Cajas Envolventes y Terminales

Download as pdf or txt
Download as pdf or txt
You are on page 1of 82

1

JUNCTION BOXES AND TERMINAL


ENCLOSURES

2
3
4
5
6
7
8

EX-TERMINAL AND JUNCTION BOXES

7.21

EX-JUNCTION BOXES

7.41

UNIVERSAL EX-TERMINAL BOXES PLASTIC

7.10

UNIVERSAL EX-TERMINAL BOXES LIGHT ALLOY

7.26

EX-TERMINAL BOXES LIGHT ALLOY FLAME PROOF

7.32

EX-TERMINAL ENCLOSURES STAINLESS STEEL

7.36

EX-INTERMEDIATE MOTOR TERMINAL BOXES

7.72

9
10
11
12

Ex-Terminal and Junction boxes

Ex-e Terminal and


Junction boxes

Connection or terminal boxes of the in-

Apparatus which do not create arcing

used in nearly every country in the

or sparking or exceed max. permissible

world are in comparison to the flame-

surface temperatures during normal

proof encapsulated version, much

operating conditions can be used in

cheaper and are generally much easier

accordance with the European standard

to install.

creased safety standard, which are

EN 60079-7 - "Ex-e" in hazardous


areas of Zone 1, 2, 21 and 22.

User-friendly technology and


cost saving installation

All CEAG junction- and terminal boxes

Large terminal compartment allows an

are manufactured according to this

easy installation or retrofitting of wiring.

standard.

Cost-saving terminal arrangements


according to the customer's specifi -

Unused cable entry holes are to be

cation speed up the total installation

closed using either a certified screw or

time.

blanking plug. Terminal boxes can be


subsequently re-fitted or upgraded

The innovative clip-on mounting system

with certified cable glands according

has in conjunction with the special

to national regulations and the manu-

designed apparatus the advantage of

facturers recommendations.

being a cost reducer.

The requirements on the EMC terminal

Installation without a hot work permit!

boxes for use in the instrumentation

Using the clip-on mounting frames for

and controlling fields are met with our

the installation on walls, trellises and

metal and interior coated housings.

pipes you save time. Simply plugged!

The coating in combination with the

In combination with the new connection

affordable cable entries shield off the

friendly apparatus you will find that

sensible instrumentation areas against

the installation is now time saving and

unwanted external radiation fields.

therefore saving you money.

7.2

COOPER CROUSE-HINDS GMBH

Ex-Terminal and Junction boxes

Various solutions for your


individual installation tasks
Terminal boxes made of moulded
plastic with type of protection Ex-e are
the most economic solution for wiring
tasks. Lightweight design, corrosion

resistance as well as wide thermal


range are only a few of the advantages.

3
Light metal termination boxes combines

light weight with heavy duty enclosure


material. External earth connectors as
well as metal cable glands directly
screwed into the wall material offers
some advantages using armoured

cables.
High chemical resistance of the
housing is ensured by the use of
impact-resistant plastic powder
coating.

Covered screws and all outside and


inside metallic parts are made of
stainless steel.
The robust design of the stainless steel
terminal enclosures provides a high degree of safety for offshore applications

and in places where particularly adverse chemical, mechanical and climatic


operating conditions prevail within
the hazardous area.

Various terminal configuration as


well as gland plates pre-manufactured
according to the customer's requirements offers more flexibility for instrumentation and control installations
using the Ex-e and Ex-i technologies.

All CEAG terminal enclosures

Beside the ATEX certification tests a

Additional type approvals from UL,

will fulfil the latest requirement on

lot of other certification procedures

GOST or Nepsi allows a world wide

testing according to international

have to be run through before the

use.

standards.

product leaves the factory.

9
10
11
12

COOPER CROUSE-HINDS GMBH

7.3

Plastic version for Zone 1 and Zone 21

The robust junction boxes made of plastic and


light alloy are featured by their friendly mounting
and installation capability and their design.
They are fitted with pillar terminals for cable
of up to 6 mm 2.
The practical orientated housing form allows
for a problem-free access to the connection
terminals for installation.
With the CEAG mounting system, the plastic
junction boxes are economical in their use for
mounting on walls, trellis and pipes. With wire
and cable entries in the sizes M25 or M32 for
8 17 mm or 12 21 mm respectively,
all requirements for the modern day installation
technology are fulfilled.
For cable with armouring there are junction
boxes available with internal metal clamps or
light alloy versions allowing for screw joints.
For the wire and cable entries that are not
used there are certified blanking plugs supplied
with the junction box.
To enable a high chemical resistance of the light
alloy junction boxes, these have been given an
impact resistant plastic powder coating.
The cover screws and all other external metal
parts are made of stainless steel (AISI 316L).
International approvals

Decisive cost reduction with the


CEAG mounting system
Free accessible connection terminals
Safety standard IP66
Version for metal entries available

7.4

Ex-junction boxes 791

1
2
GHG 791 0201 R0001

GHG 791 0201 R0006

GHG 791 0101 R0002

GHG 791 0101 R0001

Technical data
GHG 791 01 up to 6 terminals GHG 791 02 up to 6 terminals
Marking to 94/9/EC

II 2 G Ex dem ia II, IIC /

EC-Type Examination Certificate

II 2 D Ex tD A21 IP66 T80 C

PTB 00 ATEX 3108

IECEx certification of conformity

IECEx BKI 07.0034

Marking accd. to IECEx

Ex e II T6 / Ex ia IIC T6

Ex tD A21 IP66 T58 C


Permissible ambient temperature

20 C to +40 C / 55 C to +40 C (option)

Rated voltage

690 V / 550 V1)

Rated current

depends on terminal cross section

Connecting terminals

max. 4 x 4 mm2/PE 4 x 2.5 mm2 (multi-wire)

max. 2 x 6 mm2/PE 4 x 4 mm2 (solid-wire) or 2 x 6 mm2 + 1 x 2.5 mm2


Insulation class

Degree of protection accd. EN 60529

IP66

Enclosure material

Polyamide

GHG 791 01 up to 6 terminals


Cable glands/enclosure thread

max. 4 x M25 for cable 10 - 17 mm

Dimensions (L x W x H)

81.5 x 100 x 61 mm

Weight

approx. 0.3 kg

max. 4 x M20 metal thread

GHG 791 02 up to 6 terminals


Cable glands/enclosure thread

max. 6 x M25 for cable 10 - 17 mm


max. 6 x M32 for cable 12 - 21 mm
max. 6 x M20 metal thread

1)

Dimensions (L x W x H)

117.5 x 113.5 x 73.5 mm

Weight

approx. 0.5 kg

for cage clamp terminals

9
10
11
12
COOPER CROUSE-HINDS GMBH

7.5

Ex-junction boxes 791

GHG 791 0101 R0001

GHG 791 0101 R0019

GHG 791 0101 R0068

GHG 791 0201 R0006

Ordering details
Design

Cable gland

No. of terminals

Order No.

2 x M25 for cable 10-17 mm

4 x Ex-e, 1 x PE

GHG 791 0101 R0001

4 x Ex-e, 1 x PE

GHG 791 0101 R0002

incl. 2 x threaded plug M20

4 x Ex-e, 1 x PE

GHG 791 0101 R0019

4 x M25 for cable 8-17 mm

4 x 4 Ex-e1), 2 x PE

GHG 791 01 up to 6 terminals

4 x M25 for cable 10-17 mm


incl. 2 x blanking plug M25
4 x M20 metal thread

GHG 791 0101 R0069

incl. 2 x blanking plug M25


4 x 4 Ex-e1), 2 x PE

4 x M20 metal thread

GHG 791 0101 R0068

incl. 2 x threaded plug M20

GHG 791 02 up to 6 terminals


4 x M25 for cable 10-17 mm
incl. 2 x blanking plug M25

6 x Ex-e, 2 x PE

GHG 791 0201 R0006

6 x Ex-e, 2 x PE

GHG 791 0201 R0007

6 x Ex-e, 2 x PE

GHG 791 0201 R0001

6 x Ex-e, 2 x PE

GHG 791 0201 R0002

8 x Ex-e, 1 x PE

GHG 791 0201 R0003

4 x M32 for cable 12-21 mm


incl. 2 x blanking plug M32
6 x M25 for cable 10-17 mm
incl. 4 x blanking plug M25
6 x M32 for cable 12-21 mm
incl. 4 x blanking plug M32
6 x M20 metal thread
incl. 4 x threaded plug M20
Other applications available on request.
1)

Cage clamp terminal

Accessories
Mounting plate for junction box 791 01
Type

Application

Fixing method

Order No.

Size 1
Size 1
Size 1
Protective canopy Size 2

Wall mounting
Trellis mounting
Pipe mounting
for mounting plate size 1

screwless mounting
screwless mounting
screwless mounting

GHG 610 1953 R0101


GHG 610 1953 R0103
GHG 610 1953 R0102
GHG 610 1955 R0101

Mounting plate for junction box 791 02


Type

Application

Fixing method

Order No.

Size 2
Size 2
Size 2
Protective canopy Size 2

Wall mounting
Trellis mounting
Pipe mounting
for mounting plate size 2

screwless mounting
screwless mounting
screwless mounting

GHG 610 1953 R0104


GHG 610 1953 R0106
GHG 610 1953 R0105
GHG 610 1955 R0102

Details for accessories see page 7.78 pp.

7.6

COOPER CROUSE-HINDS GMBH

Ex-junction boxes 791

1
2
GHG 791 0201 R0006

GHG 791 0101 R0068

GHG 791 0101 R0019

GHG 791 0101 R0001

Dimension drawing
180
100
X 91

61
10

100
X 91

61

10

81.5

X 48.5

81.5
122

X 48.5

5.6
M20x1.5

42
M20x1.5

Type 791 01 Metal

42

Type 791 01
195
113.5
X 105

73.5
10.5

113
X 105

74

81.5

56

M20x1.5

55

X 55

158
117.5

6
7

56

X = mounting dimension

Type 791 02 Metal

8
9
10

Dimensions in mm

Type 791 02

COOPER CROUSE-HINDS GMBH

7.7

11
12

Light metal design for Zone 1 and Zone 21

The sturdy CEAG junction boxes made of light


metal are used to distribute and conduct electricity in areas of Zone 1 and Zone 2 at no risk of
explosion. Optionally, mantle terminals with a
terminal range of 6 mm 2 are available for these
branching boxes.
Four M20 threaded holes allow variable
equipment with various ducts for cables
and lines.
Drilled holes, cable and line ducts, through
which no lines are conducted, should be
closed with certified threaded stoppers.
High chemical resistance of the housing is
ensured by the use of impact-resistant plastic
powder coating.
Covered screws and all outside and inside
metallic parts are made of stainless steel
(AISI 316L).
The light metal branching box has an outside
earthing connection.
Internationally approved.

Mechanical, chemical and


thermal resistance
Impact-resistant plastic powder coating

7.8

Ex-Junction box

1
2
GHG 793 0101 R0002

GHG 793 0101 R0001

Technical data
Type 793 01 up to 4 terminal
Marking to 94/9/EC

II 2 G Ex dem ia II, IIC T6 /

EC-Type Examination Certificate

II 2 D Ex tD A21 IP66 T80 C

PTB 00 ATEX 3108

Permissible ambient temperature

20 C to +40 C
55 C to +55 C (option)

Rated voltage

690 V

Rated current

depends on terminal cross section

Connecting terminals

max. 4 x 4 mm2/PE 4 x 2.5 mm2 (multi-wire)


max. 2 x 6 mm2*/PE 4 x 4 mm2 (solid wire) or 2 x 6 mm2 + 1 x 2.5 mm2

Insulation class

Degree of protection accd. EN 60529

IP66

Cable glands/enclosure drilling

max. 4 x M20 drilling

Dimensions (L x W x H)

82 x 130 x 72 mm

Weight

approx. 0.8 kg

Enclosure material

light alloy die-casting (AISI)

Enclosure colour

light grey

5
6

Ordering details
Design

Cable gland

No. of terminals

Order No.

2 x M20 drilling

4 x Ex-e, 1 x PE

GHG 793 0101 R0001

4 x Ex-e, 1 x PE

GHG 793 0101 R0002

GHG 793 01 up to 4 terminals

4 x M20 drilling
incl. 2 x blanking plug M20

8
Other applications available on request.

Dimension drawing

82
X68

10
X 116
130

50
72
Z

Type 793

Dimensions in mm

5,5

9,5

X = mounting dimension

COOPER CROUSE-HINDS GMBH

7.9

11
12

U N I V E R S A L

T E R M I N A L

Ex-e/Ex-i Technology
plastic version measuring and controlling for Zone 1 and Zone 21

The terminal boxes were designed for measuring


and controlling utilization in the Ex-e and Ex-i
technology. They are used as a link between the
main cable to the control room and the branch
cables into the field. In addition to this, they
may also be used for the direct connection of
actuators and sensors.
The new terminal boxes for instrumentation installations are available in 5 sizes, ranging from
6 to max. 60 connection terminals. The optional
interior coating protects your data cable connections against external radiation fields. The choice
between screw and tension spring (screwless)
terminals for single and multi-wire conductors
makes it possible for engineers to select
the type of connection most suitable for the
particular application.
The CEAG installation system provides an
economical way of mounting the terminal boxes
on walls, trellis work and pipes. The terminal
boxes are suited for the use of single or multiple
cable glands.
With CEAG terminal boxes it is possible to apply
separate potentials such as screen-grid leads
or PE/PA conductors to the plug-in PE rails.
The snap-out terminal rails allow a problem-free
feeding-in of cables.
The well-proven clip-in flanges in moulded
plastic or metal design allow multiple application
possibilities. As a result of the optimized design,
a large drilling surface was created. This can be
fitted with a sufficient number of moulded plastic
glands or an equal number of metal glands.
International approvals

Decisive cost saving


with the CEAG installation system
Safety standard IP66
Freely accessible connection terminals
Clip-in flange technique
Snap-out terminal rails
Internal coating
for EMC-Protection on request

7.10

B O X E S

Overview terminal boxes / Plastic version for Zone 1

To make it easier for you to be able to choose a terminal or

Using the maximum drill surface and the interference

junction box, you will find in table-form all the basic data that

diameter of the wire and cable entries tables plus the

is required below. Using the table below you can choose and

number of terminals you require, you can choose the right

configure your terminal boxes.

terminal box for your application.

The maximum number of terminals derives from the rated

The terminal boxes can also be equipped with (when

current of the terminal. If the load per terminal lies below

requested) brass flanges and external earthing connectors.

the rated current, then the maximum number of terminals


for the terminal rail can be used.

Maximum number of terminals acc. to certification


Terminal cross section in mm2

Type
2,5

10

16

25

35

GHG 791 01

GHG 791 02

12

10

GHG 731 11

16

14

10

GHG 731 12

24

24

18

18

14

GHG 721 00

26

22

17

13

11

GHG 721 10

48

40

30

24

20

GHG 744 01

40

33

25

20

17

17

GHG 745 02

2 x 41

2 x 34

2 x 26

2 x 20

17

17

14

GHG 746 03

2 x 94

2 x 78

2 x 59

2 x 47

40

40

32

GHG 749 04

2 x 148

2 x 124

2 x 94

2 x 75

63

63

51

4
5
6

Terminal rails
Type

Rail Length

GHG 791 01

40 mm

GHG 791 02

95 mm

GHG 731 11

107 mm

GHG 731 12

169 mm

GHG 721 00

140 mm

GHG 721 10

262 mm

GHG 744 01

230 mm

GHG 745 02

2 x 235 mm

GHG 746 03

2 x 510 mm

GHG 749 04

2 x 795 mm

8
9

Dimensions
Type

Width

Space required for


wire and cable entries
x Length

x Height

GHG 791 01 100 mm

81 mm

61 mm

GHG 791 02 113 mm

x 117 mm

73 mm

GHG 731 11 120 mm

x 140 mm

95 mm

GHG 731 12 182 mm

x 140 mm

GHG 721 00 165 mm

x 165 mm

GHG 721 10 285 mm

x 165 mm

GHG 744 01 271 mm

max. drill surface


Type

Type

Width x Height

Interference Diameter

GHG 791 01

80 mm x

45 mm

Plastic

Metal

GHG 791 02

93 mm x

57 mm

M12

19 mm

21 mm

GHG 731 11

95 mm x

75 mm

95 mm

M16

25 mm

21 mm

GHG 731 12

144 mm x

75 mm

x 131 mm

M20

31 mm

26,5 mm

GHG 721 00

132 mm x

91 mm

x 143 mm

M25

37 mm

33 mm

GHG 721 10

252 mm x

95 mm

x 134 mm

x 136 mm

M32

46 mm

45,1 mm

GHG 744 01

238 mm x 134 mm

GHG 745 02 271 mm

x 271 mm

x 136 mm

M40

56 mm

53 mm

GHG 745 02

238 mm x 134 mm

GHG 746 03 544 mm

x 271 mm

x 136 mm

M50

68 mm

60,5 mm

GHG 746 03 (2x) 238 mm x 134 mm

GHG 749 04 817 mm

x 271 mm

x 136 mm

M63

84 mm

80 mm

GHG 749 04 (3x) 238 mm x 134 mm


Flange 1

70,5 mm x 48,5 mm

Flange 2

204 mm x 72,5 mm

10
11
12

COOPER CROUSE-HINDS GMBH

7.11

Ex-e/Ex-i terminal box

GHG 791 0101 R0003

GHG 791 0101 R0005

GHG 791 0201 R0011

GHG 791 0201 R0008

Technical data
GHG 791 01 up to 4 terminals GHG 791 02 up to 12 terminals
Marking to 94/9/EC
EC-Type Examination Certificate

II 2 G Ex dem ia II, IIC T6 /

II 2 D Ex tD A21 IP66 T80 C

PTB 00 ATEX 3108

IECEx certificate of conformity

IECEx BKI 07.0034

Marking accd. to IECEx

Ex e II T6 / Ex ia IIC T6
Ex tD A21 IP66 T58 C

Permissible ambient temperature

20 C to +40 C
55 C to +40 C (option)

Rated voltage

690 V

Insulation class

Degree of protection accd. EN 60529

IP66

Enclosure material

Polyamide

Enclosure colour

black

GHG 791 01 up to 6 terminals


Rated current

max. 30 A

Connecting terminals

up to 4 mm2

Cable glands/enclosure drilling

max. 2 x M25 or 1 x M25 + 2 x M12

Dimensions (L x W x H)

81.5 x 100 x 61 mm

Weight

approx. 0.3 kg

GHG 791 02 up to 12 terminals


Rated current

7.12

max. 39 A

Connecting terminals

up to 6 mm2

Cable glands/enclosure drilling

max. 2 x M25 or 1 x M32 + 1 x M25 or 1 x M25 + 4 x M12

Dimensions (L x W x H)

117.5 x 113.5 x 73.5 mm

Weight

approx. 0.5 kg

COOPER CROUSE-HINDS GMBH

Ex-e/Ex-i terminal box

1
2
GHG 791 0201 R0008

GHG 791 0201 R0011

GHG 791 0101 R0005

GHG 791 0101 R0003

Ordering details
Design

Cable gland

No. of terminals

Order No.

Type 791 01 up to 6 terminals assembled with screw terminals 2 x 2.5 mm + PE/PA-terminal 2 x 4 mm


Ex-e

1 x M25 for cable 8-17 mm

6 x Ex-e

1 x M25 for 2 cable 4.5-7 mm

4 x PE/PA

Ex-i

1 x M25 for cable 8-17 mm

6 x Ex-i

1 x M25 for 2 cable 4.5-7 mm

4 x PE/PA
GHG 791 0101 R0004

1 x blanking plug for 4.5-7 mm


Ex-e

1 x M25 for cable 8-17 mm

6 x Ex-e

2 x M12 for cable 4-7 mm

4 x PE/PA

5
GHG 791 0101 R0005

1 x blanking plug for M12


Ex-i

GHG 791 0101 R0003

1 x blanking plug for 4.5-7 mm

1 x M25 for cable 8-17 mm

6 x Ex-i

1 x M12 for cable 4-7 mm

4 x PE/PA
GHG 791 0101 R0006

1 x blanking plug for M12

Type 791 01 up to 6 terminals assembled with screwless terminals 2 x 2.5 mm + PE/PA-terminal 2 x 4 mm


Ex-i

1 x M25 for cable 8-17 mm

6 x Ex-i

1 x M25 for 2 cable 4.5-7 mm

1 x PE/PA
GHG 791 0101 R0008

1 x blanking plug for 4.5-7 mm


Ex-e

1 x M25 for cable 8-17 mm

6 x Ex-e

2 x M12 for cable 4-7 mm

1 x PE/PA

Ex-i

GHG 791 0101 R0009

1 x blanking plug for M12


1 x M25 for cable 8-17 mm

6 x Ex-i

1 x M12 for cable 4-7 mm

1 x PE/PA
GHG 791 0101 R0010

1 x blanking plug for M12

Type 791 02 up to 6 terminals assembled with screw terminals 2 x 2.5 mm + PE/PA-terminal 2 x 4 mm


Ex-e

1 x M25 for cable 8-17 mm

12 x Ex-e

1 x M25 for 2 cable 4.5-7 mm

4 x PE/PA
GHG 791 0201 R0008

2 x blanking plug for 4.5-7 mm


Ex-i

1 x M25 for cable 8-17 mm

12 x Ex-i

1 x M25 for 2 cable 4.5-7 mm

4 x PE/PA

Ex-e

1 x M25 for cable 8-17 mm

12 x Ex-e

4 x M12 for cable 4-7 mm

4 x PE/PA
GHG 791 0201 R0010

2 x blanking plug for M12


Ex-i

GHG 791 0201 R0009

2 x blanking plug for 4.5-7 mm

1 x M25 for cable 8-17 mm

12 x Ex-i

4 x M12 for cable 4-7 mm

4 x PE/PA

10

GHG 791 0201 R0011

2 x blanking plug for M12


Type 791 02 up to 6 terminals assembled with screwless terminals 2 x 2.5 mm + PE/PA-terminal 2 x 4 mm
Ex-i

1 x M25 for cable 8-17 mm

12 x Ex-i

1 x M32 for 4 cable 4.5-7 mm

4 x PE/PA
GHG 791 0201 R0013

1 x blanking plug for 4.5-7 mm


Ex-e

1 x M25 for cable 8-17 mm

12 x Ex-e

4 x M12 for cable 4-7 mm

4 x PE/PA
GHG 791 0201 R0014

2 x blanking plug for M12


Ex-i

1 x M25 for cable 8-17 mm

12 x Ex-i

4 x M12 for cable 4-7 mm

4 x PE/PA

2 x blanking plug for M12

11

GHG 791 0201 R0015

12

Other applications available on request.


