Laboratory Design Guidelines
Laboratory Design Guidelines
TABLE OF CONTENTS
Design Guidelines
1|P a g e
2. Scope ................................................................................................................................................... 22
3. Storage of Compressed Gas Cylinders General Location ................................................................ 22
4. Storage of Compressed Gas Cylinders Toxic and Highly Toxic Gases ........................................... 23
5. Storage of Compressed Gas Cylinders Medical Gases ..................................................................... 24
VI. FLAMMABLE LIQUID STORAGE CABINETS ........................................................................................... 25
1. Codes, Standards, and References ..................................................................................................... 25
2. Scope .................................................................................................................................................. 25
3. Design ................................................................................................................................................ 25
4. Construction ....................................................................................................................................... 26
VII.
HAZARDOUS MATERIALS STORAGE AND HANDLING ................................................................ 27
1. Standards ............................................................................................................................................ 27
2. Scope .................................................................................................................................................. 27
3. Requirements ..................................................................................................................................... 27
4. Procedures .......................................................................................................................................... 28
VIII. ADDITIONAL REQUIREMENTS FOR LABORATORIES USING RADIOACTIVE MATERIALS,
RADIATION PRODUCING MACHINES, OR LASERS ..................................................................................... 29
1. Codes, Standards, and References ..................................................................................................... 29
2. Scope .................................................................................................................................................. 30
3. Decommissioning of Existing Facilities Prior to Demolition or Renovation .................................... 30
4. Design Features for Radiological Labs .............................................................................................. 30
5. Ventilation Considerations ................................................................................................................. 31
5. Laser Radiation Items ........................................................................................................................ 32
5. Laser Ventilation Considerations ....................................................................................................... 32
IX. BIOSAFETY LEVEL 2 LABORATORIES..................................................................................................... 32
1. Codes, Standards, and References ..................................................................................................... 32
2. Scope .................................................................................................................................................. 33
3. Ventilation Considerations for Biosafety Level 2 Laboratories......................................................... 33
4. Biological Safety Cabinets and Other Containment Considerations ................................................. 33
X. GLOSSARY ..................................................................................................................................................... 35
2013
Design Guidelines
2|P a g e
I.
INTRODUCTION
Purpose: UNC-Chapel Hill has a continuing need to modernize and upgrade its facilities. The resulting
construction projects often have significant health and safety requirements due to regulatory oversight. Since
these requirements can impact the design of a project, the Department of Environment, Health and Safety (EHS)
prepared this EHS Laboratory Design Guide to aid the campus community with planning and design issues.
EHS believes that the Guide, in conjunction with EHSs plan review and consultation, improves design
efficiency and minimizes changes. The main number for the UNC-EHS Office is (919) 962-5507.
Application: The Guide is a resource document for use by faculty, staff, and design professionals for use
during the planning and early design phases of a project. The Guide applies to construction projects for all
UNC-Chapel Hill facilities, including leased properties.
Format of Guide: The Guide is formatted to address laboratory design issues pertinent to General Laboratories
(e.g.: chemical laboratories) in Section II through VII, with additional requirements for Radioactive Materials
Laboratories and Biosafety Level 2 Laboratories presented in Sections VIII and IX respectively. Within the
sections, specific design criteria are provided.
References: Please note that if any Design Guidelines are less stringent than the current NC Building Code,
Mechanical Code, Fire Prevention Code etc., it should be brought to the attention of the EHS Department for
discussion and revision as necessary. The Design Guidelines are not intended to preempt NC Code without
State approval of Alternate Methods and Materials, where these Guidelines are found to be less stringent.
Design criteria are designated in the following ways:
Shall: Criterion is typically mandated by applicable regulation(s). The user of the Guide is required to
include the design feature.
II.
2013
3|P a g e
5.
6.
7.
8.
2.
Scope
The primary objective in laboratory design is to provide a safe environment for laboratory personnel
to conduct their work. Therefore, all health and safety hazards must be identified and carefully
evaluated so that protective measures can be incorporated into the design. The basic laboratory
design features listed in this section illustrate some of the basic health and safety elements to include
in all new and remodeled laboratories at UNC. The subsections of Section 2.1 provide specific
guidance on additional critical features of a general laboratory (e.g., fume hoods, hazardous
materials storage, and compressed gases.) (Keep in mind, however, that no matter how well designed
a laboratory is, improper usage of its facilities will always defeat the engineered safety features.)
3.
Architectural Considerations
i. Walls/Doors/Security
The laboratory must be completely separated from outside areas (i.e., must be bound by four
walls).
The laboratory shall have means of securing specifically regulated materials such as DEA
Controlled Substances, CDC Select Agents and radioactive materials (i.e., lockable doors,
lockable cabinets, etc.)
ii.
Having secured hazardous materials storage will keep unauthorized personnel from gaining
access to them. These regulations apply specifically to laboratories containing radioactive
materials,CDC Select Agents and DEA Controlled Substances; however, UNC-Chapel Hill EHS
interprets this to include all laboratories (e.g., general chemistry and electronics).
Laboratories which may use CDC Select Agents shall have secured entry doors that upon illegal
entry alarm to DPS and EHS.
2013
Design Guidelines
4|P a g e
Doors in H-occupancy laboratories shall have doors which swing in the direction of egress.
Doors serving B-occupancy shall swing in the direction of egress if the occupant load is 50 or
more. Where possible, all B-occupancy lab doors should swing out with hardware satisfying
ADA requirements.
On the next to each door entry into the laboratory an 8.5 x 11 inch space must be provided for a
standardized clear frame with the room number and hazard warning sheet insert (landscape
orientation).
Each door into a laboratory room must have a view panel.
Inside the laboratory, on the wall adjacent to the door latch, provide 2 feet of clear space for light
switches, telephone, thermostat and fire extinguisher.
Vents are prohibited in laboratory doors which open to egress/access corridors.
Laboratories which use hoods or other larger equipment should be equipped with doorways that
have 48 inch openings. Each opening should accommodate a 36 active door leaf and a 12 inch
inactive leaf.
iii. Windows
If the laboratory has windows that open they must be fitted with insect screens.
iv. Flooring
The floor must be a one piece non-pervious and with covings to the wall. This can be achieved by
use of glue, heat welded vinyl flooring, epoxy coated concrete slab, etc.
Floors should be coved up walls and cabinets to ensure spills cannot penetrate underneath
floors/cabinets. Tiles and wooden planks are not appropriate because liquids can seep through the
small gaps between them. These references apply specifically to laboratories containing
biological and radioactive materials; however, UNC-Chapel Hill EHS interprets this to include
all laboratories (e.g., general chemistry, electronics, etc.).
Floors in storage areas for corrosive liquids shall be of liquid tight construction.
v. Sinks
Each laboratory must contain a sink for hand washing. Elbow or electronic sensing faucet
controls are recommended particularly for biological agents and/or highly toxic chemicals.
Sink faucets and hose bibs that are intended for use with attached hoses must be equipped with
back siphon prevention devices.
Laboratory sinks shall have lips that protect sink drains from spills.
Sink lips or berms should be >= 0.25 inches and designed to completely separate the lab bench or
fume hood work area from the sink drain.
2013
Design Guidelines
5|P a g e
2013
Design Guidelines
6|P a g e
Laboratory furniture must have smooth, non-porous surfaces so as to resist the absorption of
liquids and the harsh effects of disinfectants. Furniture must not be positioned in such a manner
that makes it difficult to clean spilled liquids or conduct routine maintenance. These references
apply specifically to laboratories containing biological and radioactive materials; however, UNCChapel Hill EHS interprets this to include all laboratories (e.g., general chemistry and
electronics).
ix. Breakrooms
The design of the laboratory building must incorporate adequate additional facilities for food
storage/consumption and personal hygiene tasks outside of the rooms where chemical and
biological materials are handled.
