NOTES :
1. Cable sizes, route length and number of runs have been considered based on available detail provided in Technical Specification.
2. Make, type and specification of cables shall be as per TS ( Cl. No. 4.12.1)
1
Rev. No.
01.08.13
Revised for re-submission to MECON for Approval
Date
Description
Category of Drawing
Approval
Information
Reference
Record
SAIL - ROURKELA STEEL PLANT, ROURKELA
HT/ LT SUB STATION FOR LIME PLANT, CED, PROPANE PLANT WITH
INTERPLANT CABLING & MISC. ELECTRICAL WORKS
4.2 MTPA EXPANSION, PACKAGE No. - 73A
CONSULTANT:
MECON LIMITED
STERLING & WILSON LTD., KOLKATA
CONTRACTOR:
Designed
Name
Date
Name
Date
RNB
15.02.13
INTER PLANT HT ( 33 KV & 6.6 KV)
CABLE SCHEDULE
Scale :
Drawn
Checked
RNB
15.02.13
Project's Drg. No.
Approved
ABC
15.02.13
SAIL-RSP Drg. No.
NTS
RSP-ROURKELA/S&WL/20/29/DE/242
RNB
RNB
ABC
By
Chekd
Appvd
Construction
& 6.6 KV)
LE
Sheet
Rev.
1 of 4
STERLING & WILSON LTD., KOLKATA
ECC Division - EDRC
Sl. No.
PROJECT
HT/ LT SUB STATION FOR LIME PLANT, CED, PROPANE PLANT WITH INTERPLANT CABLING & MISC. ELECTRICAL WORKS, PA
No. - 073A
TITLE
HT (33kV & 6.6kV CABLE SCHEDULE
Cable No
From
Panel No.
To
A
1
2
33 KV
73A-00-02-H1-001
73A-02-01-H1-002
MSDS-3 (O/D)
CPP-1 (AIS - I/D)
CPP-3 (GIS)
CPP-3 (GIS)
B
1
LBDS-13
73A-06-03-H2-001A
LBSS-1
73A-06-03-H2-002A
LBSS-1
73A-06-03-H2-003/1
73A-06-03-H2-003
LBSS-1
HT Isolator-1
73A-06-03-H2-003
LBSS-1
73A-03-03-H2-004/1
73A-03-03-H2-004
LBSS-1
HT Isolator-2
73A-03-03-H2-004
LBDS-13 HT Sw. Board
5
6
7
73A-03-03-H2-005A
73A-03-03-H2-006A
73A-03-03-H2-007
LBDS-13 HT Sw. Board
LBDS-13 HT Sw. Board
LBDS-13 HT Sw. Board
73A-03-03-H2-008
LBDS-13 HT Sw. Board
73A-03-03-H2-009
73A-03-03-H2-010
LBDS-13 HT Sw. Board
LBDS-13 HT Sw. Board
LBDS-13 HT Sw. Board, Incoming
Feeder-1
LBDS-13 HT Sw. Board, Incoming
Feeder-2
HT Isolator-1
630 KVA Trafo-1 at
LBDS-13
630 KVA Trafo-1 at
LBDS-13
HT Isolator-2
630 KVA Trafo-2 at
LBDS-13
630 KVA Trafo-2 at
LBDS-13
Existing NCP, Fdr.-1
Existing NCP, Fdr.-2
Existing Marshalling
Yard S/S, Fdr.-1
Existing Marshalling
Yard S/S, Fdr.-2
1MVAr Capacitor bank-1
1MVAr Capacitor bank-2
LTSS- 01A
Panel
No
Connected Load
1
2
3
4
73A-07-04-H2-001
73A-07-04-H2-001/1
73A-07-04-H2-002
73A-07-04-H2-002/1
LBSS-2
HT Isolator-1
LBSS-2
HT Isolator-2
HT Isolator-1
LTSS-01A, 1600 KVA Trafo-1
HT Isolator-2
LTSS-01A, 1600 KVA Trafo-2
D
1
LBDS-15
73A-08-05-H2-001
Existing NSP - S/S
LBDS-15 HT Sw. Board, Incoming
Feeder-1
73A-08-05-H2-002
Existing BP- II, HT S/S
73A-08-05-H2-003
LBDS-15 HT Sw. Board
73A-08-05-H2-004
LBDS-15 HT Sw. Board
5
6
73A-08-05-H2-005
73A-08-05-H2-006
LBDS-15 HT Sw. Board
LBDS-15 HT Sw. Board
LBDS-15 HT Sw. Board, Incoming
Feeder-2
1600 KVA Trafo-1 at LBDS-15 ( Open
Bus- Bar)
1600 KVA Trafo-2 at LBDS-15 (Open
Bus- Bar)
HRLS
CPTI
Note: Buried 33 kV cable shall have water swellable tape.
