Sales Number: IA811E: This Electronic Edition Is Licensed To Master Marine For 1
Sales Number: IA811E: This Electronic Edition Is Licensed To Master Marine For 1
ia811e_cover_A5.indd 1
INTERNATIONAL
MARITIME
ORGANIZATION
18/11/2008 10:01:48
Print edition
First
(ISBN
published
978-92-801-5109-1)
in 1980
by the INTERNATIONAL
Published
MARITIME
in 2001 ORGANIZATION
by the INTERNATIONAL
4 Albert Embankment,
MARITIME
London ORGANIZATION
SE1 7SR
4 Albert Embankment, London SE1 7SR
Second edition 2001
Electronic edition, 2007
Printed by the International Maritime Organization, London
2
10
ISBN 978-92-801-5109-1
IMO PUBLICATION
Sales number: EA811E
IMO PUBLICATION
Sales number: IA811E
Foreword
The Code for the Construction and Equipment of Mobile Offshore
Drilling Units, 1989 (1989 MODU Code) was adopted by Assembly
resolution A.649(16) for mobile offshore drilling units, the keels of which
are laid or are at a similar stage of construction on or after 1 May 1991. The
1989 MODU Code supersedes the 1979 MODU Code adopted by
Assembly resolution A.414(XI).
The Maritime Safety Committee, at its fifty-ninth session (13 to 24 May
1991), adopted amendments to the 1989 MODU Code (originally
circulated in MSC/Circ.561) and decided that, to maintain compatibility
with SOLAS, the amendments should become effective on 1 February
1992. New section 10.13, Radio life-saving appliances, and new chapter 11,
Radiocommunication installations, introduced by the amendments apply to
all MODUs the keels of which are laid or are at a similar stage of
construction on or after 1 May 1991, in the same way as the 1988
(GMDSS) amendments to SOLAS apply to ships. The Committee also
recommended that Member Governments encourage the fitting of all
MODUs with the GMDSS equipment specified in the amendments to the
1989 Code, and ensure that all MODUs comply with section 10.13 of the
amendments to the 1989 Code not later than 1 February 1995, and with
chapter 11 of the amendments not later than 1 February 1999.
The Maritime Safety Committee, at its sixty-third session (16 to 25 May
1994), adopted further amendments to the 1989 MODU Code (resolution
MSC.38(63)) to introduce the harmonized system of survey and certification (HSSC) into the Code (amendments to chapter 1 and the appendix);
provide guidelines for vessels with dynamic positioning systems (amendments to chapters 4 and 5); and provisions for helicopter facilities (new
chapter 13). The Committee decided that the amendments introducing the
HSSC system should become effective on the same date as the 1988 SOLAS
and Load Line Protocols relating to the HSSC (i.e. 3 February 2000), and
that those providing guidelines for vessels with dynamic positioning systems
and provisions for helicopter facilities should become effective on 1 July
1994.
In 1995, the Assembly adopted the Code on Alarms and Indicators, 1995
(resolution A.830(19)), which is intended to provide general design
guidance and to promote uniformity of type, location and priority for
those alarms and indicators which are required by the 1974 SOLAS
Convention, MARPOL 73/78 and other IMO instruments, including the
1989 MODU Code. The Assembly recommended Governments, inter alia,
to take appropriate steps to apply the Code and to use it as an international
safety standard for designing alarms and indicators for ships (and MODUs)
and their equipment and machinery.
This publication contains the consolidated text of the 1989 MODU Code
and the 1991 and 1994 amendments, but does not include the relevant
iii
Licensed to Master Marine for 1 copy. IMO
Foreword
provisions of the Code on Alarms and Indicators, 1995. The intention of
this publication is to provide an easy reference to up-to-date requirements
of the 1989 MODU Code.
iv
Licensed to Master Marine for 1 copy. IMO
Contents
Page
Preamble . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 1 General
1.1
Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2
Application. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3
Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4
Exemptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.5
Equivalents. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.6
1.7
Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
14
1.8
Casualties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
15
1.9
15
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
17
2.2
Design loads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
17
2.3
Structural analysis . . . . . . . . . . . . . . . . . . . . . . . . . .
18
2.4
19
2.5
19
2.6
20
2.7
Fatigue analysis . . . . . . . . . . . . . . . . . . . . . . . . . . . .
22
2.8
Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
22
2.9
Construction portfolio . . . . . . . . . . . . . . . . . . . . . . .
22
2.10
Welding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
22
2.11
Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
22
Inclining test . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
23
3.2
23
3.3
26
v
Licensed to Master Marine for 1 copy. IMO
Contents
Page
3.4
27
3.5
Extent of damage . . . . . . . . . . . . . . . . . . . . . . . . . .
29
3.6
Watertight integrity . . . . . . . . . . . . . . . . . . . . . . . . .
31
3.7
Freeboard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
32
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
37
4.2
Machinery requirements. . . . . . . . . . . . . . . . . . . . . .
38
4.3
38
4.4
39
4.5
Machinery controls . . . . . . . . . . . . . . . . . . . . . . . . .
39
4.6
40
4.7
40
4.8
40
4.9
42
4.10
44
4.11
44
46
4.12
47
5.2
47
5.3
48
5.4
52
5.5
53
Internal communication . . . . . . . . . . . . . . . . . . . . . .
56
5.6
vi
Licensed to Master Marine for 1 copy. IMO
Contents
Page
Chapter 6 Machinery and electrical installations
in hazardous areas for all types of units
6.1
Zones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
57
6.2
57
6.3
58
6.4
Ventilation of spaces . . . . . . . . . . . . . . . . . . . . . . . .
59
6.5
59
6.6
60
6.7
61
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
63
7.2
64
7.3
64
7.4
Machinery controls . . . . . . . . . . . . . . . . . . . . . . . . .
64
7.5
Steering gear. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
66
7.6
68
7.7
68
7.8
Engineers alarm . . . . . . . . . . . . . . . . . . . . . . . . . . .
68
7.9
68
7.10
69
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
71
8.2
Application. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
71
8.3
Fire safety. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
71
8.4
73
8.5
74
vii
Licensed to Master Marine for 1 copy. IMO
Contents
Page
8.6
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . .
75
8.7
Alarm system . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
75
8.8
75
Safety systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
76
8.9
79
9.2
82
9.3
Means of escape . . . . . . . . . . . . . . . . . . . . . . . . . . .
86
9.4
88
9.5
90
91
9.7
91
9.8
91
9.9
Firemens outfits . . . . . . . . . . . . . . . . . . . . . . . . . . .
92
9.10
92
9.11
92
9.12
94
9.13
Miscellaneous items. . . . . . . . . . . . . . . . . . . . . . . . .
95
9.6
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
97
10.2
Survival craft . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
97
10.3
98
10.4
99
10.5
99
10.6
100
viii
Licensed to Master Marine for 1 copy. IMO
Contents
Page
10.7
Rescue boats . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
101
10.8
101
10.9
101
10.10 Lifejackets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
102
102
10.12 Lifebuoys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
102
103
103
103
104
104
104
Application. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
107
11.2
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
107
11.3
107
11.4
107
108
11.6
Helicopter communications . . . . . . . . . . . . . . . . . . .
109
11.7
Internal communications . . . . . . . . . . . . . . . . . . . . .
109
11.8
Performance standards . . . . . . . . . . . . . . . . . . . . . . .
109
11.9
110
111
11.5
Cranes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
113
12.2
Personnel lifts . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
114
12.3
Drilling derricks . . . . . . . . . . . . . . . . . . . . . . . . . . .
114
ix
Licensed to Master Marine for 1 copy. IMO
Contents
Page
Chapter 13 Helicopter facilities
13.1
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
115
13.2
Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
115
13.3
Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
115
13.4
Arrangements . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
117
13.5
Visual aids . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
117
Operating manuals . . . . . . . . . . . . . . . . . . . . . . . . .
125
14.2
Dangerous goods. . . . . . . . . . . . . . . . . . . . . . . . . . .
128
14.3
Pollution prevention . . . . . . . . . . . . . . . . . . . . . . . .
128
14.4
Towing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
128
14.5
129
14.6
Diving systems . . . . . . . . . . . . . . . . . . . . . . . . . . . .
129
14.7
Safety of navigation . . . . . . . . . . . . . . . . . . . . . . . . .
129
14.8
Emergency procedures . . . . . . . . . . . . . . . . . . . . . . .
130
14.9
Emergency instructions . . . . . . . . . . . . . . . . . . . . . .
131
132
132
133
14.13 Records . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
134
Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
x.
Licensed to Master Marine for 1 copy. IMO
Preamble
1
This Code has been developed to provide an international standard for
mobile offshore drilling units of new construction which will facilitate the
international movement and operation of these units and ensure a level of
safety for such units, and for personnel on board, equivalent to that required
by the International Convention for the Safety of Life at Sea, 1974, as
amended, and the International Convention on Load Lines, 1966, as
amended, for conventional ships engaged on international voyages.
2
Throughout the development of the Code, it was recognized that it
must be based upon sound design and engineering principles and experience
gained from operating such units; it was further recognized that design
technology of mobile offshore drilling units is not only a complex
technology but is rapidly evolving and that the Code should not remain
static but be re-evaluated and revised as necessary. To this end the
Organization will periodically review the Code, taking into account both
experience and future development.
3
Any existing unit which complies with the provisions of this Code
should be considered eligible for issuance of a certificate in accordance with
this Code.
4
The Code is not intended to prohibit the use of an existing unit
simply because its design, construction and equipment do not conform to
the requirements of this Code. Many existing mobile offshore drilling units
have operated successfully and safely for extended periods of time and their
operating history should be considered in evaluating their suitability to
conduct international operations.
5
The coastal State may permit any unit designed to a lower standard
than that of the Code to engage in operations having taken account of the
local environmental conditions. Any such unit should, however, comply
with safety requirements which in the opinion of the coastal State are
adequate for the intended operation and ensure the overall safety of the unit
and the personnel on board.
6
The Code does not include requirements for the drilling of subsea
wells or the procedures for their control. Such drilling operations are subject
to control by the coastal State.
1
Licensed to Master Marine for 1 copy. IMO
Chapter 1
General
1.1
Purpose
The purpose of the Code for the Construction and Equipment of Mobile
Offshore Drilling Units, 1989, as amended, hereinafter referred to as the
Code, is to recommend design criteria, construction standards and other
safety measures for mobile offshore drilling units so as to minimize the risk
to such units, to the personnel on board and to the environment.
1.2
Application
1.2.1 The Code applies to mobile offshore drilling units as defined in 1.3.1
to 1.3.4, the keels of which are laid or which are at a similar stage of
construction on or after 1 May 1991.
1.2.2 The coastal State may impose additional requirements regarding the
operation of industrial systems not dealt with by the Code.
1.3
Definitions
For the purpose of this Code, unless expressly provided otherwise, the
terms used therein have the meanings defined in the following paragraphs.
1.3.1 Mobile offshore drilling unit or unit is a vessel capable of engaging in
drilling operations for the exploration for or exploitation of resources
beneath the sea-bed such as liquid or gaseous hydrocarbons, sulphur or salt.
1.3.2 Surface unit is a unit with a ship- or barge-type displacement hull of
single or multiple hull construction intended for operation in the floating
condition.
1.3.3 Self-elevating unit is a unit with movable legs capable of raising its hull
above the surface of the sea.
1.3.4 Column-stabilized unit is a unit with the main deck connected to the
underwater hull or footings by columns or caissons.
1.3.5 Administration means the Government of the State whose flag the unit
is entitled to fly.
1.3.6 Coastal State means the Government of the State exercising
administrative control over the drilling operations of the unit.
1.3.7 Organization means the International Maritime Organization (IMO).
1.3.8 Certificate means Mobile Offshore Drilling Unit Safety Certificate.
1.3.9 1974 SOLAS Convention means the International Convention for the
Safety of Life at Sea, 1974, as amended.
3
Licensed to Master Marine for 1 copy. IMO
Chapter 1
1.3.10 1966 Load Line Convention means the International Convention on
Load Lines, 1966.
1.3.11 Mode of operation means a condition or manner in which a unit may
operate or function while on location or in transit. The modes of operation
of a unit include the following:
.1
.2
.3
1.3.17
.1
4
Licensed to Master Marine for 1 copy. IMO
General
escape and winches for rescue boats, as well as the means of
ensuring the minimum comfortable conditions of habitability,
are in working order and functioning normally; and
.2
drilling operations.
1.3.26
.1
.2
.3
1.3.27 Maximum ahead service speed is the greatest speed which the unit is
designed to maintain in service at sea at its deepest seagoing draught.
5
Licensed to Master Marine for 1 copy. IMO
Chapter 1
1.3.28 Maximum astern speed is the speed which it is estimated the unit can
attain at the designed maximum astern power at its deepest seagoing
draught.
1.3.29 Machinery spaces of category A are all spaces which contain internal
combustion-type machinery used either:
.1
.2
or which contain any oil-fired boiler or oil fuel unit; and trunks to such
spaces.
1.3.30 Machinery spaces are all machinery spaces of category A and all other
spaces containing propelling machinery, boilers and other fired processes,
oil fuel units, steam and internal combustion engines, generators and major
electrical machinery, oil filling stations, refrigerating, stabilizing, ventilation
and air-conditioning machinery and similar spaces; and trunks to such
spaces.
1.3.31 Control stations are those spaces in which the units radio or main
navigating equipment or the emergency source of power is located or where
the fire recording or fire control equipment or the dynamical positioning
control system is centralized or where a fire-extinguishing system serving
various locations is situated. In the case of column-stabilized units a
centralized ballast control station is a control station. However, for
purposes of the application of chapter 9, the space where the emergency
source of power is located is not considered as being a control station.