Break rooms should be sized based upon floor occupancy and must be dedicated as a break area
and not serve other functions such as a copy center or equipment storage.
A minimum of 1 break room is required per floor unless separate desk space is provided for each
occupant in office areas which are walled off and separately ventilated from the laboratory space.
x. General Ventilation Considerations (see also Section 2.2 for fume hood considerations)
Laboratory room supply should discharge through a perforated ceiling/plenum at velocities not
exceeding 50 fpm. Supply terminal velocity at the face of the hood must not exceed 25 fpm or 30
per cent of the minimum face velocity (whichever is less).
The building DDC system should have spare capacity for building gas and vapor sensor inputs.
Sensor technology should be considered for emergency detection and alarm for highly hazardous
gases or vapors.
Winter: 69-76 F (at 35% RH); Summer: 73-79 F (at 60% RH)
Consider providing chilled water line services to laboratories with significant heat loads.
Certain equipment may be specified to incorporate centrally produced chilled water and reduce
water use and conditioned air.
Chilled water lines may be connected to portable fan coil units for spot cooling in rooms with
high general heat loads.
Cabinetry or other structures or equipment must not block or reduce effectiveness of supply or
exhaust air.
Supply diffusers and room exhaust openings are located along laboratory ceilings. Storage of
boxes near these openings may obstruct the circulation of air and supply or exhaust air
functioning.
General laboratories must have a minimum of 6-air changes/hour.
2013
Design Guidelines
7|P a g e
OSHA requires a minimum of 6 AC/HR in chemical storage rooms. Since most laboratories store
some quantities of chemicals, this regulation applies.
Laboratories should be equipped with an emergency exhaust button with reset capability located
next to the exit door to provide up to 12 air exchanges per hour in the event of a chemical
emergency (gas leak, volatile liquid spill, smoke, etc.)
Laboratories must be maintained under negative pressure in relation to the corridor or other less
hazardous areas.
Clean rooms requiring positive pressure should have entry vestibules (anterooms) provided with
door-closing mechanisms so that both doors are not open at the same time.
Air exhausted from the general laboratory space (as distinguished from exhaust hoods) must not
be recirculated unless one of the criteria listed in ANSI/AIHA Z9.5 are met. Exhaust air from
hoods is never recirculated.
General laboratory and Hood exhaust systems which pass conditioned building air through heat
recovery systems require maintenance at the filtration/heat exchange units. These units should be
maintainable without physical entry into the exhaust system.
If bodily entry is required into the ventilation system, isolation valves/dampers must be provided
for each section being entered. Also, Grade D air must be plumbed to the units to allow the use of
supplied air respirator hoods or masks while working inside the ventilation system.
xi. Casework and counter top recommendations
1.
Casework:
Type: Standard, floor mounted, closed-base type (may have access doors), should be used in
all laboratories.
Materials: Metal or Hardwood (such as oak or other approved equivalent) - should be used in:
a.
b.
c.
d.
General research and teaching laboratories where humidity and temperature will be
normal (standard for occupied rooms), where casework maintenance is not a compelling
factor, and where flammable, corrosive, or toxic substances will not be absorbed into the
surface.
Plastic Laminate - Should be used in:
(i) Miscellaneous storage and workrooms requiring base or wall storage facilities, and
where the infusion of appropriate colors may be architecturally desirable.
(ii) Only non-combustible and non-reactive laminates may be used where flammable or
corrosive chemicals are to be stored or used.
Millwork - Should not be considered for new construction. Variances may be considered
on renovation projects on a case-by-case basis.
Counter Tops:
Chemical Reaction and Abuse Resistance - for chemical resistance work surfaces, either
of the following should be used:
(i) Type 1 - Composition Stone -- with a chemical resistant resin finish.
(ii) Type 2 - Natural Quarry Stone -- with a chemical resistant finish.
(iii) Type 3 - Solid Resin -- for chemical resistant surfaces and in the bottom of general
purpose fume hoods
2013
Design Guidelines
8|P a g e
General Purpose - Areas where neither chemical nor physical abuse is expected and
where no liquid services are to be used, such as 30" high desk and writing surfaces,
instrument support surfaces, or storage areas may use either of the following:
(i)
Type 4 - Wood Core -- A wood fiber or wood particleboard core with chemical
resistant finish on all exposed surfaces.
(ii) Type 5 - Plastic Laminate -- Plastic Laminate surface with a wood particle core;
may be selfedged or post-formed.
(iii) Radiation and Other Special Uses -- areas where radioactive materials or other
special uses are approved should use the following:
(iv) Type 6 - Stainless Steel -- Type 316 polished stainless steel counter top surfaces
may be approved on a case-by-case basis.
Physical Abuse Resistance - areas where abrasive physical abuse is expected; Physics,
Earth Sciences, Geology, or Paleontology laboratories shall use:
(i)
(ii)
Where these casework guidelines are not deemed suitable, alternates of equal or better
quality and durability shall be discussed with the UNC Chapel Hill EHS Office.
xii. Engineering Considerations
a. Electrical
GFI protection shall be provided to electrical receptacles above counter tops and within 6 feet of
sinks. Receptacles that are not readily accessible or receptacles for appliances occupying dedicated
space, which are cord-and-plug connected in accordance with NEC Section 400-7A (6-8), are
exempted.
Circuit breakers should be located outside the lab. All breakers must be clearly labeled as to
equipment, lighting and outlets served.
In the event of an emergency, the laboratory may be unsafe to enter. Hence, the circuit breakers
for key electrical appliances should be located outside the lab.
b. Plumbing
Valves for building gas supply lines should be located outside the lab.
2013
Design Guidelines
9|P a g e
The flexible connections should be used for connecting gas and other plumbed utilities to any
freestanding device including, but not limited to; biosafety cabinets, incubators, and liquid
nitrogen freezers. Flexible connections should be appropriate for the pressure requirements and
should be constructed of material compatible with the transport gas. A shutoff valve should be
located within sight of the connection and clearly marked.
Sink drains traps must be transparent (e.g., made of glass) and easy to inspect or have drain plugs
to facilitate mercury spill control.
Lab waste water lines shall be separate from domestic sewage and sampling points shall be
installed in an easily accessible location outside the building.
The sampling point shall be installed at a location where all building lab wastes are discharged,
before the lab waste line connects to the domestic waste line. The sampling point shall be designed
so that it is perpendicular to the lab waste line, has a minimum 4 inch diameter, has a cleanout
screw on cap and is protected by a Christie Box. The sampling point should not be located in an
area where water from irrigation or flow from stormwater runoff can accumulate.
All gas and utility supply lines shall be clearly marked along their entire length through the
building. One suggested marking scheme is outlined in SEFA 7, 1994 as follows:
III.
Number
Service
Color
Code
Color of Letter
1
2
3
4
5
6
7
8
9
10
11
Cold Water
Hot Water
Steam
Air
Gas
Vacuum
Distilled Water
Oxygen
Hydrogen
Nitrogen
All Other Rare Gases
Dark Green
Red
Black
Orange
Dark Blue
Yellow
White
Light Green
Pink
Gray
Light Blue
CW
HW
STM
Air
Gas
Vac
DW
OXY
H
N
Chemical Symbol
White
White
White
Black
White
Black
Black
White
Black
Black
Black
FUME HOODS
The requirements of this Guide apply to all UNC laboratory buildings, laboratory units, and laboratory
work areas in which hazardous materials are used, handled, or stored.
