine the equivalent circuit of a 1000VA transformer from test results, calculate its voltage regulation at different power factors, and determine its efficiency at rated load and 0.8 PF lagging.

Uploaded by

adil
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
35 views1 page

EEE 361 Lab Pre Work 2

(i) The document provides instructions for lab pre-work that must be done individually and submitted on time with a calculator brought to the lab. (ii) The pre-work asks students to explain the purpose of open and short circuit transformer tests and draw the schematic diagrams for each test. (iii) It also asks students to determine the equivalent circuit of a 1000VA transformer from test results, calculate its voltage regulation at different power factors, and determine its efficiency at rated load and 0.8 PF lagging.

Uploaded by

adil
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

EEE 361 Lab pre work 2

Instructions: (i) Pre work should be done by each student on his own. The copied pre-work
would be marked as zero (ii) The students are expected to write reports of pre work on
computer (iii) The pre work should be submitted on time (iv) Bring calculator in lab

1) (a)What is the main purpose of doing open circuit and short circuit test of
transformers? (b) Draw the schematic diagrams of both open circuit and short
circuit tests

2) A 1000-VA 230/115-V transformer has been tested to determine its equivalent


circuit. The results of the
tests are shown below.
Open-circuit test Short-circuit test
VOC = 230 V VSC = 19.1 V
IOC = 0.45 A ISC = 8.7 A
POC = 30 W PSC = 42.3 W
All data given were taken from the primary side of the transformer.
(a) Find the equivalent circuit of this transformer referred to the low-voltage side of
the transformer.
(b) Find the transformers voltage regulation at rated conditions and (1) 0.8 PF
lagging, (2) 1.0 PF, (3) 0.8
PF leading.
(c) Determine the transformers efficiency at rated conditions and 0.8 PF lagging.

3) What is voltage regulation of the transformer?