1.3.32 Hazardous areas are all those areas where, due to the possible
presence of a flammable atmosphere arising from the drilling operations, the
use without proper consideration of machinery or electrical equipment may
lead to fire hazard or explosion.
1.3.33 Enclosed spaces are spaces delineated by floors, bulkheads and/or
decks which may have doors or windows.
1.3.34 Semi-enclosed locations are locations where natural conditions of
ventilation are notably different from those on open decks due to the
presence of structures such as roofs, windbreaks and bulkheads and which
are so arranged that dispersion of gas may not occur.
1.3.35 Industrial machinery and components are the machinery and
components which are used in connection with the drilling operation.
1.3.36 Non-combustible material* means a material which neither burns nor
gives off flammable vapours in sufficient quantity for self-ignition when
*
If a material passes the test as specified in annex 1, part I of the International Code for
Application of Fire Test Procedures (FTP Code) it should be considered as non-combustible
even if it consists of a mixture of inorganic and organic substances.
6
Licensed to Master Marine for 1 copy. IMO
General
heated to approximately 7508C, this being determined to the satisfaction of
the Administration by an established test procedure. Any other material is a
combustible material.
1.3.37 A standard fire test is a test as defined in regulation II-2/3.2 of the
1974 SOLAS Convention.
1.3.38 A class divisions are those divisions as defined in regulation II-2/
3.3 of the 1974 SOLAS Convention.
1.3.39 B class divisions are those divisions as defined in regulation II-2/
3.4 of the 1974 SOLAS Convention.
1.3.40 C class divisions are divisions constructed of approved noncombustible materials. They need meet neither requirements relative to the
passage of smoke and flame nor limitations relative to the temperature rise.
1.3.41 Steel or equivalent material. Where the words steel or equivalent
material occur, equivalent material means any non-combustible material
which, by itself or due to insulation provided, has structural and integrity
properties equivalent to steel at the end of the applicable standard fire test
(e.g. aluminium alloy with appropriate insulation).
1.3.42 Low flame spread means that the surface thus described will
adequately restrict the spread of flame, this being determined to the
satisfaction of the Administration by an established test procedure.
1.3.43 Continuous B class ceilings or linings are those B class ceilings or
linings which terminate only at an A or B class division.
1.3.44 Working spaces are those open or enclosed spaces containing
equipment and processes, associated with drilling operations, which are not
included in 1.3.30 or 1.3.32.
1.3.45 Accommodation spaces are those used for public spaces, corridors,
lavatories, cabins, offices, hospitals, cinemas, games and hobbies rooms,
pantries containing no cooking appliances and similar spaces. Public spaces
are those portions of the accommodation which are used for halls, dining
rooms, lounges and similar permanently enclosed spaces.
1.3.46 Service spaces are those used for galleys, pantries containing cooking
appliances, lockers and store-rooms, workshops other than those forming
part of the machinery spaces, and similar spaces and trunks to such spaces.
1.3.47 Fuel oil unit is the equipment used for the preparation of oil fuel for
delivery to an oil-fired boiler, or equipment used for the preparation for
delivery of heated oil to an internal combustion engine, and includes any oil
pressure pumps, filters and heaters dealing with oil at a pressure more than
0.18 N/mm2
1.3.48 Survival craft are craft capable of removing persons from a unit to be
abandoned and capable of sustaining persons until retrieval is completed.
7
Licensed to Master Marine for 1 copy. IMO
Chapter 1
1.3.49 Rescue boat is an easily manoeuvred power boat capable of rapid
launching and adequate for quick recovery of a man overboard and towing a
liferaft away from immediate danger.
1.3.50 Diving system is the plant and equipment necessary for the safe
conduct of diving operations from a mobile offshore drilling unit.
1.3.51 Anniversary date means the day and month of each year which will
correspond to the date of expiry of the certificate.
1.4
Exemptions
Equivalents
1.5.1 Where the Code requires that a particular fitting, material, appliance,
apparatus, item of equipment or type thereof should be fitted or carried in a
unit, or that any particular provision should be made, or any procedure or
arrangement should be complied with, the Administration may allow any
other fitting, material, appliance, apparatus, item of equipment or type
thereof to be fitted or carried, or any other provision, procedure or
arrangement to be made in that unit, if it is satisfied by trial thereof or
otherwise that such fitting, material, appliance, apparatus, item of
equipment or type thereof or that any particular provision, procedure or
arrangement is at least as effective as that required by the Code.
1.5.2 When an Administration so allows any fitting, material, appliance,
apparatus, item of equipment or type thereof, or provision, procedure,
arrangement, novel design or application to be substituted, it should
communicate to the Organization the particulars thereof, together with a
report on the evidence submitted, so that the Organization may circulate
the same to other Governments for the information of their officers.
1.6
8
Licensed to Master Marine for 1 copy. IMO
General
.2
.3
.4
.5
.6
.7
.2
.3
.4
.5
9
Licensed to Master Marine for 1 copy. IMO
Chapter 1
.6
.7
10
Licensed to Master Marine for 1 copy. IMO
General
Administration. If such corrective action is not taken the certificate
should be withdrawn and the Administration should be notified
immediately; and, if the unit is in an area under the jurisdiction of
another Government, the appropriate authorities of the port State
should be notified immediately. When an officer of the Administration, a nominated surveyor or recognized organization has
notified the appropriate authorities of the port State, the Government of the port State concerned should give such officer, surveyor
or organization any necessary assistance to carry out their obligations
under this regulation. When applicable, the Government of the port
State concerned should ensure that the unit should not continue to
operate until it can do so without danger to the unit or the persons
on board.
.4 In every case, the Administration shall fully guarantee the
completeness and efficiency of the inspection and survey, and
should undertake to ensure the necessary arrangements to satisfy this
obligation.
1.6.6.1 The condition of the unit and its equipment should be maintained
to conform with the provisions of this Code to ensure that the unit
in all respects will remain fit to operate without danger to the unit or
the persons on board.
.2 After any survey of the unit under this regulation has been
completed, no change should be made to structure, equipment,
fittings, arrangements and materials covered by the survey, without
the sanction of the Administration.
.3 Whenever an accident occurs to a unit or a defect is discovered,
either of which affects the safety of the unit or the efficiency or
completeness of structure, equipment, fittings, arrangements and
materials, the person in charge or owner of the unit should report at
the earliest opportunity to the Administration, the nominated
surveyor or recognized organization responsible, who should cause
investigations to be initiated to determine whether a survey, as
required by this regulation, is necessary. If the unit is in an area
under the jurisdiction of another Government, the person in charge
or the owner should also report immediately to the appropriate
authorities of the port State and the nominated surveyor or
recognized organization should ascertain that such a report has
been made.
1.6.7 A certificate called a Mobile Offshore Drilling Unit Safety Certificate
(1989) may be issued after an initial or renewal survey to a unit which
complies with the requirements of the Code. The Certificate should be
issued or endorsed either by the Administration or by any person or
organization recognized by it. In every case, that Administration assumes
full responsibility for the certificate.
11
Licensed to Master Marine for 1 copy. IMO
Chapter 1
1.6.8 Any exemptions granted under 1.4 should be clearly noted on the
certificate.
1.6.9 A Contracting Government to both the 1974 SOLAS Convention
and the 1966 Load Line Convention may, at the request of the
Administration, cause a unit to be surveyed and, if satisfied that the
requirements of the Code are complied with, should issue or authorize the
issue of a certificate to the unit and, where appropriate, endorse or authorize
the endorsement of a certificate on the unit in accordance with the Code.
Any certificate so issued should contain a statement to the effect that it has
been issued at the request of the Government of the State the flag of which
the unit is entitled to fly, and it should have the same force and receive the
same recognition as a certificate issued under 1.6.7.
1.6.10 The certificate should be drawn up in the form corresponding to the
model given in the appendix to the Code. If the language used is neither
English nor French, the text should include a translation into one of these
languages.
1.6.11.1
.2.1
.2.2
.2.3
.3
.4
12
Licensed to Master Marine for 1 copy. IMO
General
certificate and such a certificate should be accepted as valid for a
further period which should not exceed 5 months from the
expiry date.
.5
.6
.7
.7.1
.7.2
.7.3
.8
.8.1
.8.2
13
Licensed to Master Marine for 1 copy. IMO
Chapter 1
.8.3
1.6.12 The privileges of the Code may not be claimed in favour of any unit
unless it holds a valid certificate.
1.7
Control
14
Licensed to Master Marine for 1 copy. IMO
General
1.7.6 Notwithstanding the provisions of 1.7.1 and 1.7.2, the requirements
of 1.6 are without prejudice to any rights of the coastal State under
international law to impose its own requirements relating to the regulation,
surveying and inspection of units engaged, or intending to engage, in the
exploration or exploitation of the natural resources of those parts of the seabed and subsoil over which that State is entitled to exercise sovereign rights.
1.8
Casualties
15
Licensed to Master Marine for 1 copy. IMO
Chapter 2
Construction, strength and materials
2.1
General
Design loads
2.2.1 The modes of operation for each unit are to be investigated using
realistic loading conditions including gravity loading with relevant
environmental loading. The following environmental considerations should
be included where applicable: wind, wave, current, ice, sea-bed conditions,
temperature, fouling, and earthquake.
2.2.2 Where possible, the above design environmental conditions should be
based upon significant data with a period of recurrence of at least 50 years
for the most severe anticipated environment.
2.2.3 Results from relevant model tests may be used to substantiate or
amplify calculations.
2.2.4 Limiting design data for each mode of operation should be stated in
the operating manual.
Wind loading
2.2.5 Sustained and gust wind velocities, as relevant, should be considered
when determining wind loading. Pressures and resultant forces should be
calculated by the method referred to in 3.2 or by some other method to the
satisfaction of the Administration.
Wave loading
2.2.6 Design wave criteria should be described by design wave energy
spectra or deterministic design waves having appropriate shape and size.
Consideration should be given to waves of lesser height, where, due to their
period, the effects on structural elements may be greater.
2.2.7 The wave forces utilized in the design analysis should include the
effects of immersion, heeling and accelerations due to motion. Theories
17
Licensed to Master Marine for 1 copy. IMO
Chapter 2
used for the calculation of wave forces and the selection of coefficients
should be to the satisfaction of the Administration.
Current loading
2.2.8 Consideration should be given to the interaction of current and
waves. Where necessary, the two should be superimposed by adding the
current velocity vectorially to the wave particle velocity. The resultant
velocity should be used in calculating the structural loading due to current
and waves.
Loading due to vortex shedding
2.2.9 Consideration should be given to loading induced in structural
members due to vortex shedding.
Deck loading
2.2.10 A loading plan should be prepared to the satisfaction of the
Administration showing the maximum design uniform and concentrated
deck loading for each area for each mode of operation.
Other loadings
2.2.11 Other relevant loadings should be determined in a manner to the
satisfaction of the Administration.
2.3
Structural analysis
18
Licensed to Master Marine for 1 copy. IMO
2.4.1 The required strength of the unit should be maintained in way of the
drilling well, and particular attention should be given to the transition
between fore-and-aft members. The plating of the well should also be
suitably stiffened to prevent damage when the unit is in transit.
2.4.2 Consideration should be given to the scantlings necessary to maintain
strength in way of large hatches.
2.4.3 The structure in way of components of the position mooring system
such as fairleads and winches should be designed to withstand the stresses
imposed when a mooring line is loaded to its breaking strength.
2.5
2.5.1 The hull strength should be evaluated in the elevated position for the
specified environmental conditions with maximum gravity loads aboard and
with the unit supported by all legs. The distribution of these loads in the
hull structure should be determined by a method of rational analysis.
Scantlings should be calculated on the basis of this analysis, but should not
be less than those required for other modes of operation.
2.5.2 The unit should be so designed as to enable the hull to clear the
highest design wave including the combined effects of astronomical and
storm tides. The minimum clearance may be the lesser of either 1.2 m or
10% of the combined storm tide, astronomical tide and height of the design
wave above the mean low water level.
2.5.3 Legs should be designed to withstand the dynamic loads which may
be encountered by their unsupported length while being lowered to the
bottom, and also to withstand the shock of bottom contact due to wave
action on the hull. The maximum design motions, sea state and bottom
conditions for operations to raise or lower the hull should be clearly stated
in the operating manual.
2.5.4 When evaluating leg stresses with the unit in the elevated position, the
maximum overturning moment on the unit due to the most adverse
combination of applicable environmental and gravity loadings should be
considered.
2.5.5 Legs should be designed for the most severe environmental transit
conditions anticipated including wind moments, gravity moments and
accelerations resulting from unit motions. The Administration should be
19
Licensed to Master Marine for 1 copy. IMO
Chapter 2
provided with calculations, an analysis based on model tests, or a
combination of both. Acceptable transit conditions should be included in
the operating manual. For some transit conditions, it may be necessary to
reinforce or support the legs, or to remove sections to ensure their structural
integrity.
2.5.6 Structural members which transmit loads between the legs and the
hull should be designed for the maximum loads transmitted and so arranged
as to diffuse the loads into the hull structure.
2.5.7 When a mat is utilized to transmit the bottom bearing loads, attention
should be given to the attachment of the legs so that the loads are diffused
into the mat.
2.5.8 Where tanks in the mat are not open to the sea, the scantlings should
be based on a design head using the maximum water depth and tidal effects.