1.
2013
Design Guidelines
10 | P a g e
Fume hood openings should not be located opposite workstations where personnel will spend much of
their working day, such as desks or microscope benches.
Fume hoods should not face each other across narrow aisles.
An emergency eyewash/shower station shall be within 10 seconds of each fume hood.
Per 8 CCR 5162, the requirement for an eyewash/shower is triggered when an employee may be
exposed to substances, which are corrosive or severely irritating to the skin or which are toxic by skin
absorption during normal operations or foreseeable emergencies. Fume hoods are assumed to contain
such substances; hence, UNC interprets this regulation to mean that emergency eyewash/shower
station shall be within 10 seconds of fume hoods.
An ADA emergency eyewash/shower shall be within 10 seconds of an ADA fume hood (minimally
one ADA hood per laboratory floor).
The location of at least one ADA hood per floor will enable disabled individuals to conduct their
research without having to transport chemicals, etc. in elevators.
2.
Approved Equipment
All fume hoods shall meet the requirements of NFPA 45, Standard on Fire Protection For Laboratories
Using Chemicals, and ANSI/AIHA Z9.5.
3.
Selection/Types
i. General: Consider the following factors when selecting fume hood:
1.
2.
3.
4.
5.
6.
7.
8.
9.
2013
Design Guidelines
11 | P a g e
It is very difficult to keep the air supply and exhaust of supply hoods properly balanced. In
addition, the supply air is intemperate, causing discomfort for those working in the hot or cold air
stream. As a result, the supply vent is often either shut or blocked off, which eliminates any
potential benefit of this type of hood. Finally, the presence and movement of the user's body in the
stream of supply air creates turbulence that degrades the performance of the hood.
v. Ductless Fume Hoods:
Portable, non-ducted fume hoods are generally not permitted; however, a portable hood may be
used for limited applications (e.g., used inside of an existing hood for a special application, such
as odor control or to enclose a microbalance). Such applications must be reviewed and approved
by EHS on a case-by-case basis.
vi. Perchloric Acid Hoods:
Heated perchloric acid shall only be used in a laboratory hood specifically designed for its use and
identified as "For Perchloric Acid Operations." (Exception: Hoods not specifically designed for
use with perchloric acid shall be permitted to be used where the vapors are trapped and scrubbed
before they are released into the hood.)
Perchloric acid hoods and exhaust duct work shall be constructed of materials that are acid
resistant, non-reactive, and impervious to perchloric acid.
The exhaust fan should be acid resistant and spark-resistant. The exhaust fan motor should not be
located within the duct work. Drive belts should not be located within the duct work.
Ductwork for perchloric acid hoods and exhaust systems shall take the shortest and straightest
path to the outside of the building and shall not be manifold with other exhaust systems.
Horizontal runs shall be as short as possible, with no sharp turns or bends. The ductwork shall
provide a positive drainage slope back into the hood. Duct shall consist of sealed sections. Flexible
connectors shall not be used.
Sealants, gaskets, and lubricants used with perchloric acid hoods, duct work, and exhaust systems
shall be acid resistant and non-reactive with perchloric acid.
A water spray system shall be provided for washing down the hood interior behind the baffle and
the entire exhaust system. The hood work surface shall be watertight with a minimum depression
of 13 mm ( inch) at the front and sides. An integral trough shall be provided at the rear of the
hood to collect wash-down water.
The hood surface should have an all-welded construction and have accessible rounded corners for
cleaning ease.
The hood baffle shall be removable for inspection and cleaning.
Each perchloric acid hood must have an individually designated duct and exhaust system.
vii. Radioactive Material Use
1.
2.
3.
2013
Fume hoods intended for use with radioactive isotopes must be constructed of stainless steel
or other materials that will not be corroded by the chemicals used in the hood.
The interior of all radioisotope hoods must have coved corners to facilitate decontamination.
The hood exhaust may require filtration by HEPA or Charcoal/HEPA filters. Where such is
the likelihood, the hood must have a bag-out plenum for mounting such filters and fan
Design Guidelines
12 | P a g e
4.
5.
capacity for proper operation of the hood with the filter installed. The most appropriate
location for the plenum is near the exhaust port of the fume hood (i.e., proximal to the hood).
The cabinet on which the hood is installed shall be adequate to support shielding for the
radioactive materials to be used therein.
In general, glove boxes with HEPA filtered exhausts shall be provided for operations
involving unsealed radioactive material that emit alpha particles. Consult with the Radiation
Safety Section of EHS for specific requirements.
Labeling
Laboratory hoods and special local exhaust ventilation systems (SLEV) shall be labeled to indicate
intended use (e.g., Perchloric Acid Hood).
5.
2013
Design Guidelines
13 | P a g e
Hood inserts are only permitted for radioactive iodination procedures specifically approved by the
UNC Radiation Safety Officer.
Laboratory hoods shall be provided with a means of containing minor spills.
The means of containing minor spills might consist of a 6.4-mm ( in.) recess in the work surface, use
of pans or trays, or creation of a recess by installing a curb across the front of the hood and sealing the
joints between the work surface and the sides, back, and curb of the hood.
There must be a horizontal bottom airfoil inlet at the front of the hood.
Adjustable baffles with horizontal slots must be present in the fume hood interior at the back and top.
Before a new fume hood is put into operation, an adequate supply of makeup air must be provided to
the lab.
6.
Face Velocity
Average air velocity at the hood face must be between 100-120 linear feet per minute (LFM) with a
minimum of 90 LFM at any measured point at a minimum vertical sash opening of 18 inches. For
combination sashes, the face velocity with the vertical sash down and two panels open must be 100
fpm and must pass the ASHRAE 110 tests at constant volume when the sash is raised to the full open
(setup) position.
7.
Certification
The criteria for new fume hood installations at UNC-Chapel Hill are:
The average face velocity of the fume hood is between 100-120 fpm at an 18-in sash height or, for the
combination sash, 100-120 fpm with the vertical sash closed and two horizontal sashes open.
All single-point velocity measurements are 90 fpm or greater at the specified minimum openings.
Fume hood containment is shown using the ASHRAE 110 smoke test and tracer gas tests in 3 test
conditions:
i. Two horizontal sashes open (vertical sash lowered)
ii. Vertical sash at 18 inches
iii. The sash fully open.
Fume hoods with a vertical sash only must pass the ASHRAE 110 testing for the 18 inch and full open
sash positions.
Where the required velocity can be obtained by partly closing the sash, the sash and/or jamb shall be
marked to show the maximum opening at which the hood face velocity will meet the face velocity
requirements.
An airflow indicator and alarm shall be provided and located so that it is visible from the front of the
fume hood. In addition, a magnehelic gauge mounted on the front of the hood and connected to the
hood throat shall be installed to monitor hood suction.
Hood alarms will sound locally.
2013
Design Guidelines
14 | P a g e
Baffles shall be constructed so that they may not be adjusted to restrict the volume of air exhausted
through the laboratory hood. Manual dampers shall be locked in position as soon as the system is
balanced.
Fans should run continuously without local control from hood locations and independently of any time
clocks unless specifically exempted by the UNC EHS Department.
For new installations or modifications of existing installations, controls for laboratory hood services
(e.g., gas, air, and water) should be located external to the hood and within easy reach.