Voltage & No of Core
Size
6.6 kV , 3 Core,AL
33 kV , 3 Core,CU
240
400
Length
(Km)
31.098
5.1
Term
(Nos)
66
6
RICAL WORKS, PACKAGE
DOCUMENT NO
RSP-ROURKELA/S&WL/20/29/DE/242
PREPARED
RNB
Voltage
(kV)
CABLE DETAILS
Material
Runs
Core
Area
Sq.mm
Insul.
DATE
9/23/2015
CHECKED
SHEET
RNB
1 of 1
Route
Length
(km)
Total Length(km)
Termn
Joints
Drum length
(m)
33
33
CU
CU
1
2
3
3
400
400
XLPE
XLPE
0.9
2.1
0.9
4.2
2
4
1
8
500
500
6.6
AL
240
XLPE
2.1
8.4
16
1000
6.6
AL
240
XLPE
2.1
8.4
16
1000
6.6
6.6
AL
AL
1
1
3
3
240
240
XLPE
XLPE
0.04
0.004
0.04
0.004
2
2
0
0
1000
1000
6.6
AL
240
XLPE
2.1
2.1
1000
6.6
6.6
AL
AL
1
1
3
3
240
240
XLPE
XLPE
2.1
0.004
2.1
0.004
2
2
4
0
1000
1000
6.6
AL
240
XLPE
0.04
0.04
1000
6.6
6.6
6.6
AL
AL
AL
2
2
1
3
3
3
250
250
600
XLPE
XLPE
XLPE
0.6
0.6
0.25
1.2
1.2
0.25
4
4
2
2
2
0
1000
1000
1000
6.6
AL
600
XLPE
0.25
0.25
1000
6.6
6.6
AL
AL
1
1
3
3
240
240
XLPE
XLPE
0.04
0.04
0.04
0.04
2
2
0
0
1000
1000
6.6
6.6
6.6
6.6
AL
AL
AL
AL
1
1
1
1
3
3
3
3
240
240
240
240
XLPE
XLPE
XLPE
XLPE
0.1
0.08
0.1
0.1
0.1
0.08
0.1
0.1
2
2
2
2
0
0
0
0
1000
1000
1000
1000
6.6
AL
240
XLPE
1.25
2.5
1000
6.6
AL
240
XLPE
1.4
1.4
1000
6.6
AL
240
XLPE
0.05
0.05
1000
6.6
AL
240
XLPE
1.4
1.4
1000
6.6
6.6
AL
AL
1
1
3
3
240
240
XLPE
XLPE
0.2
1.1
0.2
1.1
2
2
0
2
1000
1000
Joints
(Nos)
54
9
REMARKS
Along Trays in Existing Cable Tunne
/Along
CableTrays
Bridge.
in Existing Cable Tunne
/ Cable Bridge, Buried U/G.
Existing Cable Tunne / Cable Bridge, Buried U/G, On
trays within SS (S2, A4)
Existing Cable Tunne / Cable Bridge, Buried U/G, On
trays within SS (Y1, A4)
Y2, A7, D3, F3
A7, D3
A4 / A5, K2 /K3, Buried U/G
A4 / A5, K2 /K3, Buried U/G
A4 / A5, K2 /K3, Buried U/G
A4 / A5, K2 /K3, Buried U/G
Buried U/G, Pipes
On trays
Buried U/G, Pipes
On trays
Buried U/G, Existing Cable Tunne, Buried U/G, On trays
within SS (S3,
A4)
Existing Cable Tunne, Buried U/G, On trays within SS
( S3, A4)
A6, D3
A6, D3, F3
A3, S2, Buried U/G
A6, D3, F3, Pipes, Buried U/G
INTER PLANT HT ( 33 KV & 6.6 KV) POWER CABLE SCHEDULE
Sl.
No.
Circuit No.
FROM
(A-End)
TO
(Z-End)
33 KV
73A-00-02-H1-001
MSDS-3 (O/D)
CPP-3 (GIS)
73A-02-01-H1-002A
CPP-1 (AIS - I/D)
CPP-3 (GIS)
73A-02-01-H1-002B
CPP-1 (AIS - I/D)
CPP-3 (GIS)
LBDS-13
73A-06-03-H2-001A
LBSS-1
LBDS-13 HT Sw. Board, Incoming Feeder-1
73A-06-03-H2-001B
LBSS-1
do
73A-06-03-H2-001C
LBSS-1
do
73A-06-03-H2-001D
LBSS-1
do
73A-06-03-H2-002A
LBSS-1
LBDS-13 HT Sw. Board, Incoming Feeder-2
73A-06-03-H2-002B
do
do
73A-06-03-H2-002C
do
do
73A-06-03-H2-002D
do
do
73A-06-03-H2-003
LBSS-1
10
73A-03-03-H2-004
11
73A-03-03-H2-005A
12
73A-03-03-H2-005B
13
73A-03-03-H2-006A
14
73A-03-03-H2-006B
15
73A-03-03-H2-007
16
73A-03-03-H2-008
LBDS-13 HT Sw.