2.5.9 Mats should be designed to withstand the loads encountered during
lowering including the shock of bottom contact due to wave action on the
hull.
2.5.10 The effect of possible scouring action (loss of bottom support)
should be considered. The effect of skirt plates, where provided, should be
given special consideration.
2.5.11 Except for those units utilizing a bottom mat, the capability should
be provided to pre-load each leg to the maximum applicable combined load
after initial positioning at a site. The pre-loading procedures should be
included in the operating manual.
2.5.12 Deckhouses located near the side shell of a unit may be required to
have scantlings similar to those of an unprotected house front. Other
deckhouses should have scantlings suitable for their size, function and
location.
2.6
2.6.1 Unless deck structures are designed for wave impact, a clearance
acceptable to the Administration should be maintained between passing
wave crests and the deck structure. The Administration should be provided
with model test data, reports on past operating experience with similar
configurations or calculations showing that adequate provision is made to
maintain this clearance.
2.6.2 For units operating while supported by the sea-bed the clearance
required in 2.5.2 should be maintained.
2.6.3 The structural arrangement of the upper hull is to be considered with
regard to the structural integrity of the unit after the assumed failure of any
primary girder. The Administration may require a structural analysis
showing satisfactory protection against overall collapse of the unit after such
20
Licensed to Master Marine for 1 copy. IMO
21
Licensed to Master Marine for 1 copy. IMO
Chapter 2
2.6.14 Where bracings are watertight they should be designed to prevent
collapse from hydrostatic pressure. Underwater bracing should normally be
made watertight and have a leak detection system to make it possible to
detect fatigue cracks at an early stage.
2.6.15 Consideration should be given to the need for ring frames to
maintain stiffness and shape in tubular bracing members.
2.7
Fatigue analysis
Materials
Construction portfolio
22
Licensed to Master Marine for 1 copy. IMO
Chapter 3
Subdivision, stability and freeboard
3.1
Inclining test
3.1.1 An inclining test should be required for the first unit of a design, when
the unit is as near to completion as possible, to determine accurately the
light ship data (weight and position of centre of gravity).
3.1.2 For successive units which are identical by design, the light ship data
of the first unit of the series may be accepted by the Administration in lieu
of an inclining test, provided the difference in light ship displacement or
position of centre of gravity due to weight changes for minor differences in
machinery, outfitting or equipment, confirmed by the results of a
deadweight survey, are less than 1% of the values of the light ship
displacement and principal horizontal dimensions as determined for the first
of the series. Extra care should be given to the detailed weight calculation
and comparison with the original unit of a series of column-stabilized,
semisubmersible types as these, even though identical by design, are
recognized as being unlikely to attain an acceptable similarity of weight or
centre of gravity to warrant a waiver of the inclining test.
3.1.3 The results of the inclining test, or deadweight survey and inclining
experiment adjusted for weight differences, should be indicated in the
operating manual.
3.1.4 A record of all changes to machinery, structure, outfitting and
equipment that affect the light ship data should be maintained in the
operating manual or in a light ship data alterations log and be taken into
account in daily operations.
3.1.5 For column-stabilized units, a deadweight survey should be
conducted at intervals not exceeding 5 years. Where the deadweight survey
indicates a change from the calculated light ship displacement in excess of
1% of the operating displacement, an inclining test should be conducted.
3.1.6 The inclining test or deadweight survey should be carried out in the
presence of an officer of the Administration, or a duly authorized person or
representative of an approved organization.
3.2
23
Licensed to Master Marine for 1 copy. IMO
Chapter 3
3.2.2 Where equipment is of such a nature that it can be lowered and
stowed, additional wind heeling moment curves may be required and such
data should clearly indicate the position of such equipment.
3.2.3 The curves of wind heeling moments should be drawn for wind forces
calculated by the following formula:
F
= 0.5CsCHrV2A
where:
F
3.2.4 Wind forces should be considered from any direction relative to the
unit and the value of the wind velocity should be as follows:
.1
.2
3.2.5 In calculating the projected areas to the vertical plane, the area of
surfaces exposed to wind due to heel or trim, such as under-deck surfaces,
etc., should be included using the appropriate shape factor. Open truss work
may be approximated by taking 30% of the projected block area of both the
front and back section, i.e. 60% of the projected area of one side.
3.2.6 In calculating the wind heeling moments, the lever of the wind
overturning force should be taken vertically from the centre of pressure of
all surfaces exposed to the wind to the centre of lateral resistance of the
underwater body of the unit. The unit is to be assumed floating free of
mooring restraint.
3.2.7 The wind heeling moment curve should be calculated for a sufficient
number of heel angles to define the curve. For ship-shaped hulls the curve
may be assumed to vary as the cosine function of vessel heel.
24
Licensed to Master Marine for 1 copy. IMO
Cs
Spherical
Cylindrical
Large flat surface (hull, deckhouse, smooth under-deck
areas)
Drilling derrick
Wires
Exposed beams and girders under deck
Small parts
Isolated shapes (crane, beam, etc.)
Clustered deckhouses or similar structures
0.4
0.5
1.0
1.25
1.2
1.3
1.4
1.5
1.1
15.3
30.5
46.0
61.0
76.0
91.5
106.5
122.0
137.0
152.5
167.5
183.0
198.0
213.5
228.5
244.0
256.0
256
25
Licensed to Master Marine for 1 copy. IMO
CH
1.00
1.10
1.20
1.30
1.37
1.43
1.48
1.52
1.56
1.60
1.63
1.67
1.70
1.72
1.75
1.77
1.79
1.80
Chapter 3
Righting moment
Heeling
moment
94012
Moment
Downflooding
angle
Second
intercept
Angle of inclination
3.3
3.3.1 The stability of a unit in each mode of operation should meet the
following criteria (see also figure 3-1):
.1
For surface and self-elevating units the area under the righting
moment curve to the second intercept or downflooding angle,
whichever is less, should be not less than 40% in excess of the
area under the wind heeling moment curve to the same limiting
angle.
.2
.3
26
Licensed to Master Marine for 1 copy. IMO
.3
.4
.5
3.4
27
Licensed to Master Marine for 1 copy. IMO
Chapter 3
Column-stabilized units
3.4.3 The unit should have sufficient freeboard and be subdivided by means
of watertight decks and bulkheads to provide sufficient buoyancy and
stability to withstand a wind heeling moment induced by a wind velocity of
25.8 m/s (50 knots) superimposed from any direction in any operating or
transit condition, taking the following considerations into account:
the angle of inclination after the damage set out in 3.5.10.2
should not be greater than 178;
.2
any opening below the final waterline should be made watertight, and openings within 4 m above the final waterline should
be made weathertight;
.3
the righting moment curve, after the damage set out above,
should have, from the first intercept to the lesser of the extent of
weathertight integrity required by 3.4.3.2 and the second
intercept, a range of at least 78. Within this range, the righting
moment curve should reach a value of at least twice the wind
heeling moment curve, both being measured at the same angle.*
See figure 3-2 below.
Moment
.1
Extent of
weathertight
integrity
Righting moment
Wind heeling moment
**
*
Angle of
inclination
First intercept
Second intercept
2
00096
**/*
28
Licensed to Master Marine for 1 copy. IMO
.3
.2
on column-stabilized units, the flooding of any one compartment as set out in 3.4.4;
the provision of an adequate margin against capsizing.
.3
3.5
Extent of damage
Surface units
3.5.1 In assessing the damage stability of surface units, the following extent
of damage should be assumed to occur between effective watertight
bulkheads:
.1
.2
*
Refer to resolution A.651(16) An example of alternative stability criteria for a range of
positive stability after damage or flooding for column-stabilized semisubmersible units.
29
Licensed to Master Marine for 1 copy. IMO
Chapter 3
3.5.2 The distance between effective watertight bulkheads or their nearest
stepped portions which are positioned within the assumed extent of
horizontal penetration should be not less than 3.0 m; where there is a lesser
distance, one or more of the adjacent bulkheads should be disregarded.
3.5.3 Where damage of a lesser extent than in 3.5.1 results in a more severe
condition, such lesser extent should be assumed.
3.5.4 All piping, ventilation systems, trunks, etc., within the extent of
damage referred to in 3.5.1 should be assumed to be damaged. Positive
means of closure should be provided at watertight boundaries to preclude
the progressive flooding of other spaces which are intended to be intact.
Self-elevating units
3.5.5 In assessing the damage stability of self-elevating units, the following
extent of damage should be assumed to occur between effective watertight
bulkheads:
.1
.2
.2
30
Licensed to Master Marine for 1 copy. IMO
.4
.5
.6
3.6
Watertight integrity
31
Licensed to Master Marine for 1 copy. IMO
Chapter 3
.1
.2
Doors and hatch covers which are used during the operation of
the unit while afloat should be remotely controlled from the
central ballast control station and should also be operable locally
from each side. Open/shut indicators should be provided at the
control station.
Doors or hatch covers which are normally closed while the unit
is afloat should be provided with an alarm system (e.g. light
signals) showing personnel both locally and at the central ballast
control station whether the doors or hatch covers in question
are open or closed. A notice should be affixed to each such door
or hatch cover stating that it is not to be left open while the unit
is afloat.
.2
External openings
3.6.6 All downflooding openings the lower edge of which is submerged
when the unit is inclined to the first intercept between the righting moment
and wind heeling moment curves in any intact or damaged condition
should be fitted with a suitable watertight closing appliance, such as closely
spaced bolted covers.
3.6.7 Where flooding of chain lockers or other buoyant volumes may
occur, the openings to these spaces should be considered as downflooding
points.
3.7
Freeboard
General
3.7.1 The requirements of the 1966 Load Line Convention, including those
relating to certification, should apply to all units and certificates should be
issued as appropriate. The minimum freeboard of units which cannot be
computed by the normal methods laid down by that Convention should be
determined on the basis of meeting the applicable intact stability, damage
stability and structural requirements for transit conditions and drilling
operations while afloat. The freeboard should not be less than that
computed from the Convention where applicable.
32
Licensed to Master Marine for 1 copy. IMO
33
Licensed to Master Marine for 1 copy. IMO
Chapter 3
3.7.10 The procedure described in 3.7.9 should also apply in cases of small
notches or relatively narrow cut-outs at the stern of the unit.
3.7.11 Narrow wing extensions at the stern of the unit should be
considered as appendages and excluded for the determination of length (L)
and for the calculation of freeboards. The Administration should determine
the effect of such wing extensions with regard to the requirements for the
strength of unit based upon length (L).
Self-elevating units
3.7.12 Load lines should be assigned to self-elevating units as calculated
under the terms of the 1966 Load Line Convention. When floating or when
in transit from one operational area to another units should be subject to all
the conditions of assignment of that Convention unless specifically
excepted. However, these units should not be subject to the terms of that
Convention while they are supported by the sea-bed or are in the process of
lowering or raising their legs.
3.7.13 The minimum freeboard of units which due to their configuration
cannot be computed by the normal methods laid down by the 1966 Load
Line Convention should be determined on the basis of meeting applicable
intact stability, damage stability and structural requirements in the afloat
condition.
3.7.14 Where it is necessary to assign a greater than minimum freeboard to
meet intact or damage stability requirements or on account of any other
restriction imposed by the Administration, regulation 6(6) of the 1966 Load
Line Convention should apply. When such a freeboard is assigned, seasonal
marks above the centre of the ring should not be marked and any seasonal
marks below the centre of the ring should be marked. If a unit is assigned a
greater than minimum freeboard at the request of the owner, regulation 6(6)
need not apply.
3.7.15 Where moonpools are arranged within the hull in open communication with the sea, the volume of the moonpool should not be included
in the calculation of any hydrostatic properties. If the moonpool has a larger
cross-sectional area above the waterline at 0.85D than below, an addition
should be made to the geometric freeboard corresponding to the lost
buoyancy. This addition for the excess portion above the waterline at 0.85D
should be made as prescribed below for wells or recesses. If an enclosed
superstructure contains part of the moonpool, deduction should be made
for the effective length of the superstructure. Where open wells or recesses
are arranged in the freeboard deck, a correction equal to the volume of the
well or recess to the freeboard deck divided by the waterplane area at 0.85D
should be made to the freeboard obtained after all other corrections, except
bow height correction have been made. Free surface effects of the flooded
well or recess should be taken into account in stability calculations.
34
Licensed to Master Marine for 1 copy. IMO
35
Licensed to Master Marine for 1 copy. IMO
Chapter 4
Machinery installations for all types of units
4.1
General*
37
Licensed to Master Marine for 1 copy. IMO
Chapter 4
4.2
Machinery requirements
4.2.1 All boilers, all parts of machinery, all steam, hydraulic, pneumatic and
other systems and their associated fittings which are under internal pressure
should be subjected to appropriate tests including a pressure test before
being put into service for the first time.
4.2.2 Adequate provisions should be made to facilitate cleaning, inspection
and maintenance of machinery including boilers and pressure vessels.
4.2.3 Where risk from overspeeding of machinery exists, means should be
provided to ensure that the safe speed is not exceeded.
4.2.4 Where machinery including pressure vessels or any parts of such
machinery are subject to internal pressure and may be subject to dangerous
overpressure, means should, where applicable, be provided which will
protect against such excessive pressure.
4.2.5 All gearing and every shaft and coupling used for transmission of
power to machinery essential for the safety of the unit or persons on board
should be designed and constructed so that they will withstand the
maximum working stresses to which they may be subjected in all service
conditions, taking into account the type of engines by which they are driven
or of which they form part.
