DataIndustrial 310m 032002

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

Model 310 Loop Powered Analog Output

Transmitter Installation Guide


by Data Industrial

Mechanical installation

The Model 310 may be surface mounted onto a panel, attached to DIN rails using adapter clips or wall
mounted using two optional enclosures.

Location

Figure 1: Model 310 Dimensions


1.50

Side
3.65

.875

Industrial

Power (4000 only)

Signal (-)

Signal (+)

Shield Ground

Mattapoisett, MA 02739
4-20mA Loop(-)

1.75

4-20mA Loop(+)

Although the Model 310 is encapsulated, all wiring


connections are made to exposed terminals. The unit
should be protected from weather and moisture in
accordance with electrical codes and standard trade
practices.
In any mounting arrangement, the primary concerns
are ease of wiring and attachment of the
programming cable.
The unit generates very little heat so no consideration
need be given to cooling or ventilation.

6HQVRU,QSXWV

61

Surface Mount Installation

The Model 310 may be mounted to the surface of any


panel using double sided adhesive tape or by attaching fasteners through the holes in the mounting
flanges of the unit.

0RGHO
3URJUDPPDEOH
$QDORJ
7UDQVPLWWHU

1.50

',&
&RPP
3RUW

2.75
3.25

DIN Rail Mounting

Figure 2: 310 Optional


Enclosure Dimensions

Optional clips snap onto the mounting flanges allowing the


Model 310 to be attached to DIN 15, 32, 35 mm DIN rail
systems.

Wall Mounting
TOP

2.8

4.5
Side

2.0

SIDE

Optional metal and plastic enclosures are available to mount


the Model 310 to a wall when no other enclosure is used. The
enclosure is first attached to the wall using fasteners through
its mounting holes.
After wiring, the transmitter may be attached to the enclosure
with the terminal headers facing in using the slots in the
mounting flanges. As an alternate mounting arrangement, the
Model 310 may be fastened to the box cover using doublesided adhesive tape.

Data
Industrial

PN# 72019
03/20/03

DATA INDUSTRIAL CORPORATION 11 Industrial Drive, P.O. Box 740 Mattapoisett, MA 02739-0740 USA
Phone: (508) 758-6390 FAX: (508) 758-4057 email: [email protected]

Data Industrial Model 310 Installation Guide

Model 310 Electrical Installation

Figure 3: Model 310 Terminal Locations


Ground
Lug

Analog
Output

Sensor
Input

Signal (-)

Power (4000 only)

2. As shown in figure 4, connect loop power supply


positive (+) to Model 310 terminal marked 4-20mA
loop (+).

Signal (+)

1. Refer to Figure 3 for terminal connections.

Shield Ground

4-20mA Loop(-)

Industrial
Mattapoisett, MA 02739
4-20mA Loop(+)

Per standard wiring practices, the loop power must be


off before making any wire connections. The terminal
strips have removable plug-in connectors to make
wiring easier.

6HQVRU,QSXWV

61

3. Connect terminal marked 4-20mA loop (-) of


Model 310 to positive (+) analog terminal of input
device (Chart Recorder, PLC, etc.).

0RGHO
3URJUDPPDEOH
$QDORJ
7UDQVPLWWHU

',&
&RPP
3RUW

DIC
Communications Port

4. Connect negative (-) analog terminal of input device to loop power


supply negative (-).

Side View - Typical 300 Series


Removable Connector Wiring

5. If Wiring a Series 200 sensor, connect the red wire (signal) to


Signal (+) terminal, black wire (common) to Signal (-) terminal and
the shield to Shield Ground terminal (Disregard shield for the IR
sensors).

Wire

Flathead
If Wiring a Series 4000 sensor, connect the clear wire (signal) to 3/32
Screwdriver
Signal (+) terminal, black wire (common) to Signal (-) terminal,
shield wire to Shield Ground terminal, and red wire (power) to Power (4000 only) terminal.

Series 300
Connector

If wiring to a sine wave output sensor consult factory.


6. For maximum EMI Protection, connect Model 310 ground lug to panel ground. See Note #1
7. Ensure that all connections are tight, then plug connector into header.
Note #1:
Included with every Model 310 is a 310IK kit containing a screw, lock washer and ground lead to
connect the Model 310 to Earth Ground. This will help prevent electrical interference from
affecting the Model 310s normal operation.

Figure 4: Model 310 Wiring to Analog Loop and Series 200 or Series 4000
Shield (if applicable)

Series 200
Sensor

Black
Red

24Vdc
Power
Supply

Power (4000 only)

Signal (-)

Analog
Input
Device

Industrial

Mattapoisett, MA 02739
Signal (+)

White(Clear)
Red

Shield Ground

Shield
Black

4-20mA Loop(-)

4-20mA Loop(+)

6HQVRU,QSXWV

61

0RGHO
3URJUDPPDEOH
$QDORJ
7UDQVPLWWHU

',&
&RPP
3RUW

D ata
I n d u s tr i a l

4 0 0 0 S e r ie s
FLOW

Series 4000
Sensor

Data Industrial Model 310 Installation Guide

Communications cable wiring

Power

Shiel

Field calibration requires a Data Industrial A310 Programming kit


(consisting of a custom cable and software) and a PC running
Windows 9x, ME, NT, 2000 or XP. In order to program the Model 310
it must be connected to Loop-Power and the A301 cable must be
connected between the Model 310 Comm port connector and an
available DB9 COM port on a computer.

Location of the
DIC Communication Port
6HQVRU,QSXWV



7UDQVPLWWHU

',&
&RPP
3RUW
DIC

Communications Port
Note:
The Data Industrial A301 Cable will work with all 300 Series
products. However the older version of the cable (A300) does not have sufficient bandwidth to
work with the newer 340 Series Transmitters or SDI Flow Sensors.