Shutoff valves for services, including gas, air, vacuum, and electricity shall be outside of the hood
enclosure in a location where they will be readily accessible in the event of fire in the hood. The
location of such a shut-off shall be legibly lettered in a related location on the exterior of the hood.
Each exhaust hood shall be permanently labeled with the unique identification number and the fan ID
to which it is attached. Each fan on the roof shall be permanently labeled with its unique ID and a
permanent listing of all room numbers, hoods and or general exhausts to which it is attached.
8.
9.
Sashes
Sashes may be horizontal, vertical, or a combination, and must have the capability to close off the hood
face substantially.
Sash panels (horizontal sliding) must be 12 to 14 inches in width.
Sashes shall be made of safety glass.
Use laminated safety glass when internal temperature is anticipated to be less than 160 F.
2013
Design Guidelines
15 | P a g e
Use tempered safety glass when high internal temperatures are anticipated that will result in sash
surface temperatures greater than 160 F.
10. Ducting
Hood exhausts should be manifold together except for:
i.
ii.
iii.
iv.
v.
Manifold fume hood exhaust ducts shall be joined inside a fire rated shaft or mechanical room, or
outside of the building at the roofline.
Horizontal ducts must slope at least 1 inch per 10 feet downward in direction of airflow to a suitable
drain or sump.
Ducts exhausting air from fume hoods should be constructed entirely of noncombustible material.
Gaskets should be resistant to degradation by the chemicals involved and fire resistant.
Automatic fire dampers shall not be used in laboratory hood exhaust systems. Fire detection and alarm
systems shall not be interlocked to automatically shut down laboratory hood exhaust fans.
Duct linings shall have a flame spread index of 25 or less when tested in accordance with NFPA 255,
Standard Method of Test of Surface Burning Characteristics of Building Materials. Test specimens
shall be of the minimum thickness used in the construction of the duct or duct lining.
Duct linings are not recommended. If they are installed then they must meet the above requirement.
Air exhausted from laboratory work areas shall not pass unducted through other areas.
11. Exhaust
New exhaust fans should be oriented in an up-blast orientation.
Hood exhaust stacks shall extend at least 10 feet above the roof. Discharge shall be directed vertically
upward.
If parapet walls are present, EHS recommends that stacks extend at least 2 feet above the top of a
parapet wall or at least 10 feet above the roof, whichever is greater.
Note: The University Architect/Planning Office must be contacted if any building features, such as
exhaust stacks, extend above the roofline.
Hood exhausts shall be located on the roof as far away from air intakes as possible to preclude recirculation of laboratory hood emissions within a building. For toxic gas applications, the separation
distance shall be at least 75 feet from any intake.
As future gas necessities are difficult to predict, EHS recommends at least 75 feet for all applications.
2013
Design Guidelines
16 | P a g e
All building exhaust and air intakes must be modeled to demonstrate that the exhaust air (including
generator exhaust) will not be recirculated within the building being constructed nor in nearby
buildings. Wind tunnel modeling should be used for complex building and terrain interactions.
Discharge from exhaust stacks must have a velocity of at least 3,000 fpm. Achieving this velocity
should not be done by the installation of a cone type reducer. The duct may be reduced, but the duct
beyond the reduction should be of sufficient length to allow the air movement to return to a linear
pattern.
Rain caps that divert the exhaust toward the roof are prohibited.
Fume hood exhaust is not required to be treated (e.g., filtered or scrubbed) except when one of the
following substances is used with content greater than the percent specified by weight or volume:
i.
ii.
iii.
iv.
v.
vi.
vii.
viii.
ix.
x.
xi.
xii.
xiii.
xiv.
xv.
xvi.
xvii.
xviii.
xix.
xx.
xxi.
When used for radioisotope work. In this instance, the fume hood exhaust treatment system must be
approved by the UNC Radiation Safety Officer prior to installation and use.
Air exhausted from laboratory hoods and other special local exhaust systems shall not be recirculated.
Exhaust fans shall be located outside the building housing the laboratory or in a separate room that is
maintained at negative pressure to the rest of the building and provides direct access to outside for fan
discharge ducts.
The minimum penthouse exhaust flow rate is 1 air change per hour.
12. Noise
System design must provide for control of exhaust system noise (combination of fan generated noise
and air-generated noise) in the laboratory. Systems must be designed to achieve an acceptable Sound
Pressure Level (SPL) frequency spectrum (room criterion) as described in the 1991 HVAC
Applications Handbook.
2013
Design Guidelines
17 | P a g e
The preferred method of exhaust noise control is with low static loss air valves and reduced exhaust
fan speeds.
Noise attenuators may be used as a last resort if constructed of 304 stainless steel and no packing
material is used.
13. Testing
Proper operation of fume hoods must be demonstrated by the contractor installing the fume hood prior
to project closeout. The recommended containment performance test is ANSI/ASHRAE 110 with the
acceptable criteria as specified in ANSI/AIHA Z9.5.ANSI/AIHA Z9.5, 5.6
IV.
2. Scope
This Guide presents the minimum performance requirements for eyewash and shower equipment or the
emergency treatment of the eyes or body of a person exposed to injurious materials. It covers the
following types of equipment: emergency showers, eyewash equipment, and combination shower and
eyewash or eye/face wash.
Plumbed eyewash shall be provided for all work areas where, during normal operations or foreseeable
emergencies, the eyes of an employee may come into contact with a substance, which can cause
corrosion, severe irritation, or is toxic by skin absorption. Drench hoses, sink faucets, or showers are
not acceptable eyewash facilities. Plumbed eyewash shall be provided at all work areas where
formaldehyde solutions in concentrations greater than or equal to 0.1% are handled.
NFPA 99 Chapter 10-6
An eyewash safety station should be installed within all acid washing areas. An eyewash safety station
should be installed in N2 dispensing stations and film processing areas using chemical developers and
fixers.
An emergency shower shall be provided for all work areas where, during normal operations or
foreseeable emergencies, areas of the body may come into contact with a substance which is corrosive,
severely irritating to the skin or is toxic by skin absorption.
A deluge shower shall be provided at all work areas where formaldehyde solutions in concentrations
greater than or equal to 1% are handled.
NFPA 99 Chapter 10-6
2013
Design Guidelines
18 | P a g e
A deluge shower should be installed within all acid washing areas. A deluge shower should be
installed in N2 dispensing stations and film processing areas using chemical developers and fixers.
3. General Location
i. Where to Install
Emergency eyewash facilities and deluge showers shall be in unobstructed and accessible
locations that require no more than 10 seconds for the injured person to reach along an
unobstructed pathway (i.e., no doors without panic bars or which don't swing open when pushed).
If both eyewash and shower are needed, they shall be located so that both can be used at the same
time by one person.
ANSI Z358.1, 4.6.1 and 5.4.4
NFPA 99, Chapter 10-6
Electrical apparatus, telephones, thermostats, or power outlets should not be located within 18
inches of either side of the emergency shower or emergency eyewash facility (i.e., a 36-inch
clearance zone).
Prevent potential electrical hazards posed when the water generated by the activated emergency
eyewash/safety shower is in proximity to live electrical equipment.
2013
Design Guidelines
19 | P a g e
4. Eyewash Requirements
i. Flushing Rates
A means shall be provided to ensure that a controlled flow of flushing fluid is provided to both
eyes simultaneously.
ANSI Z358.1, 5.1.1
Eyewash equipment shall be capable of delivering to the eyes not less than 0.4 gallons per minute
of flushing fluid for 15 minutes.