4.2.6 Internal combustion engines of a cylinder diameter of 200 mm or a
crankcase volume of 0.6 m3 and above should be provided with crankcase
explosion relief valves of an approved type with sufficient relief area. The
relief valves should be arranged or provided with means to ensure that
discharge from them is directed so as to minimize the possibility of injury to
personnel.
4.2.7 Machinery, where applicable, should be provided with automatic
shutoff arrangements or alarms in the case of failures, such as lubricating oil
supply failure, which could lead rapidly to complete breakdown, damage or
explosion. The Administration may permit provisions for overriding
automatic shutoff devices.
4.2.8 Means should be provided whereby normal operation of vital systems,
such as ballast systems in semisubmersible units, jacking systems in selfelevating units or control of blow-out preventers, can be sustained or
restored even though one of the essential auxiliaries becomes inoperable.
4.2.9 Means should be provided to ensure that machinery can be brought
into operation from the dead ship condition without external aid.
4.3
4.3.1 Every steam boiler and every unfired steam generator should be
provided with not less than two safety valves of adequate capacity. However,
the Administration may, having regard to the output or any other features of
any boiler or unfired steam generator, permit only one safety valve to be
38
Licensed to Master Marine for 1 copy. IMO
4.4.1 Every steam pipe and every fitting connected thereto through which
steam may pass should be so designed, constructed and installed as to
withstand the maximum working stresses to which it may be subjected.
4.4.2 Efficient means should be provided for draining every steam pipe
where dangerous water hammer action might otherwise occur.
4.4.3 If a steam pipe or fitting may receive steam from any source at a higher
pressure than that for which it is designed, a suitable reducing valve, relief
valve and pressure gauge should be fitted.
4.5
Machinery controls
4.5.1 Machinery essential for the safety of the unit should be provided with
effective means for its operation and control.
4.5.2 Automatic starting, operational and control systems for machinery
essential for the safety of the unit should, in general, include provisions for
manually overriding the automatic controls. Failure of any part of the
automatic and remote control system should not prevent the use of the
manual override. Visual indication should be provided to show whether or
not the override has been actuated.
39
Licensed to Master Marine for 1 copy. IMO
Chapter 4
4.6
4.7.1 Arrangements for the storage, distribution and utilization of oil fuel
should be such as to ensure the safety of the unit and persons on board.
4.7.2 Arrangements for the storage, distribution and utilization of oil used
in pressure lubrication systems should be such as to ensure the safety of the
unit and persons on board.
4.7.3 Arrangements for the storage, distribution and utilization of other
flammable oils employed under pressure in power transmission systems,
control and activating systems and heat transfer systems should be such as to
ensure the safety of the unit and persons on board.
4.7.4 In machinery spaces pipes, fittings and valves carrying flammable oils
should be of a material approved by the Administration, having regard to the
risk of fire.
4.8
40
Licensed to Master Marine for 1 copy. IMO
.2
.3
41
Licensed to Master Marine for 1 copy. IMO
Chapter 4
4.9
42
Licensed to Master Marine for 1 copy. IMO
.3
.4
.5
.6
.7
.8
.9
4.9.11 In addition to remote control of the ballast pumps and valves from
the central ballast control station, all ballast pumps and valves should be
fitted with independent local control operable in the event of remote
control failure. The independent local control of each ballast pump and of
its associated ballast tank valves should be in the same location.
4.9.12 The control and indicating systems listed in 4.9.10 should function
independently of one another, or have sufficient redundancy, such that a
failure in one system does not jeopardize the operation of any of the other
systems.
4.9.13 Each power-actuated ballast valve should fail to the closed position
upon loss of control power. Upon reactivation of control power, each such
valve should remain closed until the ballast control operator assumes control
of the reactivated system. The Administration may accept ballast valve
arrangements that do not fail to the closed position upon loss of power
provided the Administration is satisfied that the safety of the unit is not
impaired.
4.9.14 The tank level indicating system required by 4.9.10.5 should
provide means to:
.1
.2
43
Licensed to Master Marine for 1 copy. IMO
Chapter 4
stability of the unit. Tank level sensors should not be situated in
the tank suction lines.
4.9.15 The draught indicating system should indicate the draught at each
corner of the unit or at representative positions as required by the
Administration.
4.9.16 Enclosures housing ballast system electrical components, the failure
of which would cause unsafe operation of the ballast system upon liquid
entry into the enclosure, should comply with 5.5.21.
4.9.17 A means to indicate whether a valve is open or closed should be
provided at each location from which the valve can be controlled. The
indicators should rely on movement of the valve spindle.
4.9.18 Means should be provided at the central ballast control station to
isolate or disconnect the ballast pump control and ballast valve control
systems from their sources of electrical, pneumatic or hydraulic power.
Internal communication
4.9.19 A permanently installed means of communication, independent of
the units main source of electrical power, should be provided between the
central ballast control station and spaces that contain ballast pumps or valves,
or other spaces that may contain equipment necessary for the operation of
the ballast system.
4.10 Protection against flooding
4.10.1 Each seawater inlet and discharge in spaces below the assigned load
line should be provided with a valve operable from an accessible position
outside the space on:
.1
.2
all other units where the space containing the valve is normally
unattended and is not provided with high bilge water level
detection.
44
Licensed to Master Marine for 1 copy. IMO
45
Licensed to Master Marine for 1 copy. IMO
Chapter 4
4.12 Dynamic positioning systems
Dynamic positioning systems used as a sole means of position keeping
should provide a level of safety equivalent to that provided for anchoring
arrangements.*
Refer to the Guidelines for vessels with dynamic positioning systems approved by the
Maritime Safety Committee at its sixty-third session and disseminated by MSC/Circ.645.
46
Licensed to Master Marine for 1 copy. IMO
Chapter 5
Electrical installations for all types of units
5.1
5.2.1 Every unit should be provided with a main source of electrical power
which should include at least two generating sets.
5.2.2 The power of these sets should be such that it is still possible to ensure
the functioning of the services referred to in 5.1.1.1, except for services
referred to in 1.3.17.2, in the event of any one of these generating sets being
stopped.
5.2.3 Where transformers or converters constitute an essential part of the
supply system, the system should be so arranged as to ensure the same
continuity of the supply as stated in 5.2.2.
5.2.4 A main electrical lighting system which should provide illumination
throughout those parts of the unit normally accessible to and used by
personnel should be supplied from the main source of power.
5.2.5 The arrangement of the main lighting system should be such that a fire
or other casualty in the space or spaces containing the main source of power,
including transformers or converters, if any, will not render the emergency
lighting system required by 5.3 inoperative.
5.2.6 The arrangement of the emergency lighting system should be such
that a fire or other casualty in the space or spaces containing the emergency
source of power, including transformers or converters, if any, will not
render the main lighting system required by this section inoperative.
*
47
Licensed to Master Marine for 1 copy. IMO
Chapter 5
5.3
.2
48
Licensed to Master Marine for 1 copy. IMO
5.3.6 The power available should be sufficient to supply all those services
that are essential for safety in an emergency, due regard being paid to such
services as may have to be operated simultaneously. The emergency source
of power should be capable, having regard to starting currents and the
transitory nature of certain loads, of supplying simultaneously at least the
following services for the periods specified hereinafter, if they depend upon
an electrical source for their operation:
.1
.1.1
.1.2
.1.3
.1.4
.1.5
.1.6
.1.7
.1.8
.2
.3
.4
.4.1
.4.2
.4.3
49
Licensed to Master Marine for 1 copy. IMO
Chapter 5
.4.4
.5
.6
.7
.7.1
.7.2
.8
.8.1
.8.2
.2
.3
50
Licensed to Master Marine for 1 copy. IMO
carrying the emergency load without recharging while maintaining the voltage of the battery throughout the discharge
period within plus or minus 12% of its nominal voltage;
.2
.3
.2
.3
51
Licensed to Master Marine for 1 copy. IMO
Chapter 5
5.3.13 The emergency switchboard should be supplied in normal
operation from the main switchboard by an interconnector feeder which
should be adequately protected at the main switchboard against overload
and short circuit. The arrangement at the emergency switchboard should be
such that the interconnector feeder is disconnected automatically at the
emergency switchboard upon failure of the main power supply. Where the
system is arranged for feedback operation, the interconnector feeder should
also be protected at the emergency switchboard at least against short circuit.
5.3.14 In order to ensure ready availability of emergency supplies,
arrangements should be made where necessary to disconnect nonemergency circuits automatically from the emergency switchboard to
ensure that power is available automatically to the emergency circuits.
5.3.15 The emergency generator and its prime mover and any emergency
accumulator battery should be designed to function at full rated power
when upright and when inclined up to the maximum angle of heel in the
intact and damaged condition, as determined in accordance with chapter 3.
In no case need the equipment be designed to operate when inclined more
than:
.1
258 in any direction on a column-stabilized unit;
.2
.3
5.3.16 Provision should be made for the periodic testing of the complete
emergency system. This should include the testing of automatic starting
arrangements.
5.4
52
Licensed to Master Marine for 1 copy. IMO
53
Licensed to Master Marine for 1 copy. IMO
Chapter 5
to earth (ground) exceeding a voltage to be specified by the Administration
should not be installed on the front of such switchboards. There should be
non-conducting mats or gratings at the front and rear, where necessary.
5.5.6 Distribution systems with hull return should not be installed, but this
does not preclude, under conditions approved by the Administration, the
installation of:
.1
.2
.3
.4
54
Licensed to Master Marine for 1 copy. IMO
.2
.3
.4
55
Licensed to Master Marine for 1 copy. IMO
Chapter 5
5.5.21 Where spilling or impingement of liquids could occur upon any
electrical control or alarm console, or similar electrical enclosure essential to
the safety of the unit, such equipment should have suitable protection
against the ingress of liquids.*
5.6
Internal communication
56
Licensed to Master Marine for 1 copy. IMO
Chapter 6
Machinery and electrical installations
in hazardous areas for all types of units
6.1
Zones
Zone 1:
Zone 2:
6.2
.2
.3
Enclosed spaces that are on the drill floor and which are not
separated by a solid floor from the spaces in 6.2.3.2.
.4
The identification and extent of hazardous areas in this chapter have been determined taking
into account current practice.
57
Licensed to Master Marine for 1 copy. IMO
Chapter 6
specified in 6.2.3.1, any ventilation outlets of zone 1 spaces, or
any access to zone 1 spaces.
.5
6.3
.1
.2
.3
.4
.5
The areas 1.5 m beyond the zone 1 areas specified in 6.2.3.4 and
beyond the semi-enclosed locations specified in 6.2.3.2.
.6
.7
.8
6.3.1 Except for operational reasons, access doors or other openings should
not be provided between a non-hazardous space and a hazardous area or
between a zone 2 space and a zone 1 space. Where such access doors or
other openings are provided, any enclosed space not referred to under 6.2.3
or 6.2.4 and having a direct access to any zone 1 location or zone 2 location
becomes the same zone as the location except that:
.1
.1.1
.1.2
ventilation is such that the air flow with the door open is from
the zone 2 space into the zone 1 location, and
.1.3
58
Licensed to Master Marine for 1 copy. IMO
Ventilation of spaces
ventilation systems, except fans necessary for supplying combustion air to prime movers for the production of electrical power;
59
Licensed to Master Marine for 1 copy. IMO
Chapter 6
.2
.3
6.6
Zone 0
Certified intrinsically safe circuits or equipment and associated
wiring.
.2
Zone 1
.2.1
.2.2
60
Licensed to Master Marine for 1 copy. IMO
.2.4
.2.5
.3
Zone 2
3.1
.3.2
.3.3
.3.4
.3.5
.3.6
61
Licensed to Master Marine for 1 copy. IMO
Chapter 7
Machinery and electrical installations
for self-propelled units
7.1
General
7.1.1 The requirements of this chapter apply to units which are designed to
undertake self-propelled passages without external assistance and are not
applicable to units which are fitted only with means for the purpose of
positioning or of assistance in towing operations. These requirements are
additional to those in chapters 4, 5 and 6.
7.1.2 Means should be provided whereby normal operation of propulsion
machinery can be sustained or restored even though one of the essential
auxiliaries becomes inoperative. Special consideration should be given to
the malfunction of:
.1
a generator set which serves as a main source of electrical power;
.2
.3
4
.5
.6
.7
.8
.9
.10
However, the Administration, having regard to overall safety considerations, may accept a partial reduction in capability from full normal
operation.
7.1.3 Main propulsion machinery and all auxiliary machinery essential to
the propulsion and the safety of the unit should, as fitted in the unit, be
capable of operating under the static conditions required by 4.1.4 and the
following dynamic conditions:
.1
column-stabilized units 22.58 in any direction;
.2
.3
63
Licensed to Master Marine for 1 copy. IMO
Chapter 7
The Administration may permit deviation from these angles, taking into
consideration the type, size and service conditions of the unit.
7.1.4 Special consideration should be given to the design, construction and
installation of propulsion machinery systems so that any mode of their
vibrations should not cause undue stresses in this machinery in the normal
operating ranges.
7.2
7.2.1 Units should have sufficient power for going astern to secure proper
control of the unit in all normal circumstances.
7.2.2 The ability of the machinery to reverse the direction of thrust of the
propeller in sufficient time and so to bring the unit to rest within a
reasonable distance from maximum ahead service speed should be
demonstrated.
7.2.3 The stopping times, unit headings and distances recorded on trials,
together with the results of trials to determine the ability of units having
multiple propellers to navigate and manoeuvre with one or more propellers
inoperative, should be available on board for the use of the master or other
designated personnel.*
7.2.4 Where the unit is provided with supplementary means for manoeuvring or stopping, these should be demonstrated and recorded as referred to in
7.2.2 and 7.2.3.
