Variable Refrigerant Flow Systems: Floor Concealed - Indoor Unit 1/2 Tons - Model JFMHX0762N

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Variable Refrigerant Flow Systems

Floor Concealed - Indoor Unit


1/2 Tons - Model JFMHX0762N

SUBMITTAL DATA

Capacities:
Cooling: Btu/h
Heating: Btu/h

7,500
8,500

Cooling Mode Nominal Conditions:

Sensible Heat Ratio:

0.72

Heating Mode Nominal Conditions:

Indoor: F WB/ F DB
Outdoor: F DB
Pipe Length: Feet
Level Difference: Feet

80 / 67
95
25
0

Indoor: F DB
Outdoor: F DB/ F WB
Pipe Length: Feet
Level Difference: Feet

70
47 / 43
25
0

Power Supply:
V/PH/Hz.
Minimum Circuits Amps (MCA): (A)
Nominal Power Input - Cooling (W)

208 / 230 / 1 / 60
15
49 / 43

Running Load Amps (RLA): (A)


Max. Overcurrent Protection (MOCP): (A)
Nominal Power Input - Heat (W)

0.23
15
50 / 43

Refrigerant and Piping:


Refrigerant Type
Metering Device (Electronic Expansion Valve)

410A
EEV

Liquid Piping Inches


Gas Piping Inches

1/4
1/2

Fan:
Type:
Drive:

Centrifugal
Direct

Fan Motor Output: (W)


Airflow rate (L/M/H)

10
177 / 212 / 247

Sound Data:
Sound Level (L/M/H) 5' below unit (dB-A)
Weight:(lbs)

28 / 30 / 33
46

Coil:
Coil Face Area:(sq. ft.)

1.1

Condensate:
Drain Piping (OD) Inches

1.25

Number of Rows:

Job Name:
Location:
Engineer:
Submitted To:
Submitted By:
Reference:
Approval:
Date:

Submittal Data:
Parts Warranty: One Year.
Washable Filters
Drain Pump Available
Wired or Wireless Remote Controller Options

Construction
Unit #:
Drawing #

Form 121.00-P22 (512)


Supersedes: 121.00-P22 (1110)
2012 Johnson Controls, Inc. P.O. Box 423, Milwaukee, WI 53201
www.johnsoncontrols.com

Remote Sensor Option