COOPER CROUSE-HINDS GMBH

7.13

Ex-e/Ex-i terminal box

GHG 791 0101 R0003

GHG 791 0101 R0005

GHG 791 0201 R0011

GHG 791 0201 R0008

Accessories
Mounting plate for junction box 791 01
Type

Application

Fixing method

Order No.

Size 1
Size 1
Size 1
Protective canopy Size 1

Wall mounting
Trellis mounting
Pipe mounting
for mounting plate size 1

screwless mounting
screwless mounting
screwless mounting

GHG 610 1953 R0101


GHG 610 1953 R0103
GHG 610 1953 R0102
GHG 610 1955 R0101

Mounting plate for junction box 791 02


Type

Application

Fixing method

Order No.

Size 2
Size 2
Size 2
Protective canopy Size 2

Wall mounting
Trellis mounting
Pipe mounting
for mounting plate size 2

screwless mounting
screwless mounting
screwless mounting

GHG 610 1953 R0104


GHG 610 1953 R0106
GHG 610 1953 R0105
GHG 610 1955 R0102

Details for accessories see page 7.78 pp.

Dimension drawing

61

X 48.5

PE PE 1 2 3

81.5

100
X 91

Type 791 01

113.5
X 104.5

73.5

X 54

117.5

PE PE PE 1 2 3 4

X = Mounting dimension

Dimensions in mm

Type 791 02

7.14

COOPER CROUSE-HINDS GMBH

Ex-e/Ex-i terminal box

1
2
GHG 731 1202 R0976

GHG 731 1202 R0387

GHG 731 1102 R1088

GHG 731 1102 R0531

Technical data
GHG 731 11 up to 16 terminals GHG 731 12 up to 24 terminals
Marking to 94/9/EC

II 2 G Ex de ia/ib [ia/ib] m IIC T6 /

EC-Type Examination Certificate

II 2 D Ex tD A21 IP65 T 80 C

PTB 99 ATEX 1044

IECEx certification of conformity

IECEx BKI 05.0004

Marking accd. to IECEx

Ex e ia [ia] IIC T6/T5

Ex tD A21 IP66 T80 C


Permissible ambient temperature

20 C to +40 C
55 C to +55 C (option)

Rated voltage

690 V

Rated current

Depends on terminal mounting

Insulation class

Degree of protection accd. EN 60529

IP66

Enclosure material

Glass-fibre reinforced polyester

Enclosure colour

black

5
6

GHG 731 11 up to 16 terminals


Connecting terminals

up to 16 mm2

Dimensions (L x W x H)

140 x 120 x 95 mm

Weight

approx. 0.8 kg

Drillings/cable glands

M12

Max. number up/down

15

M16

M20

M25

M32

M40

M50

Terminal mounting space on the terminal rail

107 mm

Max. number of terminals acc. to certification

2.5 mm2 4 mm2


16

14

6 mm2

10 mm2

16 mm2

10

GHG 731 12 up to 24 terminals


Connecting terminals

up to 16 mm2

Dimensions (L x W x H)

140 x 182.5 x 95 mm

Weight

approx. 1.1 kg

Drillings/cable glands

M12

Max. number up/down

24

M16

M20

M25

M32

M40

M50

17

10

Length of assembling of the terminal rail

169 mm

Max. number of terminals acc. to certification

2.5 mm2 4 mm2


24

24

6 mm2

10 mm2

16 mm2

18

18

14

9
10
11
12

COOPER CROUSE-HINDS GMBH

7.15

Ex-e/Ex-i terminal box

GHG 731 1102 R0531

GHG 731 1102 R1485

GHG 731 1202 R0387

GHG 731 1202 R1345

Ordering details
Design

Cable gland

Terminals

Order No.

Type 731 11 up to 16 terminals assembled with screw terminals 2 x 2.5 mm + PE/PA-rail 2.5 mm
Ex-e

without drilling

1 x Ex-e*/UT 3 N/7 x PE/PA

GHG 731 1102 R0531

Ex-e

without drilling

14 x Ex-e/UT 5 N/7 x PE/PA

GHG 731 1102 R1088

Ex-e

4 x M25

16 x Ex-e/UT 3 N/7 x PE/PA

GHG 731 1102 R1485

Type 731 12 up to 24 terminals assembled with screw terminals 2 x 2.5 mm + PE/PA-rail 2.5 mm
Ex-e

without drilling

1 x Ex-e*/UT 3 N/14 x PE/PA

GHG 731 1202 R0387

Ex-e

without drilling

24 x Ex-e/UT 5 N/14 x PE/PA

GHG 731 1202 R0976

Ex-e

4 x M25

28 x Ex-e/UT 3 N/14 x PE/PA

GHG 731 1202 R1345

* according to type examination certificate individual extensible

Accessories
Mounting plate for junction box 731 11
Type

Application

Fixing method

Order No.

Size 2
Size 2
Size 2
Protective canopy Size 2

Wall mounting
Trellis mounting
Pipe mounting
for mounting plate size 2

screwless mounting
screwless mounting
screwless mounting

GHG 610 1953 R0104


GHG 610 1953 R0106
GHG 610 1953 R0105
GHG 610 1955 R0102

Mounting plate for junction box 731 12


Type

Application

Fixing method

Order No.

Size 2A
Size 2A
Size 2A
Protective canopy Size 2A

Wall mounting
Trellis mounting
Pipe mounting
for mounting plate size 2A

screwless mounting
screwless mounting
screwless mounting

GHG 610 1953 R0107


GHG 610 1953 R0109
GHG 610 1953 R0108
GHG 610 1955 R0103

Details for accessories see page 7.78 pp.

Dimension drawing
182.5
X168.5

95

120
5.6

95
10

10
140
X90

X 90

140

5.6

X 106

Type 731 12

Dimensions in mm

Type 731 11

7.16

COOPER CROUSE-HINDS GMBH

Ex-e/Ex-i terminal box

1
2
GHG 721 1001 R0013

GHG 721 1001 R0003

GHG 721 0001 R0005

GHG 721 0001 R0001

Technical data
GHG 721 00 up to 26 terminals GHG 721 10 up to 48 terminals
Marking to 94/9/EC

II 2 G Ex de ia/ib [ia/ib] m IIC T4 /

EC-Type Examination Certificate

II 2 D Ex tD A21 IP66 T 80 C

PTB 99 ATEX 1044

IECEx certification of conformity

IECEx BKI 05.0005

Marking accd. to IECEx

Ex e ia/ib [ia/ib] IIC T4/T6

Ex tD A21 IP66 T80 C


Permissible ambient temperature

20 C to +40 C
55 C to +55 C (option)

Rated voltage

690 V

Rated current

Depends on terminal mounting

Insulation class

Degree of protection accd. EN 60529

IP66

Enclosure material

Glass-fibre reinforced polyester

Enclosure colour

black

5
6

GHG 721 00 up to 26 terminals


Connecting terminals

up to 16 mm2

Dimensions (L x W x H)

165 x 165 x 131.5 mm

Weight

approx. 1.1 kg

Drillings/cable glands

M12

M16

M20

M25

M32

M40

M50

M63

Max. number down

35

20

12

11

Max. number flange plastic

11

Max. number flange metal

Terminal mounting space on the terminal rail

140 mm

Max. number of terminals acc. to certification

2.5 mm2

4 mm2

6 mm2

10 mm2

16 mm2

26

22

17

13

11

7
8

GHG 721 10 up to 48 terminals


Connecting terminals

up to 16 mm2

Dimensions (L x W x H)

165 x 285 x 143 mm

Weight

approx. 1.7 kg

Drillings/cable glands

M12

M16

M20

M25

M32

M40

M50

Max. number down

75

42

32

21

11

Max. number flange plastic

46

25

20

11

12

Max. number flange metal


Terminal mounting space on the terminal rail

262 mm

Max. number of terminals acc. to certification

2.5 mm2

4 mm2

6 mm2

10 mm2

16 mm2

48

40

30

24

20

M63

9
10
11
12

COOPER CROUSE-HINDS GMBH

7.17

Ex-e/Ex-i terminal box

GHG 721 0001 R0001

GHG 721 0001 R0011

GHG 721 1001 R0003

GHG 721 1001 R0004

Ordering details
Design

Cable gland

No. of Terminals

Order No.

Type 721 00 up to 26 terminals assembled with screw terminals 2 x 2.5 mm + PE/PA-rail 2.5 mm
Ex-e
Ex-i
Ex-e

1 x M32 for cable 12-21 mm

24 x Ex-e

3 x M32 for 4 cable 4.5-7 mm

12 x PE/PA

1 x M32 for cable 12-21 mm

24 x Ex-i

3 x M32 for 4 cable 4.5-7 mm

12 x PE/PA

1 x M32 for cable 12-21 mm

24 x Ex-e

12 x M20 for cable 5.5-13 mm


Ex-i

1 x M32 for cable 12-21 mm


12 x M20 for cable 5.5-13 mm

12 x PE/PA

GHG 721 0001 R0005


GHG 721 0001 R0006
GHG 721 0001 R0007

24 x Ex-i
12 x PE/PA

GHG 721 0001 R0008

Type 721 00 up to 26 terminals assembled with screwless terminals 2 x 2.5 mm + PE/PA-rail 2.5 mm
Ex-i
Ex-e

1 x M32 for cable 12-21 mm

24 x Ex-i

3 x M32 for 4 cable 4.5-7 mm

12 x PE/PA

1 x M32 for cable 12-21 mm

24 x Ex-e

12 x M20 for cable 5.5-13 mm


Ex-i

1 x M32 for cable 12-21 mm


12 x M20 for cable 5.5-13 mm

12 x PE/PA

GHG 721 0001 R0010


GHG 721 0001 R0011

24 x Ex-i
12 x PE/PA

GHG 721 0001 R0012

Type 721 10 up to 48 terminals assembled with screw terminals 2 x 2.5 mm + PE/PA-rail 2.5 mm
Ex-e

1 x Ex-e1) / 24 x PE

without drilling

GHG 721 1001 R0003

Type 721 10 up to 48 terminals assembled with screw terminals 2 x 2.5 mm + PE/PA-rail 2.5 mm
Ex-i
Ex-e

1 x M40 for cable 16-28 mm

48 x Ex-i

6 x M32 for 4 cable 4.5-7 mm

24 x PE/PA

1 x M40 for cable 16-28 mm

48 x Ex-e

24 x M20 for cable 5.5-13 mm


Ex-i

1 x M40 for cable 16-28 mm


24 x M20 for cable 5.5-13 mm

24 x PE/PA

GHG 721 1001 R0013


GHG 721 1001 R0004

48 x Ex-i
24 x PE/PA

GHG 721 1001 R0015

Type 721 10 up to 48 terminals assembled with screwless terminals 2 x 2.5 mm + PE/PA-rail 2.5 mm
Ex-i
Ex-e

1 x M40 for cable 16-28 mm

48 x Ex-i

6 x M32 for 4 cable 4.5-7 mm

24 x PE/PA

1 x M40 for cable 16-28 mm

48 x Ex-e

24 x M20 for cable 5.5-13 mm


Ex-i

1 x M40 for cable 16-28 mm


24 x M20 for cable 5.5-13 mm

1)

24 x PE/PA

GHG 721 1001 R0018

48 x Ex-i
24 x PE/PA

according to type examination certificate individual extensible

Other types on request

7.18

GHG 721 1001 R0017

COOPER CROUSE-HINDS GMBH

GHG 721 1001 R0019

Ex-e/Ex-i terminal box

1
2
GHG 721 1001 R0004

GHG 721 1001 R0003

GHG 721 0001 R0011

GHG 721 0001 R0001

Accessories
Mounting plate for junction box 721 00
Type

Application

Fixing method

Order No.

Size 2A
Size 2A
Size 2A
Protective canopy Size 2A

Wall mounting
Trellis mounting
Pipe mounting
for mounting plate size 2A

screwless mounting
screwless mounting
screwless mounting

GHG 610 1953 R0107


GHG 610 1953 R0109
GHG 610 1953 R0108
GHG 610 1955 R0103

Mounting plate for junction box 721 10


Type

Application

Fixing method

Order No.

Size 3
Size 3
Size 3
Protective canopy Size 3

Wall mounting
Trellis mounting
Pipe mounting
for mounting plate size 3

screwless mounting
screwless mounting
screwless mounting

GHG 610 1953 R0107


GHG 610 1953 R0109
GHG 610 1953 R0108
GHG 610 1955 R0104

Details for accessories see page 7.78

Dimension drawing
138.5
11

165

X 141

165

X151
Type 721 00

150
11

285

165

X141

7
X 272
Type 721 10

Dimensions in mm

10

COOPER CROUSE-HINDS GMBH

7.19

11
12

Ex-e/Ex-i terminal box

GHG 744 0101 R0005

Type 745 02

GHG 745 0201 R0012

Technical data
GHG 744 01 up to 40 terminals GHG 745 02 up to 82 terminals
Marking to 94/9/EC
EC-Type Examination Certificate

II 2 G Ex de ia/ib [ia/ib] m IIC T4 /

II 2 D Ex tD A21 IP66 T 80 C

PTB 99 ATEX 1044

IECEx certification of conformity

IECEx BKI 05.0006

Marking accd. to IECEx

Ex ed ia/ib m [ia/ib] IIC T4 T6


Ex tD A21 IP66 T80 C

Permissible ambient temperature

20 C to +40 C
55 C to +55 C (option)

Rated voltage

690 V

Rated current

Depends on terminal mounting

Insulation class

Degree of protection accd. EN 60529

IP66

Enclosure material

Glass-fibre reinforced polyester

Enclosure colour

black

GHG 744 01 up to 31 terminals


Connecting terminals

up to 25 mm2

Dimensions (L x W x H)

271 x 134 x 136 mm

Weight

approx. 1.5 kg

Drillings/cable glands

M12

M16

M20

M25

M32

M40

M50

Max. number down

60

36

26

18

10

Max. number flange plastic

46

25

20

11

11

Max. number flange metal


Terminal mounting space on the terminal rail
Max. number of terminals acc. to certification

M63

1 x 230 mm
2.5 mm2

4 mm2

31

31

6 mm2 10 mm2 16 mm2 25 mm2 35 mm2


24

24

23

15

GHG 745 02 up to 82 terminals


Connecting terminals

up to 70 mm2

Dimensions (L x W x H)

271 x 270 x 36 mm

Weight

approx. 2.5 kg

Drillings/cable glands

M12

M16

M20

M25

M32

M40

M50

Max. number down

60

36

26

18

10

Max. number flange plastic

46

25

20

11

11

Max. number flange metal


Terminal mounting space on the terminal rail

2 x 230 mm
2.5 mm2 4 mm2

Max. number of terminals acc. to certification

7.20

M63

38

38

6 mm2 10 mm2 16 mm2 25 mm2 35 mm2 50 mm2 70 mm2


29

29

23

16

COOPER CROUSE-HINDS GMBH

15

Ex-e/Ex-i terminal box

1
2
GHG 745 0201 R0012

Type 745 02

GHG 744 0101 R0005

Ordering details
Design

Cable gland

No. of Terminals

Order No.

Type 744 01 up to 40 terminals assembled with screw terminals 2 x 4 mm + PE-rail 4 mm


Ex-e

1 x plastic flange down

1 x Ex-e1)

without drilling

7 x PE

GHG 744 0101 R0005

Type 745 02 up to 82 terminals assembled with screw terminals 2 x 2.5 mm + PE/PA-rail 4 mm


Ex-e

1 x plastic flange down

1 x Ex-e1)

without drilling

14 x PE

GHG 745 0201 R0004

Type 745 02 up to 82 terminals assembled with screw terminals 2 x 2.5 mm + PE/PA-rail 4 mm


Ex-i
Ex-e

1 x M40 for cable 22-35 mm


8 x M32 for 4 cable 4.5-7 mm

27 x PE/PA

1 x M40 for cable 22-35 mm

60 x Ex-e

30 x M16 for cable 5.5-10 mm


Ex-i

1 x M40 for cable 22-35 mm


30 x M16 for cable 5.5-10 mm

Ex-e

1 x M40 for cable 22-35 mm


24 x M20 for cable 5.5-13 mm

Ex-i

60 x Ex-i

1 x M40 for cable 22-35 mm


24 x M20 for cable 5.5-13 mm

27 x PE/PA

GHG 745 0201 R0012


GHG 745 0201 R0013

60 x Ex-i
27 x PE/PA

GHG 745 0201 R0014

60 x Ex-e
27 x PE/PA

GHG 745 0201 R0015

60 x Ex-i
27 x PE/PA

GHG 745 0201 R0021

Type 745 02 up to 82 terminals assembled with screwless terminals 2 x 2.5 mm + PE/PA-rail 4 mm


Ex-i
Ex-e

1 x M40 for cable 22-35 mm

27 x PE/PA

1 x M40 for cable 22-35 mm

60 x Ex-e

30 x M16 for cable 5.5-10 mm


Ex-i

1 x M40 for cable 22-35 mm


30 x M16 for cable 5.5-10 mm

Ex-e

1 x M40 for cable 22-35 mm


24 x M20 for cable 5.5-13 mm

Ex-i

1 x M40 for cable 22-35 mm


24 x M20 for cable 5.5-13 mm

1)

60 x Ex-i

8 x M32 for 4 cable 4.5-7 mm

27 x PE/PA

GHG 745 0201 R0016


GHG 745 0201 R0017

60 x Ex-i
27 x PE/PA

GHG 745 0201 R0018

60 x Ex-e
27 x PE/PA

GHG 745 0201 R0020

60 x Ex-i
27 x PE/PA

GHG 745 0201 R0022

according to type examination certificate individual extensible

Other types on request

10
11
12
COOPER CROUSE-HINDS GMBH

7.21

Ex-e/Ex-i terminal box

GHG 744 0101 R0005

Type 745 02

GHG 745 0201 R0012

Accessories
Mounting plate for junction box 744 01
Type

Application

Fixing method

Order No.

Size 3
Size 3
Size 3
Protective canopy Size 3

Wall mounting
Trellis mounting
Pipe mounting
for mounting plate size 3

screw mounting
screw mounting
screw mounting

GHG 610 1953 R0107


GHG 610 1953 R0109
GHG 610 1953 R0108
GHG 610 1955 R0104

Mounting plate for junction box 745 02


Type

Application

Fixing method

Order No.

Size 3
Protective canopy Size 3

Pipe mounting
for mounting plate size 3

screw mounting on 2 plates

GHG 610 1953 R0108


GHG 610 1955 R0104

Details for accessories see page 7.78 pp.

Dimension drawing
271
X 247

136
116

136
116

271
X 247

271
X 247

134
X110

7
11
Type 745 02

X = Mounting dimension

Dimensions in mm

Type 744 01

7.22

COOPER CROUSE-HINDS GMBH

Ex-e/Ex-i terminal box

1
2
Type 749 04

Type 746 03

Technical data
GHG 746 03 up to 188 terminals GHG 749 04 up to 296 terminals
Marking to 94/9/EC

II 2 G Ex de ia/ib [ia/ib] m IIC T4 /

EC-Type Examination Certificate

II 2 D Ex tD A21 IP66 T 80 C

PTB 99 ATEX 1044

IECEx certificate of conformity

IECEx BKI 05.0006

Marking accd. to IECEx

Ex ed ia/ib m [ia/ib] IIC T4 T6

Ex tD A21 IP66 T80 C


Permissible ambient temperature

20 C to +40 C
55 C to +55 C (option)

Rated voltage

690 V

Rated current

Depends on terminal mounting

Insulation class

Degree of protection accd. EN 60529

IP66

Enclosure material

Glass-fibre reinforced polyester

Enclosure colour

black

5
6

GHG 746 03 up to 188 terminals


Connecting terminals

300 mm2

Dimensions (L x W x H)

544 x 271 x 136 mm

Weight

approx. 4.2 kg

Drillings/cable glands

M12

M16

M20

M25

M32

M40

M50

Max. number down

120

72

52

36

20

14

Max. number flange plastic

46

25

20

11

Max. number flange metal

11

Terminal mounting space on the terminal rail


Max. number of terminals acc. to certification

M63

horiz. 2 x 510 mm / vert. 4 x 230 mm


2.5 mm2

4 mm2

6 mm2 10 mm2 16 mm2 25 mm2 35 mm2

2 x 94

2 x 78

2 x 59

2 x 47

40

40

32

GHG 749 04 up to 296 terminals


Connecting terminals

up to 240 mm2

Dimensions (L x W x H)

817 x 271 x 136 mm

Weight

approx. 5.8 kg

Drillings/cable glands

M12

M16

M20

M25

M32

M40

M50

M63

Max. number down

180

108

78

54

30

21

12

46

25

20

11

11

Max. number flange plastic


Max. number flange metal
Terminal mounting space on the terminal rail
Max. number of terminals acc. to certification

horiz. 2 x 795 mm / vert. 6 x 230 mm


2.5 mm2

4 mm2

6 mm2 10 mm2 16 mm2 25 mm2 35 mm2

2 x 148

2 x 124

2 x 94

2 x 75

63

63

51

10
11
12

COOPER CROUSE-HINDS GMBH

7.23

Ex-e/Ex-i terminal box

Type 746 03

Type 749 04

Ordering details
Design

Cable gland

No. of Terminals

Order No.