7.3
Machinery controls
7.4.1 Main and auxiliary machinery essential for the propulsion of the unit
should be provided with effective means for its operation and control. A
pitch indicator should be provided on the navigating bridge for
controllable-pitch propellers.
*
Reference is made to the Recommendation on the provision and display of manoeuvring information
on board ships, adopted by the Organization by resolution A.601(15).
64
Licensed to Master Marine for 1 copy. IMO
.2
.3
.4
.5
.6
.7
.8
.8.1
.8.2
.9
65
Licensed to Master Marine for 1 copy. IMO
Chapter 7
7.4.3 Where the main propulsion and associated machinery including
sources of main electrical supply are provided with various degrees of
automatic or remote control and are under continuous manned supervision
from a control room, this control room should be designed, equipped and
installed so that the machinery operation will be as safe and effective as if it
were under direct supervision; for this purpose 8.3 to 8.6 should apply as
appropriate. Particular consideration should be given to protection against
fire and flooding.
7.5
Steering gear
66
Licensed to Master Marine for 1 copy. IMO
67
Licensed to Master Marine for 1 copy. IMO
Chapter 7
7.6
Engineers alarm
7.9.1 In addition to complying with 5.2, the main source of electrical power
should comply with the following:
.1
68
Licensed to Master Marine for 1 copy. IMO
.2
.3
.2
.2.1
.2.2
.3
69
Licensed to Master Marine for 1 copy. IMO
Chapter 8
Periodically unattended machinery
spaces for all types of unit
8.1
General
Application
8.2.1 The requirements of 8.3 to 8.9 apply to units which are designed to
undertake self-propelled passages without external assistance.
8.2.2 Units other than those designed for unassisted passages, having
periodically unattended spaces in which machinery associated with the
marine mode is located, should comply with the applicable parts of 8.3, 8.4,
8.7, 8.8 and 8.9.
8.2.3 Where in any unit machinery spaces of category A for drilling
purposes are intended to be periodically unattended the application of 8.3
and 8.9 to machinery spaces of category A should be considered by the
Administration, due consideration being given to the characteristics of the
machinery concerned and to the supervision envisaged to ensure safety.
8.2.4 Measures should be taken to the satisfaction of the Administration to
ensure that the equipment of every unit is functioning in a reliable manner
and that satisfactory arrangements are made for regular inspections and
routine tests to ensure continuous reliable operation.
8.2.5 Every unit should be provided with documentary evidence, to the
satisfaction of the Administration, of its fitness to operate with periodically
unattended machinery spaces.
8.3
Fire safety
Fire prevention
8.3.1 Where necessary, oil fuel and lubricating oil pipes should be screened
or otherwise suitably protected to avoid, as far as practicable, oil spray or oil
leakages on to hot surfaces or into machinery air intakes. The number of
joints in such piping systems should be kept to a minimum and, where
practicable, leakages from high-pressure oil fuel pipes should be collected
and arrangements provided for an alarm to be given.
71
Licensed to Master Marine for 1 copy. IMO
Chapter 8
8.3.2 Where daily service oil fuel tanks are filled automatically, or by remote
control, means should be provided to prevent overflow spillages. Other
equipment which treats flammable liquids automatically, e.g. oil fuel
purifiers, which, whenever practicable, should be installed in a special space
reserved for purifiers and their heaters, should have arrangements to prevent
overflow spillages.
8.3.3 Where daily service oil fuel tanks or settling tanks are fitted with
heating arrangements, a high-temperature alarm should be provided if the
flashpoint of the oil fuel can be exceeded.
Fire detection
8.3.4 An approved fire detection system based on the self-monitoring
principle and including facilities for periodical testing should be installed in
periodically unattended machinery spaces.
8.3.5 The fire detection system, required by 8.3.4, should comply with the
following general requirements.
.1
This fire detection system should be so designed and the
detectors so positioned as to detect rapidly the onset of fire in
any part of those spaces and under any normal conditions of
operation of the machinery and variations of ventilation as
required by the possible range of ambient temperatures. Except
in spaces of restricted height and where their use is specially
appropriate, detection systems using only thermal detectors
should not be permitted. The detection system should initiate
audible and visual alarms distinct in both respects from the
alarms of any other system not indicating fire, in sufficient places
to ensure that the alarms are heard and observed at the locations
required by 8.7.1.
.2
After installation the system should be tested under varying
conditions of engine operation and ventilation.
.3
The fire detection system, where electrically supplied, should be
fed automatically from an emergency source of power by a
separate feeder if the main source of power fails.
8.3.6 Means should be provided in case of fire:
.1
in boiler air supply casings and exhausts (uptakes); and
.2
to detect fires and give alarms at an early stage, unless the Administration
considers this to be unnecessary in a particular case.
8.3.7 Internal combustion engines of 2,250 kW and above or having
cylinders of more than 300 mm bore should be provided with crankcase oil
mist detectors or engine bearing temperature monitors or equivalent
devices.
72
Licensed to Master Marine for 1 copy. IMO
.2
.2.1
.2.2
8.3.10 The Administration should give special consideration to maintaining the fire integrity of the machinery spaces, to the location and
centralization of the fire-extinguishing system controls and to the required
shutdown arrangements (e.g. ventilation, fuel pumps, etc.); it may require
additional fire-extinguishing appliances and other fire-fighting equipment
and breathing apparatus.
8.4
73
Licensed to Master Marine for 1 copy. IMO
Chapter 8
8.5
74
Licensed to Master Marine for 1 copy. IMO
Communication
Alarm system
.2
.3
.4
8.8.1 The special requirements for the machinery, boiler and electrical
installations should be to the satisfaction of the Administration and should
include at least the requirements of this section.
75
Licensed to Master Marine for 1 copy. IMO
Chapter 8
8.8.2 The main source of electrical power should comply with the
following:
.1
Where the electrical power can normally be supplied by one
generator, suitable load-shedding arrangements should be
provided to ensure the integrity of supplies to services required
for propulsion and steering as well as the safety of the unit. In
the case of loss of the generator in operation, adequate provision
should be made for automatic starting and connecting to the
main switchboard of a stand-by generator of sufficient capacity
to ensure safe navigation when under way and to ensure the
safety of the unit with automatic restarting of the essential
auxiliaries including, where necessary, sequential operations.
The Administration may dispense with this requirement for a
unit where the power necessary to ensure the functioning of the
service referred to in 5.1.1.1, except for services referred to in
1.3.17.2, is 250 kW or less.
.2
Change-over function
8.8.3 Where stand-by machines are required for other auxiliary machinery
essential to propulsion, automatic change-over devices should be provided.
An alarm should be given on automatic change-over.
Automatic control and alarm systems
8.8.4 The control systems should be such that the services needed for the
operation of the main propulsion machinery and its auxiliaries are ensured
through the necessary automatic arrangements.
8.8.5 Means should be provided to keep the starting air pressure at the
required level where internal combustion engines are used for main
propulsion.
8.8.6 An alarm system complying with 8.7 should be provided for all
important pressures, temperatures and fluid levels and other essential
parameters.
8.9
Safety systems
76
Licensed to Master Marine for 1 copy. IMO
77
Licensed to Master Marine for 1 copy. IMO
Chapter 9
Fire safety
9.1
9.1.1 These requirements have been formulated principally for units having
their hull superstructure, structural bulkheads, decks and deckhouses
constructed of steel.
9.1.2 Units constructed of other materials may be accepted, provided that,
in the opinion of the Administration, they provide an equivalent standard of
safety.
Fire integrity of bulkheads and decks
9.1.3 In addition to complying with the specific provisions for fire integrity
of bulkheads and decks in this section and in 9.2, the minimum fire integrity
of bulkheads and decks should be as prescribed in tables 9-1 and 9-2.
Exterior boundaries of superstructures and deckhouses enclosing accommodation, including any overhanging decks which support such accommodation, should be constructed to A-60 standard for the whole of the
portion which faces and is within 30 m of the centre of the rotary table. For
units that have a movable substructure the 30 m should be measured with
the substructure at its closest drilling position to the accommodation. The
Administration may accept equivalent arrangements.
9.1.4 The following requirements should govern application of the tables:
.1
.2
(2)
(3)
(4)
79
Licensed to Master Marine for 1 copy. IMO
Spaces
Control stations
(1)
(1) A-0
Corridors
(2)
Accommodation spaces
(3)
Stairways
(4)
(5)
Machinery spaces
of category A
(6)
80
(d)
(2)
A-0
C
(3)
(8)
(9)
Open decks
(10)
(11)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
A-60
A-0
A-15
A-60
A-15
A-60
A-60
A-0
B-0
B-0
A-0(b)
B-0
A-60
A-0
A-0
A-0
B-0
B-0
A-0(b)
B-0
A-60
A-0
A-0
A-0
B-0
A-0(b)
B-0
A-0(b)
A-60
A-0
A-0
A-0
*
*
B-0
A-0(b)
A-60
A-0
A-0
A-0
B-0
*(a)
A-0(a)
A-60
A-60
A-0
A-0
A-0
A-0
A-0
A-0
A-0(c)
A-0
(7)
Hazardous areas
(4)
A-0
(a)(c)
Chapter 9
Space
above ?
Control stations
(1)
(1) A-0
(2)
A-0
(3)
A-0
(4)
A-0
(5)
A-0
(6)
A-60
(7)
A-0
(8)
A-0
(9)
A-0
(10)
*
(11)
A-0
Corridors
(2) A-0
A-0
A-60
A-0
A-0
A-0
Accommodation spaces
(3) A-60
A-0
A-0
A-60
A-0
A-0
A-0
Stairways
(4) A-0
A-0
A-0
A-0
A-60
A-0
A-0
A-0
A-0
(5) A-15
A-0
A-0
A-0
A-60
A-0
A-0
A-0
A-0
Machinery spaces
of category A
(6)
A-60
A-60
A-0
A-60
(a)
81
A-60
A-60
A-60
A-60
A-60
(7) A-15
A-0
A-0
A-0
A-0
A-0(a)
*(a)
A-0
A-0
A-0
Hazardous areas
(8) A-60
A-0
A-0
A-0
A-0
A-60
A-0
A-0
A-0
(9) A-60
A-0
A-0
A-0
A-0
A-0
A-0
A-0
A-0(c)
A-0
A-0
A-0
A-0
A-0
A-0
A-0
Open decks
(10) *
Sanitary and
similar spaces
(11)
A-0
Fire safety
Chapter 9
(5)
(6)
(7)
(8)
(9)
82
Licensed to Master Marine for 1 copy. IMO
Fire safety
bulkhead, in which case the bulkhead may terminate at the continuous
ceiling or lining. In corridor bulkheads, ventilation openings may be
permitted only in and under the doors of cabins, public spaces, offices and
sanitary spaces. The openings should be provided only in the lower half of
the door. Where such an opening is in or under a door, the total net area of
any such opening or openings should not exceed 0.05 m2. When such an
opening is cut in a door it should be fitted with a grille made of noncombustible material. Such openings should not be provided in a door in a
division forming a stairway enclosure.
9.2.2 Stairs should be constructed of steel or equivalent material.
9.2.3 Stairways which penetrate only a single deck should be protected at
least at one level by A or B class divisions and self-closing doors so as to
limit the rapid spread of fire from one deck to another. Personnel lift trunks
should be protected by A class divisions. Stairways and lift trunks which
penetrate more than a single deck should be surrounded by A class
divisions and protected by self-closing doors at all levels. Self-closing doors
should not be fitted with hold-back hooks. However, hold-back
arrangements incorporating remote release fittings of the fail-safe type
may be utilized.
9.2.4 Air spaces enclosed behind ceilings, panellings or linings should be
divided by close fitting draught stops spaced not more than 14 m apart.
9.2.5 Except for insulation in refrigerated compartments, insulation
material, pipe and vent duct lagging, ceilings, linings and bulkheads should
be of non-combustible material. Insulation of pipe fittings for cold service
systems and vapour barriers and adhesives used in conjunction with
insulation need not be non-combustible but they should be kept to a
minimum and their exposed surfaces should have low flame spread
characteristics.* In spaces where penetration of oil products is possible,
the surfaces of the insulation should be impervious to oil or oil vapours.
9.2.6 The framing, including grounds and the joint pieces of bulkheads,
linings, ceilings and draught stops, should be of non-combustible material.
9.2.7 All exposed surfaces in corridors and stairway enclosures and surfaces
in concealed or inaccessible spaces in accommodation and service spaces and
control stations should have low flame spread characteristics. Exposed
surfaces of ceilings in accommodation and service spaces and control
stations should have low flame spread characteristics.*
9.2.8 Bulkheads, linings and ceilings may have combustible veneers
provided that the thickness of such veneers should not exceed 2 mm
within any space other than corridors, stairway enclosures and control
*
Refer to IMO resolution A.653(16) Recommendation on improved fire test procedures for
surface flammability of bulkhead, ceiling and deck finish materials, in conjunction with
resolution A.166(ES.IV) Guidelines on the evaluation of fire hazard properties of materials and
Annex I, Part I of the International Code for Application of Fire Test Procedures (FTP Code).
83
Licensed to Master Marine for 1 copy. IMO
Chapter 9
stations where the thickness should not exceed 1.5 mm. Alternatively,
veneers which have a calorific value not exceeding 45 mJ/m2 of the area for
the thickness used may be accepted by the Administration, irrespective of
the thickness of those veneers.
