Zero Sequence Filtering PDF
Zero Sequence Filtering PDF
P64x/EN AP/C63
(AP) 6-21
To ensure stability of the protection, the LV zero sequence current must be eliminated from
the differential current. Traditionally this has been achieved by either delta connected line
CTs or by the inclusion of a delta winding in the connection of an interposing current
transformer.
In accordance with its definition, the zero-sequence current is determined as follows from
vector and amplitude matched phase currents:
&
1 &
,
3
&
&
The current that is used in the differential equation is the filtered current per phase:
&
&
&
&
,
,
&
&
_
_
,
&
0
&
&
Setting the zero-sequence current filtering function is very simple and does not require any
calculations. Zero-sequence current filtering should only be activated for those ends where
there is operational earthing (grounding) of a neutral point:
AP
Figure 12 shows the current distribution for an AN fault on the delta side of a Yd1
transformer with a grounding transformer inside the protected zone.