Type 746 03 up to 188 terminals assembled with screw terminals 2 x 4 mm + PE-rail 4 mm


Ex-e

2 x plastic flange down

1 x Ex-e1)

without drilling

2 x 14 x PE

GHG 746 0301 R0002

Type 749 04 up to 296 terminals assembled with screw terminals 2 x 2.5 mm + PE-rail 4 mm
Ex-e
1)

3 x plastic flange down

1 x Ex-e1)

without drilling

3 x 14 x PE

GHG 749 0401 R0001

according to type examination certificate individual extensible

Other types on request

Dimension drawing

116

271

136

X 247

116

Type 749 04

X 273

X = mounting dimension

Dimensions in mm

Type 746 03

X 793

817

544

136

X 520

271
X 247

7.24

COOPER CROUSE-HINDS GMBH

1
2
3
4
5
6
7
8
9
10
11
12
COOPER CROUSE-HINDS GMBH

7.25

Light alloy metal design for Zone 1 and Zone 21

The new sturdy CEAG terminal boxes made


of a light alloy metal are used to distribute and
conduct electricity in hazardous explosive areas
of the Zones 1, 2, 21 and 22. Optionally, all of
the modular terminals up to 35 mm 2 pursuant
to EN 60079-7 are available in these terminal
boxes.
Variable equipment with various cable and line
ducts pursuant to customer specification can
be realised with the terminal boxes made of
light alloy metal.
Drilled holes, cable and line ducts, through
which no lines are conducted, should be
closed with certified threaded stoppers.
High chemical resistance of the housing is
ensured by the use of impact-resistant plastic
powder coating.
Covered screws and all outside and inside
metallic parts are made of stainless steel.
The terminal boxes made of light metal
have an outside earthing connection.
Internationally approved.

Mechanical, chemical and thermal


resistance
Plastic powder coating
Can be equipped individually,
Impact-resistant

7.26

Overview of terminal boxes

To make the choice of the right terminal boxes or branching

the number can be interpreted on the maximum length of

boxes for your application, the tables on this page contain

the terminal strip that can be equipped.

the basic data. You can use these tables to identify and
configure your terminal boxes.

On the basis of the maximum drilled and the faulty circuit


diameter of the cable and line duct, you can select the

In the table of the maximum number of terminals, the infor-

relevant terminal box by means of the number of ducts that

mation is based on the rated current of the terminal concer-

you need.

ned. If the current per terminal is below the rated current,

Maximum number of terminals


acc. to certification
Terminal cross-section in mm2

Type
2.5

10

16

25

GHG 793 0101

35

GHG 723 0001

33

27

20

16

15

GHG 723 1001

88

72

54

44

40

15

15

GHG 723 2001

136

112

84

68

60

22

22

4
5
6

Terminal rail
Type

Rail length

GHG 793 0101

46 mm

GHG 723 0001

185 mm

GHG 723 1001

2 x 242 mm

GHG 723 2001

2 x 362 mm

8
9
Dimensions
Type

Width

Space required for


wire and cable entries
x Length

x Height

max. drilled surface


Type

Width x Height

Type

Interference Diameter

GHG 793 0101

80 mm x 45 mm

Plastic

Metal

GHG 723 0001

180 mm x 53 mm

GHG 723 1001 280 mm x 230 mm x 111 mm

M12

19 mm

21 mm

GHG 723 1001

232 mm x 83 mm

GHG 723 2001 400 mm x 230 mm x 111 mm

M16

25 mm

21 mm

GHG 723 2001

352 mm x 80 mm

M20

31 mm

26.5 mm

M25

37 mm

33 mm

M32

46 mm

45.1 mm

M40

56 mm

53 mm

M50

68 mm

60.5 mm

M63

84 mm

80 mm

GHG 793 0101 130 mm x

82 mm x

72 mm

GHG 723 0001 220 mm x 120 mm x

81 mm

10
11
12

COOPER CROUSE-HINDS GMBH

7.27

Ex-e/Ex-i terminal box

GHG 793 0101 R0003

Technical data
Type 793 01 up to 11 terminals
Marking to 94/9/EC

II 2 G Ex dem ia II, IIC T6 /

Permissible ambient temperature

II 2 D A21 IP66 T80 C

20 C to +40 C
55 C to +55 C (option)

EC-Type Examination Certificate

PTB 00 ATEX 3108

Rated voltage

up to 690 V

Rated current

depends on terminal mounting

Degree of EN 60529

IP66

Enclosure material

light alloy die-casting (AlSi)

Enclosure colour

light grey

Terminal cross section

up to 6 mm2

Weight

approx. 0.68 kg

Drillings/cable glands

M16

M20

M25

M32

M40

M50

M63

Max. number down


Max. number of terminals acc. to certification

2.5 mm2

4 mm2

6 mm2

16

14

10

Ordering details
Design

Cable gland

No. of Terminals

Order No.

Typ 793 01 up to 11 terminals with screw terminals 2 x 2.5 mm + PE-terminal 2 x 4 mm


Ex-e

without drilling

1 x Ex-e*/1 x PE

GHG 793 0101 R0003

* according to type examination certificate individual open ended

Dimension drawing

82
X68

X 116
130

50
72

Z
5.5

9.5

Dimensions in mm

Type 793 01

7.28

COOPER CROUSE-HINDS GMBH

Ex-e/Ex-i terminal box

1
2
GHG 723 2001 R0002

GHG 723 1001 R0002

GHG 723 0001 R0002

Technical data
Type 723 00 723 10 723 20 up to 96 terminals
Marking to 94/9/EC

II 2 G Ex de ia/ib [ia/ib] m IIC T4 /

Permissible ambient temperature

II 2 D Ex tD A21 IP66 T 80 C

20 C to +40 C

55 C to +55 C (option)
EC-Type Examination Certificate

PTB 99 ATEX 1044

Rated voltage

up to 690 V

Rated current

depends on terminal mounting

Degree of EN 60529

IP66

Enclosure material

light alloy die-casting (AlSi)

Enclosure colour

light grey

Type 723 00 up to 24 terminals


Terminal cross section

max. 35 mm2

Weight

approx. 1.41 kg

Max. number drillings/cable glands

M16

M20

M25

M32

M40

M50

down

Terminal mounting space on the terminal rail

1 x 185 mm

Max. number of terminals acc. to certification

2.5 mm2

4 mm2

6 mm2

10 mm2

16 mm2

25 mm2

35 mm2

24

24

18

18

14

Type 723 10 up to 82 terminals

Terminal cross section

max. 50 mm2

Weight

approx. 3.84 kg

Drillings/cable glands

M16

M20

M25

M32

M40

M50

22

10

Max. number down


Terminal mounting space on the terminal rail

2 x 242 mm

Max. number of terminals acc. to certification

2.5 mm2

4 mm2

6 mm2

10 mm2

16 mm2

25 mm2

35 mm2

2 x 41

2 x 34

2 x 26

2 x 20

1 x 17

1 x 17

1 x 14

Type 723 20 up to 96 terminals


Terminal cross section

max. 95 mm2

Weight

approx. 4.87 kg

Drillings/cable glands

M16

M20

M25

M32

M40

M50

30

18

10

Max. number down

Terminal mounting space on the terminal rail

3 x 362 mm

Max. number of terminals acc. to certification

2.5 mm2

4 mm2

6 mm2

10 mm2

16 mm2

25 mm2

35 mm2

2 x 48

2 x 48

2 x 36

2 x 36

1 x 28

1 x 23

1 x 22

10
11
12
COOPER CROUSE-HINDS GMBH

7.29

Ex-e/Ex-i terminal box

GHG 723 0001 R0002

GHG 723 1001 R0002

GHG 723 2001 R0002

Ordering details
Design

Cable gland

No. of Terminals

Order No.

Type 723 00 mounted with screw terminals 2 x 2.5 mm2 + PE-terminal 4 mm2
Ex-e

without drilling

1 x Ex-e1)/1 x PE

GHG 723 0001 R0002

Type 723 10 mounted with screw terminals 2 x 2.5 mm2 + PE-terminal 4 mm2
Ex-e

without drilling

1 x Ex-e1)/14 x PE

GHG 723 1001 R0002

Type 723 20 mounted with screw terminals 2 x 2.5 mm2 + PE-terminal 4 mm2
Ex-e
1)

without drilling

1 x Ex-e1)/14 x PE

according to type examination certificate individual extensible

7.30

COOPER CROUSE-HINDS GMBH

GHG 723 2001 R0002

Ex-e/Ex-i terminal box

1
2
GHG 723 2001 R0002

GHG 723 1001 R0002

GHG 723 0001 R0002

Dimension drawing
Z
Z

120
X78

20.8

60
80

X 204
220

Type 723 00
Z
Z
26

230
X180

6.5

7
X 260
280

91
111

Type 723 10
Z
Z
26

230
X180

6.5

10
X 380
400

X = mounting dimension
Dimensions in mm

Type 723 20

91
111

COOPER CROUSE-HINDS GMBH

7.31

11
12

Light metal design, explosion-proof for Zone 1 and Zone 21

Series C30 and C31 explosion-protected


terminal boxes made of light metal are used
to distribute and conduct electricity in areas
of Zone 1, 2, 21 and 22 at no risk of explosion.
Optionally, they are equipped with a assembly
plate with pillar terminals or with terminals
on an assembly plate with a terminal strip for
individual equipment.
The connection cross-section can vary by up to
6 mm 2 or up to 10 mm 2 .
A high IP degree of protection allows universal
use in areas at risk of explosion.
Optionally, the cables can be introduced into the
terminal boxes via conduits or explosion-proof
screw connections. Drilled holes through which
no cables are conducted should be closed with
certified threaded stoppers.
The light metal terminal boxes have an outside
earthing connection.

High mechanical, chemical and


thermal resistance
High degree of protection IP67

7.32

Ex-d terminal box

1
2
Terminal block C31

Type C31

Terminal block C30

Type C30

Technical data
Type C30 Type C31
Marking to 94/9/EC

II 2 G Ex d IIC T6 /

EC-Type Examination Certificate

II 2 D IP67 T 85 C

LOM 02 ATEX 2037 X

IECEx Certificate of Conformity

IECEx BKI 07.0026

Marking accd. to IECEx

Ex d IIC T6

Ex tD A21 IP67 T85 C


Permissible ambient temperature

20 C to +55 C

Rated voltage

690 V

Rated current (max.)

C30: 40 A / C31: 61 A

Insulation class

Degree of protection accd. EN 60529

IP67

Enclosure material

light alloy

Enclosure colour

natural finish

5
6

Type C30
Connecting terminals

up to 6 mm2

Weight

approx. 0.8 kg (empty)

Max. number of drillings/cable glands

Terminal mounting space on the terminal rail

45 mm

Type C31
Connecting terminals

up to 10 mm2

Weight

approx. 1.3 kg (empty)

Max. number of drillings/cable glands

Terminal mounting space on the terminal rail

82 mm

8
9
10
11
12
COOPER CROUSE-HINDS GMBH

7.33

Ex-d terminal box

Type C30

Type SUSC30

Type C31

Terminal block C31

Ordering details
Thread ISO 7/11)

Order No.

C30 T1

3 x 1/ 2

NOR 000 001 151 181

C30 T2

3 x 3/ 4

NOR 000 001 151 199

C30 X1

4 x 1/ 2

NOR 000 001 151 206

C30 X2

4 x 3/ 4

NOR 000 001 151 214

C31 T1

3 x 1/ 2

NOR 000 111 150 001

C31 T2

3 x 3/ 4

NOR 000 111 150 002

C31 T3

3 x 1

NOR 000 111 150 003

C31 X1

4 x 1/ 2

NOR 000 111 150 004

C31 X2

4 x 3/ 4

NOR 000 111 150 005

C31 X3

4 x 1

NOR 000 111 150 006

Type
Type C30

Type C31

Accessories
Build-in components type C30
Type

Version

No. of terminals

Order No.

BC 30

Mounting plate with


pillor terminals 4 x 4 mm2
Terminal rail DIN 46877
Mounting plate without terminals

4 x Ex-e 2)

NOR 000 001 151 222

Mounting rail

NOR 000 000 115 314


NOR 000 000 115 302

PBPD 30
PC 30

Mounting angel for housing fixing type C30


Type

Order No.

SUSC 30

NOR 000 000 115 311

Build-in components type C31


Type

Version

No. of terminals

Order No.

BC31
P C31
PBPD 31

Mounting plate with pillar terminals


Mounting plate without terminals
Terminal rail DIN 46877

4 x 4 mm2 2)

NOR 000 111 150 009


NOR 000 000 115 306
NOR 000 000 115 015

1)

Other threads on request

2)

4 x 4 mm2 multi-wire or 2 x 6 mm2 solid

7.34

COOPER CROUSE-HINDS GMBH

Ex-d terminal box

1
2
Terminal block C31

Type C31

Terminal block C30

Type C30

Dimension drawing

4
Type C30 T

Type C31 T

5
6

Thread

Thread

Type C30 X

Type C31 X

X 95

90

104

150
X 130

150

90

60

98

108

X = mounting dimensions

Dimensions in mm

10

COOPER CROUSE-HINDS GMBH

7.35

11
12

E X - T E R M I N A L

E N C L O S U R E S

Stainless steel version for Zone 1 and Zone 21

The new explosion-protected terminal


enclosures made of stainless steel (AISI 316 L)
with ground surfaces was developed for
instrumentation and control installations using
the Ex-e and Ex-i technologies.
They act as a link between the main cable to
the control room and the branch cables into
the field. In addition to this, they may also be
used for the direct connection of actuators
and sensors. Here the metal cable glands
also allow electromagnetically compatible
connection methods.
The robust design of the stainless steel terminal
boxes provides a high degree of safety for
offshore applications and in places where
particularly adverse chemical, mechanical and
climatic operating conditions prevail within the
hazardous area.
Three terminal enclosures series in various sizes
are available for accommodating up to terminals.
The choice between screw and tension-spring
(screwless) terminals for single and multi-wire
conductors makes it possible for the installation
engineers to select the type of connection that
is most suitable for the respective application.
Two separate PE rails are available for the
separate connection of PE/PA and screened
cables. Due to the optimized design, there is
a large drilling area for fitting a large number
of metal glands. Unused entry holes must be
sealed safely with certified blanking plugs. As
an alternative, a screw-on metal flange can
be used for a wide variety of applications.
International approvals

Stainless steel AISI 316 L,


electro-polished surface
Highly resistant silicone seals
Metal flanges available on request
Safety standard IP66
PE/PA rails

7.36

Overview of terminal enclosures

This external & internal brass earth/ground stud assembly

The enclosure is mounted by four heavy-duty 3 mm thick

enables rapid and reliable protective earth/ground connec-

surface welded and stainless steel lugs, with slotted bottom

tion, which is mounted on the side of the enclosure for ease

lugs for ease of mounting. These provide a secure, reliable

of access.

means of mounting the enclosure

2
3
To make the choice of the right terminal boxes or branching

the number can be interpreted on the maximum length of

boxes for your application, the tables on this page contain

the terminal strip that can be equipped.

the basic data. You can use these tables to identify and
configure your terminal boxes.

On the basis of the maximum drilled and the interference


diameter of the cable and line duct, you can select the

In the table of the maximum number of terminals, the infor-

relevant terminal box by means of the number of ducts

mation is based on the rated current of the terminal concer-

that you need.

ned. If the current per terminal is below the rated current,

Next Range
Max.

Ex-Cell Range
Max. entry

Max.

terminal

guide (M16)

capacity

Top-Bottom/

STB Range

Max. entry

Max.

Max. entry

terminal

guide (M16)

terminal

guide (M16)

capacity

Top-Bottom/

capacity

Top-Bottom/

Size

(2.5 mm2)

Left/Right

Size

(2.5 mm2)

Left/Right

Size

(2.5 mm2)

Left/Right

22/15/13

1 x 21

6/6/6

23/15/13

1 x 21

6/6/6

12/12/08

1x 8

7/7/4

26/26/16

2 x 27

20/9/9

26/26/15

1 x 27

21/11/11

15/12/08

1 x 13

7/9/6

26/26/20

2 x 27

28/18/18

30/20/15

1 x 36

15/15/15

15/15/09

1 x 13

9/9/6

30/30/16

2 x 36

26/20/26

30/30/15

2 x 36

26/15/15

19/15/09

1 x 21

9/12/8

30/30/20

2 x 36

34/28/34

30/30/20

2 x 36

34/28/34

19/19/10

1 x 21

18/18/14

38/26/16

2 x 51

20/20/20

40/30/15

2 x 56

26/26/26

25/25/12

2 x 31

32/32/26

38/26/20

2 x 51

28/28/28

40/30/20

2 x 56

34/34/34

16/38/12

1 x 55

50/20/44

45/38/16

2 x 67

29/29/29

40/40/15

3 x 56

35/26/26

25/40/13

3 x 31

54/32/48

45/38/20

2 x 67

46/46/46

40/40/20

3 x 56

44/34/34

38/38/22

3 x 42

100/100/88

48/48/20

3 x 71

53/46/53

40/50/15

4 x 56

48/26/26

40/60/22

3 x 46

164/108/92

50/35/20

3 x 75

40/40/40

40/50/20

4 x 56

62/34/34

60/40/22

5 x 79

108/164/152

62/45/20

4 x 99

53/53/53

50/40/15

3 x 77

35/35/35

74/55/20

5 x 124

60/60/60

50/40/20

3 x 77

44/44/44

76/50/20

3 x 128

53/82/82

50/50/15

4 x 77

48/35/35

86/64/20

6 x 147

82/80/80

50/50/20

4 x 77

62/44/44

91/61/20

5 x 158

72/72/72

50/60/20

6 x 77

78/44/44

Size

98/74/20

6 x 171

80/106/106

60/40/15

3 x 97

35/48/48

744 21

60/40/20

3 x 97

44/62/62

745 22

82

60/50/15

4 x 97

48/48/48

746 23

188

60/50/20

4 x 97

62/62/62

749 24

296

60/60/15

6 x 97

59/48/48

60/60/20

6 x 97

78/62/62

60/76/20

7 x 97

100/62/62

76/50/20

4 x 128

62/78/78

76/60/20

6 x 128

78/78/78

76/76/20

7 x 128

100/78/78

30/35/20
landscape

3 x 36

40/28/34

4 x 36

53/28/28

5 x 67

60/44/44

38/45/20
landscape
45/55/20
landscape
50/64/20
landscape

6 x 75

82/53/53

7
8

GHG 74 . 2 Range

Max. terminal
capacity (2.5 mm2)
40

10
11
12

COOPER CROUSE-HINDS GMBH

7.37

E X - T E R M I N A L

E N C L O S U R E S

Stainless Steel Version for Zone 1 and Zone 21


NEXT

The NEXT enclosure has been specifically


designed for installation in locations with
aggressively hostile environmental con ditions.
These include such locations as petrochemical
hazardous areas, pharmaceutical, food process
and utility applications.
Manufactured from high quality stainless steel
that is electro-polished for a highly corrosion
resistant Chromium enriched surface.
This multi certified enclosure is available in a
comprehensive range of 17 different sizes and
two depths, each with the facility for many con figuration possibilities for a multitude of appli cations.
Using the highest quality materials, unique
design benefits and precision manufacturing
the NEXT range is the benchmark in heavy-duty
gauge enclosures of its class with a 25 year
design life.
An integral drainage channel prevents liquids
or other solids contaminates from running in
or falling into the enclosure when the door is
opened, and to minimise gasket path conta mination.
The high integrity one piece sealing gasket
for superior ingress protection (IP) of 66 and
excellent recovery and re-sealing properties
for continuous environmental protection.
An option for the mounting of up to four 3 mm
thick gland-plates on each side in 4 possible
combinations of 1, 2, 3 or 4 gland-plates. All
sealed to IP66 by a high integrity Chloroprene
gasket and secured by stainless steel bolts
into blind inserts.
316L Stainless Steel (1.4404 to EN 10088)
Superior corrosion resistant electro
chemically polished
High integrity one piece closed cell
chloroprene or optional silicone gasket
Detachable hinged door, stainless steel
hinges with captive stainless steel hex
screws
4 x external welded lugs,
11 mm holes / slots.
Optional Gland Plate / Entries 3 mm thick
Extended ambient temperatures -65 C to
+ 55 C as option.
Certification GOST-R, AEx, cULus and
Germanischer Lloyd on request.

7.38

Ex-e terminal enclosures

1
2
NEXT

NEXT

Technical data
Ex-e Terminal Enclosure NEXT
Marking to 94/9/EC

II 2 G Ex e ia II, IIC T6, T5 /

Temperature class

T6 up to +40 C / T5 up to +55 C

EC-Type Examination Certificate

PTB 04 ATEX 1015

Permissible ambient temperature

45 C to +55 C

II 2 D Ex tD A21 IP66 T80 C, T95 C

65 C to +55 C (option: Silicone gasket)


Rated voltage

up to 1100 V1)

Rated current

up to 500 A1)

Connecting terminals

up to 240 mm2

Insulation class

Degree of protection accd. EN 60529

IP66

Cable glands/Gland plates/Enclosure drilling

1)

up to 4 side optional gland plate (3 mm)


combination with entries to meet requirements

Type of mounting

4 x 3 mm welded lugs with 11 mm holes/slots, horizontal

Enclosure material

stainless steel 316 L electro chemically polished or

sheet steel polyester powder coated (RAL 7032)


Material thickness

1.5 mm, 2 mm (- 62/45/20 and over)

Equipment mountings

4 x stand off pillars 9 mm, 25 mm height, tapped M6 x 10,


for rail or mounting plate

Enclosure earth

M10 external/internal brass earth stud assembly,


M6 intern. stud on lid & painted gland plates

Gasket material
1)

Chloroprene gasket, Silicone gasket (option)

depending on type of terminal and Ex-components used

Additional Approvals:
cULUs types 3S, 4, 4 x approval suitable for
Class I, Div 2 applications, Class I Zone 1, AExe II T6 (Limited range available),

GOST R, Germanischer Lloyd

Dimension drawing
Width

Height

Fixing Centres
(vertical)

Rail Fixing
Pillars

10

Dimensions in mm

Depth

Fixing Centres
(horizontal)

COOPER CROUSE-HINDS GMBH

7.39

11
12

Ex-e terminal enclosures

NEXT

Ordering details NEXT METRIC up to 2 x 51 terminals


NEXT

Dimensions1)

Fixing

Weight

Terminal mounting rail

Terminal content

H x W x D in mm

Centres1)

in kg

Rail fixing

Row orientation vertical (thickness in mm)

Fvertical x

(empty

centres

Fhorizontal

enclosure) vert.