9.2.9 Primary deck coverings, if applied, should be of approved material
which will not readily ignite, or give rise to toxic or explosive hazards at
elevated temperatures.*
9.2.10 Paints, varnishes and other finishes used on exposed interior
surfaces should not offer an undue fire hazard in the judgement of the
Administration and should not be capable of producing excessive quantities
of smoke.
9.2.11 Ventilation ducts should be of non-combustible material. Short
ducts, however, not generally exceeding 2 m in length and with a crosssectional area not exceeding 0.02 m2 need not be non-combustible, subject
to the following conditions:
.1
these ducts should be of a material which, in the opinion of the
Administration, has a low fire risk;
.2
they may only be used at the end of the ventilation device;
.3
they should not be situated less than 600 mm, measured along
the duct, from where it penetrates any A or B class division
including continuous B class ceilings.
84
Licensed to Master Marine for 1 copy. IMO
Fire safety
closed manually from both sides of the bulkhead or deck. The
damper should be provided with an indicator which shows
whether the damper is open or closed. Fire dampers are not
required, however, where ducts pass through spaces surrounded
by A class divisions, without serving those spaces, provided
those ducts have the same fire integrity as the divisions which
they pierce. The Administration may, given special considerations, permit operation from one side of a division only.
9.2.13 Ducts provided for the ventilation of machinery spaces of category
A, galleys and hazardous areas should not pass through accommodation
spaces, service spaces or control stations. However, the Administration may
permit a relaxation from this requirement, except for the ducts serving
hazardous areas passing through accommodation spaces, control stations
and galleys, provided that the ducts are:
.1
constructed of steel having a thickness of at least 3 mm for ducts
of 300 mm in width or less and of at least 5 mm for ducts of
760 mm in width and over; in the case of ducts the width or
diameter of which is between 300 mm and 760 mm, the
thickness should be obtained by interpolation;
.2
fitted with automatic fire dampers close to the boundaries
penetrated; and
.3
insulated to A-60 standard from the machinery spaces or
galleys to a point at least 5 m beyond each fire damper;
or
.4
constructed of steel in accordance with .1; and
.5
insulated to A-60 standard throughout the accommodation
spaces, service spaces or control stations.
9.2.14 Ducts provided for the ventilation of accommodation spaces,
service spaces or control stations should not pass through machinery spaces
of category A, galleys or hazardous areas. However, the Administration may
permit a relaxation from this requirement, except for the ducts passing
through hazardous areas, provided that:
.1
the ducts where they pass through a machinery space of category
A or a galley are constructed of steel in accordance with
9.2.13.1;
.2
automatic fire dampers are fitted close to the boundaries
penetrated; and
.3
the integrity of the machinery space or galley boundaries is
maintained at the penetrations;
or
.4
the ducts where they pass through a machinery space of category
A or a galley are constructed of steel in accordance with
9.2.13.1; and
85
Licensed to Master Marine for 1 copy. IMO
Chapter 9
.5
.3
.4
9.2.17 The main inlets and outlets of all ventilation systems should be
capable of being closed from outside the spaces being ventilated.
9.2.18 Power ventilation of accommodation spaces, service spaces, control
stations, machinery spaces and hazardous areas should be capable of being
stopped from an easily accessible position outside the space being served.
The accessibility of this position in the event of a fire in the spaces served
should be specially considered. The means provided for stopping the power
ventilation serving machinery spaces or hazardous areas should be entirely
separate from the means provided for stopping ventilation of other spaces.
9.2.19 Windows and sidescuttles in boundaries which are required to meet
an A-60 standard which face the drill floor area should be:
.1
constructed to an A-60 standard; or
.2
protected by a water curtain; or
.3
fitted with shutters of steel or equivalent material.
9.2.20 The ventilation of the accommodation spaces and control stations
should be arranged in such a way as to prevent the ingress of flammable,
toxic or noxious gases or smoke from surrounding areas.
9.3
Means of escape
9.3.1 Within the accommodation spaces, service spaces and control stations
the following requirements should be applied:
.1
86
Licensed to Master Marine for 1 copy. IMO
Fire safety
means of escape, due regard being paid to the nature and
location of spaces and to the number of persons who might
normally be accommodated or employed there.
.2
.3
Every escape route should be readily accessible and unobstructed and all exit doors along the route should be readily
operable. Dead-end corridors exceeding 7 m in length should
not be permitted.
9.3.2 Two means of escape should be provided from every machinery space
of category A by one of the following:
.1
.2
one steel ladder leading to a door in the upper part of the space
from which access is provided to the open deck and additionally,
in the lower part of the space and in a position well separated
from the ladder referred to, a steel door capable of being
operated from each side and which provides access to a safe
escape route from the lower part of the space to the open deck.
Exceptionally, the Administration may require only one means
of escape, due regard being paid to the nature and location of
spaces and to the number of persons who might normally be
employed there.
9.3.3 From machinery spaces other than those of category A, escape routes
should be provided to the satisfaction of the Administration having regard to
the nature and location of the space and whether persons are normally
employed there.
9.3.4 Lifts should not be considered as forming one of the required means
of escape.
9.3.5 Consideration should be given by the Administration to the siting of
superstructures and deckhouses such that in the event of fire at the drill floor
at least one escape route to the embarkation position and survival craft is
protected against radiation effects of that fire as far as practicable.
87
Licensed to Master Marine for 1 copy. IMO
Chapter 9
9.4
88
Licensed to Master Marine for 1 copy. IMO
Fire safety
9.4.11 The diameter of the fire main and water service pipes should be
sufficient for the effective distribution of the maximum required discharge
from the required fire pumps operating simultaneously.
9.4.12 With the required fire pumps operating simultaneously, the
pressure maintained in the fire mains should be to the satisfaction of the
Administration and be adequate for the safe and efficient operation of all
equipment supplied therefrom.
9.4.13 The fire main should, where practicable, be routed clear of
hazardous areas and be arranged in such a manner as to make maximum use
of any thermal shielding or physical protection afforded by the structure of
the unit.
9.4.14 The fire main should be provided with isolating valves located so as
to permit optimum utilization in the event of physical damage to any part of
the main.
9.4.15 The fire main should not have connections other than those
necessary for fire-fighting purposes.
9.4.16 All practical precautions consistent with having water readily
available should be taken to protect the fire main against freezing.
9.4.17 Materials readily rendered ineffective by heat should not be used for
fire mains and hydrants unless adequately protected. The pipes and hydrants
should be so placed that the fire hoses may be easily coupled to them.
9.4.18 A cock or valve should be fitted to serve each fire hose so that any
fire hose may be removed while the fire pumps are operating.
9.4.19 The number and position of the hydrants should be such that at
least two jets of water, not emanating from the same hydrant, one of which
should be from a single length of fire hose, may reach any part of the unit
normally accessible to those on board while the unit is being navigated or is
engaged in drilling operations A hose should be provided for every hydrant.
9.4.20 Fire hoses should be of material approved by the Administration
and be sufficient in length to project a jet of water to any of the spaces in
which they may be required to be used. Their maximum length should be
to the satisfaction of the Administration. Every fire hose should be provided
with a dual-purpose nozzle and the necessary couplings. Fire hoses, together
with any necessary fittings and tools, should be ready for use at any time and
should be kept in conspicuous positions near the water service hydrants or
connections.
9.4.21
.1
89
Licensed to Master Marine for 1 copy. IMO
Chapter 9
.2
.3
9.4.22 The surface unit should be provided with at least one international
shore connection complying with regulation II-2/19.3 and 19.4 of the 1974
SOLAS Convention.
9.4.23 Facilities should be available enabling such a connection to be used
on any side of the unit.
9.5
9.5.1 In spaces where main or auxiliary oil-fired boilers and other fired
processes of equivalent thermal rating are situated, or in spaces containing
oil fuel units or settling tanks, the unit should be provided with the
following:
.1
.1.1
.1.2
.1.3
.2
.3
90
Licensed to Master Marine for 1 copy. IMO
Fire safety
9.5.2 Spaces containing internal combustion machinery used either for
main propulsion or for other purposes, when such machinery has a total
power output of not less than 750 kW, should be provided with the
following arrangements:
.1
.2
9.5.3 The Administration should give special consideration to the fireextinguishing arrangements to be provided in spaces not fitted with fixed
fire-extinguishing installations containing steam turbines which are
separated from boiler rooms by watertight bulkheads.
9.5.4 Where, in the opinion of the Administration, a fire hazard exists in
any machinery space for which no specific provisions for fire-extinguishing
appliances are prescribed in 9.5.1 to 9.5.3, there should be provided in, or
adjacent to, that space a number of approved portable fire extinguishers or
other means of fire extinction to the satisfaction of the Administration.
9.6
9.8.1 A fixed automatic gas detection and alarm system should be provided
to the satisfaction of the Administration so arranged as to monitor
continuously all enclosed areas of the unit in which an accumulation of
flammable gas may be expected to occur and capable of indicating at the
91
Licensed to Master Marine for 1 copy. IMO
Chapter 9
main control point by aural and visual means the presence and location of an
accumulation.
9.8.2 At least two portable gas monitoring devices should be provided, each
capable of accurately measuring a concentration of flammable gas.
9.9
Firemens outfits
92
Licensed to Master Marine for 1 copy. IMO
Fire safety
top and the underside of the helicopter deck as an alternative to the A-0
requirement. Deckhouse tops directly below helicopter decks should have
no openings.
9.11.2 On any helicopter deck there should be provided and stored near to
the means of access to that deck:
.1
.2
.3
.4
9.11.3 A designated area should be provided for the storage of fuel tanks
which should be:
.1
.2
.2
.3
.4
inspection procedures.
93
Licensed to Master Marine for 1 copy. IMO
Chapter 9
9.11.7 Storage tank fuel pumps should be provided with means which
permit shutdown from a safe remote location in the event of a fire. Where a
gravity-fed fuelling system is installed, equivalent closing arrangements
should be provided.
9.11.8 The fuel pumping unit should be connected to one tank at a time
and the piping between the tank and the pumping unit should be of steel or
equivalent material, as short as possible and protected against damage.
9.11.9 Fire-extinguishing arrangements for protection of the designated
area should be to the satisfaction of the Administration.
9.11.10 Electrical fuel pumping units and associated control equipment
should be of a type suitable for the location and potential hazard.
9.11.11 Fuel pumping units should incorporate a device which will prevent
over-pressurization of the delivery or filling hose.
9.11.12 The procedures and precautions during refuelling operations
should be in accordance with good recognized practice.
9.11.13 Attention should be paid to the electrical bonding of all equipment
used in refuelling operations.
9.11.14 NO SMOKING signs should be displayed at appropriate
locations.
9.12 Storage of gas cylinders
9.12.1 Where more than one cylinder of oxygen and more than one
cylinder of acetylene are carried simultaneously, such cylinders should be
arranged in accordance with the following:
.1
.2
.3
.4
.5
.6
.6.1
Permanent piping systems for oxyacetylene systems are acceptable provided that they are designed having due regard to
standards and codes of practice to the satisfaction of the
Administration.
Where two or more cylinders of each gas are intended to be
carried in enclosed spaces, separate dedicated storage rooms
should be provided for each gas.
Storage rooms should be constructed of steel, and be well
ventilated and accessible from the open deck.
Provision should be made for the expeditious removal of
cylinders in the event of fire.
NO SMOKING signs should be displayed at the gas cylinder
storage rooms.
Where cylinders are stowed in open locations means should be
provided to:
protect cylinders and associated piping from physical damage;
94
Licensed to Master Marine for 1 copy. IMO
Fire safety
.6.2
.6.3
95
Licensed to Master Marine for 1 copy. IMO
Chapter 10
Life-saving appliances and equipment
10.1 General
Definitions
10.1.1 For the purpose of this chapter, unless expressly provided otherwise,
the terms used, relating to life-saving appliances, are as defined in regulation
III/3.*
Visitors are personnel not regularly assigned to the unit.
Evaluation, testing and approval of life-saving appliances
10.1.2 Life-saving appliances should be evaluated, tested and approved, as
provided in regulations III/4 and III/5.
Life-saving appliances
10.1.3
Each reference to a regulation in this chapter means a regulation in the 1974 SOLAS
Convention in force prior to 1 July 1998. On that date, a thoroughly revised chapter III
(adopted by resolution MSC.47(66)) and the associated International Life-Saving Appliance
(LSA) Code (adopted by resolution MSC.48(66)) entered into force.
97
Licensed to Master Marine for 1 copy. IMO
Chapter 10
Self-elevating and column-stabilized units
10.2.4 Each unit should carry lifeboats complying with the requirements of
regulation III/46, installed in at least two widely separated locations on
different sides or ends of the unit. The arrangement of the lifeboats should
provide sufficient capacity to accommodate the total number of persons on
board if:
.1
.2
all the lifeboats on any one side, any one end, or any one corner
of the unit are lost or rendered unusable.
10.2.5 In addition, each unit should carry liferafts complying with the
requirements of regulation III/39 or III/40, of such aggregate capacity as will
accommodate the total number of persons on board.
10.2.6 In the case of a self-elevating unit where, due to its size or
configuration, lifeboats cannot be located in widely separated locations to
satisfy 102.4, the Administration may permit the aggregate capacity of the
lifeboats to accommodate only the total number of persons on board.
However, the liferafts under 10.2.5 should be served by launching
appliances complying with the requirements of regulation III/48.5 or
III/48.6.