5. Eyewash Positioning
The eyewash unit shall be positioned with the water nozzles 33-45 inches from the floor and 6
inches minimum from the wall or nearest obstruction. The unit must be located at an operable
sink.
ANSI Z358.1, 5.4.1
6. Eyewash Activation
The valve shall be designed so that the flushing fluid remains on without requiring the use of the
operator's hands. The valve shall be designed to remain activated until intentionally shut off.
ANSI Z358.1, 5.2 (a)
ANSI Z358.1, 5.1.5
1.
2013
Design Guidelines
20 | P a g e
The shower head should not be mounted flush or recessed within any constructed surfaces or
partitions and the center of the spray pattern shall be located at least 16 inches from any
obstruction.
ANSI Z358.1, 4.1
Recessing the shower head may limit access and/ or affect spray pattern.
The spray pattern shall have a minimum diameter of 20 inches at 60 inches above the surface
on which the user stands
ANSI Z358.1, 4.1
2.
Flushing Rates
Emergency shower heads shall be capable of delivering a minimum of 75.7 liters per minute
(20 GPM) of flushing fluid.
ANSI Z358.1, 4.1
The shower should be attached to a flushing fluid supply from a 1-inch minimum iron pipe
size (IPS).
Good Practice (based on ANSI manufacturer's test procedures)
9. Equipment Activation
The valve shall be designed so that the flushing fluid remains on without requiring the use of the
operator's hands. The valve shall be designed to remain activated until intentionally shut off.
ANSI Z358.1, 4.2
The manual actuator, triangle pull, shall be located not more than 69 inches above the surface on
which the user stands. The manual actuator shall be free from obstruction for 18 to 24 inches in all
directions. The actuator shall not be mounted flush or recessed within any constructed surfaces or
partitions.
ANSI Z358.1, 4.3
Design Guidelines
21 | P a g e
By testing the equipment, UNC can be assured that it is working properly before the users begin
their research.
12. Approved Equipment
All emergency showers and eyewash facilities shall meet the requirements of NFPA 99 Chapter
10, and ANSI Z358.1 and shall be installed in accordance with ANSI Z358.1.
NFPA 99, Chapter 10
ANSI Z358.1
V.
2.
Scope
The Guide applies to all UNC-Chapel Hill facilities, including leased properties. It covers the design of
storage for compressed gas cylinders. Note that there are numerous regulations governing the proper
use of compressed gas cylinders; use is not addressed by the Guide, as it is a work practices issue,
rather than design feature.
3.
Design features which are prohibited: Unventilated enclosures such as lockers and cupboards.
Work practice issues: Oxygen cylinders shall not be stored near highly combustible materials,
especially oil or grease, or near any other substance likely to cause or accelerate fire
a)
Restraint Systems
Laboratory design shall include restraints for the storage of cylinders greater than 26 inches tall; the
restraint system shall include at least 2 restraints (made of noncombustible materials), which are
located at one-third and two-thirds the height of the cylinder.
NFPA 45, 8-1.5
NFPA 99, 4-3.1.1.2.3
2013
Design Guidelines
22 | P a g e
A restraint system of chains, metal straps, or storage racks provides a reliable method of securing gas
cylinders. Chains or a metal strap at the bottom and top one third of each cylinder provides protection
against tipping and falling. [Work Practice Note: When compressed gas cylinders in service, they shall
be adequately secured by chains, metal straps, or other approved materials, to prevent cylinders from
falling or being knocked over.]
The purchase and installation of compressed gas cylinder securing systems must be subject to review
and approval of EHS.
Gas cylinder securing systems should be anchored to a permanent building member or fixture.
Provisions shall be made for securing cylinders that are delivered to locations outside of the laboratory.
4.
a)
Storage Systems
Laboratory design shall include one of the following storage systems for toxic and highly toxic
compressed gas cylinders:
i. ventilated gas cabinets/exhausted enclosures/ laboratory fume hoods; or
ii. separate ventilated gas storage rooms without other occupancy or use, which has explosion
control.
When gas cabinets or exhausted enclosures are provided they shall (be):
i. located in a room or area which has independent exhaust ventilation;
ii. operate at negative pressure in relation to the surrounding area;
iii. have self-closing limited access parts or noncombustible windows toprovide access to equipment
controls, with an average face velocity of at least 200 fpm and with a minimum of 150 fpm at any
part of the access port or window;
iv. connected to an exhaust system;
v. have self-closing doors and is constructed of at least 0.097 inch (12 gauge) steel;
vi. internally sprinklered;
vii. anchored;
viii. contain not more than 3 cylinders per gas cabinet, except where cylinder contents are 1 pound net
or less, in which case gas cabinets may contain up to 100 cylinders.
2013
Design Guidelines
23 | P a g e
Emergency Power
Emergency power shall be provided for exhaust ventilation, gas-detection systems, emergency alarm
systems, and temperature control systems.
d) Detection System
A continuous gas detection system shall be provided to detect the presence of gas at or below the
permissible exposure limit or ceiling limit. The detection system shall initiate a local alarm and
transmit a signal to a constantly attended location. Activation of the monitoring system shall
automatically close the shut-off valve on toxic and highly toxic gas supply lines to the system being
monitored.
An approved supervised smoke detection system shall be provided in rooms or areas where highly
toxic compressed gases are stored indoors.
e)
Security
Storage areas shall be secured against unauthorized entry.
5.
Other nonflammable (inert) medical gases may be stored in the enclosure. Flammable gases shall not
be stored with oxidizing agents. Storage of full or empty cylinders is permitted. Such enclosures shall
serve no other purpose.
A 1-hour exterior room shall be a room or enclosure separated form the rest of the building by not less
than 1-hour-rated fire-resistive construction. Openings between the room or enclosure and interior
spaces shall be smoke-and draft-control assemblies having no less than a 1-hour fire-protection rating.
Rooms shall have at least one exterior wall provided with at least two vents. Each vent shall not be less
than 36 square inches in area. One vent shall be within 6 inches of the floor and one shall be within 6
inches of the ceiling. Containers of medical gases shall be provided with at least one fire sprinkler to
provide container cooling in case of fire.
2013
Design Guidelines
24 | P a g e
When an exterior wall cannot be provided for the room, automatic sprinklers shall be installed within
the room. The room shall be exhausted through a duct to the exterior. Makeup air to the room shall be
taken from the exterior. Both separate air streams shall be enclosed in a 1-hour-rated shaft enclosure
from the room to the exterior. Approved mechanical ventilation shall be in accordance with the
California Mechanical Code and provided at a minimum rate of 1 cubic foot per minute per square foot
of the room area.
Medical gas system cabinets shall be in accordance with the following:
i. Operated at a negative pressure in relation to surrounding area,
ii. Provided with self-closing, limited-access ports or noncombustible windows to give access to
equipment controls. The average velocity of ventilation at the face of access ports or windows
shall not be less than 200 feet per minute, with a minimum of 150 feet per minute at any point of
the access port or window,
iii. Connected to an exhaust system,
iv. Provided with a self-closing door,
v. Constructed of not less than 0.097-inch (12 gage) steel, and
vi. Internally sprinklered.
VI.
1.
2.
2. Scope
Flammable liquid storage cabinets are intended for the storage of flammable and combustible liquids.
This Guide applies to all UNC-Chapel Hill facilities, including leased properties. It covers the design,
construction, and installation of Flammable Liquid Storage Cabinets; the Guide does not address the
proper use of Flammable Liquid Storage Cabinets.
3. Design
1.