Size

Rail length

horiz. vert.

horiz.

2.5 (5)

4 (6)

6 (8)

10 (10)

Enclosure dimensions and terminal content


22/15/13 229x152x130

152x2082)

3.25

129

52

149

72

1x21

1x17

1x13

1x10

26/26/16 260x260x160

170x316

5.50

160

160

180

180

2x27

2x23

1x17

1x13

26/26/20 260x260x205

170x316

5.50

160

160

180

180

2x27

2x23

1x17

1x13

30/30/16 306x306x160

203x3612)

7.00

206

260

226

226

2x36

2x30

2x23

2x18

30/30/20 306x306x205

203x3612)

7.00

206

206

226

226

2x36

2x30

2x23

2x18

38/26/16 380x260x160

250x316

7.00

280

180

300

160

2x51

2x43

1x32

1x25

38/26/20 380x260x205

250x316

7.00

280

180

300

160

2x51

2x43

1x32

1x25

NEXT

Available glanding area

Top &

Left

Order No.3)

Max. Entry Guide (metric)

Right

Top & Bottom / Left / Right

Bottom
Size

(with gland plates fitted) in mm

M16

M20

M25

M32

M40

M50

M63

Gland entry detail


22/15/13

NXTS12215130

58x108

58x108

58x108

6/6/6

3/3/3

2/2/2

1/1/1

26/26/16 214x 80

114x 80

114x 80

20/9/9

10/6/6

6/3/2

3/2/3

3/1/1

2/1/1

NXTS12626160

26/26/20 214x124

114x124

114x124

28/18/18 15/9/9

12/5/5

6/4/4

5/2/2

2/1/1

2/1/1

NXTS12626200

30/30/16 261x 80

214x 80

261x 80

26/20/26 14/10/14 8/6/8

4/3/4

3/3/3

3/2/3

NXTS13030160

30/30/20 261x124

214x124

261x124

34/28/34 20/15/20 15/12/15 8/6/8

6/5/6

3/2/3

2/2/2

NXTS13030200

38/26/16 214x 80

214x 80

214x 80

20/20/20 10/10/10 6/6/6

3/3/3

3/3/3

2/2/2

NXTS13826160

38/26/20 214x124

214x124

214x124

28/28/28 15/15/15 12/12/12 6/6/6

5/5/5

2/2/2

2/2/2

NXTS13826200

Options
with 1 gland plate

NXT S1 XXYYZZ 1

with 2 gland plates

NXT S1 XXYYZZ 2

with 3 gland plate

NXT S1 XXYYZZ 3

with 4 gland plates

NXT S1 XXYYZZ 4

NXT Painted

NXT PS XXYYZZ N

Permanent Padlock Hasp Facility


(Factory Fitted ONLY)

Type

NXT NN XXYYZZ0-HASP
Order No.

Example
30/30/16 with 3 gland plates, painted and Padlock HASP facility

NXTPS13030163-HASP

Notes: 1) Dimensions drawing see page 7.39

7.40

2)

1233) Subtract 30 mm when no side gland plates

3)

Refer to OPTIONS for full order number detail

COOPER CROUSE-HINDS GMBH

Ex-e terminal enclosures

1
2
NEXT

Ordering details NEXT METRIC up to 3 x 128 terminals


NEXT

Dimensions1)

Fixing

Weight

Terminal mounting rail

Terminal content

H x W x D in mm

Centres1)

in kg

Rail fixing

Row orientation vertical (thickness in mm)

Fvertical x

(empty

centres

Fhorizontal

enclosure) vert.

Size

Rail length

horiz. vert.

horiz.

2.5 (5)

4 (6)

6 (8)

10 (10)

2x33

Enclosure dimensions and terminal content


45/38/16 458x382x160

305x4372)

9.75

358

282

378

302

2x 67

2x 56

2x42

45/38/20 458x382x205

305x4372)

9.75

358

282

378

302

2x 67

2x 56

2x42

2x33

48/48/20 480x480x205

327x5352)

10.40

380

380

400

400

3x 71

3x 59

3x44

3x35

50/35/20 500x350x205

350x406

10.50

400

260

420

270

3x 75

2x 63

2x47

2x37

62/45/20 620x450x205

450x506

17.00

520

350

540

370

4x 99

3x 83

3x62

3x49

74/55/20 740x550x205

540x606

30.40

640

450

660

470

5x124

4x103

4x77

4x61

76/50/20 762x508x205

508x5642)

23.50

662

408

682

428

3x128

3x106

3x80

3x64

NEXT

Available glanding area

Top &

Left

Order No.3)

Max. Entry Guide (metric)

Right

Top & Bottom / Left / Right

Bottom
Size

(with gland plates fitted) in mm

M16

M20

M25

M32

M40

M50

M63

Gland entry detail


45/38/16 337x 80

337x 80

337x 80

29/29/29 18/18/18 10/10/10 6/6/6

5/5/5

4/4/4

NXTS14538160

45/38/20 337x124

337x124

337x124

46/46/46 26/26/26 21/21/21 11/11/11 9/9/9

4/4/4

3/3/3

NXTS14538200

48/48/20 404x124

337x124

404x124

53/46/53 30/26/30 24/21/24 14/11/14 11/9/11 5/4/5

4/3/4

NXTS14848200

50/35/20 304x124

304x124

304x124

40/40/40 24/24/24 18/18/18 10/10/10 7/7/7

4/4/4

3/3/3

NXTS15035200

62/45/20 404x124

404x124

404x124

53/53/53 30/30/30 24/24/24 14/14/14 11/11/11 5/5/5

4/4/4

NXTS16245200

74/55/20 504x124

504x124

504x124

60/60/60 39/39/39 30/30/30 18/18/18 13/13/13 6/6/6

5/5/5

NXTS17455200

76/50/20 404x124

594x124

594x124

53/82/82 30/47/47 24/39/39 14/20/20 11/17/17 5/7/7

4/6/6

NXTS17650200

Options
with 1 gland plate

NXT S1 XXYYZZ 1

with 2 gland plates

NXT S1 XXYYZZ 2

with 3 gland plate

NXT S1 XXYYZZ 3

with 4 gland plates

NXT S1 XXYYZZ 4

NXT Painted

NXT PS XXYYZZ N

Permanent Padlock Hasp Facility


(Factory Fitted ONLY)

Type

NXT NN XXYYZZ0-HASP

Order No.

Example
62/45/20 with 3 gland plates, 316L SS and Padlock HASP facility

NXTS162445203-HASP

Notes: 1) Dimensions drawing see page 7.39


2)

1233) Subtract 30 mm when no side gland plates

3)

Refer to OPTIONS for full order number detail

10
11
12

COOPER CROUSE-HINDS GMBH

7.41

Ex-e terminal enclosures

NEXT

Ordering details NEXT METRIC up to 6 x 171 terminals


NEXT

Dimensions1)

Fixing

Weight

Terminal mounting rail

Terminal content

H x W x D in mm

Centres1)

in kg

Rail fixing

Row orientation vertical (thickness in mm)

Fvertical x

(empty

centres

Fhorizontal

enclosure) vert.

horiz. vert.

horiz.

2.5 (5)

4 (6)

6 (8)

10 (10)

4x73

Size

Rail length

Enclosure dimensions and terminal content


86/64/20 860x640x205

570x696

29.00

760

540

780

560

6x147

5x123

5x 92

91/61/20 914x610x205

559x6662)

31.00

814

510

834

530

5x158

5x132

4x 99

4x79

98/74/20 980x740x205

700x796

38.00

880

640

900

660

6x171

6x143

5x107

5x85

NEXT

Available glanding area

Top &

Left

Order No.3)

Max. Entry Guide (metric)

Right

Top & Bottom / Left / Right

Bottom
Size

(with gland plates fitted) in mm

M16

M20

M25

M32

M40

M50

M63

82/80/80

47/48/48 39/36/36 20/20/20 17/14/14 7/8/8

6/6/6

42/42/42 24/24/24 18/18/18 8/8/8

Gland entry detail


86/64/20 594x124

NXTS18664200

2x

2x

(304x124)

(304x124)

91/61/20 566x108

566x108

566x108

72/72/72

6/6/6

NXTS19161200

98/74/20 2x

2x

2x

80/106/106 48/60/60 36/48/48 20/28/28 14/22/22 8/10/10 6/8/8

NXTS19874200

(404x124)

(404x124)

(304x124)

7/7/7

Options
with 1 gland plate

NXT S1 XXYYZZ 1

with 2 gland plates

NXT S1 XXYYZZ 2

with 3 gland plate

NXT S1 XXYYZZ 3

with 4 gland plates

NXT S1 XXYYZZ 4

NXT Painted

NXT PS XXYYZZ N

Permanent Padlock Hasp Facility


(Factory Fitted ONLY)

Type

NXT NN XXYYZZ0-HASP
Order No.

Example
91/61/20 with 1 gland plate, 316L SS and Padlock HASP facility

NXTS19161201-HASP

Notes: 1) Dimensions drawing see page 7.39

7.42

2)

1233) Subtract 30 mm when no side gland plates

3)

Refer to OPTIONS for full order number detail

COOPER CROUSE-HINDS GMBH

Ex-e terminal enclosures

1
2
NEXT

Ordering details NEXT METRIC up to 6 x 75 terminals


NEXT

Dimensions1)

Fixing

Weight

Terminal mounting rail

Terminal content

H x W x D in mm

Centres1)

in kg

Rail fixing

Row orientation vertical (thickness in mm)

Fvertical x

(empty

centres

Fhorizontal

enclosure) vert.

Size

Rail length

horiz. vert.

horiz.

2.5 (5)

4 (6)

6 (8)

10 (10)

Enclosure dimensions and terminal content landscape orientation


30/35/20 306x350x205

203x405

7.70

206

250

226

270

3x36

2x30

2x23

2x18

38/45/20 380x450x205

250x506

10.60

280

350

300

370

4x36

3x36

3x30

3x23

45/55/20 458x550x205

305x606

14.90

358

450

378

470

5x67

4x56

4x42

4x33

50/64/20 500x640x205

350x696

20.90

400

540

420

560

6x75

5x63

5x47

4x37

NEXT

Available glanding area

Top &

Left

Order No.3)

Max. Entry Guide (metric)

Right

Top & Bottom / Left / Right

Bottom
Size

(with gland plates fitted) in mm

M16

M20

M25

M32

M40

M50

M63

Gland entry detail landscape orientation


30/35/20 304x124

214x124

258x124

40/28/34 24/15/18 18/12/15 10/6/8

7/5/6

4/2/3

3/2/2

NXTS13035201

38/45/20 404x124

214x124

214x124

53/28/28 30/15/15 24/12/12 14/6/6

11/5/5

5/2/2

4/2/2

NXTS13845201

45/55/20 504x124

334x124

334x124

60/44/44 39/26/26 30/21/21 18/11/11 13/9/9

6/4/4

5/3/3

NXTS14555201

50/64/20 594x124

404x124

404x124

82/53/53 47/30/30 39/24/24 20/14/14 17/11/11 7/5/5

6/4/4

NXTS15064201

Options
with 1 gland plate

NXT S1 XXYYZZ 1

with 2 gland plates

NXT S1 XXYYZZ 2

with 3 gland plate

NXT S1 XXYYZZ 3

with 4 gland plates

NXT S1 XXYYZZ 4

NXT Painted

NXT PS XXYYZZ N

Permanent Padlock Hasp Facility


(Factory Fitted ONLY)

Type

NXT NN XXYYZZ0-HASP

Order No.

Example
30/35/20 with 3 gland plates, painted and Padlock HASP facility

NXTPS303520-HASP

Notes: 1) Dimensions drawing see page 7.39


2)

1233) Subtract 30 mm when no side gland plates

3)

Refer to OPTIONS for full order number detail

10
11
12

COOPER CROUSE-HINDS GMBH

7.43

Ex-e terminal enclosures

NEXT

Ordering details NEXT IMPERIAL up to 2 x 51 terminals


NEXT

Dimensions1)

Fixing

Weight

HxWxD

Centres1)

in pounds Rail fixing

Fvertical x

(empty

Fhorizontal

enclosure) vert.

in inches
Size

Terminal mounting rail

Terminal content

Rail length

Row orientation vertical

centres
horiz. vert.

horiz.

2.5 (5)

4 (6)

6 (8)

10 (10)

Enclosure dimensions and terminal content


22/15/13

5.98x 8.192)

7.15

5.08 2.05

5.87 2.83

1x21

1x17

1x13

1x10

6.69x12.44

12.10

6.30 6.30

7.09 7.09

2x27

2x23

1x17

1x13

26/26/20 10.24x10.24x8.07

6.69x12.44

12.10

6.30 6.30

7.09 7.09

2x27

2x23

1x17

1x13

30/30/16 12.05x12.05x6.3

0.79x 1.422)

15.40

8.11 8.11

8.90 8.90

2x36

2x30

2x23

2x18

30/30/20 12.05x12.05x8.07

0.79x 1.422)

15.40

8.11 8.11

8.90 8.90

2x36

2x30

2x23

2x18

38/26/16 14.96x10.24x6.3

9.84x12.44

15.40

11.02 7.09

11.81 6.30

2x51

2x43

1x32

1x25

38/26/20 14.96x10.24x8.07

9.84x12.44

15.40

11.02 7.09

11.81 6.30

2x51

2x43

1x32

1x25

9.02x 5.98x5.12

26/26/16 10.24x10.24x6.3

NEXT

Available glanding area

Top &

Left

Order No.3)

Max. Entry Guide (imperial)

Right

Top & Bottom / Left / Right

Bottom
Size

(with gland plates fitted) in inches

/2 NPT

/4 NPT 1 NPT

11/4 NPT 11/2 NPT 2 NPT 21/2 NPT

Gland entry detail


22/15/13

4.25x2.28 4.25x2.28

4.25x2.28

3/3/3

2/2/2

2/2/2

NXTS12215130

26/26/16

8.43x3.15 4.49x3.15

4.49x3.15

11/5/5

4/2/2

4/2/2

3/1/1

2/1/1

NXTS12626160

26/26/20

17/8/8

12/6/6

NXTS12626200

8.43x4.88 4.49x4.88

4.49x4.88

7/3/3

5/2/2

2/1/1

2/1/1

2/1/1

30/30/16 10.28x3.15 8.43x3.15

10.28x3.15

13/11/13 5/4/5

4/4/4

4/3/4

3/2/3

NXTS13030160

30/30/20 10.28x4.88 8.43x4.88

10.28x4.88

20/17/20 15/12/15 8/7/8

7/5/7

3/2/3

2/2/2

2/2/2

NXTS13030200

38/26/16

8.43x3.15 8.43x3.15

8.43x3.15

11/11/11 4/4/4

4/4/4

3/3/3

2/2/2

NXTS13826160

38/26/20

8.43x4.88 8.43x4.88

8.43x4.88

17/17/17 12/12/12 7/7/7

5/5/5

2/2/2

2/2/2

2/2/2

NXTS13826200

Options
with 1 gland plate

NXT S1 XXYYZZ 1

with 2 gland plates

NXT S1 XXYYZZ 2

with 3 gland plate

NXT S1 XXYYZZ 3

with 4 gland plates

NXT S1 XXYYZZ 4

NXT Painted

NXT PS XXYYZZ N

Permanent Padlock Hasp Facility


(Factory Fitted ONLY)

Type

NXT _ XXYYZZ0-HASP
Order No.

Example
38/26/20 with 1 gland plate, painted and Padlock HASP facility

NXTPS13826201-HASP

Notes: 1) Dimensions drawing see page 7.39

7.44

2)

1233) Subtract 30 mm when no side gland plates

3)

Refer to OPTIONS for full order number detail

COOPER CROUSE-HINDS GMBH

Ex-e terminal enclosures

1
2
NEXT

Ordering details NEXT IMPERIAL up to 3 x 128 terminals


NEXT

Dimensions1)

Fixing

Weight

HxWxD

Centres1)

in pounds Rail fixing

Fvertical x

(empty

Fhorizontal

enclosure) vert.

in inches
Size

Terminal mounting rail

Terminal content

Rail length

Row orientation vertical

centres
horiz. vert.

horiz.

2.5 (5)

4 (6)

6 (8)

10 (10)

Enclosure dimensions and terminal content


45/38/16 18.03x15.04x6.30

12.01x17.202)

21.45

14.09 11.10 14.88 11.89

2x 67

2x 56

2x42

2x33

45/38/20 18.03x15.04x8.07

12.01x17.202)

21.45

14.09 11.10 14.88 11.89

2x 67

2x 56

2x42

2x33

48/48/20 18.09x18.09x8.07

12.87x21.062)

22.88

14.96 14.96 15.75 15.75

3x 71

3x 59

3x44

3x35

50/35/20 19.69x13.78x8.07

13.78x15.98

23.10

15.75 10.24 16.54 10.63

3x 75

2x 63

2x47

2x37

62/45/20 24.41x17.72x8.07

17.72x19.92

37.40

20.47 13.78 21.26 14.57

4x 99

3x 83

3x62

3x49

74/55/20 29.13x21.65x8.07

21.26x23.86

66.88

25.20 17.72 25.98 18.50

5x124

4x103

4x77

4x61

76/50/20 30.00x20.00x8.07

20.00x22.202)

51.70

26.06 16.06 26.85 16.85

3x128

3x106

3x80

3x64

NEXT

Available glanding area

Top &

Left

Order No.3)

Max. Entry Guide (imperial)

Right

Top & Bottom / Left / Right

Bottom
Size

(with gland plates fitted) in inches

/2 NPT

/4 NPT 1 NPT

11/4 NPT 11/2 NPT 2 NPT 21/2 NPT

Gland entry detail


45/38/16 13.27x3.15 13.27x3.15 13.27x3.15

18/18/18 7/7/7

5/5/5

4/4/4

NXTS14538160

45/38/20 13.27x4.88 13.27x4.88 13.27x4.88

27/27/27 21/21/21 11/11/11 9/9/9

4/4/4

3/3/3

3/3/3

NXTS14538200

48/48/20 15.91x4.88 13.27x4.88 15.91x4.88

33/27/33 26/21/26 14/11/14 11/9/11 5/4/5

4/3/4

3/3/3

NXTS14848200

50/35/20 11.97x4.88 11.97x4.88 11.97x4.88

24/24/24 18/18/18 10/10/10 8/8/8

4/4/4

3/3/3

2/2/2

NXTS15035200

62/45/20 15.91x4.88 15.91x4.88 15.91x4.88

33/33/33 26/26/26 14/14/14 11/11/11 5/5/5

4/4/4

3/3/3

NXTS16245200

74/55/20 19.84x4.88 19.84x4.88 19.84x4.88

41/41/41 32/32/32 18/18/18 14/14/14 6/6/6

5/5/5

4/4/4

NXTS17455200

76/50/20 15.91x4.88 23.39x4.88 23.39x4.88

33/48/48 26/39/39 14/21/21 11/17/17 5/7/7

4/6/6

3/5/5

NXTS17650200

6/6/6

Options
with 1 gland plate

NXT S1 XXYYZZ 1

with 2 gland plates

NXT S1 XXYYZZ 2

with 3 gland plate

NXT S1 XXYYZZ 3

with 4 gland plates

NXT S1 XXYYZZ 4

NXT Painted

NXT PS XXYYZZ N

Permanent Padlock Hasp Facility


(Factory Fitted ONLY)

Type

NXT NN XXYYZZ0-HASP

Order No.

Example
62/45/20 with 3 gland plates, painted and Padlock HASP facility

NXTPS62445203-HASP

Notes: 1) Dimensions drawing see page 7.39


2)

1233) Subtract 30 mm when no side gland plates

3)

Refer to OPTIONS for full order number detail

10
11
12

COOPER CROUSE-HINDS GMBH

7.45

Ex-e terminal enclosures

NEXT

Ordering details NEXT IMPERIAL up to 6 x 171 terminals


NEXT

Dimensions1)

Fixing

Weight

HxWxD

Centres1)

in pounds Rail fixing

in inches
Size

Terminal mounting rail

Terminal content

Rail length

Row orientation vertical

centres

Fvertical x

(empty

Fhorizontal

enclosure) vert.

horiz. vert.

horiz.

2.5 (5)

4 (6)

6 (8)

10 (10)

4x73

Enclosure dimensions and terminal content


86/64/20 33.86x25.20x8.07

22.44x27.40

83.80

29.92 21.26 30.71 22.05

6x147

5x123

5x 92

91/61/20 35.98x24.02x8.07

22.01x26.222)

68.20

32.05 20.08 32.83 20.87

5x158

5x132

4x 99

4x79

98/74/20 38.58x29.13x8.07

27.56x31.34

83.60

34.65 25.20 35.43 25.98

6x171

6x143

5x107

5x85

NEXT

Available glanding area

Top &

Left

Order No.3)

Max. Entry Guide (imperial)

Right

Top & Bottom / Left / Right

Bottom
Size

(with gland plates fitted) in inches

/2 NPT

/4 NPT 1 NPT

11/4 NPT 11/2 NPT 2 NPT 21/2 NPT

Gland entry detail


86/64/20 1x

2x

2x
6/5/3

5/4/2

NXTS18664200

7/7/7

6/6/6

5/5/5

NXTS19161200

(11.97x4.88) (15.91x4.88) (15.91x4.88) 48/66/33 36/51/26 20/28/14 16/22/11 7/9/5

5/7/4

4/6/3

NXTS19874200

(23.39x4.88) (11.97x4.88) (11.97x4.88) 48/8/24 39/36/18 21/20/10 17/16/8 7/7/4


91/61/20 22.28x4.25 22.28x4.25 22.28x4.25
98/74/20 2x

2x

47/47/47 24/24/24 20/20/20 8/8/8

2x

Options
with 1 gland plate

NXT S1 XXYYZZ 1

with 2 gland plates

NXT S1 XXYYZZ 2

with 3 gland plate

NXT S1 XXYYZZ 3

with 4 gland plates

NXT S1 XXYYZZ 4

NXT Painted

NXT PS XXYYZZ N

Permanent Padlock Hasp Facility


(Factory Fitted ONLY)

Type

NXT NN XXYYZZ0-HASP
Order No.

