GRC Screen Lower

This document provides calculations for a panel located at an opening in the Dubai Mall Fashion Avenue Extension project. It details the given data, calculations for wind load, bending stress, shear stress, and deflection to check if the panel design meets allowable limits.

Uploaded by

Kilaru Hareesh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
69 views4 pages

GRC Screen Lower

This document provides calculations for a panel located at an opening in the Dubai Mall Fashion Avenue Extension project. It details the given data, calculations for wind load, bending stress, shear stress, and deflection to check if the panel design meets allowable limits.

Uploaded by

Kilaru Hareesh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

PROJECT: DUBAI MALL FASHION AVENUE EXTENSION

LOCATION: DUBAI, UAE


SUBJECT:
GRC SCREEN LOUVER
The following calculation is for the panel at the location of the opening (of size 1300x1635).
This is an integral part of the overall panel.
FIG. 1

1300
a

1635
FIG. 2 section aa

FIG. 3

II

GIVEN DATA
GRC UNIT WEIGHT =
MODULUS OF ELASTICITY (E) =
FOR THE SCREEN
GRC THICKNESS =
LENGTH (Span)=
Wp =
WIND PRESSURE =
TRIBUTARY AREA = 1300x 1635=
LESS AREA OF OPENINGS =
NET EFFECTIVE AREA Ag =
NET AREA FACTOR

2000 kg/m
6895 MPa
35 mm
1635 mm
3.16
2,125,500.00
2.1255
1223675.77
1.224
0.902
0.902/2.1255

kPa
mm
m
mm
m
m

(Suction)

0.424

FOR THE SECTION OF THE SCREEN

N. Axis
c = 18.33

35

35

see at section bb

COMPUTE THE M.I. (I) OF SECTION

Fw

Width of the panel


= 1300 mm
Effective width after reduction of the openings
= 846 mm
Effective moment of Inertia
3
= 846 x 35
12
=

4
3,022,688 mm

Wp =

-3.16 kPa

(Suction)

Effective wind pressure

= Wp x Net area factor


= 3.16 x 0.424
= 1.340 kPa

Wind load per unit length

= 1.340 x 1.3
= 1.742
kN/m

The panel is part of the overall panel and consequently, partial fixity condition at the edges are assumed.

1635
V = w L/2

1424.09 N

118,000 Nmm

M = wL
10

M = wL
10
465,676 Nmm

BENDING
1.742 x 1.6352
10
= 0.466 kNm
= 465,676 Nmm
CHECK FOR BENDING STRESS AND SHEAR STRESS
max M =

fb =

fb =

Mc
I
465,676 x 18.33
3,022,688
2.82 N/mm

ALLOWABLE BENDING STRESS OR FLEXURAL =

900 Psi (minimum)


6.2 N/mm

fb IS LESS THAN ALLOWABLE, HENCE OK


SHEAR :
fv =

V
A

fv = 1424.09
6825
fv =
0.209 N/mm

A = (35 x 35)x2 + (25 x 35) x 5


6825 mm
OK

FOR ALLOWABLE SHEAR STRESS=

400 Psi
2.758 N/mm

fv IS LESS THAN ALLOWABLE, HENCE OK


DEFLECTION
Max. Deflection

Allowable Deflection

=
=
=

wl4
384 EI
1.56 mm
span/200
8.175 mm

Maximum deflection is less than allowable. HENCE OK