Approval/Submittal
Flammable Liquid Storage Cabinets must be UL listed and must meet NC Fire Prevention
Code requirements.
2.
Cabinet Capability
Where flammable liquid storage cabinets are required, they shall be designed such that they
do not exceed 120 gallons for the combined total quantity of all liquids (i.e., Classes 1, 2, and
3).
NFPA 30, Chapter 4-3.1
NFPA 30 Chapter 4-3.1 still contains the limit (Check most recent NC Fire Protection Code)
2013
Design Guidelines
25 | P a g e
One or more Flammable Liquid Storage Cabinets are required for laboratories which store,
use, or handle more than 10 gallons of flammable or combustible liquids.
3.
Labeling
Flammable Liquid Storage Cabinets shall be conspicuously labeled in red letters on
contrasting background "FLAMMABLE - KEEP FIRE AWAY."
NFPA 30, Chapter 4-3.5
When flammable or combustible liquids present multiple hazards, the laboratory design shall
address the storage requirements for each hazard.
For example, acetic acid is a corrosive and flammable material.
Therefore, if stored in a flammable cabinet with other flammable materials, it must be
segregated through the use of separate barriers (e.g., secondary containment). Incompatible
material shall not be stored within the same cabinet.
4. Construction
1.
2.
Doors
Cabinet doors shall be self-closing and self-latching.
3.
Venting (NFPA 30, Chapter 4-3.4 and NFPA 99, Chapter 10-7.2.3)
Flammable Liquid Storage Cabinets are not required to be vented except for odor control of
malodorous materials. Vent openings shall be sealed with the bungs supplied with the cabinet
or with bungs specified by the manufacturer of the cabinet. If vented, cabinet should be
vented from the bottom with make-up air supplied to the top. It shall be vented outdoors to an
approved location or through a flame arrester to a fume hood exhaust system. Construction of
the venting duct should be equal to the rating of the cabinet.
4.
2013
Location
Design Guidelines
26 | P a g e
Flammable Liquid Storage Cabinets shall NOT be located near exit doorways, stairways, or in
a location that would impede egress. Flammable Liquid Storage Cabinets must NOT be wall
mounted.Wall mounted cabinets are not UL Listed or Fire Marshal Approved.
5.
6.
7.
VII.
Laboratory design must ensure that Flammable Liquid Storage Cabinets are NOT located near
an open flame or other ignition source.
Good Practice per UNC-Chapel Hill EHS
An open flame or other ignition source could start a fire or cause an explosion if an accident
or natural disaster brought the ignition source and flammable liquids or vapors together.
Highly toxic flammable or toxic flammable gases when not stored in gas cabinets, exhausted
enclosures or gas rooms.
Combustible dusts.
Class 4 oxidizers.
Unclassified detonable and Class 1 organic peroxides.
Pyrophoric gases.
Class 3 and 4 unstable (reactive) materials.
Class 2 and 3 water-reactive solids and liquids.
When the hazardous materials stored in a control area are not in excess of the amounts specified in
the International Building and Fire codes, such storage shall conform to the Building Code
requirements for Group B Occupancy. (See Building and Fire Codes)
When the hazardous materials stored in a control area exceed the amounts specified such storage
shall conform to the Building Code requirements for Group H, Occupancy.
2013
Design Guidelines
27 | P a g e
When the hazardous materials stored in laboratories and similar areas used for scientific
experimentation or research are not in excess of the table below and are not otherwise classified as
Group B Occupancies, shall conform to the Building Code requirements for Group H.
4. Procedures
Permitting and reporting procedures
1.
2.
3.
4.
2013
Design Guidelines
28 | P a g e
VIII.
Regulations:
a.
b.
c.
d.
2.
University Policies:
Policies of the Administrative Panel on Radiological Safety
3.
Recommendations:
NC Radiation Protection Section
"Safe Handling of Radioactive Materials," National Council on Radiation Protection (NBS
Handbook 92)
"Safe Handling of Radionuclides," International Atomic Energy Agency (IAEA), Safety
Series No. 1, (1973 ed. is still current as of 1999)
"Structural Shielding and Evaluation for Medical Use of X-rays and Gamma Rays of Energies
up to 10 MeV", National Council on Radiation Protection, Report No. 49
Structural Shielding Design for Medical X-ray Imaging Facilities, NCRP, Report No. 147
"Radiation Protection Design Guidelines for0.1-100MeV Particle Accelerators," National
Council on Radiation Protection, Report No. 51, (NCRP51)
Guide for the Preparation of Application for Medical Use Programs, (Proposed Revision2 to
Regulatory Guide 10.8, USNRC (NRC 10.8)
Guide for the Preparation of Applications for Type A Licenses of Broad Scope, 2nd Proposed
Revision 2 to Regulatory Guide 10.5, Revision 2, USNRC (NRC10.5)
"CRC Handbook of Laboratory Safety, 4th Ed." CRC Press 1995, (CRCLAB)
"Recommendations for the Safe Use Of LASERS," American National Standards Institute.
(ANSI Z136.1)
2013
Design Guidelines
29 | P a g e
2. Scope
All radioactive materials used at UNC-Chapel Hill are governed by the terms and conditions of the
UNC-Chapel Hill Radioactive Materials Licenses, issued by the Department of Environment and
Natural Resources, Division of Environmental Health, Radiation Protection Section. All radiation
producing devices are registered with the State of NC, Radiation Protection Section, Electronic
Products Branch.
3. Decommissioning of Existing Facilities Prior to Demolition or Renovation
Contact the Radiation Safety Section of EHS as early as possible (at least 120 days) before the
planned initiation of construction. A plan for decommissioning must be prepared following the
UNC EHS Guidelines for decommissioning. The laboratory must be cleared of all radioactive
sources/contamination before demolition, renovation or construction can begin.
4. Design Features for Radiological Labs
1.
Approval Process
Proposals for new facilities must be submitted to the Radiation Safety Section of EHS for
review. New facilities may require the multiple approvals prior to construction.
NC Radioactive Material License
UNC-Chapel Hill Radiation Safety Manual
2.
Architectural Considerations
Benches in laboratories must be capable of supporting weight of necessary shielding (e.g.
lead).
NBS Handbook 92
IAEA, Safe Handling of Radionuclides
When work involves gamma emitters (especially gamma irradiators) the floors and coatings
must be able to support the gamma shielding.
NBS Handbook 92
IAEA, Safe Handling of Radionuclides
When applicable, lead shielding must be incorporated in the structure. Based on the proposed
type and quantities of radioactive materials, the Radiation Safety Section of EHS will
determine the need for the shielding.
Note that for x-ray producing machines, shielding calculations will be performed by the
Radiation Safety Section of EHS. Shielding design is to be in accordance with all applicable
State Regulations and NCRP and ANSI standards. Designs must be submitted to the State
through the Radiation Safety Section of EHS. During construction the shielding must be
completed, the effectiveness of the installed shielding and protective design features shall be
2013
Design Guidelines
30 | P a g e
evaluated by the Radiation Safety Section of EHS and required reports submitted to and
accepted by the State prior to operation of the radiation producing machine.
NC Radiation Control Regulations
National Council on Radiation Protection, Report No. 49, 147
NC Radioactive Material License
3.
Security
Areas where radioactive materials or other radiation sources are used or stored shall be
provided with adequate security (e.g., locks) to prevent removal or use by unauthorized
personnel.