Example
98/74/20 with 1 gland plate, 316L and Padlock HASP facility

NXTS19874201-HASP

Notes: 1) Dimensions drawing see page 7.39

7.46

2)

1233) Subtract 30 mm when no side gland plates

3)

Refer to OPTIONS for full order number detail

COOPER CROUSE-HINDS GMBH

Ex-e terminal enclosures

1
2
NEXT

Ordering details NEXT IMPERIAL up to 6 x 75 terminals


NEXT

Dimensions1)

Fixing

Weight

HxWxD

Centres1)

in pounds Rail fixing

Fvertical x

(empty

centres

Fhorizontal

enclosure)

vert.

in inches
Size

Terminal mounting rail

horiz.

Terminal content

Rail length

Row orientation vertical

vert.

2.5 (5) 4 (6)

horiz.

6 (8)

10 (10)

Enclosure dimensions and terminal content landscape orientation


35/30/20 12.05x13.78x8.07

7.99x15.94

17.0

8.11

9.84

8.90

10.63

3x36

2x30

2x23

2x18

45/38/20 14.96x17.72x8.07

9.84x19.92

23.2

11.02

13.78

11.81

14.57

4x36

3x36

3x30

3x23

55/45/20 18.03x21.65x8.07

12.01x23.86

32.7

14.09

17.72

14.88

18.50

5x67

4x56

4x42

4x33

64/50/20 19.69x25.20x8.07

13.78x27.40

46.1

15.75

21.26

16.54

22.05

6x75

5x63

5x47

4x37

NEXT

Max. Entry Guide (metric) Top & Bottom / Left / Right

Available glanding area

Top &
Size

Left

Right

Bottom

hub (second row)


1

/2 NPT

/4 NPT 1 NPT

Order No.3)

gland (first row)

(with gland plates fitted) in inches

11/4 NPT 11/2 NPT 2 NPT 21/2 NPT

Gland entry detail landscape orientation


35/30/20
45/38/20
55/45/20
64/50/20

11.97x4.88
15.91x4.88
19.84x4.88
23.39x4.88

8.43x4.88

10.16x4.88

8.43x4.88

8.43x4.88

13.15x4.88
15.91x4.88

13.15x4.88
15.91x4.88

38/26/32 23/15/20 18/12/15 10/6/8

8/5/5

3/2/3

21/14/18 12/8/10

4/2/3

3/2/3

3/2/2

52/26/26 32/15/15 26/12/12 13/6/6

11/5/5

5/2/2

4/2/2

29/14/14 16/8/8

5/2/2

4/2/2

4/2/2

64/42/42 39/26/26 33/21/21 17/11/11 14/9/9

6/4/4

5/3/3

36/23/23 20/13/13 17/11/11 14/9/9

5/3/3

5/3/3

78/52/52 47/32/32 39/26/26 20/13/13 17/11/11 7/5/5

6/4/4

42/29/29 24/16/16 21/13/13 17/11/11 8/5/5

6/4/4

10/6/8
13/6/6

8/5/7
11/5/5

6/4/4

6/4/4

3/2/2
NXTS13530201
NXTS14538201

NXTS15545201
NXTS16450201

Options
with 1 gland plate

NXT S1 XXYYZZ 1

with 2 gland plates

NXT S1 XXYYZZ 2

with 3 gland plate

NXT S1 XXYYZZ 3

with 4 gland plates

NXT S1 XXYYZZ 4

NXT Painted

NXT PS XXYYZZ N

Permanent Padlock Hasp Facility


(Factory Fitted ONLY)

Type

NXT NN XXYYZZ0-HASP
Order No.

Example
45/38/20 with 2 gland plates, 316L and Padlock HASP facility

NXTS14538202-HASP

Notes: 1) Dimensions drawing see page 7.39


2)

1233) Subtract 30 mm when no side gland plates

3)

Refer to OPTIONS for full order number detail

10
11
12

COOPER CROUSE-HINDS GMBH

7.47

E X - T E R M I N A L

E N C L O S U R E S

Stainless Steel Version for Zone 1 and Zone 21


Ex-Cell

The Ex-Cell enclosure range is an ATEX certified


enclosure / termination solution for category 2
(Zone1) application with an ingress protection of
IP66. Ex-Cell is available in a comprehensive
range of sizes, each with the facility for various
configuration possibilities for a multitude of
applications. Using the highest quality materials,
some unique design benefits and precision
manufacturing, the Ex-Cell range is the benchmark in enclosure for both instrumentation and
electrical applications.
The Ex-Cell product line is designed and ATEX
certified for hazardous areas, UL-approved
for heavy industrial appli cations and are
predominantly used in the petrochemical,
pharmaceutical, food process and utilities market sectors. As a result of this our enclo sures
have the inherent benefits of a high degree of
ingress protection (IP) to environmental charac teristics such as ingress of water and dust. The
ingress protection (IP) of the complete product
line is IP66 (water & dust), have an impact
resistance of a minimum of 7 Nm whilst main taining IP66, thus making them ideal for washdown applications.
The Ex-Cell-I series is made for instrumentation
with easy access central locking system and
hinged cover.
The 1/4 turn embossed latch or bolt down
fastening provides rapid means of achieving
high integrity ingress protection (IP) of 66
environmental seal for reliable, rapid
environmental protection.
An option for up to 3 gland plates (3 mm thick)
on each side. Three possible combinations of 0,
1 or 3 gland-plates available. All sealed to IP66
rating by a high integrity Chloroprene gasket
and secured by rapid fixing Hytork fixing bolts.
An integral drainage channel prevents liquids
or other solids contaminates from running in
or falling into the en closure when the door
is opened, and to minimise gasket path
con tamination.
Stainless steel 316 L options and 304
Safety standard IP66
Hinges and central locking device
for easy access
Extended ambient temperatures -20 C to
+60 C using chloroprene sponge gasket
External and internal earthing bolts

7.48

Ex-e/Ex-i terminal enclosures

1
2
ID TAG label & bracket

Door document holder opti.

Security padlock Hasp opti.

Ex-Cell

Technical data
Type Ex-Cell METRIC and IMPERIAL
Marking to 94/9/EC

II 2 G Ex dem ia/ib IIC T6, T5, T4 /

Temperature class

II 2 D Ex tD A21 IP66 T80 C, T95 C

T6 up to +40 C / T5 up to +55 C

EC-Type Examination Certificate

PTB 02 ATEX 1014

Permissible ambient temperature

20 C to +40 C

55 C to +55 C (option: closed cell expanded Silicone gasket)


Rated voltage

up to 750 V*

Rated current

up to 500 A*

Connecting terminals

u to 240 mm2*

Insulation class

Degree of protection accd. EN 60529

IP66

Cable glands/Gland plates/Enclosure drilling

up to 4 side optional gland plate combination with entries to meet requirements

Type of mounting

4 x 3 mm welded lugs with 11 mm holes/slots, vertical or horizontal

Enclosure material

stainless steel 316 L or 304 electro chemically polished or


sheet steel polyester powder coated (RAL 7032)

Material thickness

1.2 mm (body), 1.5 mm (door)

Equipment mountings

4 x stand off pillars 9 mm, 25 mm height, tapped M6 x 10,

for rail or mounting plate


Enclosure earth

M10 external and internal brass earth stud assembly

Gasket material

PUR, Chloroprene gasket (option), closed cell expended Silicone gasket (option)

* depending on type of terminal and Ex-components used

cULUs types 3S, 4, 4x approval, Germanischer Lloyd available on request.

Dimension drawing

Fixing Centres
(horizontal)

Fixing Centres
(vertical)

Rail Fixing
Pillars

Height

Height

Rail Fixing
Pillars

Depth

Fixing Centres
(horizontal)
Depth

10

Imperial version

Dimensions in mm

Metric version

Width

Fixing Centres
(vertical)

Width

COOPER CROUSE-HINDS GMBH

7.49

11
12

Ex-e/Ex-i terminal enclosures

1/4 turn lock

Bolt fastening

Ordering details Ex-Cell METRIC up to 2 x 56 terminals


316L SS-

Dimensions1)

Fixing

Weight

Terminal mounting rail

Terminal content

Centres1)

in kg

Rail fixing

Row orientation vertical

Fastening

vertical x

(empty

centres

Size

horizontal

enclosure) vert.

/4 Turn Lock H x W x D in mm

Rail length

horiz. vert.

horiz.

2.5 mm2 4 mm2 6 mm2 10 mm2 16 mm2

Enclosure dimensions and terminal content


23/15/13

229x152x127

152x208

2.35

129

52

149

72

1x21

1x17

1x13

1x10

1x 9

26/26/15

260x260x152

170x316

2.8

160

160

180

180

2x27

2x23

1x17

1x13

1x11

30/20/15

305x203x152

203x259

3.4

205

103

225

123

1x36

1x30

1x23

1x18

1x15

30/30/15

305x305x152

203x361

4.6

205

205

225

225

2x36

2x30

2x23

2x18

2x15

30/30/20

305x305x203

203x361

5.8

205

205

225

225

2x36

2x30

2x23

2x18

2x15

40/30/15

406x305x152

267x361

5.7

306

205

326

225

2x56

2x47

2x35

2x28

2x23

40/30/20

406x305x203

267x361

6.6

306

205

326

225

2x56

2x47

2x35

2x28

2x23

316L SS -

Available glanding area

/4 Turn Lock Top &

Left

Right

Fastening

Bottom

Size

(with gland plates fitted) in mm

Order No.2)

Max. Entry Guide (metric)

Top & Bottom / Left / Right


M16

M20

2/2/2

M25

M32

M40

M50

M63

Gland entry detail


23/15/13

108x 58

108x 58

108x 58

6/6/6

26/26/15

214x 80

114x 80

114x 80

21/11/11 10/5/5

2/2/2

1/1/1

XLHS12315130

4/2/2

3/2/2

3/1/1

2/1/1

XLHS12626150

30/20/15

156x 80

156x 80

156x 80

15/15/15 7/7/7

3/3/3

2/2/2

2/2/2

2/2/2

XLHS13020150

30/30/15

261x 80

156x 80

156x 80

26/15/15 13/7/7

5/3/3

4/2/2

3/2/2

3/2/2

XLHS13030150

30/30/20

261x124

214x124

261x124

34/28/34 18/15/18 15/12/15 8/6/8

6/5/6

3/2/3

2/2/2

XLHS13030200

40/30/15

261x 80

261x 80

261x 80

26/26/26 13/13/13 5/5/5

4/4/4

3/3/3

3/3/3

XLHS14030150

40/30/20

261x124

261x124

261x124

34/34/34 18/18/18 15/15/15 8/8/8

6/6/6

3/3/3

2/2/2

XLHS14030200

Options
with 1 gland plate

XLH S1 XXYYZZ 1

with 3 gland plates

Ex-Cell 316L SS - Bolt Fastening

XLH S1 XXYYZZ0-B

Ex-Cell 304 SS - 1/4 Turn Lock Fastening

XLH S2 XXYYZZ 0

Ex-Cell 304 SS - Bolt Fastening

XLH S2 XXYYZZ0-B

Ex-Cell Painted - 1/4 Turn Lock Fastening

XLH PS XXYYZZ 0

Ex-Cell Painted - Bolt Fastening

XLH PS XXYYZZ0-B

Permanent Padlock Hasp Facility


(Factory Fitted ONLY)

Type

XLH S1 XXYYZZ 3

XLH NN XXYYZZ0-HASP
Order No.

Example
30/20/15 with 3 gland plates, painted with bolt fastening and permanet padlock HASP facility
Notes: 1) Dimensions drawing see page 7.49
2)

7.50

Refer to OPTIONS for full order number detail

COOPER CROUSE-HINDS GMBH

XLHPS 3020153-B-HASP

Ex-e/Ex-i terminal enclosures

1
2
Ex-Cell 40/50/15

Ordering details Ex-Cell METRIC up to 3 x 77 terminals


316L SS-

Dimensions1)

Fixing

Weight

Terminal mounting rail

Terminal content

Centres1)

in kg

Rail fixing

Row orientation vertical

Fastening

vertical x

(empty

centres

Size

horizontal

enclosure) vert.

horiz. vert.

horiz.

2.5 mm2 4 mm2 6 mm2 10 mm2 16 mm2

/4 Turn Lock H x W x D in mm

Rail length

Enclosure dimensions and terminal content


40/40/15

406x406x152

267x462

7.1

306

306

326

326

3x56

3x47

3x35

3x28

3x23

40/40/20

406x406x203

267x462

8.1

306

306

326

326

3x56

3x47

3x35

3x28

3x23

40/50/15

406x508x152

267x564

8.5

306

408

326

428

4x56

4x47

4x35

4x28

4x23

40/50/20

406x508x203

267x564

9.7

306

408

326

428

4x56

4x47

4x35

4x28

4x23

50/40/15

508x406x152

354x462

8.5

408

306

428

326

3x77

3x64

3x48

3x38

3x32

50/40/20

508x406x203

354x462

9.7

408

306

428

326

3x77

3x64

3x48

3x38

3x32

316L SS -

Available glanding area

/4 Turn Lock Top &

Left

Right

Fastening

Bottom

Size

(with gland plates fitted) in mm

M20

M25

Order No.2)

Max. Entry Guide (metric)

Top & Bottom / Left / Right


M16

M32

M40

M50

M63

6/4/4

Gland entry detail


40/40/15

337x 80

261x 80

261x 80

35/26/26 17/13/13 7/5/5

5/3/3

4/3/3

XLHS14040150

40/40/20

334x124

261x124

261x124

44/34/34 26/18/18 21/15/15 11/8/8

9/6/6

4/3/3

3/2/2

XLHS14040200

40/50/15

464x 80

261x 80

261x 80

48/26/26 24/13/13 10/5/5

7/3/3

6/3/3

XLHS14050150

40/50/20

460x124

261x124

261x124

62/34/34 35/18/18 29/15/15 15/8/8

13/6/6

5/3/3

4/2/2

XLHS14050200

50/40/15

337x 80

337x 80

337x 80

35/35/35 17/17/17 7/7/7

5/5/5

4/4/4

XLHS15040150

50/40/20

334x124

334x124

334x124

44/44/44 26/26/26 21/21/21 11/11/11 9/9/9

4/4/4

3/3/3

XLHS15040200

8/4/4
6/6/6

Options
with 1 gland plate

XLH S1 XXYYZZ 1

with 3 gland plates


1

XLH S1 XXYYZZ 3

Ex-Cell 316L SS - Bolt Fastening

XLH S1 XXYYZZ0-B

Ex-Cell 304 SS - /4 Turn Lock Fastening

XLH S2 XXYYZZ 0

Ex-Cell 304 SS - Bolt Fastening

XLH S2 XXYYZZ0-B

Ex-Cell Painted - 1/4 Turn Lock Fastening

XLH PS XXYYZZ 0

Ex-Cell Painted - Bolt Fastening

XLH PS XXYYZZ0-B

Permanent Padlock Hasp Facility


(Factory Fitted ONLY)

Type

XLH NN XXYYZZ0-HASP
Order No.

Example
40/50/20 with 1 gland plates, 316L SS with bolt fastening and permanet padlock HASP facility

XLHS14050201-B-HASP

Notes: 1) Dimensions drawing see page 7.49


2)

10

Refer to OPTIONS for full order number detail

11
12
COOPER CROUSE-HINDS GMBH

7.51

Ex-e/Ex-i terminal enclosures

Ex-Cell

Ordering details Ex-Cell METRIC up to 4 x 97 terminals


316L SS-

Dimensions1)

Fixing

Weight

Terminal mounting rail

Terminal content

Centres1)

in kg

Rail fixing

Row orientation vertical

Fastening

vertical x

(empty

centres

Size

horizontal

enclosure) vert.

horiz. vert.

horiz.

2.5 mm2 4 mm2 6 mm2 10 mm2 16 mm2

/4 Turn Lock H x W x D in mm

Rail length

Enclosure dimensions and terminal content


50/50/15

508x508x152

354x564

10.2

408

408

428

428

4x77

4x64

4x 48

4x38

4x32

50/50/20

508x508x203

354x564

11.4

408

408

428

428

4x77

4x64

4x 48

4x38

4x32

50/60/20

508x610x203

354x666

13.2

408

510

428

530

6x77

6x64

6x 48

6x38

6x32

60/40/15

610x406x152

445x462

9.9

510

306

530

326

3x97

3x81

3x61

3x49

3x40

60/40/20

610x406x203

445x462

11.2

510

306

530

326

3x97

3x81

3x61

3x49

3x40

60/50/15

610x508x152

445x564

11.8

510

408

530

428

4x97

4x81

4x61

4x49

4x40

60/50/20

610x508x203

445x564

13.2

510

408

530

428

4x97

4x81

4x61

4x49

4x40

316L SS -

Available glanding area

/4 Turn Lock Top &

Left

Right

Fastening

Bottom

Size

(with gland plates fitted) in mm

Order No.2)

Max. Entry Guide (metric)

Top & Bottom / Left / Right


M16

M20

M25

M32

M40

M50

M63

8/6/6

7/5/5

Gland entry detail


50/50/15

464x 80

337x 80

337x 80

48/35/35 24/17/17 10/7/7

6/4/4

XLHS15050150

50/50/20

460x124

334x124

334x124

62/44/44 35/26/26 29/21/21 15/11/11 13/9/9

5/4/4

4/3/3

XLHS15050200

50/60/20

562x124

334x124

334x124

78/44/44 44/26/26 36/21/21 19/11/11 16/9/9

7/4/4

5/3/3

XLHS15060200

60/40/15

337x 80

464x 80

464x 80

35/48/48 17/24/24 7/10/10 6/8/8

4/6/6

XLHS16040150

60/40/20

334x124

460x124

460x124

44/62/62 26/35/35 21/29/29 11/15/15 9/13/13 4/5/5

3/4/4

XLHS16040200

60/50/15

464x 80

464x 80

464x 80

48/48/48 24/24/24 10/10/10 8/8/8

XLHS16050150

60/50/20

460x124

460x124

460x124

62/62/62 35/35/35 29/29/29 15/15/15 13/13/13 5/5/5

4/4/4

XLHS16050200

5/7/7
7/7/7

6/6/6

Options
with 1 gland plate

XLH S1 XXYYZZ 1

with 3 gland plates

Ex-Cell 316L SS - Bolt Fastening

XLH S1 XXYYZZ0-B

Ex-Cell 304 SS - 1/4 Turn Lock Fastening

XLH S2 XXYYZZ 0

Ex-Cell 304 SS - Bolt Fastening

XLH S2 XXYYZZ0-B

Ex-Cell Painted - 1/4 Turn Lock Fastening

XLH PS XXYYZZ 0

Ex-Cell Painted - Bolt Fastening

XLH PS XXYYZZ0-B

Permanent Padlock Hasp Facility


(Factory Fitted ONLY)

Type

XLH S1 XXYYZZ 3

XLH NN XXYYZZ0-HASP
Order No.

Example
60/50/20 with 3 gland plates, painted 1/4 turn lock fastening and permanent padlock HASP facility
Notes: 1) Dimensions drawing see page 7.49
2)

7.52

Refer to OPTIONS for full order number detail

COOPER CROUSE-HINDS GMBH

XLHPS6050203-HASP

Ex-e/Ex-i terminal enclosures

1
2
Ex-Cell

Ordering details Ex-Cell METRIC up to 7 x 128 terminals


316L SS-

Dimensions1)

Fixing

Weight

Terminal mounting rail

Terminal content

Centres1)

in kg

Rail fixing

Row orientation vertical

Fastening

vertical x

(empty

centres

Size

horizontal

enclosure) vert.

horiz. vert.

horiz.

2.5 mm2 4 mm2 6 mm2 10 mm2 16 mm2

/4 Turn Lock H x W x D in mm

Rail length

Enclosure dimensions and terminal content


60/60/15

610x610x152

445x666

13.7

510

510

530

530

6x 97 6x 81 6x61

6x49

6x40

60/60/20

610x610x203

445x666

15.3

510

510

530

530

6x 97 6x 81 6x61

6x49

6x40

60/76/20

610x762x203

445x818

18.3

510

662

530

682

7x 97 7x 81 7x61

7x49

7x40

76/50/20

762x508x203

508x564

15.9

662

408

682

428

4x128 4x106 4x80

4x64

4x53

76/60/20

762x610x203

508x666

18.3

662

510

682

530

6x128 6x106 6x80

6x64

6x53

76/76/20

762x762x203

508x818

21.9

662

662

682

682

7x128 7x106 7x80

7x64

7x53

316L SS -

Available glanding area

/4 Turn Lock Top &

Left

Right

Fastening

Bottom

Size

(with gland plates fitted) in mm

M20

M25

Order No.2)

Max. Entry Guide (metric)

Top & Bottom / Left / Right


M16

M32

M40

M50

M63

8/7/7

7/6/6

Gland entry detail


60/60/15

562x 80

464x 80

464x 80

59/48/48

29/24/24 12/10/10 10/8/8

XLHS16060150

60/60/20

562x124

460x124

460x124

78/62/62

44/35/35 36/29/29 19/15/15 16/13/13 7/5/5

5/4/4

XLHS16060200

60/76/20

714x124

460x124

460x124

100/62/62 56/35/35 47/29/29 24/15/15 20/13/13 9/5/5

7/4/4

XLHS16076200

76/50/20

460x124

562x124

562x124

62/78/78

35/44/44 29/36/36 15/19/19 13/16/16 5/7/7

4/5/5

XLHS17650200

76/60/20

562x124

562x124

562x124

78/78/78

44/44/44 36/36/36 19/19/19 16/16/16 7/7/7

5/5/5

XLHS17660200

76/76/20

714x124

562x124

562x124

100/78/78 56/44/44 47/36/36 24/19/19 20/16/16 9/7/7

7/5/5

XLHS17676200

Options
with 1 gland plate

XLH S1 XXYYZZ 1

with 3 gland plates


1

XLH S1 XXYYZZ 3

Ex-Cell 316L SS - Bolt Fastening

XLH S1 XXYYZZ0-B

Ex-Cell 304 SS - /4 Turn Lock Fastening

XLH S2 XXYYZZ 0

Ex-Cell 304 SS - Bolt Fastening

XLH S2 XXYYZZ0-B

Ex-Cell Painted - 1/4 Turn Lock Fastening

XLH PS XXYYZZ 0

Ex-Cell Painted - Bolt Fastening

XLH PS XXYYZZ0-B

Permanent Padlock Hasp Facility


(Factory Fitted ONLY)

Type

XLH PS XXYYZZ0-HASP
Order No.