Data Industrial provides free programming software updates via the Internet for all of 300 Series
devices. Go to www.dataindustrial.com for these updates.

Programming Software Installation


Floppy Installation
Place the software installation Disk 1 into the floppy drive and run the setup.exe program to install.
CDROM Installation
Place the software CD into the CDROM drive and it should autostart. Click programming software, then
click the Model 310 and the software installation will begin.
Web Installation
The Installation software can be found at the Data Industrial web site (www.dataindustrial.com) in the
support section.

Model 310 Programming


Programming the Model 310 is accomplished by installing the Data Industrial programming software on
a computer and entering data on templates of the Windows based program.
1. Install the 310 PC Interface Software into the computer.
2. Connect the computer to the Model 310 transmitter using the Data Industrial A301 communications
cable. Plug A301 cable to the socket labeled D.I.C Comm Port taking care to properly align the tab
on the plug and socket to maintain polarity then plug the DB9 connector of the Data Industrial A301
communications cable to an avaliable PC com port that has the Model 310 software installed.
3. Connect the Model 310 transmitter to a powered 4-20mA loop. (if setting up in the office a 9-24VDC
power source can be used to simulate the loop).
4. Open the interface software and select the appropriate COM PORT as shown in the dialog box
below.

Data Industrial Model 310 Installation Guide

5. Open the Parameters Screen as shown below.

To go to calibration settings
screen select "Parameters"
from either place shown

6. Program using diagram below as a reference.


Step #1
Select Flow Rate Units.
Step #2
Select Sensor Type and
Enter K and offset numbers.
See Note #1
Step #3
Enter 4mA Rate and
20mA Rate.
Step #4
Press Send to transmit
calibration data to the 310.
Step #5
Press to exit Parameters screen and
go back to the main screen.
Press to refresh the parameters
screen with the current 310 settings.

Press to restore the factory defaults


To save the factory defaults Send
must be pressed before values take effect.

Note #1
Sdi - If the SDI sensor type is selected the required K and offset values can be found the the SDI
owners manual.
4000 - If the 4000 sensor type is selected, click the choose button and select the sensor from the pull
down box that appears.
Sine - Provided for connection to sensors which have a sine wave output. Please consult sensor
manufacturer for the calibration settings.
200 Insert Type - If the 200 Insert Sensor type is selected the required K and offset can be found the
the 200 owners manual or if the manual is not handy the calculate button can be pushed and an inside
pipe diameter can be entered and once calculate is pressed a K and offset will automatically be entered
in.
200 Tee Type - If the 200 tee type is selected, click the choose button and select the sensor from the
pull down box that appears.
4

Data Industrial Model 310 Installation Guide

Model 310 Specifications


Power Requirements:
Loop Input Voltage 9-35VDC
Input Frequency:
0.4 to 10 KHz
Load Resistance
Max 750@24VDC
Output Response Time
Varies with filter

Temperature (operating):
-29C to 70C
-20F to 158F
Temperature (storage):
-40C to 85C
-40F to 185F
Accuracy
0.04% of reading over entire span
Linearity
0.1% of full scale

Wa r r a n t y
Data Industrial Corporation (Seller) of 11 Industrial Drive, Mattapoisett, Massachusetts 02739-0740, U.S.A., warrants to the original purchaser of its product that such product manufactured by Data Industrial Corporation shall be
free from defects in materials or workmanship when installed, serviced and operated according to Data Industrial
Corporation instructions or in other such normal use. This warranty is effective for a period of 12 months from the date
of installation by the Purchaser or 18 months from the date of shipment by the Seller whichever occurs or terminates
first. This limited warranty does not cover damage or loss resulting from corrosion or erosion caused by acids or other
chemicals or by severe environmental conditions or negligent or improper installation or improper operation, misuse,
accident, unauthorized repair or substitution of components other than those provided by the Seller, and does not
cover limited life components such as bearings, shafts, impellers where wear rate is a function of application and
environment. Any component not manufactured by the Seller but included in its products shall not be covered by
this warranty and is sold only under such warranty as the manufacturer may provide.
If Buyer or Purchaser wishes to make a claim hereunder, he shall send written notice of any defect within the warranty
period, to Seller at the above address. Seller may at its sole option instruct Buyer to ship subject part, postage
prepaid, to the Seller at above address or authorize a representative to inspect the part on site. Seller will at its
sole option repair or replace any defective product covered by this warranty. If Buyer makes repairs or alterations to
any product or part covered by this warranty without Sellers prior written approval, this warranty shall be null and
void.
The foregoing shall constitute Buyers or Purchasers sole and exclusive remedy against Seller, and no other remedy, including but not limited to, incidental or consequential damages for personal injury, loss of fluids, gases or other
substances or for loss of profits or injury to property or person shall be available to the Buyer or Purchaser. The
warranty extended herein shall be in lieu of any other implied warranty of merchantability or fitness for a particular
purpose, and seller shall bear no liability for representatives or retail sellers. In no event shall Data Industrial Corporation be liable for any contingent, incidental, or consequential damage or expenses due to partial or complete
inoperability of its product.
All rights reserved. No part of this work covered by the copyrights hereon may be reproduced or copied in any
form or by any means - graphic, electronic, or mechanical, including photocopying, recording, taping, or information and retrieval systems -- without written permission of Data Industrial.
Copyright 2003
Data Industrial Corporation
11 Industrial Drive
Mattapoisett, MA 02739
TEL: 508-758-6390
FAX: 508-758-4057
email: [email protected]
[email protected]
web site: www.dataindustrial.com

You might also like