NC Radiation Control Regulations
UNC-Chapel Hill Radiation Safety Manual
High radiation areas or very high radiation areas (as defined in 15 A NCAC 11.0104) shall be
equipped with means to prevent inadvertent access and restrict access to only authorized
personnel. Means to reduce exposure levels in the area may be required via an interlock
device. In some applications, means to monitor the radiation levels in the areas shall be
provided.
NC Radiation Control Regulations
High radiation areas or very high radiation areas (as defined in 15 A NCAC 11.0104) shall be
equipped with a control device that energizes a conspicuous visible or audible signal so that
an individual entering the area and the operator of the device are made aware of the entry.
NC Radiation Control Regulations
4.
Waste Storage
Adequate space must be available for radioactive wastes generated by projects within the lab.
Most radioisotope projects will need about 15 sq. ft. of floor space for containers and shields
within a lockable area.
UNC-Chapel Hill Radiation Safety Manual
5. Ventilation Considerations
Ventilation requirements for the laboratories utilizing radioactive materials are dependent
upon the types of materials used. Facilities that use radioactive gases shall be equipped with
ventilation to adequately maintain concentrations to below allowable occupational exposure
levels and to not permit escape of the gas to adjacent non-use areas such that concentrations
exceed those allowed for uncontrolled areas. These range from no special requirements to
those requiring separate exhaust systems equipped with "panic button" shut down switches.
The Radiation Safety Program will review the proposed uses and make specific
recommendations appropriate for each facility.
10 CFR 20: Appendix B
2013
Design Guidelines
31 | P a g e
Depending on the type and quantities of radioactive materials or the location of the facility,
fume hoods used with volatile radioactive materials have specific design requirements. These
are detailed in the Fume Hoods Section of this Design Guide.
5. Laser Radiation Items
Class IIIb and IV Laser facilities must be equipped with adequate shielding (e.g. thermal curtains
using materials approved by the University's Fire Marshal, window glass that does not transmit
direct laser radiation or the specula or diffuse reflections of the laser radiation (shutters or filters)).
Portals and viewing windows must be designed to prevent any exposure above the permissible
threshold limit value.
ANSI Z136.1
CRC Handbook of Laboratory Safety, 4th Ed.
Class IIIb and Class IV laser facilities must be in rooms secured by locks. Class IV laser
installations must be provided with interlocked warnings that indicate the status of the laser prior
to entering the facility.
ANSI Z136.1
Electrical outlets need to be positioned is such a manner that leakage of water coolant will not lead
to risks of electrocution.
ANSI Z136.1
Gas cabinets and adequate ventilation must be provided to mitigate the hazards associated with
excimer laser gases or other lasers using toxic gases.
ANSI Z136.1
IX.
2013
Design Guidelines
32 | P a g e
The Centers for Disease Control and Prevention (CDC) and the National Institutes of Health
(NIH).
Primary Containment for Biohazards: Selection, Installation and Use of Biological Safety
Cabinets the Centers for Disease Control and Prevention (CDC) and the National Institutes of
Health (NIH).
Guidelines for Research Involving Recombinant DNA Molecules, October 31, 1997, Federal
Register, Vol. 62, No 211.
National Sanitation Foundation (NSF) International Standard 49
2. Scope
All of the biological research conducted at UNC-Chapel Hill involves low to moderate risk
etiological agents as defined by the NIH. Section 1 of this Guide, General Requirements for UNC
Laboratories, covers all design requirements for Biosafety Level 1 laboratory work areas. This
section focuses primarily on the biosafety considerations for a Biosafety Level 2 laboratory. Please
see Biosafety Level 3 guidelines for BSL3 laboratories.
3. Ventilation Considerations for Biosafety Level 2 Laboratories
Air pressure in laboratories and animal care rooms should be negative in relation to the corridor or
adjacent non-laboratory areas.
Potentially harmful aerosols can escape from the containment of the laboratory room unless the
room air pressure is negative to adjacent non-laboratory areas. As a general rule, air should flow
from low hazard to high hazard areas.
Tissue culture rooms should be negative with respect to adjoining areas.
An autoclave should be provided with a canopy hood with slotted exhaust or other suitable means
of local exhaust. In addition, autoclave rooms should have a minimum of 10 air changes per hour.
Unpleasant heat and odors will linger in the room unless provided with effective local exhaust and
adequate frequency of air changes.
4. Biological Safety Cabinets and Other Containment Considerations
1.
Approval/Type
All cabinets must be NSF listed, UL approved, and installed in accordance with the
manufacturer's requirements.
Cabinets, which when used and installed properly, will provide both product, environment
and personnel protection.
For Biosafety Level 2 applications involving toxic chemicals or radionuclides, a Class II- B
type cabinet must be installed.
2013
Design Guidelines
33 | P a g e
Class II-B cabinets do not recirculate exhaust air and are appropriate for such uses. The exact
type of BSC should be specified early in the design process.
2.
Location
Biological safety cabinets (BSCs) must be located away from doors and other high traffic
areas.
Currents of air can disrupt and degrade the protective capability of the cabinet. All attempts
should be made to neutralize any interference.
A biosafety cabinet should not be installed directly opposite of another biosafety cabinet if
spatial considerations allow otherwise.
Laminar airflow is greatly hindered by the operation of a biosafety cabinet located directly
opposite of another biosafety cabinet or autoclave.
3.
Natural Gas
Open flames are not to be used in Biosafety Cabinets.
4.
Restraints
When initially installed or reinstalled, biosafety cabinets must be provided with an appropriate
means of seismic stabilization.
5.
Testing
Biological safety cabinets are to be certified as part of the building contract.
Remote HEPA Filtration Units in ductwork Remote HEPA filters must have provisions for
testing and decontamination, with test ports before and after the HEPA, isolation dampers,
and decontamination ports according to the drawing.
6.
Autoclaves
Laboratory designs must include an autoclave for sterilizing media, lab instruments, and
medical waste as necessary.
2013
Design Guidelines
34 | P a g e
An autoclave is required since heat and pressure can kill potentially infectious spores that
resist other disinfectants. The autoclave need not be in the actual lab room, however should be
available on the floor.
X.
GLOSSARY
Biohazardous Materials: Infectious agents, the products of infectious agents, or the components of infectious
agents presenting a risk of injury or illness.
Biosafety Level: Biosafety levels consist of laboratory practices and techniques, safety equipment, and a laboratory
facility appropriate for the operations performed and the hazard posed by the particular biohazard material. The
Centers for Disease Control (CDC) and the National Institute of Health (NIH) define the four biosafety levels in the
publication, Biosafety in Microbiological and Biomedical Laboratories.
Biosafety Cabinet: A ventilated cabinet which serves as a primary containment device for operations involving
biohazard materials. The three classes of biosafety cabinets are described below:
Class I Biosafety Cabinet: The Class I biosafety cabinet is an openfronted negatively pressured ventilated
cabinet with a minimum inward average face velocity at the work opening of at least 75 feet per minute.
The exhaust air from the cabinet is filtered by a HEPA filter and discharged without recirculation
Class II Biosafety Cabinet: The Class II biosafety cabinet is an open-fronted, ventilated cabinet. Exhaust
air is filtered with a high efficiency particulate air filter (HEPA). This cabinet provides HEPA-filtered
downward airflow within the workspace. Class II Cabinets are further classified as type A1, A2, B1, and
B2.
Class III Biosafety Cabinet: The Class III biosafety cabinet is a totally enclosed, negative pressure,
ventilated cabinet of gas-tight construction. Operations within the Class III cabinet are conducted through
protective gloves. Supply air is drawn into the cabinet through high-efficiency particulate air filters.
