ECG Engineering Consultants Group

PROJECT NAME: Nozha City Center

DATE: MAY-2007

PROJECT NO.: 1127

COMPUTED BY: A .Salah

SMOKE MANAGEMENT DESIGN CALCULATION SHEET


Area Served:

Retails

Ventilation Type:

Mechanical Ventilation Fans

Brief description:

Exhaust through high temperature rated fans.

Design Parameters
Heat Production (Q)

= 1000 kw

M = 0.071 Q1/3 X Z 5/3 + 0.0018 Q

NFPA part 92B Chapter 6

Where
M = Total fuel mass consumed
Z = Height above the fuel

M = 0.071 X ( 1000)

1/3

X ( 2.5 )

5/3

+ 0.0018 X 1000

M = 5.06 kg/sec
V=m/p
Where
P = 1.2 kg /m3 @20 CO

V = 9000 cfm
Note:
4 Nos. Smoke exhaust fans of 9000 cfm shall be provided on the Roof inter locked with fire system
The Exhaust fans shall be Rated for 300 Deg.c for 1 hr.