Design Parameters of Steel SMF Connections - Adan - 08 22 11 PDF
Design Parameters of Steel SMF Connections - Adan - 08 22 11 PDF
Design Parameters of Steel SMF Connections - Adan - 08 22 11 PDF
where:
Ru =
(4)
where:
db = beam depth,
in.
where:
of the expected yield stress to the specified
Ry = ratio
minimum yield stress, Fy (per Table A3.1 of the
Provisions)
Fyb = Fy of the beam, ksi
Zb = plastic section modulus of the beam, in.3
M f
Vcol
db
Mf = 1.1RyMp + VhSh
(4)
Mf = 1.1RyMp + Vh Sh
(5)
Vcol =
(1)
M f
h
(6)
where:
where:
(2)
(3)
Where:
Mp = FyZ = nominal plastic flexural strength, kip-in.
Lh = distance between plastic hinges, in.
wu = uniform beam gravity load, kips per linear ft.
Doubler Plates
At the connection to a beam, the column panel-zone must
have adequate thickness to prevent excessive distortion or
shear buckling. If the thickness is insufficient, the panel-zone
can be strengthened with the addition of a doubler plate.
As defined by Section E3.6e.(1) of the Provisions, the
required shear strength of the panel-zone is determined from
3b t 2
v Rn = 0.60Fy dc t w 1+ cf cf
db d c t w
For Puc
0.75 Pc
where:
(7)
where:
3b t 2
V pz = 1+ cf cf
db dc t w
(8)
Given:
Refer to the special moment frame connection J-1 shown in
Figure 1. Determine the connection design parameters for the
W14257 column and W36150 beam. The beam and
column are both ASTM A992 wide-flange sections (Fy = 50
ksi, Fu = 65 ksi, Es =29,000 ksi).
where:
tw = 1.18 in.
Zx = 487 in.3
tw = 0.63 in.
Zx = 581 in.3
(9)
Continuity Plates
At the connection to a beam, the column flange must be
sufficiently rigid to prevent deformation or local bending.
The column web must also be sufficiently rigid to prevent
local yielding due to the corresponding high state of stress
concentrations. The installation of stiffeners or continuity
plates can address these local limit states. If the flange and
web thicknesses are sufficient, the concentrated beam flange
forces can be adequately transferred without the required
stiffening effects or secondary load path.
Section E3.6f of the Provisions requires continuity plates
unless the column flange thickness satisfies equations E3-8
and E3-9, reproduced here:
t cf 0.4 1.8bbf t bf
t cf
Fyb Ryb
Fyc Ryc
bcf
6
where:
bbf = beam flangewidth, in.
tbf = beam flange thickness, in.
tcf = minimum required thickness of column flange when no
continuity plates are provided, in.
Fyc = Fy of the column, ksi
Ryb = Ry of the beam (per Table A3.1 of the Provisions)
Ryc = Ry of the column (per Table A3.1 of the Provisions)
Mpc*= 3951kip-ft.
Determine the distance between plastic hinges, Lh:
Puc
Vh = 2[1.1(1.1)(50ksi)(581in. )(1ft./12in.)/(28.6ft.)]
+1.0 kip/ft.(28.6ft.)/2
Vh = 218.9kips
3(16in.)(1.89in.) 2
V pz = 1+
= 1.25
(35.9in.)(16.4in.)(1.18in.)
vRn = 0.60(50ksi)(16.4in.)(1.18in.)(1.25)
tpz tcwRu/vRn
Mpb*= 3079kip-ft.
tdp 0.53in.
Therefore, try a 5/8 in. doubler plate, tdp = 0.63in., and check
if the doubler plate provides adequate panel-zone thickness
using the following equation:
2(2929kip ft.)
= 209kips
2(14 ft.)
2929kip ft.
209kips = 770kips
35.9in.(1 ft./12in.)
t cf 0.4 1.8(12.0in.)(0.94in.)
(11)
Mf = 1.1(1.1)(50ksi)(581in.3)(1ft./12in.) = 2929kip-ft.
Vcol =
(10)
Mpb*=(1.1)(1.1)(50ksi)(581in. 3)(1ft./12in.)+149.6kip-ft.
50ksi(1.1)
50ksi(1.1)
t cf
12.0in.
6
Beam
Span,
ft
Load,
w u,
kips/ft
S h,
in.
Column
Height,
h, ft
Moment
Ratio
Variation
20
30
40
20
30
40
20
30
40
20
30
40
20
30
40
1.0
1.0
1.0
2.0
2.0
2.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
12
12
12
24
24
24
14
14
14
14
14
14
16
16
16
14
14
14
14
14
14
1.25
1.28
1.30
1.25
1.28
1.30
1.25
1.28
1.30
1.12
1.19
1.22
0.98
1.10
1.15
0.98
1.00
1.02
0.98
1.00
1.02
0.98
1.00
1.02
0.88
0.93
0.95
0.76
0.86
0.90
Load,
w u,
kips/ft
S h,
in.
Column
Height,
h, ft
Panel
Zone, tpz,
in
Variation
20
30
40
20
30
40
20
30
40
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
0
0
0
12
12
12
24
24
24
14
14
14
14
14
14
14
14
14
1.25
1.25
1.25
1.41
1.36
1.33
1.60
1.47
1.41
1.00
1.00
1.00
1.13
1.08
1.06
1.28
1.18
1.13
Figure 11. Doubler plate thickness of a singlesided W14x193 column. Assumes local buckling of
the doubler plate is not prevented per Section E3.6e(2)
of the Provisions.
Figure 15. Doubler plate thickness of a singlesided W14x233 column. Assumes local buckling of
the doubler plate is not prevented per Section E3.6e(2)
of the Provisions.
Figure 19. Doubler plate thickness of a singlesided W14x283 column. Assumes local buckling of
the doubler plate is not prevented per Section E3.6e(2)
of the Provisions.
10
Figure 23. Doubler plate thickness of a singlesided W14x342 column. Assumes local buckling of
the doubler plate is not prevented per Section E3.6e(2)
of the Provisions.
11
12
References