Example
60/76/20 with 3 gland plates, 316 SS with bolt fastening and permanent padlock HASP facility

XLHS16076203-B-HASP

Notes: 1) Dimensions drawing see page 7.49


2)

10

Refer to OPTIONS for full order number detail

11
12
COOPER CROUSE-HINDS GMBH

7.53

Ex-e/Ex-i terminal enclosures

Ex-Cell

Ordering details Ex-Cell IMPERIAL up to 2 x 36 terminals


316L SS1

Dimensions1)

/4 Turn Lock H x W x D

Fastening

in inches

Size

Fixing

Weight

Terminal mounting rail

Terminal content

Centres1)

in lbs

Rail fixing

Row orientation vertical

vertical x

(empty

centres

horizontal

enclosure) vert.

Rail length

horiz. vert.

horiz.

2.5 mm2 4 mm2 6 mm2 10 mm2 16 mm2

Enclosure dimensions and terminal content


9/6/5

9x6x5

10.24x3.50

5.17

5.08

2.05

5.87

2.83

1x21

1x17

1x13

1x10

1x9

12/8/6

12x8x6

13.24x5.50

7.54

8.07

4.06

8.86

4.84

1x36

1x30

1x23

1x18

1x15

12/12/6

12x12x6

13.24x9.50

10.07

8.07

8.07

8.86

8.86

2x36

2x30

2x23

2x18

2x15

12/12/8

12x12x8

13.24x9.50

12.76

8.11

8.11

8.90

8.90

2x36

2x30

2x23

2x18

2x15

316L SS -

Available glanding area

/4 Turn Lock Top &

Left

Right

Max. Entry Guide (imperial) Top & Bottom / Left / Right

Order No.2)

Gland (first row)

Fastening

Bottom

Hub (second row)

Size

(with gland plates fitted) in inches

/4 NPT

1 NPT

11/4 NPT 11/2 NPT 2 NPT

21/2 NPT

6/6/6

2/2/2

2/2/2

1/1/1

2/2/2

2/2/2

2/2/2

7/7/7

3/3/3

2/2/2

2/2/2

2/2/2

/2 NPT

Gland entry detail


9/6/5

4.25x2.28 4.25x2.28 4.25x2.28

XLVS10906050

12/8/6

6.14x3.15 6.14x3.15 6.14x3.15

9/9/9
3/3/3

3/3/3

2/2/2

12/12/6

10.28x3.15 6.14x3.15 6.14x3.15

16/9/9

13/7/7

5/3/3

4/2/2

3/2/2

3/2/2

12/3/3

5/3/3

4/2/2

4/0/0

3/0/0

12/12/8

10.27x4.88 8.42x4.88 10.27x4.88 32/26/32 20/15/20 15/12/15 8/6/8

6/5/6

3/2/3

2/2/2

3/2/3

3/2/3

2/2/2

18/14/18 10/8/10 8/6/8

7/5/7

XLVS11208060
XLVS11212060
XLVS11212080

Options
with 1 gland plate

XLV S1 XXYYZZ 1

with 3 gland plates

Ex-Cell 316L SS - Bolt Fastening

XLV S1 XXYYZZ0-B

Ex-Cell 304 SS - 1/4 Turn Lock Fastening

XLV S2 XXYYZZ 0

Ex-Cell 304 SS - Bolt Fastening

XLV S2 XXYYZZ0-B

Ex-Cell Painted - 1/4 Turn Lock Fastening

XLV PS XXYYZZ 0

Ex-Cell Painted - Bolt Fastening

XLV PS XXYYZZ0-B

Permanent Padlock Hasp Facility


(Factory Fitted ONLY)

Type

XLV S1 XXYYZZ 3

XLV PS XXYYZZ0-HASP
Order No.

Example
12/8/6 with 3 gland plates, painted with bolt fastening

XLVS11208063-B

Notes: 1) Dimensions drawing see page 7.49


2)

7.54

Refer to OPTIONS for full order number detail

COOPER CROUSE-HINDS GMBH

Ex-e/Ex-i terminal enclosures

1
2
Ex-Cell

Ordering details Ex-Cell IMPERIAL up to 3 x 56 terminals


316L SS1

Dimensions1)

/4 Turn Lock H x W x D

Fastening

in inches

Size

Fixing

Weight

Terminal mounting rail

Terminal content

Centres1)

in lbs

Rail fixing

Row orientation vertical

vertical x

(empty

centres

horizontal

enclosure) vert.

Rail length

horiz. vert.

horiz.

2.5 mm2 4 mm2 6 mm2 10 mm2 16 mm2

Enclosure dimensions and terminal content


16/12/6

16x12x6

17.24x 9.50

12.57

12.05

8.07 12.83

8.86

2x56

2x47

2x35

2x28

2x23

16/12/8

16x12x8

17.24x 9.50

14.54

12.05

8.07 12.83

8.86

2x56

2x47

2x35

2x28

2x23

16/16/6

16x16x6

17.24x10.00

15.63

12.05 12.05 12.83 12.83

3x56

3x47

3x35

3x28

3x23

16/16/8

16x16x8

17.24x10.00

17.87

12.05 12.05 12.83 12.83

3x56

3x47

3x35

3x28

3x23

316L SS -

Available glanding area

/4 Turn Lock Top &

Left

Right

Max. Entry Guide (imperial) Top & Bottom / Left / Right

Bottom

Hub (second row)

Size

(with gland plates fitted) in inches

/2 NPT

/4 NPT

1 NPT

11/4 NPT 11/2 NPT 2 NPT

Order No.2)

Gland (first row)

Fastening

21/2 NPT

Gland entry detail


16/12/6
16/12/8
16/16/6
16/16/8

10.28x3.15 10.28x3.15 10.28x3.15


10.27x4.88 10.27x4.88 10.27x4.88
13.27x3.15 10.28x3.15 10.28x3.15
13.15x4.88 10.27x4.88 10.27x4.88

16/16/16 13/13/13 5/5/5

4/4/4

3/3/3

3/3/3

12/12/12 5/5/5

4/4/4

3/3/3

32/32/32 20/20/20 15/15/15 8/8/8

6/6/6

3/3/3

2/2/2

18/18/18 10/10/10 8/8/8

7/7/7

3/3/3

3/3/3

2/2/2

21/16/16 17/13/13 7/5/5

6/4/4

5/3/3

4/3/3

15/12/12 7/5/5

5/4/4

4/3/3

42/32/32 26/20/20 21/15/15 11/8/8

9/6/6

4/3/3

3/2/2

23/18/18 13/10/10 11/8/8

4/3/3

3/3/3

3/2/2

4/4/4

6/4/4

9/7/7

XLVS11612060
XLVS11612080

XLVS11616060
XLVS11616080

Options
with 1 gland plate

XLV S1 XXYYZZ 1

with 3 gland plates

Ex-Cell 316L SS - Bolt Fastening

XLV S1 XXYYZZ0-B

Ex-Cell 304 SS - 1/4 Turn Lock Fastening

XLV S2 XXYYZZ 0

Ex-Cell 304 SS - Bolt Fastening

XLV S2 XXYYZZ0-B

Ex-Cell Painted - 1/4 Turn Lock Fastening

XLV PS XXYYZZ 0

Ex-Cell Painted - Bolt Fastening

XLV PS XXYYZZ0-B

Permanent Padlock Hasp Facility


(Factory Fitted ONLY)

Type

XLV S1 XXYYZZ 3

XLV PS XXYYZZ0-HASP

Order No.

Example
16/16/06 with 1 gland plates, 304 SS with 1/4 turn lock fastening and permanent padlock HASP facility

XLVS21616061-HASP

10

Notes: 1) Dimensions drawing see page 7.49


2)

Refer to OPTIONS for full order number detail

11
12
COOPER CROUSE-HINDS GMBH

7.55

Ex-e/Ex-i terminal enclosures

Ex-Cell

Ordering details Ex-Cell IMPERIAL up to 3 x 77 terminals


316L SS1

Dimensions1)

/4 Turn Lock H x W x D

Fastening

in inches

Size

Fixing

Weight

Terminal mounting rail

Terminal content

Centres1)

in lbs

Rail fixing

Row orientation vertical

vertical x

(empty

centres

horizontal

enclosure) vert.

Rail length

horiz. vert.

horiz.

2.5 mm2 4 mm2 6 mm2 10 mm2 16 mm2

Enclosure dimensions and terminal content


16/20/6

16x20x6

17.24x14.00

18.71

12.05 16.06 12.83 16.85

4x56

4x47

4x35

4x28

4x23

16/20/8

16x20x8

17.24x14.00

21.24

12.05 16.06 12.83 16.85

4x56

4x47

4x35

4x28

4x23

20/16/6

20x16x6

21.24x10.00

18.71

16.06 12.05 16.85 12.83

3x77

3x64

3x48

3x38

3x32

20/16/8

20x16x8

21.24x10.00

21.24

16.06 12.05 16.85 12.83

3x77

3x64

3x48

3x38

3x32

316L SS -

Available glanding area

/4 Turn Lock Top &

Left

Right

Max. Entry Guide (imperial) Top & Bottom / Left / Right

Order No.2)

Gland (first row)

Fastening

Bottom

Hub (second row)

Size

(with gland plates fitted) in inches

/2 NPT

/4 NPT

1 NPT

11/4 NPT 11/2 NPT 2 NPT

21/2 NPT

Gland entry detail


16/20/6

18.27x3.15 10.28x3.15 10.28x3.15

16/20/8

18.11x4.88 10.27x4.88 10.27x4.88

20/16/6

13.27x3.15 13.27x3.15 13.27x3.15

20/16/8

13.15x4.88 13.15x4.88 13.15x4.88

30/16/16 24/13/13 10/5/5

8/4/4

7/3/3

6/3/3

22/12/12 10/5/5

7/4/4

6/3/3

58/32/32 36/20/20 30/15/15 15/8/8

13/6/6

5/3/3

4/2/2

33/18/18 18/10/10 16/8/8

13/7/7

6/3/3

5/3/3

4/2/2

21/21/21 17/17/17 7/7/7

6/6/6

5/5/5

4/4/4

15/15/15 7/7/7

5/5/5

4/4/4

8/4/4

6/6/6

XLVS11620060

XLVS12016060

42/42/42 26/26/26 21/21/21 11/11/11 9/9/9

4/4/4

3/3/3

23/23/23 13/13/13 11/11/11 9/9/9

3/3/3

3/3/3

4/4/4

XLVS11620080

XLVS12016080

Options
with 1 gland plate

XLV S1 XXYYZZ 1

with 3 gland plates

Ex-Cell 316L SS - Bolt Fastening

XLV S1 XXYYZZ0-B

Ex-Cell 304 SS - 1/4 Turn Lock Fastening

XLV S2 XXYYZZ 0

Ex-Cell 304 SS - Bolt Fastening

XLV S2 XXYYZZ0-B

Ex-Cell Painted - 1/4 Turn Lock Fastening

XLV PS XXYYZZ 0

Ex-Cell Painted - Bolt Fastening

XLV PS XXYYZZ0-B

Permanent Padlock Hasp Facility


(Factory Fitted ONLY)

Type

XLV S1 XXYYZZ 3

XLV PS XXYYZZ0-HASP
Order No.

Example
20/16/8 with 3 gland plates, painted with bolt fastening and permanent padlock HASP facility
Notes: 1) Dimensions drawing see page 7.49
2)

7.56

Refer to OPTIONS for full order number detail

COOPER CROUSE-HINDS GMBH

XLVPS2016083-B-HASP

Ex-e/Ex-i terminal enclosures

1
2
Ex-Cell

Ordering details Ex-Cell IMPERIAL up to 6 x 77 terminals


316L SS1

Dimensions1)

/4 Turn Lock H x W x D

Fastening

in inches

Size

Fixing

Weight

Terminal mounting rail

Terminal content

Centres1)

in lbs

Rail fixing

Row orientation vertical

vertical x

(empty

centres

horizontal

enclosure) vert.

Rail length

horiz. vert.

horiz.

2.5 mm2 4 mm2 6 mm2 10 mm2 16 mm2

Enclosure dimensions and terminal content


20/20/6

20x20x6

21.24x14.00

22.36

16.06 16.06 16.85 16.85

4x77

4x64

4x48

4x38

4x32

20/20/8

20x20x8

21.24x14.00

25.17

16.06 16.06 16.85 16.85

4x77

4x64

4x48

4x38

4x32

20/24/8

20x24x8

21.24x18.00

29.10

16.06 20.08 16.85 20.87

6x77

6x64

6x48

6x38

6x32

4
5

316L SS 1

Available glanding area

/4 Turn Lock Top &

Left

Right

Max. Entry Guide (imperial) Top & Bottom / Left / Right

Order No.2)

Gland (first row)

Fastening

Bottom

Hub (second row)

Size

(with gland plates fitted) in inches

/2 NPT

/4 NPT

1 NPT

11/4 NPT 11/2 NPT 2 NPT

21/2 NPT

Gland entry detail


20/20/6
20/20/8
20/24/8

18.27x3.15 13.27x3.15 13.27x3.15


18.11x4.88 13.15x4.88 13.15x4.88
22.13x4.88 13.15x4.88 13.15x4.88

30/21/21 24/17/17 10/7/7

8/6/6

7/5/5

6/4/4

22/15/15 10/7/7

7/5/5

6/4/4

58/42/42 36/26/26 30/21/21 15/11/11 13/9/9

5/4/4

4/3/3

33/23/23 18/13/13 16/11/11 13/9/9

5/3/3

4/3/3

8/6/6

6/4/4

XLVS12020060

72/42/42 44/26/26 36/21/21 19/11/11 16/9/9

7/4/4

5/3/3

41/23/23 23/13/13 19/11/11 16/9/9

6/3/3

5/3/3

7/4/4

XLVS12020080

XLVS12024080

Options
with 1 gland plate

XLV S1 XXYYZZ 1

with 3 gland plates

Ex-Cell 316L SS - Bolt Fastening

XLV S1 XXYYZZ0-B

Ex-Cell 304 SS - 1/4 Turn Lock Fastening

XLV S2 XXYYZZ 0

Ex-Cell 304 SS - Bolt Fastening

XLV S2 XXYYZZ0-B

Ex-Cell Painted - 1/4 Turn Lock Fastening

XLV PS XXYYZZ 0

Ex-Cell Painted - Bolt Fastening

XLV PS XXYYZZ0-B

Permanent Padlock Hasp Facility


(Factory Fitted ONLY)

Type

XLV S1 XXYYZZ 3

XLV PS XXYYZZ0-HASP

Order No.

Example
20/20/8 with 1 gland plates, 316L SS with bolt fastening

XLVS12020081-B

10

Notes: 1) Dimensions drawing see page 7.49


2)

Refer to OPTIONS for full order number detail

11
12
COOPER CROUSE-HINDS GMBH

7.57

Ex-e/Ex-i terminal enclosures

Ex-Cell

Ordering details Ex-Cell IMPERIAL up to 4 x 97 terminals


316L SS1

Dimensions1)

/4 Turn Lock H x W x D

Fastening

in inches

Size

Fixing

Weight

Terminal mounting rail

Terminal content

Centres1)

in lbs

Rail fixing

Row orientation vertical

vertical x

(empty

centres

horizontal

enclosure) vert.

Rail length

horiz. vert.

horiz.

2.5 mm2 4 mm2 6 mm2 10 mm2 16 mm2

Enclosure dimensions and terminal content


24/16/6

24x16x6

25.24x10.00

21.80

20.08 12.05 20.87 12.83

3x97

3x81

3x61

3x49

3x40

24/16/8

24x16x8

25.24x10.00

24.61

20.08 12.05 20.87 12.83

3x97

3x81

3x61

3x49

3x40

24/20/6

24x20x6

25.24x14.00

26.01

20.08 16.06 20.87 16.85

4x97

4x81

4x61

4x49

4x40

24/20/8

24x20x8

25.24x14.00

29.01

20.08 16.06 20.87 16.85

4x97

4x81

4x61

4x49

4x40

316L SS -

Available glanding area

/4 Turn Lock Top &

Left

Right

Max. Entry Guide (imperial) Top & Bottom / Left / Right

Order No.2)

Gland (first row)

Fastening

Bottom

Hub (second row)

Size

(with gland plates fitted) in inches

/2 NPT

/4 NPT

1 NPT

11/4 NPT 11/2 NPT 2 NPT

21/2 NPT

Gland entry detail


24/16/6

13.27x3.15 18.27x3.15 18.27x3.15

24/16/8

13.15x4.88 18.11x4.88 18.11x4.88

24/20/6

18.27x3.15 18.27x3.15 18.27x3.15

24/20/8

18.11x4.88 18.11x4.88 18.11x4.88

21/30/30 17/24/24 7/10/10 6/8/8

5/7/7

4/6/6

15/22/22 7/10/10 6/8/8

4/6/6

5/7/7

42/58/58 26/36/36 21/30/30 11/15/15 9/13/13 4/5/5

XLVS12416060

3/4/4

23/33/33 13/18/18 11/16/16 9/13/13 4/6/6

3/5/5

3/4/4

30/30/30 24/24/24 10/10/10 8/8/8

7/7/7

6/6/6

22/22/22 10/10/10 8/8/8

6/6/6

7/7/7

XLVS12420060

58/58/58 36/36/36 30/30/30 15/15/15 13/13/13 5/5/5

4/4/4

33/33/33 18/18/18 16/16/16 13/13/13 6/6/6

4/4/4

5/5/5

XLVS12416080

XLVS12420080

Options
with 1 gland plate

XLV S1 XXYYZZ 1

with 3 gland plates

Ex-Cell 316L SS - Bolt Fastening

XLV S1 XXYYZZ0-B

Ex-Cell 304 SS - 1/4 Turn Lock Fastening

XLV S2 XXYYZZ 0

Ex-Cell 304 SS - Bolt Fastening

XLV S2 XXYYZZ0-B

Ex-Cell Painted - 1/4 Turn Lock Fastening

XLV PS XXYYZZ 0

Ex-Cell Painted - Bolt Fastening

XLV PS XXYYZZ0-B

Permanent Padlock Hasp Facility


(Factory Fitted ONLY)

Type

XLV S1 XXYYZZ 3

XLV PS XXYYZZ0-HASP
Order No.

Example
24/16/6 with 1 gland plates, painted with bolt fastening and permanent padlock HASP facility
Notes: 1) Dimensions drawing see page 7.49
2)

7.58

Refer to OPTIONS for full order number detail

COOPER CROUSE-HINDS GMBH

XLVPS2416061-B-HASP

Ex-e/Ex-i terminal enclosures

1
2
Ex-Cell

Ordering details Ex-Cell IMPERIAL up to 7 x 97 terminals


316L SS1

Dimensions1)

/4 Turn Lock H x W x D

Fastening

in inches

Size

Fixing

Weight

Terminal mounting rail

Terminal content

Centres1)

in lbs

Rail fixing

Row orientation vertical

vertical x

(empty

centres

horizontal

enclosure) vert.

Rail length

horiz. vert.

horiz.

2.5 mm2 4 mm2 6 mm2 10 mm2 16 mm2

Enclosure dimensions and terminal content


24/24/6

24x24x6

25.24x18.00

30.22

20.08 20.08 20.87 20.87

6x97

6x81

6x61

6x49

6x40

24/24/8

24x24x8

25.24x18.00

33.60

20.08 20.08 20.87 20.87

6x97

6x81

6x61

6x49

6x40

24/30/8

24x30x8

25.24x24.00

40.30

20.08 26.06 20.87 26.85

7x97

7x81

7x61

7x49

7x40

4
5

316L SS 1

Available glanding area

/4 Turn Lock Top &

Left

Right

Max. Entry Guide (imperial) Top & Bottom / Left / Right

Order No.2)

Gland (first row)

Fastening

Bottom

Hub (second row)

Size

(with gland plates fitted) in inches

/2 NPT

/4 NPT

1 NPT

11/4 NPT 11/2 NPT 2 NPT

21/2 NPT

Gland entry detail


24/24/6
24/24/8
24/30/8

22.13x3.15 18.27x3.15 18.27x3.15


22.13x4.88 18.11x4.88 18.11x4.88
28.11x4.88 18.11x4.88 18.11x4.88

36/30/30 29/24/24 12/10/10 10/8/8

8/7/7

7/6/6

27/22/22 12/10/10 10/8/8

7/6/6

8/7/7

XLVS12424060

72/58/58 44/36/36 36/30/30 19/15/15 16/13/13 7/5/5

5/4/4

41/33/33 23/18/18 19/16/16 16/13/13 7/6/6

6/5/5

5/4/4

94/58/58 57/36/36 47/30/30 24/15/15 20/13/13 9/5/5

7/4/4

51/33/33 30/18/18 25/16/16 21/13/13 9/6/6

7/4/4

8/5/5

XLVS12424080

XLVS12430080

Options
with 1 gland plate

XLV S1 XXYYZZ 1

with 3 gland plates

Ex-Cell 316L SS - Bolt Fastening

XLV S1 XXYYZZ0-B

Ex-Cell 304 SS - 1/4 Turn Lock Fastening

XLV S2 XXYYZZ 0

Ex-Cell 304 SS - Bolt Fastening

XLV S2 XXYYZZ0-B

Ex-Cell Painted - 1/4 Turn Lock Fastening

XLV PS XXYYZZ 0

Ex-Cell Painted - Bolt Fastening

XLV PS XXYYZZ0-B

Permanent Padlock Hasp Facility


(Factory Fitted ONLY)

Type

XLV S1 XXYYZZ 3

XLV PS XXYYZZ0-HASP

Order No.