Exhaust air is filtered by two high efficiency particulate air filters placed in series or by high efficiency
particulate air filtration and incineration, and discharged to the outdoor environment without recirculation.
Boiling Point: The temperature at which the vapor pressure of a liquid equals the surrounding atmospheric
pressure. For purposes of defining the boiling point, atmospheric pressure shall be considered to be 14.7 PSIA (760
mm Hg).
2013
Design Guidelines
35 | P a g e
It has been evaluated by the International Agency for Research on Cancer (IARC) Monographs and
found to be a carcinogen or potential carcinogen; or
It is listed as a carcinogen or potential carcinogen in the Sixth Annual Report on Carcinogens
published by the National Toxicology Program (NTP) or,
It is regulated by Fed/OSHA as a carcinogen
Combustible Liquid: A combustible liquid shall be defined as any liquid that has a closed-cup flash point at or
above 100F (37.8C).
Class II Liquid. Any liquid that has a flash point at or above 100F (37.8C) and below 140F (60C).
Class IIIA Liquid. Any liquid that has a flash point at or above 140F (60C) but below 200F (93C).
Class IIIB Liquid. Any liquid that has a flash point at or above 200F (93C).
Compressed Gas:
2013
Class IA liquids shall include those liquids that have flash points below 73F (22.8C) and boiling
points below 100F (37.8C).
Design Guidelines
36 | P a g e
Class IB liquids shall include those liquids that have flash points below 73F (22.8C) and boiling
points at or above 100F (37.8C).
Class IC liquids shall include those liquids that have flash points at or above 73F (22.8C), but
below 100F (37.8C).
Flash Point: The minimum temperature of a liquid at which sufficient vapor is given off to form an ignitable
mixture with air, near the surface of the liquid or within the vessel used.
Fume Hood: A device enclosed on three sides, as well as the top and bottom, with an adjustable sash or fixed partial
enclosure on the remaining side. They are designed, constructed and maintained so as to draw air inward by means
of mechanical ventilation, and so that any operation involving hazardous materials within the enclosure does not
require the insertion of any portion of a person's body other than the hands and arms into the work area. (Note:
Laboratory fume hoods prevent toxic, flammable, or noxious vapors from entering the laboratory, present a physical
barrier from chemical reactions, and serve to contain accidental spills.)
Hazardous Material: A material for which there is statistically significant evidence based on at least one study
conducted in accordance with established scientific principles that acute or chronic health effects may occur in
exposed employees. The term health hazard includes materials which are carcinogens, toxic or highly toxic
agents, reproductive toxins, irritants, corrosives, sensitizers, hepatoxins, nephrotoxins, neurotoxins, agents that act
on the hematopoietic systems, and agents which damage the lungs, skin, eyes, or mucous membranes. The term
physical hazardincludes materials for which there is scientifically valid evidence that it is a combustible liquid, a
compressed gas, cryogenic, explosive, flammable, an organic peroxide, an oxidizer, pyrophoric, unstable (reactive),
or water-reactive.
Hazard Warning: Any words, pictures, symbols, or combination thereof appearing on a label or other appropriate
form of warning that convey the health and physical hazards of the substance(s) present.
Highly Toxic: A substance is considered to be highly toxic if:
A substance that has a median lethal dose (LD50) of 50 milligrams or less per kilogram of body weight
when administered orally to albino rats weighing between 200 and 300 grams each.
A substance that has a median lethal dose (LD50) of 200 milligrams or less per kilogram of body
weight when administered by continuous contact for 24 hours (or less if death occurs within 24 hours)
with the bare skin of albino rabbits weighing between 2 and 3 kilograms each.
A substance that has a median lethal dose (LD50) in air of 200 parts per million by volume or less of
gas or vapor, or 2 milligrams per liter or less of mist, fume, or dust, when administered by continuous
inhalation for 1 hour (or less if death occurs within 1 hour) to albino rats weighing between 200 and
300 grams each.
HIV/HBV Research/Production Facility: A laboratory producing or using research laboratory scale amounts of
HIV or HBV. Research laboratories may produce high concentrations of HIV or HBV but not in the volume found
in production facilities.
Irritant: A substance, which is not corrosive, but which causes a reversible inflammatory effect on living tissue by
chemical action at the site of contact. A substance is a skin irritant if, when tested on the intact skin of albino rabbits
by the methods of 16 CFR 1500.41 for 24 hours exposure or by other appropriate techniques, it results in an
empirical score of 5 or more. Substance is an eye irritant if so determined under the procedure listed in 16 CFR
1500.42 or other appropriate techniques.
NIH: National Institute of Health
Nonflammable Medical Gas: A compressed gas, such as oxygen or nitrous oxide, which is nonflammable and used
for therapeutic purposes.
2013
Design Guidelines
37 | P a g e
Organic Peroxide: An organic compound that contains the bivalent -O-O- structure and which may be considered to
be a structural derivative of hydrogen peroxide where one or both of the hydrogen atoms has been replaced by an
organic radical.
Oxidizer: A substance, other than a blasting agent or explosive, that initiates or promotes combustion in other
materials, thereby causing fire either of itself or through the release of oxygen or other gases.
Pyrophoric: A substance that will ignite spontaneously in air at a temperature of 1300 F (54.40 C) or below.
Risk Levels:
LOW RISK: Risk level of agents and/or operations having minimal effect on personnel, other animal
or plants under ordinary use. This classification is restricted to all etiologic agents designated as
Biosafety Level 1 by the CDC.
MODERATE RISK: Risk level of agents/or operations requiring special conditions for control or
containment because of (a) known pathogenicity to personnel, other animals or plants; (b)
concentration; or (c) genetic alteration (synergistic effect) with other materials. This classification
includes all etiologic agents designated as Class 2 or 3 by the CDC (Biosafety level 2 or 3) and
oncogenic viruses specified as moderate risk by the National Cancer Institute (NCI).
HIGH RISK: Risk level of agents and/or operations requiring additional control measures beyond
those for moderate risk. This classification includes all etiologic agents designated Class 4 by the CDC
and oncogenic viruses classified as high risk by the NCI.
Sensitizer: A substance that causes a substantial proportion of exposed people or animals to develop an allergic
reaction in normal tissue after repeated exposure to the substance.
Toxic: A substance is considered to be toxic if:
A substance that has a median lethal dose (LD50) of more than 50 milligrams per kilogram but not
more than 500 milligrams per kilogram of body weight when administered orally to albino rats
weighing between 200 and 300 grams each.
A substance that has a median lethal dose (LD50) of more than 200 milligrams per kilogram but not
more than 1000 milligrams per kilogram of body weight when administered by continuous contact for
24 hours (or less if death occurs within 24 hours) with the bare skin of albino rabbits weighing between
two and three kilograms each.
A substance that has a median lethal dose (LD50) in air of more than 200 parts per million but not
more than 2000 parts per million by volume of gas or vapor, or more than 2 milligrams per liter but not
more than 20 milligrams per liter of mist, fume, or dust, when administered by continuous inhalation
for one hour (or less if death occurs within one hour) to albino rats weighing between 200 and 300
grams each.
Unstable (reactive): A substance which in the pure state, or as produced or transported, will vigorously polymerize,
decompose, condense, or will become self-reactive under conditions or shocks, pressure or temperature.
Vapor Pressure: The pressure, measured in PSIA, exerted by a liquid.
Water-reactive: A substance that reacts with water to release a gas that is either flammable or presents a health
hazard.
(END OF SECTION)
2013
Design Guidelines
38 | P a g e