Board
LBDS-13 HT Sw.
Board
LBDS-13 HT Sw.
Board
LBDS-13 HT Sw.
Board
LBDS-13 HT Sw.
Board
LBDS-13 HT Sw.
Board
LBDS-13 HT Sw.
Board
630 KVA Trafo-1 at
LBDS-13
630 KVA Trafo-2 at
LBDS-13
Existing NCP, Fdr.-1
Existing NCP, Fdr.-1
Existing NCP, Fdr.-2
Existing NCP, Fdr.-2
Existing Marshalling
Yard S/S, Fdr.-1
Existing Marshalling
Yard S/S, Fdr.-2
INTER PLANT HT ( 33 KV & 6.6 KV) POWER CABLE SCHEDULE
Sl.
No.
C
Sl.
No.
1
C
3
Circuit No.
FROM
(A-End)
TO
(Z-End)
LTSS- 01A
73A-07-04-H2-001
LBSS-2
HT Isolator-1
73A-07-04-H2-001/1
HT Isolator-1
73A-07-04-H2-002
LBSS-2
LTSS-01A, 1600 KVA
Trafo-1
HT Isolator-2
73A-07-04-H2-002/1
HT Isolator-2
LTSS-01A, 1600 KVA
Trafo-2
D
1
LBDS-15
73A-08-05-H2-001A
Existing NSP - S/S
LBDS-15 HT Sw. Board, Incoming
Feeder-1
73A-08-05-H2-001B
Existing NSP - S/S
LBDS-15 HT Sw. Board, Incoming
Feeder-1
73A-08-05-H2-002
Existing BP- II, HT S/S LBDS-15 HT Sw. Board, Incoming
Feeder-2
73A-08-05-H2-003
LBDS-15 HT Sw.
Board
1600 KVA Trafo-1 at LBDS-15 ( Open Bus- Bar)
73A-08-05-H2-004
LBDS-15 HT Sw.
Board
1600 KVA Trafo-2 at LBDS-15 (Open Bus- Bar)
73A-08-05-H2-005
LBDS - 15
HRLS
73A-08-05-H2-006
LBDS - 15
CPTI
No. Of
Core
3
3
Cond.
Size (Sq mm)
Cable Description
400 33 KV, CU, XLPE,
Armd.
400 33 KV, CU, XLPE, Armd.
400 34 KV, CU, XLPE,
Armd.
240 6.6 KV( UE ), AL, XLPE, ST2, inner and outer sheathed, Armd.
240 do
240 do
240 do
240 do
240 do
240 do
240 do
240 do
240 do
250 do
250 do
250 do
250 do
600 do
600 do
No. Of
Core
Cond.
Size (Sq mm)
Cable Description
240 6.6 KV( UE ), AL, XLPE, ST2, inner and outer
sheathed, Armd.
240 do
240 do
240 do
240
6.6 KV( UE ), AL, XLPE, ST2, inner and outer
sheathed, Armd.
240
do
240
do
240
do
240
do
240 do
240 do
Route
Route Detail
Length, as per TS (M)
900
2100
Along Trays in Existing Cable Tunne
/ Cable Bridge.
Along Trays in Existing Cable Tunne
/ Cable Bridge, Buried U/G.
2100
do
2100
Existing Cable Tunne / Cable Bridge, Buried U/G, On trays within SS (S2, A4)
2100
do
2100
do
2100
do
2100
Existing Cable Tunne / Cable Bridge, Buried U/G, On trays within SS (Y1, A4)
2100
do
2100
do
2100
do
2100
Y2, A7, D3, F3
40
A7, D3
600
A4 / A5, K2 /K3, Buried U/G
600
A4 / A5, K2 /K3, Buried U/G
600
A4 / A5, K2 /K3, Buried U/G
600
A4 / A5, K2 /K3, Buried U/G
250
A4 / A5, K2 /K3, Buried U/G
250
A4 / A5, K2 /K3, Buried U/G
Route
Route Detail
Length, as per TS (M)
100
8
100
Buried U/G, Pipes
On trays
Buried U/G, Pipes
On trays
1250
Buried U/G, Existing Cable Tunne, Buried U/G, On trays within SS (S3,
A4)
1250
do
1400
Existing Cable Tunne, Buried U/G, On trays within SS ( S3, A4)
50
A6, D3
1400
A6, D3, F3
200
A3, S2, Buried U/G
1100
A6, D3, F3, Pipes, Buried U/G
Remarks
Remarks