Example
24/22/8 with 3 gland plates, 316L SS with bolt fastening

XLVS12422083-B

10

Notes: 1) Dimensions drawing see page 7.49


2)

Refer to OPTIONS for full order number detail

11
12
COOPER CROUSE-HINDS GMBH

7.59

Ex-e/Ex-i terminal enclosures

Ex-Cell

Ordering details Ex-Cell IMPERIAL up to 7 x 128 terminals


316L SS1

Dimensions1)

/4 Turn Lock H x W x D

Fastening

in inches

Size

Fixing

Weight

Terminal mounting rail

Terminal content

Centres1)

in lbs

Rail fixing

Row orientation vertical

vertical x

(empty

centres

horizontal

enclosure) vert.

Rail length

horiz. vert.

horiz.

2.5 mm2 4 mm2 6 mm2 10 mm2 16 mm2

Enclosure dimensions and terminal content


30/20/8

30x20x8

31.24x14.00

34.96

26.06 16.06 26.85 16.85

4x128

4x106 4x80

4x64

4x53

30/24/8

30x24x8

31.24x18.00

40.30

26.06 20.08 26.85 20.87

6x128

6x106 6x80

6x64

6x53

30/30/8

30x30x8

31.24x24.00

48.25

26.06 26.06 26.85 26.85

7x128

7x106 7x80

7x64

7x53

316L SS -

Available glanding area

/4 Turn Lock Top &

Left

Right

Max. Entry Guide (imperial) Top & Bottom / Left / Right

Order No.2)

Gland (first row)

Fastening

Bottom

Hub (second row)

Size

(with gland plates fitted) in inches

/2 NPT

/4 NPT

1 NPT

11/4 NPT 11/2 NPT 2 NPT

21/2 NPT

Gland entry detail


30/20/8

18.11x4.88 22.13x4.88 22.13x4.88

58/72/72 36/44/44 30/36/36 15/19/19 13/16/16 5/7/7


33/41/41 18/23/23 16/19/19 13/16/16 6/7/7

30/24/8

22.13x4.88 22.13x4.88 22.13x4.88

30/30/8

28.11x4.88 22.13x4.88 22.13x4.88

4/5/5

5/6/6

4/5/5

72/72/72 44/44/44 36/36/36 19/19/19 16/16/16 7/7/7

5/5/5

41/41/41 23/23/23 19/19/19 16/16/16 7/7/7

6/6/6

5/5/5

94/72/72 57/44/44 47/36/36 24/19/19 20/16/16 9/7/7

7/5/5

51/41/41 30/23/23 25/19/19 21/16/16 9/7/7

7/5/5

8/6/6

XLVS13020080
XLVS13024080
XLVS13030080

Options
with 1 gland plate

XLV S1 XXYYZZ 1

with 3 gland plates

Ex-Cell 316L SS - Bolt Fastening

XLV S1 XXYYZZ0-B

Ex-Cell 304 SS - 1/4 Turn Lock Fastening

XLV S2 XXYYZZ 0

Ex-Cell 304 SS - Bolt Fastening

XLV S2 XXYYZZ0-B

Ex-Cell Painted - 1/4 Turn Lock Fastening

XLV PS XXYYZZ 0

Ex-Cell Painted - Bolt Fastening

XLV PS XXYYZZ0-B

Permanent Padlock Hasp Facility


(Factory Fitted ONLY)

Type

XLV S1 XXYYZZ 3

XLV PS XXYYZZ0-HASP
Order No.

Example
30/30/8 with 1 gland plates, 304 SS with bolt fastening and permanent padlock HASP facility
Notes: 1) Dimensions drawing see page 7.49
2)

7.60

Refer to OPTIONS for full order number detail

COOPER CROUSE-HINDS GMBH

XLVS23030081-B-HASP

1
2
3
4
5
6
7
8
9
10
11
12
COOPER CROUSE-HINDS GMBH

7.61

E X - T E R M I N A L

E N C L O S U R E S

Stainless Steel Version for Zone 1 and Zone 21


STB

The STB range is an ATEX certified terminal


box solution available in various options of
materials and finishes fully compliant with the
impact, thermal and ingress requirements of
EN 60079-0 ff. and EN 6124-0 ff. and is
available in a comprehensive range of
12 different sizes. With for the possibilities
many configuration for a multitude of appli cations. Using the highest quality materials,
unique design benefits and precision manu facturing the STB range is the benchmark in
heavy-duty gauge enclosures of its class.
STB has unique wrap-round lid cover design
that wraps around the body of the enclosures
eliminate ingress of either liquids such as greenwater or powder, such as sand. This design
provides a significant advantage as the gasket
sealing area is not exposed to the external
environment, preventing contamination from ice
for mations and abrasion of sand storms. The
lid cover is secured and sealed to IP66 by the
retained stainless steel bolts around the outside
of the enclosure, whilst being supported a floppy
hinge that allow the lid cover to be removed.
The superior quality one piece Chloroprene
closed cell gasket material that maintains the
enclosures high ingress protection integrity
providing IP66. This material has a wide
operating temperature range for the most
hostile environments.
The body of the STB enclosure has a superior
wide surface area gasket sealing area 10 mm
wide compared to conventional enclosures that
use a knife-edge seal, that is only the thickness
of the material, typically only 1.5 mm.

316L Stainless Steel (1.4404 to EN 10088)


Superior corrosion resistant electro
chemically polished.
Sheet Steel - Polyester powder coated
to RAL 7032.
High integrity one piece solid Chloroprene
rubber or High integrity one piece closed
cell chloroprene sponge.
Optional Silicone gasket available
on all sizes.
Safety standard IP66
Extended ambient temperatures 65 C to
+55 C as option.
Certification GOST-R, AEx, cULus and
Germanischer Lloyd on request

7.62

Ex-e Terminal enclosures

1
2
STB

STB

Technical data
Type STB Terminal Enclosure METRIC and IMPERIAL
Marking to 94/9/EC

II 2 G Ex e ia IIC T6/T5
II 1 G Ex ia IIC T6, T5

II 2 D Ex tD A21 IP66 T95 C


Temperature class

T6 up to +40 C / T5 up to +55 C

EC-Type Examination Certificate

PTB 04 ATEX 1015

Permissible ambient temperature

30 C to +40 C
65 C to +55 C (option: Silicone gasket)

Rated voltage

up to 690 V*

Rated current

up to 500 A*

Connecting terminals

up to 240 mm2*

Insulation class

Degree of protection accd. EN 60529

IP66

Cable glands/Gland plates/Enclosure drilling

up to 4 side optional gland plate combination with entries to meet requirements


(38/38/20 - 60/40/20) combination with entries to meet requirements

Type of mounting

STB 12/12/08 - 25/25/12 2 welded lugs with 8 mm holes


STB 16/38/12 - 25/40/13 4 welded lugs with 8 mm holes
STB 38/38/22 - 60/40/20 4 welded lugs with 11 mm holes

Enclosure material

stainless steel 316 L or sheet steel polyester powder coated (RAL 7032)

Material thickness

1.5 mm

Equipment mountings

12/12/08 - 25/40/13 internely welded TAS 20 rail terminals mounting

38/38/20 - 60/40/20 4 x stand off pillars 9 mm, 25 mm height,


tapped M6 x 10, for rail or mounting plate
Enclosure earth

12/12/08 - 25/40/13 M6 external/internal earth stud assembly


38/38/20 - 60/40/20 M10 external/internal earth stud assembly

Gasket material

Neoprene, Silicone gasket (option)

* depending on type of terminal and Ex-components used

Additional certifications:
GOST-R, cULUs types 3S, 4, 4 x and Germanischer Lloyd approved on request.

Dimension drawing

Fixing Centres
(vertical)

Height

Fixing Lug and Rail / Pillar configuration


(not to scale)

Width

STB 121208191910
(STB 1-3)

STB 252512
(STB 4)

STB 163812
(STB 5)

10

Rail Fixing
Pillars
STB 254013
(STB 6)

COOPER CROUSE-HINDS GMBH

STB 383822-406022
(STB 7-9) Grand Plate
Options Available

Dimensions in mm

Depth

Fixing Centres
(horizontal)

7.63

11
12

Ex-e Terminal enclosures

STB

STB

Ordering details STB METRIC up to 3 x 51 terminals


STB

Dimensions1)

Fixing

Weight

Terminal mounting rail

Terminal content

H x W x D in mm

Centres1)

in kg

Rail fixing

Row orientation vertical

vertical x

(empty

centres

horizontal

enclosure) vert.

Size

Rail length

horiz. vert.

horiz.

2.5 (6)

4 (6.5)

6 (8)

10 (10)

Enclosure dimensions and terminal content


12/12/082) 120x120x 80

145x145

1.4

62

82

1x 8

1x 6

1x 5

1x 4

15/12/082) 150x120x 80

175x175

1.6

90

110

1x13

1x11

1x 8

1x 7

15/15/092) 150x150x 90

175x175

1.9

90

110

1x13

1x11

1x 8

1x 7

19/15/092) 190x150x 90

175x175

2.3

130

150

1x21

1x18

1x13

1x10

19/19/102) 190x190x100

215x215

3.0

130

150

1x21

1x18

1x13

1x10

25/25/122) 250x250x120

275x275

3.7

180

200

2x31

2x26

2x19

2x15

16/38/122) 160x380x120

80x405

3.7

300

320

1x55

1x46

1x34

1x28

25/40/132) 250x400x130

150x425

5.4

180

200

3x31

3x26

3x19

3x15

STB

Available glanding area

Top &

Left

Order No.4)

Max. Entry Guide (metric)

Right

Top & Bottom / Left / Right

Bottom
Size

(with gland plates fitted) in mm

M16

M20

M25

M32

M40

M50

M63

Gland entry detail


12/12/082) 114x 63

114x 63

70x 63

7/7/4

3/3/1

2/2/1

2/2/1

STBS1121208

15/12/082) 114x 63

114x 63

100x 63

7/9/6

3/3/2

2/3/2

2/2/1

STBS1151208

15/15/092) 144x 73

144x 73

100x 73

9/9/6

6/6/4

3/3/2

2/2/1

2/2/1

STBS1151509

19/15/092) 144x 73

184x 73

130x 73

9/12/8

6/8/6

3/4/2

2/3/2

2/2/1

STBS1191509

19/19/102) 184x 83

184x 83

140x 83

18/18/14 8/8/6

7/7/5

3/3/2

2/2/2

2/2/1

STBS1191910

25/25/122) 244x103

244x103

200x103

32/32/26 18/18/14 10/10/8 7/7/6

3/3/3

3/3/2

2/2/2

STBS1252512

16/38/122) 372x103

154x103

330x103

50/20/44 29/11/24 15/6/14 12/4/10 5/2/5

4/1/4

3/1/3

STBS1163812

25/40/132) 394x113

244x113

350x113

54/32/48 30/18/26 16/10/14 13/7/11 6/3/5

5/3/4

4/2/3

STBS1254013

Options
STB Painted

STB PS 1XXYYZZ

STB with additional UL CERT2)

STB S 1XXYYZZ UL

STB with gland 1 plate3)

STB S 1XXYYZZ 1

STB with gland 3 plate3)

STB S 1XXYYZZ 3

Type

Order No.

Example
15/15/09 painted with 3 gland plates and UL-certification

STBPS1151509-UL

The information provided is based on the physical constraints of the enclosure. Please refer to the certificate for hazardous area applications.
Notes: 1) Dimensions drawing see page 7.63

7.64

2)

this types can be ordered with additional UL-Certification

3)

only this types includes UL-Certification and can be ordered with 1 or 3 gland plates

4)

Refer to OPTIONS for full order number detail

COOPER CROUSE-HINDS GMBH

Ex-e Terminal enclosures

1
2
STB

Ordering details STB METRIC up to 5 x 79 terminals


STB

Dimensions1)

Fixing

Weight

Terminal mounting rail

Terminal content

H x W x D in mm

Centres1)

in kg

Rail fixing

Row orientation vertical

vertical x

(empty

centres

horizontal

enclosure) vert.

Size

Rail length

horiz. vert.

horiz.

2.5 (6)

4 (6.5)

6 (8)

10 (10)

Enclosure dimensions and terminal content


38/38/222) 380x380x220

250x435

8.5

280

300

3x42

3x39

3x32

3x25

40/60/222) 400x600x220

264x656

13.0

300

320

3x46

3x42

3x34

3x27

60/40/222) 600x400x220

464x456

13.0

500

520

5x79

5x73

5x59

5x47

5
STB

Available glanding area

Top &

Left

Max. Entry Guide (metric)

Right

Order No.

Top & Bottom / Left / Right

Bottom
Size

(with gland plates fitted) in mm

M16

M20

M25

M32

M40

M50

M63

Gland entry detail


38/38/222) 374x203

374x203

324x203

100/100/88 57/57/48 40/40/33 24/24/20 15/15/12 8/8/7

6/6/5

STBS13838220

40/60/222) 594x203

394x203

344x203

164/108/92 93/60/51 65/40/35 40/26/22 26/17/14 14/9/7

11/7/6

STBS14060220

60/40/222) 337x124

337x124

337x124

108/164/152 60/93/84 40/65/60 26/40/38 17/26/23 9/14/13 7/11/10

STBS16040220

7
8

Options
STB Painted

STB PS 1XXYYZZ

STB with gland 3 plate3)

STB S 1XXYYZZ 3

STB with gland 1 plate2)

Type

STB S 1XXYYZZ 1

Order No.

Example
38/38/22 316L SS with 3 gland plates incl. UL-certification

STBS13838223

The information provided is based on the physical constraints of the enclosure. Please refer to the certificate for hazardous area applications.

10

Notes: 1) Dimensions drawing see page 7.63


2)

only this types includes UL-Certification and can be ordered with 1 or 3 gland plates

3)

Refer to OPTIONS for full order number detail

11
12
COOPER CROUSE-HINDS GMBH

7.65

Ex-e Terminal enclosures

STB

Ordering details STB IMPERIAL up to 21 terminals


STB

Dimensions1)

Fixing

Weight

Terminal mounting rail

Terminal content

HxWxD

Centres1)

in lbs

Rail fixing

Row orientation vertical

vertical x

(empty

centres

horizontal

enclosure) vert.

in inches
Size

Rail length

horiz. vert.

horiz.

2.5 (6)

4 (6.5)

6 (8)

10 (10)

1x 4

Enclosure dimensions and terminal content


12/12/082) 4.72x4.72x3.15

5.71x5.71

3.08

2.44

3.23

1x 8

1x 6

1x 5

15/12/082) 5.91x4.72x3.15

6.89x6.89

3.52

3.54

4.33

1x13

1x11

1x 8

1x 7

15/15/092) 5.91x5.91x3.54

6.89x6.89

4.18

3.54

4.33

1x13

1x11

1x 8

1x 7

19/15/092) 7.48x5.91x3.54

6.89x6.89

5.06

5.12

5.91

1x21

1x18

1x13

1x10

STB

Max. Entry Guide (imperial) Top & Bottom / Left / Right

Available glanding area

Top &
Size

Left

Right

Order No.

Gland (first row)

Bottom

Hub (second row)

(with gland plates fitted) in inches

/2 NPT

/4 NPT 1 NPT

11/4 NPT 11/2 NPT 2 NPT 21/2 NPT

Gland entry detail


12/12/082) 4.49x2.48

4.49x2.48

2.76x2.48

6/6/3

3/3/1

2/2/1

2/2/1

2/2/1

2/2/1

2/2/1

3/3/2

2/3/2

2/2/1

15/12/082) 4.49x2.48

5.67x2.48

3.94x2.48

6/8/5
2/3/2

2/3/2

2/2/1

15/15/092) 5.67x2.87

5.67x2.87

3.94x2.87

8/8/5

6/6/4

3/3/2

2/2/1

2/2/1

3/3/2

3/3/2

2/2/1

2/2/1

19/15/092) 5.67x2.87

7.24x2.87

5.12x2.87

8/11/7

6/9/6

3/4/2

2/3/2

2/2/1

3/4/3

3/3/2

2/3/2

2/2/2

STBS1121208
STBS1151208
STBS1151509
STBS1191509

Options
STB Painted

STB PS 1XXYYZZ

STB with additional UL CERT2)

STB S 1XXYYZZ UL

STB with gland 1 plate3)

STB S 1XXYYZZ 1

STB with gland 3 plate3)

STB S 1XXYYZZ 3

Type

Order No.

Example
15/15/09 painted with 3 gland plates and UL-certification

STBPS151509UL

The information provided is based on the physical constraints of the enclosure. Please refer to the certificate for hazardous area applications.
Notes: 1) Dimensions drawing see page 7.63

7.66

2)

only this types includes UL-Certification and can be ordered with 1 or 3 gland plates

3)

Refer to OPTIONS for full order number detail

COOPER CROUSE-HINDS GMBH

Ex-e Terminal enclosures

1
2
STB

Ordering details STB IMPERIAL up to 3 x 31 terminals


STB

Dimensions1)

Fixing

Weight

Terminal mounting rail

Terminal content

HxWxD

Centres1)

in lbs

Rail fixing

Row orientation vertical

vertical x

(empty

centres

horizontal

enclosure) vert.

in inches
Size

Rail length

horiz. vert.

horiz.

2.5 (6)

4 (6.5)

6 (8)

10 (10)

Enclosure dimensions and terminal content


19/19/103) 7.48x 7.48x3.94

8.46x8.46

6.60

5.12

5.91

1x21

1x18

1x13

1x10

25/25/123) 9.48x 9.84x4.72

10.83x10.83

8.14

7.09

7.87

2x31

2x26

2x19

2x15

16/38/123) 6.30x14.96x4.72

3.15x15.94

8.14

11.81

12.60

1x55

1x46

1x34

1x28

25/40/133) 9.84x15.75x5.12

5.91x16.73

11.88

7.09

7.87

3x31

3x26

3x19

3x15

STB

Max. Entry Guide (imperial) Top & Bottom / Left / Right

Available glanding area

Top &
Size

Left

Right

Hub (second row)

(with gland plates fitted) in inches

/2 NPT

/4 NPT 1 NPT

Order No.

STBS1191910

Gland (first row)

Bottom

11/4 NPT 11/2 NPT 2 NPT 21/2 NPT

Gland entry detail


19/19/102) 7.24x3.27

7.24x3.27

7.24x3.27

17/17/12 9/9/6

7/7/5

3/3/2

2/2/2

2/2/1

8/8/6

3/3/2

2/2/2

2/2/1

7/7/6

3/3/3

3/3/2

2/2/2

3/3/3

25/25/122) 9.61x4.06

9.61x4.06

7.87x4.06

23/23/18 18/18/14 10/10/8

3/3/3

3/3/2

2/2/2

2/2/2

16/38/122) 14.65x4.06

6.06x4.06

12.99x4.06

36/14/29 29/11/23 16/6/12

12/4/9

5/2/4

4/1/3

3/1/3

17/6/15

5/2/5

5/2/4

4/1/3

3/1/3

25/40/132) 15.51x4.45

9.61x4.45

13.78x4.45

50/30/44 30/18/27 17/10/15 13/7/11

6/3/5

5/3/4

4/2/3

27/17/24 16/9/14

5/3/4

4/2/4

4/2/3

11/11/9

9/9/7
15/5/13

8/8/6
12/4/11
13/8/11

6/3/5

STBS1252512
STBS1163812
STBS1254013

Options
STB Painted

STB PS 1XXYYZZ

STB with additional UL CERT2)

STB S 1XXYYZZ UL

STB with gland 1 plate3)

STB S 1XXYYZZ 1

STB with gland 3 plate3)

STB S 1XXYYZZ 3

Type

Order No.

Example
16/38/12 316L SS with 1 gland plate with UL-certification

STBS11638121UL

The information provided is based on the physical constraints of the enclosure. Please refer to the certificate for hazardous area applications.

10

Notes: 1) Dimensions drawing see page 7.63


2)

only this types includes UL-Certification and can be ordered with 1 or 3 gland plates

3)

Refer to OPTIONS for full order number detail

11
12
COOPER CROUSE-HINDS GMBH

7.67

Ex-e Terminal enclosures

STB

Ordering details STB IMPERIAL up to 5 x 79 terminals


STB

Dimensions1)

Fixing

Weight

Terminal mounting rail

Terminal content

HxWxD

Centres1)

in lbs

Rail fixing

Row orientation vertical

vertical x

(empty

centres

horizontal

enclosure) vert.

in inches
Size

Rail length

horiz. vert.

horiz.

2.5 (6)

4 (6.5)

6 (8)

10 (10)

Enclosure dimensions and terminal content


38/38/222) 14.96x14.96x8.66

9.84x17.13

18.70

11.02

11.81

3x42

3x39

3x32

3x25

40/60/222) 15.75x23.62x8.66

10.39x25.83

28.60

11.81

12.60

3x46

3x42

3x34

3x27

60/40/222) 23.62x15.75x8.66

18.27x17.95

28.60

19.69

20.47

5x79

5x73

5x59

5x47

STB

Max. Entry Guide (imperial) Top & Bottom / Left / Right

Available glanding area

Top &
Size

Left

Right

Order No.