10.3 Survival craft muster and embarkation arrangements
10.3.1 If separate, muster stations should be provided close to the
embarkation stations. Each muster station should have sufficient space to
accommodate all persons assigned to muster at that station.
10.3.2 Muster and embarkation stations should be readily accessible from
accommodation and work areas.
10.3.3 Muster and embarkation stations should be adequately illuminated
by emergency lighting.
10.3.4 Alleyways, stairways and exits giving access to the muster and
embarkation stations should be adequately illuminated by emergency
lighting.
10.3.5 Davit-launched survival craft muster and embarkation stations
should be so arranged as to enable stretcher cases to be placed in survival
craft.
Survival craft embarkation arrangements should be so designed that:
10.3.6
.1
.2
98
Licensed to Master Marine for 1 copy. IMO
.4
10.3.7 At least two widely separated fixed metal ladders or stairways should
be provided extending from the deck to the surface of the water. The fixed
metal ladders or stairways and sea areas in their vicinity should be adequately
illuminated by emergency lighting.
10.3.8 If fixed ladders cannot be installed, alternative means of escape with
sufficient capacity to permit all persons on board to descend safely to the
waterline should be provided.
10.4 Survival craft launching stations
Launching stations should be in such positions as to ensure safe launching
having particular regard to clearance from any exposed propeller. As far as
possible, launching stations should be located so that survival craft can be
launched down a straight side of the unit, except for:
.1
.2
.4
.5
99
Licensed to Master Marine for 1 copy. IMO
Chapter 10
10.5.3
100
Licensed to Master Marine for 1 copy. IMO
101
Licensed to Master Marine for 1 copy. IMO
Chapter 10
10.9.2
10.9.3 Rapid recovery of the rescue boat should be possible when loaded
with its full complement of persons and equipment. If the rescue boat is also
a lifeboat, rapid recovery should be possible when loaded with its lifeboat
equipment and the approved rescue boat complement of at least six persons.
10.10 Lifejackets
10.10.1 A lifejacket complying with the requirements of regulation III/32.1
or III/32.2 should be provided for every person on board the unit. In
addition, a sufficient number of lifejackets should be stowed in suitable
locations for those persons who may be on duty in locations where their
lifejackets are not readily accessible.
10.10.2 Each lifejacket should be fitted with a light complying with the
requirements of regulation III/32.3.
10.11 Immersion suits
10.11.1 Each unit should carry an immersion suit complying with the
requirements of regulation III/33 for each person on board. In addition, a
sufficient number of immersion suits should be stowed in suitable locations
for those persons who may be on duty in locations where their immersion
suits are not readily accessible.
10.11.2 Immersion suits need not be carried if the unit is constantly in
operation in warm climates where, in the opinion of the Administration,
immersion suits are unnecessary.
10.12 Lifebuoys
10.12.1 At least eight lifebuoys of a type complying with the requirements
of regulation III/31 should be provided on each unit. The number and
placement of lifebuoys should be such that a lifebuoy is accessible from
exposed locations. Surface units over 100 m in length should carry not less
than the number of lifebuoys prescribed in the following table:
Length of unit
in metres
Minimum number
of lifebuoys
10
12
14
10.12.2 Not less than one-half of the total number of lifebuoys should be
provided with self-igniting lights of an approved electric battery type
complying with the requirements of regulation III/31.2. Not less than two
of these should also be provided with self-activating smoke signals
102
Licensed to Master Marine for 1 copy. IMO
103
Licensed to Master Marine for 1 copy. IMO
Chapter 10
10.16 Emergency warnings
10.16.1 Each unit should be provided with a general alarm system so
installed as to be clearly perceptible in all parts of the unit. Control stations
for activating the alarm should be installed to the satisfaction of the
Administration. The number of signals used should be limited to the
following: general emergency signal, fire alarm signal and abandon unit
signal. These signals should be described in the muster list.
10.16.2 The warning signals given over the general alarm system should be
supplemented by instructions over a public address system.
10.17 Operating instructions
Illustrations and instructions should be provided on or in the vicinity of
survival craft and their launching controls and should:
.1
.2
.3
104
Licensed to Master Marine for 1 copy. IMO
.1
.2
Refer to the Recommendation on conditions for the approval of servicing stations for
inflatable liferafts, adopted by the Organization by resolution A.761(18).
105
Licensed to Master Marine for 1 copy. IMO
Chapter 10
.2
106
Licensed to Master Marine for 1 copy. IMO
Chapter 11
Radiocommunication installations
11.1 Application
11.1.1 The purpose of this chapter is to provide minimum requirements
for distress and safety radiocommunications between mobile offshore
drilling units and coast stations, ships and supporting aircraft in the maritime
mobile service.
11.1.2 The requirements are applicable to the following modes of
operation of mobile offshore drilling units:
.1
.2
.3
11.2 General
Coastal States in common areas of interest should, to the extent possible,
establish similar radiocommunication requirements to avoid confusion in
case any ancillary craft have to divert to another coastal State in an
emergency.
107
Licensed to Master Marine for 1 copy. IMO
Chapter 11
11.4.2 In cases where the towing ship complies fully with all applicable
requirements concerning radiocommunications for ships prescribed in
chapter IV of the 1988 SOLAS amendments, the non-self-propelled unit
under tow when manned should:
.1
.2
.3
11.4.3 In cases where the towing ship does not comply fully with the
applicable requirements concerning radiocommunications for ships prescribed in chapter IV of the 1988 SOLAS amendments, the MODU under
tow when manned should comply with all the applicable provisions
concerning radiocommunications prescribed in chapter IV of the 1988
SOLAS amendments.*
11.4.4 Each self-propelled unit accompanied by one or more escort vessels
should comply with the provisions of 11.3.
All requirements of chapter IV of the 1988 SOLAS amendments referring to from the
position the ship is normally navigated should be applied as meaning from a position which is
continuously manned and which is controlling the MODU while under tow.
{
All requirements of chapter IV of the 1988 SOLAS amendments referring to from the
position at which the ship is normally navigated should be applied as meaning from a position
(or from the positions) which is continuously manned and which is controlling the MODU
while stationary at the site including its drilling operations (i.e. normally the control room).
108
Licensed to Master Marine for 1 copy. IMO
Radiocommunication installations
The additional radio equipment should comply with the following
regulations of the 1988 SOLAS amendment for MODUs drilling in:
.1
sea area A1, the equipment prescribed by regulation IV/7.1.1;
.2
sea area A2, the equipment prescribed by regulations IV/7.1.1
and IV/9.1.1;
.3
sea area A3, the equipment prescribed in regulations IV/7.1.1
and IV/10.1.1, plus 10.1.2; or alternatively, as required by
regulations IV/7.1.1 and 10.2.1;
.4
sea area A4, the equipment prescribed by regulations IV/7.1.1
and IV/10.2.1.
11.5.3 If the acoustic noise level in a room fitted with operating controls
for radio equipment is so high or could be so high, during particular
operating conditions, that it may disturb or prevent proper use of the radio
equipment, then adequate noise protection should be provided by
mechanical or other means, in association with the operating controls for
the radio equipment.
11.6 Helicopter communications
In order to ensure communication with helicopters, MODUs serviced by
helicopters should carry an aeromobile VHF radiotelephone station
complying with the relevant requirements of ICAO.
11.7 Internal communications
All types of MODUs should be fitted with efficient means of communication between the control room, the bridge (if provided) and position or
positions fitted with facilities for operation of radio equipment.
11.8 Performance standards
11.8.1 All radio equipment should be of a type approved by the
Administration issuing the licence. Subject to section 11.8.2, such
equipment should conform to appropriate performance standards not
inferior to those adopted by the Organization.*
*
109
Licensed to Master Marine for 1 copy. IMO
Chapter 11
11.8.2 Equipment installed prior to 1 February 1992 may be exempted
from full compliance with the appropriate performance standards at the
discretion of the Administration, provided that the equipment is compatible
with equipment complying with the performance standards, having due
regard to the criteria which the Organization may adopt in connection with
such standards.
_
(footnote continued from previous page)
.5 Resolution A.804(19): Performance standards for shipborne MF radio installations capable of voice communication and digital selective calling, as amended,
and resolution MSC.68(68), annex 2 (valid for equipment installed on or after
1 January 2000).
.6 Resolution A.806(19): Performance standards for shipborne MF/HF radio
installations capable of voice communication, narrow-band direct-printing and
digital selective calling, as amended, and resolution MSC.68(68), annex 3 (valid
for equipment installed on or after 1 January 2000).
.7 Resolution A.810(19): Performance standards for float-free satellite emergency
position-indicating radio beacons (EPIRBs) operating on 406 MHz (see also
resolution A.696(17): Type approval of satellite emergency position-indicating
radio beacons (EPIRBs) operating in the COSPASSARSAT system).
.8 Resolution A.802(19): Performance standards for survival craft radar transponders for use in search and rescue operations.
.9 Resolution A.805(19): Performance standards for float-free VHF emergency
position-indicating radio beacons.
.10 Resolution A.807(19): Performance standards for Inmarsat-C ship earth stations
capable of transmitting and receiving direct-printing communications, as
amended, and resolution MSC.68(68), annex 3 (valid for equipment installed
on or after 1 January 2000), and resolution A.570(14): Type approval of ship
earth stations.
.11 Resolution A.664(16): Performance standards for enhanced group call equipment.
.12 Resolution A.812(19): Performance standards for float-free satellite emergency
position-indicating radio beacons operating through the geostationary Inmarsat
satellite system on 1.6 GHz.
.13 Resolution A.662(16): Performance standards for float-free release and activation
arrangements for emergency radio equipment.
.14 Resolution A.699(17): System performance standard for the promulgation and
co-ordination of maritime safety information using high-frequency narrow-band
direct printing.
.15 Resolution A.700(17): Performance standards for narrow-band direct-printing
telegraph equipment for the reception of navigational and meteorological
warnings and urgent information to ships (MSI) by HF.
.16 Resolution A.811(19): Performance standards for a shipborne integrated
radiocommunication system (IRCS) when used in the GMDSS.
.17 Resolution MSC.80(70), annex 1: Performance standards for on-scene
(aeronautical) two-way portable VHF radiotelephone apparatus.
110
Licensed to Master Marine for 1 copy. IMO
Radiocommunication installations
11.10
.2
.3
111
Licensed to Master Marine for 1 copy. IMO
Chapter 12
Lifting devices
12.1 Cranes
12.1.1 Each crane, including its supporting structure, which is used for the
transfer of material, equipment or personnel between the unit and attending
vessels should be of a design and construction to the satisfaction of the
Administration and adequate for the service intended in accordance with
the requirements of a recognized classification society or with national or
international standards or codes.
12.1.2 Cranes should be so located and protected as to reduce to a
minimum any danger to personnel, due regard being paid to moving parts
or other hazards. Their design should have regard to the materials used in
construction, the working conditions to which they will be subjected and
the environmental conditions. Adequate provisions should be made to
facilitate cleaning, inspection and maintenance.
12.1.3 Consideration should be given to the failure mode for each crane in
the event of extreme overload so that the crane operator is exposed to
minimum danger.
12.1.4 An officer of the Administration or a duly authorized person or
organization should survey the installation of each crane, with particular
regard to its supporting structure.
12.1.5 After each crane has been erected on board, and before it is placed in
service, operational and load tests should be conducted. These tests should
be witnessed and verified by an officer of the Administration or a duly
authorized person or organization. A record of these tests and other
information concerning initial certification should be readily available.
12.1.6 Each crane should be examined at intervals not exceeding 12
months. It should be further tested and recertified, at intervals not
exceeding 5 years, or after substantial alteration or repairs. These tests
should be witnessed and verified by an officer of the Administration or a
duly authorized person or organization. A record of these examinations,
tests and certifications should be readily available.
12.1.7 Cranes used for loading and discharging of offshore supply vessels
should be furnished with rating tables or curves which take into account the
dynamics associated with the units and vessels motions.
12.1.8 Except when loads are determined and marked prior to lifting, each
crane should be fitted, to the satisfaction of the Administration, with a safety
device to give the crane operator a continuous indication of hook load and
rated load for each radius. The indicator should give a clear and continuous
warning when approaching the rated capacity of the crane.
113
Licensed to Master Marine for 1 copy. IMO
Chapter 12
12.1.9 The Administration should give consideration to the installation of
limit switches to provide for the safe operation of the crane.
12.1.10 A crane manual should be provided for each crane and should be
readily available. This manual should contain full information concerning:
.1
design standard, operation, erection, dismantling and transportation;
.2
all limitations during normal and emergency operations with
respect to safe working load, safe working moment, maximum
wind, maximum heel and trim, design temperatures and braking
systems;
.3
.4
.5
.6
114
Licensed to Master Marine for 1 copy. IMO
Chapter 13
Helicopter facilities*
13.1 General
Each helicopter deck should be of sufficient size and located so as to provide
a clear take-off and approach to enable the largest helicopter using the
helideck to operate under the most severe conditions anticipated for
helicopter operations.
13.2 Definitions
13.2.1 Helideck is a purpose-built helicopter landing platform located on a
mobile offshore drilling unit (MODU).
13.2.2 RD means the main rotor diameter of the largest single-rotor
helicopter intended to use the facility.
13.2.3 LD means the largest dimension of the helicopter when the rotors
are turning.
13.2.4 Obstacle-free sector is a sector formed by an arc originating at the
reference point of the edge of a helideck and extending outward in the
horizontal plane level with the elevation of the helideck.
13.2.5 Limited obstacle sector is a sector extending outward which is formed
by that portion of the 3608 arc, excluding the obstacle-free sector, the centre
of which is the reference point from which the obstacle-free sector is
determined. Obstacles within the limited obstacle sector are limited to
specified heights.
