Concrete Fundamentals
Concrete Fundamentals
5. Using the unit weight of cement, the weight of cement may be converted
into the volume of cement (cubic feet of cement per cubic yard of
concrete).
6. The recommended bulk volume of coarse aggregate is given by Table 9.4.
7. The bulk volume of coarse aggregate is multiplied by the bulk density to
obtain the weight of coarse aggregate (pounds of aggregate per cubic
yard of concrete).
8. Using the unit weight of coarse aggregate, the weight of aggregate may
be converted into the volume of aggregate (cubic feet of coarse aggregate
per cubic yard of concrete).
9. The volume of air in the mix is obtained from the air content determined in
step 2.
10. The volume of ne aggregate is obtained as the volume remaining by
subtracting air, water, cement, and coarse aggregate volumes from 1 yd 3
(27 ft 3).
11. The weight of ne aggregate is calculated (pounds of aggregate per cubic
yard of concrete) based on the known specic gravity.
12. Corrections are made to the mixing water for moisture contained within
ne and coarse aggregates according to the following formula:
(104.1)
The volume of each component (SSD coarse aggregate, SSD ne aggregate,
and cement) can be calculated as
(104.2a )
(104.2b )
(104.2c )
Water-cement ratio = W water/W cement (using total or adjusted weight of mixing
water)
Sometimes, in the eld, w/c ratio is expressed as gallons per sack instead of a
dimensionless weight ratio. The decimal w/c ratio is multiplied by 11.27 to
convert to gallons per sack.
Example 104.1 Concrete Mix Design
The following aggregates are used in a concrete mix:
Coarse Aggregate:
Moisture content of wet aggregate 2.8%
Moisture content of SSD aggregate 0.6%
Specic gravity of SSD aggregate 2.65
Fine Aggregate:
Moisture content of wet aggregate 6.0%
(104.3)
where f
and is given by
ACI as
(104.4)
In the United States, a standard bag of cement contains 94 lb. A concrete mix
referred to as a 6-bag mix contains 6 standard (94 lb) bags of cement per
cubic yard (564 lb cement per cubic yard concrete). Cements are designated
as the following types:
Type I Normal
Type II Modied for hot weather or large structures
Type III High early strength
104.3. Reinforcement
Reinforcement bars are available in various sizesin the U.S. system of
nomenclature, these sizes are designated No. 3, No. 4, and so on, up to No.
18 bars. Nominal diameters and areas of these sizes are given in Table 104.1.
(104.5)
The strength reduction factor is given by ACI according to Table 104.2.
0.90
0.005)
For all beams (0.004 < t < 0.005)
Compression-controlled sections (t
0.48 + 83 t
< 0.002)
Members with spiral reinforcement
0.70
0.65
0.57 + 67 t
0.48 + 83 t
0.75
Bearing on concrete
0.65
Source ACI 318, 2005, Building Code Requirements for Reinforced Concrete
, American
(104.6)
where Q i = the i th service load level (e.g., dead load and live load).
i = corresponding load factor.
The load combination that produces the maximum load eect for the member
is said to "govern."
(104.7a )
(104.7b )
(104.7c )
(104.7d )
(104.7e )
(104.7f )
where D = dead load, F = uid pressure load, T = self-straining force, L =
live load, W = wind load, E = earthquake load, L r = roof live load, S =
snow load, R = rain load, H = earth pressure loads.
Notes
1. The load factor on live load (L ) in load combinations in Eqs. (104.7c ),
(104.7d ), and (104.7e ) may be reduced to 0.5 except for garages, places of
public assembly, and all areas where L is greater than 100 psf.
2. Where the wind load (W ) has not been reduced by a directionality factor, it
shall be permitted to use 1.3 W instead of 1.6 W in load combinations in
Eqs. (104.7d ) and (104.7f ).
3. Where the earthquake load (E ) is based on service-level seismic forces,
replace 1.0 E with 1.4 E in load combinations in Eqs. (104.7e ) and
(104.7f ).
However, when only dead and live loads are present, the factored load may
be taken as
(104.8)
This exception is noted in App. C of the specications. However, when using
this factored load, the strength reduction factors must be taken as shown
in Table 104.3.
0.90
0.005)
Compression-controlled sections (t
< 0.002)
Members with spiral reinforcement
0.75
0.70
0.85
Bearing on concrete
0.70
Thus, the alternative approaches in chap. 9 and App. C of the ACI 318
specications result in signicantly dierent factored loads, but the nal
result can be quite similar due to dierent strength-reduction factors.
According to the current syllabus for the Structural Depth of the PE Civil
exam, "Appendix C does not apply to the Civil Structural examination."
[1]S.
, ASCE/SEI 7-
Citation
EXPORT
Indranil Goswami: Civil Engineering All-In-One PE Exam Guide: Breadth and Depth,
Second Edition. Concrete Fundamentals, Chapter (McGraw-Hill Professional, 2012),
AccessEngineering