Bus Bar Protection
Bus Bar Protection
PROTECTION
Bus bar is just like junction in Railway network. In Railway junction, Train are coming from
different directions and leaving for other destinations. A bus bar is one of the more critical
elements of Power System. It is the connecting point of a variety of elements and a
number of transmission lines. Any incorrect operation would cause isolation the all of
these elements.
Bus Bar Arrangements:The buses typically illustrated are such as:i. Single bus, single breaker.
ii. Double bus bar with bus sectionalizer - single
breaker.
iii. Main and transfer bus single breaker.
iv. Double bus with single breaker.
v. Double bus with two breakers
vi. Ring bus
vii. Breaker and a half scheme.
Bus Bar Faults:Busbar faults are very rave, but are very
serious. They can result in considerable
loss and should be cleared in minimum
possible time. The common causes of
bus bar faults are as under:i. Equipment failures Circuit breaker
failure / C.T. failure.
ii. Small animal contacts.
iii. Broken conductors.
iv. Wind driven objects falling debris.
v. Contamination.
vi. Safety earths left connected.
vii. Isolators operated outside their ratings.
Critical Problem
The major problem with bus bar protection
has been unequal saturation of current
transformers connected to the bus bar.
This unequal core saturation is due to
possible variation of current magnitude
and residual flux in the individual current
transformers connected to the bus bar.
Zone Arrangement
1. Single Bus Bar
Distance Protection
Basic Condition
A. Normal Operation.
B. External Fault.
C. Internal fault.
C. Internal Fault
C.T. Saturation
C.T. saturation occurs when the flux
required to produce the secondary
current exceeds the saturation density of
the core. C.T. saturation depends on the
following factors.
i. C.T. Ratio.
ii. Core cross Sectional area
iii. Connected burden.
C.T. Circuit
= 0
IF = Fault current
=
US
RCT+2RL+RS
=
IF (RCT+2RL)
RCT+2RL+RS
If RS is small
IS = IF
If RS is large, then
IS = US
RS
UF = IS RS
Is
Rs = U s - R R
Is
Example
The setting of relay is determined by
US = IS RS
High resistance RS is connected in series
with the relay. Voltage across the shunt
patch is given due to external fault is given
by
UF =
IF
C.T. Ratio
(RCT + 2RL)
= 1 Ohm
UF
= 40,000
=
1200
200 V
(4+2x1)
Differential Relays
i.
MCAG14/34
Current calibrated relay with external
stabilizing resistor.
ii. MFAC14/34
Voltage calibrated relay with internal
high impedance.
Normal Operation
In high impedance bus bar protection, each phase
of C.T. of all bays are connected together.
The fig ( ) shows that secondary currents of all
current transformers are connected in parallel
with high impedance relay. The differential
measurement principle applies that sum of
current entering is equal to sum of current
leaving i.e. Vectorial sum of all outgoing and
incoming primary current is zero.
Requirements
The following conditions should be fulfilled
for reliable operation of high impedance
differential protection.
1. All C.Ts must possess same
transformation ratio.
2. All C.Ts should have same saturation
characteristics.
Use of LC Circuit
The LC circuit in series with over voltage
relay is turned to 50 Hz to prevent over
voltage relay from mis-operation on d.c.
offset or harmonics.
UARISTOR
Leakage current of the uaristor = I v = 24 ma
At relay pick-up voltage
2 VS
=
=
2 x 240
480 V
If No Uaristor is provided , IV = 0
Stability during external fault.
IF (Through fault = N RR
IR
RL + RCT
=
2 VK VF
IF x RR x
I
N
V peak = 2 2 VkR - VF
= Stabilizing resistor
a. Normal Connections