Gland (first row)

Bottom

Hub (second row)

(with gland plates fitted) in inches

/2 NPT

/4 NPT

1 NPT

11/4 NPT 11/2 NPT 2 NPT 21/2 NPT

Gland entry detail


38/38/222) 14.72x7.99

14.72x7.99

12.76x7.99

40/60/222) 23.39x7.99

15.51x7.99

13.54x7.99

60/40/222) 15.51x7.99

23.39x7.99

21.42x7.99

84/84/70 57/57/48 40/40/33 24/24/20 15/15/12 8/8/7

6/6/5

43/43/38 30/30/26 24/24/22 15/15/14 14/14/11 7/7/6

6/6/5

137/88/77 93/60/51 65/43/35 40/26/22 26/17/14 14/9/7

11/7/6

70/45/40 48/32/26 42/26/22 26/17/14 23/14/12 12/8/7 11/7/5

STBS13838220
STBS14060220

88/137/123 60/93/84 43/65/58 26/40/36 17/26/23 9/14/13 7/11/10


45/70/65 32/48/44 26/42/38 17/26/24 14/23/20 8/12/11 7/11/10

STBS16040220

Options
STB Painted

STB PS 1XXYYZZ

STB with gland 3 plate3)

STB S 1XXYYZZ 3

STB with gland 1 plate2)

Type

STB S 1XXYYZZ 1

Order No.

Example
38/38/22 painted with 3 gland plates incl. UL-certification

STBS3838223

The information provided is based on the physical constraints of the enclosure. Please refer to the certificate for hazardous area applications.
Notes: 1) Dimensions drawing see page 7.63

7.68

2)

only this types includes UL-Certification and can be ordered with 1 or 3 gland plates

3)

Refer to OPTIONS for full order number detail

COOPER CROUSE-HINDS GMBH

1
2
3
4
5
6
7
8
9
10
11
12
COOPER CROUSE-HINDS GMBH

7.69

Ex-e/Ex-i Terminal box

Type 744 21

Type 745 22

Technical data
Type 744 21/745 22/746 23/749 24 up to 296 terminal
Marking to 94/9/EC
EC-Type Examination Certificate

II 2 G Ex de ia/ib [ia/ib] m IIC T6 /

II 2 D Ex tD A21 IP66 T80 C

PTB 99 ATEX 1044

IECEx certificate of conformity

IECEx BKI 07.0023

Marking accd. to IECEx

Ex de ia/ib m [ia/ib] IIC T4 ... T6


Ex tD A21 IP66 T80 C

Rated voltage

up to 690 V

Rated current

depends on terminal mounting

Degree of EN 60529

IP66

Enclosure material

Stainless steel AISI 316 L (1.4404)

Type 744 21 up to 40 terminal


Terminal cross section

max. 16 mm2

Weight

approx. 3.5 kg

Max. number drillings/cable glands

M16

M20

M25

M32

M40

M50

M63

down

37

23

15

with flange

29

17

12

Terminal mounting space on the terminal rail


Max. number of terminals acc. to certification

1 x 230 mm
2.5 mm2

4 mm2

6 mm2

10 mm2

16 mm2

25 mm2

35 mm2

1 x 40

1 x 33

1 x 25

1 x 20

1 x 17

1 x 17

Type 745 22 up to 82 terminal


Terminal cross section

max. 70 mm2

Weight

approx. 7.5 kg

Max. number drillings/cable glands

M16

M20

M25

M32

M40

M50

M63

down

37

23

15

with flange

29

17

12

Terminal mounting space on the terminal rail

2 x 230 mm

Max. number of terminals acc. to certification

2.5 mm2

4 mm2

6 mm2

10 mm2

16 mm2

25 mm2

35 mm2

2 x 41

2 x 34

1 x 26

2 x 20

1 x 17

1 x 17

1 x 14

Type 746 23 up to 188 terminal


Terminal cross section

max. 240 mm2

Weight

approx. 11.5 kg

Max. number drillings/cable glands

M16

M20

M25

M32

M40

M50

M63

down

71

46

30

18

10

with flange

58

34

24

14

Terminal mounting space on the terminal rail


Max. number of terminals acc. to certification

2 x 510 mm
2.5 mm2

4 mm2

6 mm2

10 mm2

16 mm2

25 mm2

35 mm2

2 x 94

2 x 78

1 x 59

2 x 47

1 x 40

1 x 40

1 x 32

Type 749 24 up to 296 terminal


Terminal cross section

max. 240 mm2

Weight

approx. 16.5 kg

Max. number drillings/cable glands

M16

M20

M25

M32

M40

M50

M63

down

108

69

45

27

15

with flange

87

51

36

21

12

Terminal mounting space on the terminal rail

2 x 795 mm

Max. number of terminals acc. to certification

7.70

2.5 mm2

4 mm2

6 mm2

10 mm2

16 mm2

25 mm2

35 mm2

2 x 148

2 x 124

1 x 94

2 x 75

1 x 63

1 x 63

1 x 51

COOPER CROUSE-HINDS GMBH

Ex-e/Ex-i Terminal box

1
2
Type 749 24

Type 746 23

Ordering details
Type

Cable gland

No. of terminals

Order No.

Terminal boxes 744 21 mounted with screw terminals 2 x 2.5 mm2 + PE-rail 4 mm2
Ex-e

1 x Stainless steel down

1 x Ex-e*

without drilling

7 x PE
2

Terminal boxes 745 22 mounted with screw terminals 2 x 2.5 mm + PE-rail 4 mm


Ex-e

1 x Stainless steel down

1 x Ex-e*

without drilling

14 x PE
2

Terminal boxes 745 22 mounted with screw terminals 2 x 2.5 mm + PE-rail 4 mm


Ex-e

GHG 744 2101 R0001

GHG 745 2201 R0001

2 x Stainless steel down

1 x Ex-e*

without drilling

2 x 14 x PE

GHG 746 2301 R0001

Terminal boxes 749 24 mounted with screw terminals 2 x 2.5 mm2 + PE-rail 4 mm2
Ex-e

3 x Stainless steel down

1 x Ex-e*

without drilling

3 x 14 x PE

GHG 749 2401 R0001

* acc. to type examination certificate individual extensible


Other versions available on request.

Dimension drawing
151
135

X362.5
312.5

151
135

X362.5
312.5

151
135

312.5
X247

312.5
X247

X225
175

Type 744 21

Type 745 22

151
135

8
9

941.5
X876

627
X561.5

X362.5
312.5

10

Type 746 23

X = mounting dimension

Type 749 24

COOPER CROUSE-HINDS GMBH

Dimensions in mm

151

7.71

11
12

EX-INTERMEDIATE MOTOR TERMINAL BOXES


up to 240 mm2
Plastic version for Zone 1 and Zone 21

The CEAG connection and junction boxes are


for example used in Zones 1, 2, 21 and 22 as
junction boxes for the connection of pumps,
heating, motordrives etc. in hazardous explosion
endangered areas.
The connection and junction boxes are fitted
with certified terminals accommodating for
240 mm 2 according to EN 50 019. For larger
terminal cross sections, versions with terminal
bolts are also used.
A special version with terminal rails accommodating for 240 mm 2 and a double cable end box
enables the connection of larger terminal cross
sections. The cable to be connected is put
through the front side and is laid into the double
cable terminal box where it is then connected
to the terminal bolts on the copper rail.
The terminal boxes are fitted with trumpet
shaped cable glands and a strain relief or just
a strain relief for a flexible cable outing.
International approvals

Decisive cost reduction with the CEAG


mounting system using junction boxes
accommodating for 70 mm 2
With four cables, connections of
up to 240 mm 2 possible
Mechanical, chemical and thermal durability

7.72

Ex-Intermediate motor terminal boxes 4 mm2

1
2
Type 791 02

Technical data
Type 791 02
Marking to 94/9/EC

II 2 G Ex dem ia II, IIC T6 /

Permissible ambient temperature

20 C to +40 C

EC-Type Examination Certificate

PTB 00 ATEX 3108

IECEx certificate of conformity

IECEx BKI 07.0034

Marking accd. to IECEx

II 2 D Ex tD A21 IP66 T80 C

Ex e II T6 / Ex ia IIC T6
Ex tD A21 IP66 T58 C

Rated voltage

up to 690 V

Rated current

depends on terminal mounting

Degree of EN 60529

IP66

Enclosure material

Polyamide

Terminal cross section

up to 6 mm2

Weight

approx. 0.7 kg

Ordering details
Type

Cable gland

No. of terminals

Order No.

Type 791 02 mounted with screw terminals 2 x 4 mm2 + 1 x PE-terminal 2 x 4 mm2


Ex-e

1 x M25 for cable 8-17 mm

4 x Ex-e

1 x M32 trompet-shaped gland


for cable 15-20 mm

GHG 791 0201 R0016

1 x PE

Other versions for cable 15 - 20 mm available on request.

Accessories
Mounting plate for intermediate motor terminal box 791 02
Type

Application

Fixing method

Order No.

Size 2
Size 2
Size 2
Protective canopy Size 2

Wall mounting
Trellis mounting
Pipe mounting
for mounting plate size 2

screwless mounting
screwless mounting
screwless mounting

GHG 610 1953 R0104


GHG 610 1953 R0106
GHG 610 1953 R0105
GHG 610 1955 R0102

Dimension drawing

73.5

10

Dimensions in mm

X 54

117.5

113.5
X 104.5

Type 791 02

COOPER CROUSE-HINDS GMBH

7.73

11
12

E x - I n t e r m e d i a t e m o t o r t e r m i n a l b o x e s 1 0 m m 2/ 1 6 m m 2

Type 721 00 10 mm2

Type 721 00 16 mm2

Technical data
Type 721 00
Marking to 94/9/EC

II 2 G Ex de ia/ib [ia/ib] m IIC T6 /

Permissible ambient temperature

20 C to +40 C

EC-Type Examination Certificate

PTB 99 ATEX 1044

IECEx certificate of conformity

IECEx BKI 07.0023

Marking accd. to IECEx

Ex ed ia/ib m [ia/ib] IIC T4 T6

II 2 D Ex tD A21 IP66 T80 C

Ex tD A21 IP66 T80 C


Rated voltage

up to 690 V

Rated current

depends on terminal mounting

Degree of EN 60529

IP66

Terminal cross section

721 00 max. 10 mm2 / 721 10 max. 16 mm2

Enclosure material

Glass-fibre reinforced polyester

Weight

721 00 approx. 1.0 kg / 721 10

approx. 1.1 kg

Ordering details
Type

Cable gland

No. of terminals

Order No.

Type 721 00 mounted with screw terminals 2 x 10 mm2 + 1 x PE-terminal 2 x 10 mm2


Ex-e

1 x M40 for cable 17-28 mm

4 x Ex-e

1 x M40 trompet-shaped gland

1 x PE
GHG 721 0001 R0013

for cable 19-27 mm


Type

Cable gland

No. of terminals
2

Type 721 00 mounted with screw terminals 2 x 16 mm + 1 x PE-terminal 2 x 16 mm


Ex-e

1 x M50 for cable 21-35 mm

4 x Ex-e

1 x M50 trompet-shaped gland

1 x PE

Order No.

GHG 721 0001 R0014

for cable 26-34 mm


Other versions available on request.

Accessories
Mounting plate for junction box 721 00
Type

Application

Fixing method

Order No.

Size 2A
Size 2A
Size 2A
Protective canopy Size 2A

Wall mounting
Trellis mounting
Pipe mounting
for mounting plate size 2A

screwless mounting
screwless mounting
screwless mounting

GHG 610 1953 R0107


GHG 610 1953 R0109
GHG 610 1953 R0108
GHG 610 1955 R0103

Dimension drawing
165
X 151

131.5

M 40

X 141

Dimensions in mm

267 (10 mm2 )


280 (16 mm2 )

165

M 40 (1)
M 50 (2)
80

Type 721 00

7.74

COOPER CROUSE-HINDS GMBH

E x - I n t e r m e d i a t e m o t o r t e r m i n a l b o x e s 3 5 m m 2/ 7 0 m m 2

1
2
Type 745 02

Technical data
Type 745 02
Marking to 94/9/EC

II 2 G Ex de ia/ib [ia/ib] m IIC T6 /

Permissible ambient temperature

20 C to +40 C

EC-Type Examination Certificate

PTB 99 ATEX 1044

IECEx certificate of conformity

IECEx BKI 07.0034

Marking accd. to IECEx

II 2 D Ex tD A21 IP66 T80 C

Ex ed ia/ib m [ia/ib] IIC T4 T6


Ex tD A21 IP66 T80 C

Rated voltage

up to 690 V

Rated current

depends on terminal mounting

Degree of EN 60529

IP66

Enclosure material

Glass-fibre reinforced polyester

Terminal cross section

up to 35 mm2 or max. 70 mm2

Weight

745 0201 R0002 approx. 3.0 kg / 745 0201 R0003 approx. 3.2 kg

Ordering details
Type

Cable gland

No. of terminals

Order No.

Type 745 02 mounted with screw terminals 2 x 35 mm2 + 1 x PE-terminal 2 x 35 mm2


Ex-e

1 x M50 for cable 21-35 mm

4 x Ex-e

1 x M63 trompet-shaped gland

1 x PE

Type

Cable gland

GHG 745 0201 R0002

for cable 35-46 mm


No. of terminals

Order No.

Type 745 02 mounted with screw terminals 2 x 50/70 mm2 + 1 x PE-terminal 2 x 50/70 mm2
Ex-e

1 x M50 for cable 21-35 mm

4 x Ex-e

1 x M63 trompet-shaped gland

1 x PE

GHG 745 0201 R0003

for cable 35-46 mm


Other versions available on request.

Accessories
Mounting plate for junction box 745 02
Type

Application

Fixing method

Order No.

Size 3
Protective canopy Size 3

Pipe mounting
for mounting plate size 3

screw mounting on 2 plates

GHG 610 1953 R0108


GHG 610 1955 R0104

Dimension drawing
271
X 247

10

271

X 247

136

11

~110

Dimensions in mm

M 63
120

Type 745 02

COOPER CROUSE-HINDS GMBH

7.75

11
12

E x - I n t e r m e d i a t e m o t o r t e r m i n a l b o x e s 1 8 5 m m 2/ 2 4 0 m m 2

GHG 746 0301 R0001

GHG 746 0301 R0020

Technical data
Type 746 03
Marking to 94/9/EC

II 2 G Ex de ia/ib [ia/ib] m IIC T6 /

Permissible ambient temperature

20 C to +40 C

EC-Type Examination Certificate

PTB 99 ATEX 1044

IECEx certificate of conformity

IECEx BKI 07.0023

Marking accd. to IECEx

Ex de ia/ib m [ia/ib] IIC T4 ... T6

II 2 D Ex tD A21 IP66 T80 C

Ex tD A21 IP66 T80 C


Rated voltage

up to 690 V

Rated current

depends on terminal mounting

Degree of EN 60529

IP54

Cable gland

via double cable pothead

Enclosure material

Glass-fibre reinforced polyester

Terminal cross section

up to 180 mm2 or max. 240 mm2

Weight

746 0301 R0001 approx. 6.3 kg / 746 0301 R0008 approx. 16.5 kg

Ordering details
Type

Cable gland

No. of terminals

Order No.

Type 746 03 assembled with bold clamp 2 x 185 mm2 + PE-bold clamp 2 x 185 mm2
Ex-e

Double cable end box

3 x Ex-e

1 x Entry sleeve 21-45 mm

1 x PE
GHG 746 0301 R0001

1 x Entry sleeve 46-72 mm


Type

Cable gland

No. of terminals

Type 746 03 assembled with bold clamp 240 mm + PE-bold clamp 240 mm
Ex-e

Type

Double cable end box

6 x Ex-e

2 x Entry sleeve 46-72 mm

2 x PE

GHG 746 0301 R0008

Cable gland

No. of terminals

Order No.

Type 746 03 assembled with bold clamp 240 mm + PE-bold clamp 240 mm
Ex-e

Double cable end box

12 x Ex-e

3 x Entry sleeve 46-72 mm

4 x PE

Other versions available on request.

7.76

Order No.

COOPER CROUSE-HINDS GMBH

GHG 746 0301 R0020

E x - I n t e r m e d i a t e m o t o r t e r m i n a l b o x e s 1 8 5 m m 2/ 2 4 0 m m 2

1
2
GHG 746 0301 R0020

GHG 746 0301 R0001

Dimension drawing
136
116

271
X247

544
X520

203
150

5
6

GHG 746 0301 R0001


X247

544

X247

116

544
X520

203
150

8
GHG 746 0301 R0008
544

X247

116

210

10

203
150

Dimensions in mm

544
X520

X247

GHG 746 0301 R0020

X = fixing dimension

COOPER CROUSE-HINDS GMBH

7.77

11
12

FIXING

MATERIALS

Distribution and junction boxes

The CEAG mounting plates are the innovative


answer to the customer requested ability for
mounting apparatus without having to use tools.
In close cooperation with our customers, this
intelligent and innovative solution for the mounting of a variety of terminal boxes an appliances
onto trellis, piping and walls was developed.
The clip-on mounting system in connection
with the CEAG explosion-protected distribution,
plugs and sockets and terminal boxes renders
a decisive cost reduction.
No hot work permits are needed!
Optional clip-on protection canopies made
of stainless steel offer protection against
aggressive environmental influences, direct
sunlight and rain.

Decisive cost reduction just clip-it-on


Quick appliance mounting with clip-on
technology no hot work permit needed
Easy installation of the mounting plates
on walls, trellis and pipes
Universal use as appliance holder
just clip-it-on

7.78

AND

ACCESSORIES

Fitting materials and accessories

1
2
GHG 610 1953 R0105

GHG 610 1953 R0106

GHG 610 1953 R0102

GHG 610 1953 R0103

Mounting plates

Type

Application

Order No.

Size 1

Wall mounting

GHG 610 1953 R0101

Size 1

Trellis mounting

GHG 610 1953 R0103

Size 1

Pipe mounting

GHG 610 1953 R0102

Size 2

Wall mounting

GHG 610 1953 R0104

Size 2

Trellis mounting

GHG 610 1953 R0106

Size 2

Pipe mounting

GHG 610 1953 R0105

Size 2A

Wall mounting

GHG 610 1953 R0107

Size 2A

Trellis mounting

GHG 610 1953 R0109

Size 2A

Pipe mounting

GHG 610 1953 R0108

Size 3

Wall mounting

GHG 610 1953 R0118

Size 3

Trellis mounting

GHG 610 1953 R0118


GHG 610 1953 R0110

Size 3

Pipe mounting

Size 4

Wall mounting

GHG 610 1953 R0126

Size 4

Trellis mounting

GHG 610 1953 R0126

Size 4

Pipe mounting

GHG 610 1953 R0130

Size 5

Wall mounting

GHG 610 1953 R0128

Size 5

Trellis mounting

GHG 610 1953 R0128

Size 5

Pipe mounting

GHG 610 1953 R0132

4
5
6
7
8
9
10
11
12

COOPER CROUSE-HINDS GMBH

7.79

Fitting materials and accessories

Canopy

Plug in fastener

Blind plug

Label holder with label

Accessories
For mounting plate
Type

OU

Label holder with type label (blank) for mounting plates size 1, 2, 2A and 3

10

GHG 610 1953 R0057

Type label for label holder and mounting plates size 4 and size 5

10

GHG 610 1953 R0011

10

GHG 610 1953 R0134

10

GHG 610 1953 R0041

10

GHG 610 1953 R0020

Blind plug for unused fixing points of mounting plates size 4 and size 5
Plug-in fastener for CEAG modules with 5.5 mm and 11 mm fixing elements
Mounting set for pipes 1 ( 27 - 30 mm) for mounting plates with pipe fixing

1 set = 4 pcs.

Order No.

The order No. will show 1 pcs.


Please note that only pack quantities (OU) can be ordered.
Protective canopy for mounting plate
Type

Application

Order No.

Size 1

for mounting plate size 1

GHG 610 1955 R0101

Size 2

for mounting plate size 2

GHG 610 1955 R0102

Size 2A

for mounting plate size 2A

GHG 610 1955 R0103

Size 3

for mounting plates pipe fixing size 3 verticaly

GHG 610 1955 R0104

Size 3A

for mounting plates wall/trellis fixing size 3 verticaly

GHG 610 1955 R0105

Size 3B

for mounting plates pipe fixing size 3 horizontal

GHG 610 1955 R0106

Size 4

for mounting plate size 4

GHG 610 1955 R0107

Size 5

for mounting plate size 5

GHG 610 1955 R0108

7.80

COOPER CROUSE-HINDS GMBH

Fitting materials and accessories

1
2
GHG 610 1953 R0105

GHG 610 1953 R0106

GHG 610 1953 R0102

GHG 610 1953 R0103

Dimensions
9

134.5

189

23

127

23

125

158

X94
X105

186

X51
X62

118.5

95

X30

X54
X66

Size 1 for wall- and trellis mounting


82

134.5

Canopy Size 1

X54
X66

127

118.5

Size 2A for wall- and trellis mounting


189

140
95

208

82

134.5

23

186

Size 1 for pipe mounting

Canopy Size 2
140

181

186

Size 2A for pipe mounting

Size 2 for wall- and trellis mounting


134.5

305

X54
X66

X196

X30

208

X94
X105

95

82

Canopy Size 2A

186

174

X48

5
10

X70
180

171
95

Size 3 for wall- and trellis mounting


82

305

172

321

Size 2 for wall- and trellis mounting

10

Canopy Size 3B

Dimensions in mm

Size 3 for pipe mounting

COOPER CROUSE-HINDS GMBH

7.81

11
12

Fitting materials and accessories

GHG 610 1953 R0105

GHG 610 1953 R0106

GHG 610 1953 R0108

Canopy

Dimensions
134.5

27

129

68

134.5

146

237

Mounting plate size 4


for wall/trellis mounting

Mounting plate size 4


for pipe mounting

277

237

95

180

180

27

Protective canopy size 4

174

68

171

265

305

Mounting plate size 5


for wall/trellis mounting

Mounting plate size 5


for pipe mounting

Protective canopy size 5

Dimensions in mm

265

95

7.82

COOPER CROUSE-HINDS GMBH

You might also like