13.3 Construction
13.3.1 The helideck should be of a design and construction, adequate for
the intended service and for the appropriate prevailing climatic conditions,
approved to the satisfaction of the Administration.
13.3.2 For adverse climates as determined by the coastal State, taking into
account the type of helicopter used, the conditions of wind, turbulence, sea
state, water temperature and icing conditions, the helideck should meet the
following requirements with reference to ICAO Annex 14, Volume II
(Heliports):
.1
Reference is made to regulations of national civil aviation authorities in the units area of
operation, applicable international standards of the International Civil Aviation Organization
(ICAO) and recommended practices developed in accordance with the Memorandum of
Understanding between IMO and ICAO.
115
Licensed to Master Marine for 1 copy. IMO
Chapter 13
single main rotor helicopters and not less than 0.9LD for
tandem main rotor helicopters;
.2
.3
.4
.5
for omnidirectional operations by tandem main rotor helicopters, within the 1508 limited obstacle-free sector out to a
distance of 0.62LD, measured from the centre of the helideck,
no fixed obstacles should be allowed. Beyond that arc, out to an
overall distance of 0.83LD, the obstacle height is limited to
0.05LD (see figure 13-2);
.6
.7
116
Licensed to Master Marine for 1 copy. IMO
Helicopter facilities
.2
.3
13.3.4
13.4.5
13.5.2
.1
117
Licensed to Master Marine for 1 copy. IMO
Chapter 13
.2
.3
.4
.5
118
Licensed to Master Marine for 1 copy. IMO
Helicopter facilities
15
210 obstacle-free sector
for take-off and approach
LD
Point
of
origin
PLAN VIEW
Obstacle limited
to 1:2 slope
15
Object height
limited to
0.05LD
0.83LD
0.62LD
Landing area level
LD
00091
PROFILE VIEW
119
Licensed to Master Marine for 1 copy. IMO
Chapter 13
15
Obstacle-free
150 sector
(Alternative positions on
the periphery and swinging
the whole sector 15 from
that shown may be used in
satisfying requirements)
ee
-fr
le
ac
bs
A
0.
9L
Obstacle-free
Obstacles limited
to 0.05LD
LD = Helicopter largest
overall dimension
Obstacle-free
15
00092
0.83LD
0.62LD
Section AA
120
Licensed to Master Marine for 1 copy. IMO
Helicopter facilities
0.9LD
Point
of
origin
0.75LD
[5 m max]
[5 m max]
PLAN VIEW
Obstacles limited
to 1.1 m
0.62LD
Landing area level
PROFILE VIEW
00093
0.75LD
121
Licensed to Master Marine for 1 copy. IMO
Chapter 13
Point
of
origin
RD
(or 0.75LD for
tandem main rotor
helicopters)
PLAN VIEW
Obstacles limited
to 1:2 slope
PROFILE VIEW
122
Licensed to Master Marine for 1 copy. IMO
00094
RD
Helicopter facilities
white perimeter marking
0.30
black
18
0.10
18
0.79
15
1.00
30 cm
18
00095
60 cm
123
Licensed to Master Marine for 1 copy. IMO
Chapter 14
Operating requirements
14.1 Operating manuals
14.1.1 Operating manuals containing guidance for the safe operation of the
unit for both normal and envisaged emergency conditions, to the
satisfaction of the Administration, should be provided on board and be
readily available to all concerned. The manuals should, in addition to
providing the necessary general information about the unit, contain
guidance on and procedures for the operations that are vital to the safety
of personnel and the unit. The manuals should be concise and be compiled
in such a manner that they are easily understood. Each manual should be
provided with a contents list, an index and wherever possible be crossreferenced to additional detailed information which should be readily
available on board.
14.1.2 The operating manual for normal operations should include the
following general descriptive information, where applicable:
.1
.2
.3
.4
.5
.6
.7
.8
.9
125
Licensed to Master Marine for 1 copy. IMO
Chapter 14
.10
.11
.12
.13
.14
.15
.16
.17
.18
.19
14.1.3 The operating manual for normal operations should also include,
where applicable:
.1
.2
.3
.4
.5
.6
126
Licensed to Master Marine for 1 copy. IMO
Operating requirements
.7
.8
.9
.10
.11
.12
.13
.14
.15
guidance for the placement and safe operation of the well testing
equipment. The areas around possible sources of gas release
should be classified in accordance with 6.1 for the duration of
well test operations;
.16
.17
.2
.3
.4
.5
.6
.7
127
Licensed to Master Marine for 1 copy. IMO
Chapter 14
.8
.9
128
Licensed to Master Marine for 1 copy. IMO
Operating requirements
14.5 Transfer of material, equipment or personnel
14.5.1 Transfer operations, including the weights of loads to be handled,
any limiting conditions of operation and emergency procedures should be
discussed and agreed between personnel on the unit and on attending
vessels prior to commencement of such transfers. Direct communications
should be maintained with the crane operator throughout such operations.
14.5.2 The unit should be equipped with at least two independent means
for mooring attending vessels. The mooring positions should be such that
sufficient crane capacity in terms of lift and outreach is available to handle
loads in a safe manner.
14.5.3 The arrangement of mooring attachments on the unit to facilitate
transfer operations should have regard to the risk of damage should the
attending vessel come in contact with the unit.
14.5.4 The mooring arrangements and procedures should be such as to
reduce to a minimum any danger to personnel during mooring operations.
14.5.5 The mooring lines between the unit and the attending vessel
should, as far as practicable, be arranged so that if a line breaks, danger to
personnel on both the attending vessel and the unit is minimized.
14.5.6 Discharges from the unit, such as those from the sewage system or
ventilation from bulk tanks, should be arranged so that they minimize
danger to personnel on the deck of attending vessels.
14.6 Diving systems
14.6.1 Diving systems, if provided, should be installed, protected and
maintained so as to minimize, so far as practicable, any danger to personnel
or the unit, due regard being paid to fire, explosion or other hazards.
14.6.2 Diving systems should be designed, constructed, maintained and
certified in accordance with a national or international standard or code
acceptable to the Administration, such as the Code of Safety for Diving
Systems (resolution A.536(13)), which may be employed for fixed diving
systems, if provided.
14.7 Safety of navigation
14.7.1 The requirements of the Convention on the International Regulations for Preventing Collisions at Sea in force should apply to each unit
except when stationary and engaged in drilling operations.
14.7.2 Each unit when stationary and engaged in drilling operations should
comply with the requirements for the safety of navigation of the coastal
State in whose territorial sea or on whose continental shelf the unit is
operating.
129
Licensed to Master Marine for 1 copy. IMO
Chapter 14
14.7.3 Each unit when stationary and engaged in drilling operations should
inform the national hydrographic office concerned about its position in
latitude and longitude, together with the approximate duration of the
operation so as to facilitate the promulgation of a temporary Notice to
Mariners. Details of future movements of units should also be passed to
national hydrographic offices so that temporary Notices may be promulgated before a unit gets under way.
14.8 Emergency procedures
Person in charge
14.8.1 The person on each unit to whom all personnel on board are
responsible in an emergency should be clearly defined. This person should
be designated by title by the owner or operator of the unit or the agent of
either of them.
14.8.2 The person in charge should be well acquainted with the
characteristics, capabilities and limitations of the unit. This person should
be fully cognizant of his responsibilities for emergency organization and
action, for conducting emergency drills and training, and for keeping
records of such drills.
Manning of survival craft and supervision
14.8.3 There should be a sufficient number of trained persons on board for
mustering and assisting untrained persons.
14.8.4 There should be a sufficient number of certificated persons on board
for launching and operating the survival craft to which personnel are
assigned.
14.8.5 Certificated persons should be placed in command and as secondin-command of each lifeboat.
14.8.6 The person in command of the lifeboat and the second-incommand should have a list of all persons assigned to the boat and should
see that persons under their command are acquainted with their duties.
14.8.7 Every lifeboat should have a person assigned who is capable of
operating the lifeboat radio equipment.
14.8.8 Every lifeboat should have a person assigned who is capable of
operating the engine and carrying out minor adjustments.
14.8.9 The person in charge of the unit should ensure the equitable
distribution of persons referred to in 14.8.3, 14.8.4 and 14.8.5 among the
units survival craft.
Muster list
14.8.10 Muster lists should be exhibited in conspicuous places throughout
the unit including the control rooms and accommodation spaces.
130
Licensed to Master Marine for 1 copy. IMO
Operating requirements
14.8.11 The muster list should specify details of the general alarm system
signals and also the action to be taken in all operating modes by every person
when these alarms are sounded, indicating the location to which they
should go and the general duties, if any, they would be expected to perform.
14.8.12
.1
closing of the watertight doors, fire doors, valves, vent inlets and
outlets, scuppers, sidescuttles, skylights, portholes and other
similar openings in the unit;
.2
.3
.4
.5
muster of visitors;
.6
.7
.8
.9
.10
14.8.13 The muster list should specify substitutes for key persons who may
become disabled, taking into account that different emergencies may call for
different actions.
14.8.14 The muster list should show the duties assigned to regularly
assigned personnel in relation to visitors in case of emergency.
14.8.15 Each unit should have a current muster list revised as necessary to
reflect any procedural changes.
14.8.16 In deciding on the level of detail to be included in the muster list,
account should be taken of information available in other documents, e.g.
operating manual.
14.9 Emergency instructions
14.9.1 Illustrations and instructions should be conspicuously displayed at
muster stations, control positions, working spaces and accommodation
spaces to inform all on board of:
.1
.2
131
Licensed to Master Marine for 1 copy. IMO
Chapter 14
14.9.2 All persons arriving on a unit for the first time, including visitors,
should upon arrival on board the unit be properly instructed in the
following:
.1
.2
.3
.4
.5
the dangers and preferred method of jumping into the sea from a
height, particularly when wearing a lifejacket;
.6
.7
the need to participate in any drills held during the time they are
on board; and
.8
132
Licensed to Master Marine for 1 copy. IMO
Operating requirements
Each abandon unit drill should include:
14.11.2
.1
.2
.3
.4
.5
.6
.7
.2
133
Licensed to Master Marine for 1 copy. IMO
Chapter 14
.3
Records
The date when musters are held, details of abandonment drills, drills of
other life-saving appliances and on-board training should be recorded in
such log-book as may be prescribed by the Administration. If a full muster,
drill or training session is not held at the appointed time, an entry should be
made in the log-book stating the circumstances and the extent of the
muster, drill or training session held.
134
Licensed to Master Marine for 1 copy. IMO
Appendix
Model form of Mobile Offshore Drilling Unit
Safety Certificate (1989)
MOBILE OFFSHORE DRILLING UNIT
SAFETY CERTIFICATE (1989)
(Official seal)
(State)
Issued under the provisions of the
Type
(1.3 of the Code)
Port of registry
That the survey showed that the structure, equipment, fittings, radio
station arrangements and materials of the unit and the condition
thereof are in all respects satisfactory and that the unit complies with
the relevant provisions of the Code.
135
Licensed to Master Marine for 1 copy. IMO
Appendix
3
That, in accordance with 1.4 of the Code, the provisions of the Code
are modified in respect of the unit in the following manner:
................................................
That this unit has been issued with an approval for the continuous
survey techniques under 1.6.4 of the Code in lieu of renewal and
intermediate surveys in respect of:
Hull
Machinery
&
.....................
signature and seal of approving
authority
&
.....................
date of continuous survey
programme approval
.....................
(signature of authorized official
issuing the certificate)
....................................................
(seal or stamp of the issuing authority, as appropriate)
136
Licensed to Master Marine for 1 copy. IMO
Certificates
signed . . . . . . . . . . . . . . . . . . . .
(signature of authorized official)
place . . . . . . . . . . . . . . . . . . . .
date . . . . . . . . . . . . . . . . . . . . .
(seal or stamp of authority, as appropriate)
Annual/intermediate survey:
signed: . . . . . . . . . . . . . . . . . . .
(signature of authorized official)
place . . . . . . . . . . . . . . . . . . . .
date . . . . . . . . . . . . . . . . . . . . .
signed: . . . . . . . . . . . . . . . . . . .
(signature of authorized official)
place . . . . . . . . . . . . . . . . . . . .
date . . . . . . . . . . . . . . . . . . . . .
signed: . . . . . . . . . . . . . . . . . . .
(signature of authorized official)
place . . . . . . . . . . . . . . . . . . . .
date . . . . . . . . . . . . . . . . . . . . .
(seal or stamp of authority, as appropriate)
137
Licensed to Master Marine for 1 copy. IMO
Appendix
signed . . . . . . . . . . . . . . . . . . . .
(signature of authorized official)
place . . . . . . . . . . . . . . . . . . . .
date . . . . . . . . . . . . . . . . . . . . .
(seal or stamp of authority, as appropriate)
signed . . . . . . . . . . . . . . . . . . . .
(signature of authorized official)
place . . . . . . . . . . . . . . . . . . . .
date . . . . . . . . . . . . . . . . . . . . .
(seal or stamp of authority, as appropriate)
Second inspection:
signed . . . . . . . . . . . . . . . . . . . .
(signature of authorized official)
place . . . . . . . . . . . . . . . . . . . .
date . . . . . . . . . . . . . . . . . . . . .
138
Licensed to Master Marine for 1 copy. IMO
Certificates
139
Licensed to Master Marine for 1 copy. IMO
Appendix
140 .
Licensed to Master Marine for 1 copy. IMO